CIPP Lateral Renewal Connection System

Similar documents
CIPMH (Cured-in-Place Manhole) Lining System

Installation Practice InnerSeal

I&I Mitigation: Rehabilitation of Sewer Laterals and Sealing the Collection System

SPECIFICATIONS FOR PREMIER-PIPE USA CURED-IN-PLACE TECH LINER

I&I Mitigation: Reconstruction of Sewer Laterals and Sealing the Connections to the Main Rick Gage

A COMPREHENSIVE UNDERSTANDING

SPECIAL SPECIFICATION 4411 Cured-In-Place Pipe (CIPP) (Drainage Structures)

Service Lateral Rehabilitation

SPECIAL SPECIFICATION 4631 Cured-In-Place Pipe (CIPP)

SECTION IRRIGATION PIPELINE LINING (CURED-IN-PLACE PIPE)

SECTION 809 CURED-IN-PLACE PIPE (CIPP) LATERALS

Special Specification SS1- INTERNAL CIPP POINT REPAIR OF PIPELINES. A. General. 1. Scope

Service Lateral Rehabilitation Using Cured-In-Place-Pipe (CIPP)

Rehabilitation of the Coral Gables Wastewater Collection System

CITY OF TAMPA ADDENDUM NO. 1. DATE: September 15, Contract 11-C-00001; Wastewater Sewer Rehabilitation by Cured-in-Place Pipe (C.I.P.P.

Cured-in-Place Pipe (CIPP) for Pressure Pipe. Presented by: Mike Moore

ESTABLISHING OBJECTIVE TEST PROTOCOLS FOR THE QUANTIFICATION OF WATER-TIGHTNESS OF A REHABILITATED MAIN/LATERAL SEWER CONNECTION

TECHNICAL SPECIFICATION FOR CURED-IN-PLACE MANHOLE REHABILITATION LINER SYSTEM

North American Society for Trenchless Technology (NASTT) NASTT s 2016 No-Dig Show. Dallas, Texas March 20-24, 2016 WM-T3-01

North American Society for Trenchless Technology (NASTT) No-Dig Show Nashville, TN March 11-15, Paper B-3-02

PIPE REHABILITATION. Comply with Division 1 - General Provisions and Covenants, as well as the following:

Product Information. Polyester Felt Cured-In-Place Pipe (CIPP) Lining Tube

STANDARD SPECIFICATIONS FOR CONSTRUCTING SANITARY SEWER FACILITIES DIVISION III - CONSTRUCTION SPECIFICATIONS

Table 1 Description of Work Pipe Size (mm) 1 Sunshine Way A/C No. A/C Yes

EVALUATION SUBJECT: HAMMERHEAD CURED-IN- PLACE PIPE (CIPP) LINING SYSTEM DIVISION: PLUMBING SECTION: SANITARY WASTE AND VENT PIPING

Mokapu CIPP Case Study & Innovations in Trenchless Technologies for Wastewater System Rehabilitation

CIPP REFERENCE SPECIFICATION

Sample Bid Specification Revision 2 PVC Expanded-in-Place Pipeline Reconstruction

Overview of Lateral and Main/Lateral Connection Lining and Sealing Technologies

Overview of Lateral and Main/Lateral Connection Lining and Sealing Technologies

CIPP Cured-in-Place Pipeline CIPP. cured-in-place pipe. trenchless pipe rehabilitation

INTERFIT LATERAL SEALING SYSTEM INSTALLATION GUIDELINE SPECIFICATION

UNIFIED FACILITIES GUIDE SPECIFICATIONS

DISPUTING THE MYTH OF INFLOW AND INFILTRATION REMOVAL EFFICIENCY

HIGH CHEMICAL RESISTANCE LINER (EPOXY RESIN FORMAPOX 301)

TECHNICAL SPECIFICATIONS FIBERGLASS/ULTRAVIOLET LIGHT CURED-IN-PLACE PIPE (CIPP) FOR MAINLINE RENEWAL

Michelle D. Beason, PE National Plant Services, Inc.

Method One: Liner/Bladder Assembly-Inversion Method.

SECTION 808 CURED-IN-PLACE-PIPE (CIPP)

GENERAL SPECIFICATION FOR THE REHABILITATION OF SEWERS

SPECIAL SPECIFICATION 5256 Cured-In-Place Pipe (Sanitary Sewer)

Trenchless Technology

LS 2760 CURED-IN-PLACE SEWER LINING

The Rehabilitation of Existing Building Drains and Building Sewers by the

GENERAL SPECIFICATION FOR THE REHABILITATION OF SEWERS USING THE THERMOFORM (PVC) PIPE LINING SYSTEM

Specifying Trenchless Sewer Rehabilitation Projects. Presented by: Todd Stelmacher Visu-Sewer, Inc.

SPECIFICATIONS. Cured-in-Place Pipe Liner (CIPP Liner). Shall comply with Subsection

ITEM NO SLIPLINING SANITARY SEWERS

INLINER LAY_InLiner Brochure_FA_ indd 1

CITY OF TAMPA ADDENDUM NO. 3. DATE: February 15, 2017

FOX METRO WATER RECLAMATION DISTRICT MANHOLE / SEWER PIPE MATERIALS AND INSTALLATION SPECIFICATIONS MATERIALS 1. PIPE & FITTINGS

ADDENDUM No. 2. City of Joliet, 2017 Spring Creek Interceptor Sewer Lining at CN Railyard

Cured-In-Place-Pipe (CIPP) LATERAL SEALS

PIPE BURSTING GRAVITY SEWER MAINS WITH HDPE PIPE

SECTION SANITARY SEWERAGE PART 1 GENERAL 1.01 RELATED DOCUMENTS

Infrastructure Point Repair System Technical Specifications

Inland Pipe Rehabilitation. August 17 OAWWA Canton, OH

International Aramoon Corp. Pipe Inspection and Rehabilitation By: Faiz Al-Elweet. SAWEA Al-Khobar KSA February 24