TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

Similar documents
TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly

TEST REPORT. Report No.: G Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

Structural Performance Certification Authorization Report

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee

Structural Performance Certification Authorization Report

Architectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310

TEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

PERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio

TEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania

TEST REPORT. Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California. PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series

Structural Performance Certification Authorization Report

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

TEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS:

TEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

AAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania

PERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel

TEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut

Structural Performance Certification Authorization Report

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO)

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window

TEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems

Dennis Fassnacht Jr :59:35-04'00'

TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas. Cycles 2,000,000. Summary of Results

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC.

MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door

TEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina

OSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A AAMA TEST REPORT SUMMARY

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

INTERNATIONAL WINDOW TEST REPORT

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America LLC. SERIES/MODEL: FCM B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

TEST REPORT AAMA 501.5

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT SUMMARY. Rendered to:

TEST REPORT. Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

AAMA/WDMA/CSA 101/I.S.2/A440-08

TEST REPORT. Report No.: C Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door

TEST REPORT. Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois. AD Skylight without Guard

KNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

MOCK-UP TEST REPORT. Report No: NCTL Test Dates:06/22, 07/23-27/10 Test Dates: 08/23-25/10 Report Date: 08/26/10

ETC Laboratories Measuring Up To Your Standards And More

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

Construction Consulting Laboratory, International

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)

MOCK-UP TEST REPORT NCTL ACURLITE STRUCTURAL SKYLIGHTS MOCKUP TEST UNIT TEST DATES 03/13/17, 03/21/17 03/23/17 REPORT DATE 04/03/17

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: TUBELITE, INC.

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

Carter Architectural Panels Inc. 221 E. Willis Road A Unit 18 Chandler, AZ Mr. Bruce Bourne

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition

SECTION ALUMINUM WINDOWS

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall)

Cardinal Commercial Products ALUMINUM STOREFRONT SYSTEM SERIES CF450 GUIDE SPECIFICATIONS SECTION ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS

7000 Series Curtain Wall Information Specifications

LATICRETE International Inc. One LATICRETE Park North Bethany, CT USA

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: Solutions Aluminum Guardrail System with Glass Balustrades

SECTION ALUMINUM STORM WINDOWS

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

AAMA/WDMA/CSA 101/I.S.2/A440-08

Transcription:

Architectural Testing TEST REPORT Report No.: B2739.02-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Air Barrier System SERIES/MODEL: ExoAir 230, ProGlaze ETA System 1, Spectrem 1, TremFlex 834, and Tremco 2011 mesh SPECIFICATION: ASTM E 2357-05, Standard Test Method for Determining Air of Air Barrier Assemblies. AND ASTM E 331-00, Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference. Test Date: 08/03/11 And: 08/04/11 Test Record Retention Date: 08/04/15

Test Record Retention End Date: 08/04/15 Page 1 of 8 1.0 Report Issued To: TREMCO, INCORPORATED 3735 Green Road P.O. Box 1014 Beachwood, Ohio 44122 2.0 Test Laboratory: Architectural Testing, Inc. 1140 Lincoln Avenue Springdale, Pennsylvania 15144 724-275-7100 3.0 Project Summary: 3.1 Product Type: Air Barrier Wall 3.2 Series/Model: ExoAir 230, ProGlaze ETA System 1, Spectrem 1, TremFlex 834, and Tremco 2011 mesh 3.3 Compliance Statement: Results obtained are tested values and were secured by using the designated test method(s). The mock-up tested was representative of target installation methods. Testing was performed on one penetrated wall. 3.4 Test Dates: 08/03/2011-08/04/2011 3.5 Test Location: Tremco Incorporated test facility in Cleveland, Ohio. 3.6 Test Sample Source: The test specimen was provided by the client 3.7 Test Specimen Installation: The test specimen was installed by representatives from Tremco Incorporated. 3.8 Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimen(s) reported herein. Test specimen construction was verified by Architectural Testing. 3.9 List of Official Observers: Name Company Tim Mattox Tremco Peter Poirier Tremco Pam Hernandez Tremco Joe Allison Architectural Testing, Inc.

Test Record Retention End Date: 08/04/15 Page 2 of 8 4.0 Test Specification(s): ASTM E 2357-05, Standard Test Method for Determining Air of Air Barrier Assemblies. ASTM E 283, Standard Test Method for Determining Rate of Air Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen. ASTM E 330, Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference. ASTM E 331-00, Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference. A series of laboratory tests were performed to determine air leakage resistance, and durability of air barrier coating. The installation was tested for air leakage, and water penetration resistance using ASTM E 2357, ASTM E 283, and ASTM E331. The durability of the selected installations was evaluated. 5.0 Test Specimen Description: 5.1 Product Sizes: (Penetrated Wall) Overall Area: Width Height 5.9 m² (64.0 ft 2 ) millimeters inches millimeters inches Overall size 2438 96 2438 96 5.2 Test Wall Construction: The penetrated wall was constructed of 2 x 6 wood studs, spaced 16" on center. The wall was sheathed with nominal 5/8" thick USG SecuRock sheathing, secured with #6 x 1-1/4" long bugle head screws, spaced 8" on center. The USG sheathing was applied with one 8' long horizontal seam. The sheathing was coated with a 70 mil wet thickness of ExoAir 230 and allowed to cure to a film thickness of 30 mil. The perimeter of the wall and the window rough opening were reinforced with Tremco 2011 fiberglass mesh and coated with the ExoAir 230.

Test Record Retention End Date: 08/04/15 Page 3 of 8 5.0 Test Specimen Description: (Continued) 5.2 Test Wall Construction: (Continued) The penetrations included a 635 mm x 1219 mm rough opening with a 600 mm x 1200 mm aluminum fixed window, a 100 mm x 100 mm HVAC duct, a 38 mm PVC pipe, and an octagonal junction box penetration per ASTM E 2357. A Proglaze ETA System 1, with molded corners, was applied to three sides of the window and sealed in place with Tremco Spectrum 1 sealant. A 10mm perimeter clearance space at the other penetrations was sealed with TremFlex 834. The clear anodized aluminum fixed window was a Kawneer Series/Model Trifab 451 center-glazed storefront system with sill pan, single glazed with 1/4" clear tempered glass. The unit was anchored through the jambs and sill using twelve #12 x 3" long screws, five at each jamb, and two at the sill, evenly spaced. The window was sealed with Proglaze ETA Connection and System 3 molded corners. The ETA connection was sealed to the ExoAir coating with Tremco Sprectrum 1 sealant. The wall system incorporated a 1" wide horizontal 'drift joint" near the top. The drift joint was bridged with interlocking galvanized plates. The drift joint was sealed with Proglaze ETA Connection and System 3 molded corners. The ETA connection was sealed to the ExoAir coating with Tremco Sprectrum 1 sealant. The wall was then covered with Grade D 15 lb felt paper and secured with 10mm T50 staples spaced nominally 8" to 12" on center. A metal J channel screed edge was applied to the wall perimeter, window perimeter, three sides of the drift joint, and at the penetration perimeters (except PVC pipe). The J channel was secured at the perimeter with #8 x 1-3/4" long bugle head screws spaced 16" OC horizontal (2 each), and 8" OC vertically. The J channel at the outlet box was secured with 1-1/4" long drywall screws, and at the duct with 1-3/4" long sheet metal screws. The wall was then covered with expanded metal lath secured with #8 x 1-3/4" long bugle head self drilling screws at each stud and 8" OC vertically. The assembly was then covered with a three-coat stucco system. The system consisted of a 3/8" thick scratch coat, a 3/8" thick brown coat, and a nominal 1/8" thick tan finish coat.

Test Record Retention End Date: 08/04/15 Page 4 of 8 5.0 Test Specimen Description: (Continued) 5.2.1 Test Wall Installation: The test wall was installed into an Spruce/Pine/Fir wood buck and secured at the perimeter with #8 x 3" long drywall screws spaced approximately 16" on center. The perimeter of the wall was reinforced with Tremco 2011 fiberglass mesh and coated with the ExoAir 230.

Test Record Retention End Date: 08/04/15 Page 5 of 8 6.0 Test Results: Tape and film were not used to seal against air leakage during structural testing. The temperature during testing was 22 C (72 F). The test results are recorded in the following tables: Pressure Air Infiltration (before racking sequence) Total Tare Specimen Rate (L/s m 2 ) (cfm/ft 2 ) 25 Pa (0.52 psf) 0.065 0 0.065 0.005 0.001 50 Pa (1.04 psf) 0.103 0 0.103 0.008 0.002 75 Pa (1.57 psf) 0.139 0 0.139 0.011 0.002 100 Pa (2.09 psf) 0.178 0 0.178 0.014 0.003 150 Pa (3.13 psf) 0.228 0 0.228 0.018 0.004 250 Pa (5.22 psf) 0.325 0 0.325 0.026 0.005 300 Pa (6.27 psf) 0.270 0 0.270 0.021 0.004 Pressure Air Exfiltration (before racking sequence) Total Tare Specimen Rate (L/s m 2 ) (cfm/ft 2 ) 25 Pa (0.52 psf) 0.061 0 0.061 0.005 0.001 50 Pa (1.04 psf) 0.109 0 0.109 0.008 0.002 75 Pa (1.57 psf) 0.143 0 0.143 0.011 0.002 100 Pa (2.09 psf) 0.172 0 0.172 0.014 0.003 150 Pa (3.13 psf) 0.236 0 0.236 0.018 0.004 250 Pa (5.22 psf) 0.366 0 0.366 0.026 0.006 300 Pa (6.27 psf) 0.406 0 0.406 0.021 0.006 Note: Reference Appendix A for Air Charts and 95% confidence Interval Note: By means of two All-thread rods incorporated at the sides of the top panel, the drift joint was then racked 3/4" to each side for three cycles and returned to the nominal position.

Test Record Retention End Date: 08/04/15 Page 6 of 8 6.0 Test Results: (Continued) Pressure Air Infiltration (after drift joint racking sequence) Total Tare Specimen Rate (L/s m 2 ) (cfm/ft 2 ) 25 Pa (0.52 psf) 0.055 0 0.055 0.004 0.001 50 Pa (1.04 psf) 0.103 0 0.103 0.008 0.002 75 Pa (1.57 psf) 0.125 0 0.125 0.010 0.002 100 Pa (2.09 psf) 0.172 0 0.172 0.014 0.003 150 Pa (3.13 psf) 0.246 0 0.246 0.019 0.004 250 Pa (5.22 psf) 0.339 0 0.339 0.027 0.005 300 Pa (6.27 psf) 0.388 0 0.388 0.031 0.006 Pressure Air Exfiltration (after drift joint racking sequence) Total Tare Specimen Rate (L/s m 2 ) (cfm/ft 2 ) 25 Pa (0.52 psf) 0.073 0 0.073 0.006 0.001 50 Pa (1.04 psf) 0.117 0 0.117 0.009 0.002 75 Pa (1.57 psf) 0.149 0 0.149 0.012 0.002 100 Pa (2.09 psf) 0.188 0 0.188 0.015 0.003 150 Pa (3.13 psf) 0.240 0 0.240 0.019 0.004 250 Pa (5.22 psf) 0.360 0 0.360 0.029 0.006 300 Pa (6.27 psf) 0.436 0 0.436 0.035 0.007 Note: Reference Appendix A for Air Charts and 95% confidence Interval

Test Record Retention End Date: 08/04/15 Page 7 of 8 6.0 Test Results: (Continued) Title of Test Results Allowed Water Penetration, per ASTM E 331 at 300 Pa (6.24 psf) See Notes (Two hour duration) No Observations: 1. After approximately 61 minutes, water penetrated internal to the duct. No leakage occurring from the perimeter of the penetration. 2. After approximately 108 minutes, some water dripping from the interior of the duct. All dripping is relative to leaks internal to the duct. No leakage occurring from the perimeter of the penetration. 3. Testing was terminated after 120 minutes of water spray with a 6.24 psf pressure difference. Pressure Air Infiltration (After water resistance test sequence) Total Tare Specimen Rate (L/s m 2 ) (cfm/ft 2 ) 25 Pa (0.52 psf) 0.083 0 0.083 0.007 0.001 50 Pa (1.04 psf) 0.101 0 0.101 0.008 0.002 75 Pa (1.57 psf) 0.142 0 0.142 0.011 0.002 100 Pa (2.09 psf) 0.158 0 0.158 0.013 0.002 150 Pa (3.13 psf) 0.162 0 0.162 0.013 0.003 250 Pa (5.22 psf) 0.299 0 0.299 0.024 0.005 300 Pa (6.27 psf) 0.329 0 0.329 0.026 0.005

Test Report No.: B2379.02-501-47 Test Record Retention End Date: 08/04/15 Page 8 of 8 The service life of this report will expire on the stated Test Record Retention End Date, at which time such materials as drawings, data sheets, samples of test specimens, copies of this report, and any other pertinent project documentation, shall be discarded without notice. If test specimen contains glazing, no conclusions of any kind regarding the adequacy or inadequacy of the glass in any glazed test specimen(s) can be made. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, Inc. Joseph E. Allison Senior Technician Lynn George Director Regional Operations JPG:sld Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Charts (5) Appendix-B: Photographs (5) This report produced from controlled document template ATI 00523, issued 03/08/11.

Test Record Retention End Date: 06/15/15 Appendix A Charts

Test Record Retention End Date: 06/15/15 Appendix B Photographs Photo No. 1 Exterior view of wall system Photo No. 2 Interior view of wall system

Test Record Retention End Date: 06/15/15 Photo No. 3 Interior view of drift joint Photo No. 4 Exterior view of drift joint

Test Record Retention End Date: 06/15/15 Photo No. 5 Interior view of water penetration internal of duct dripping out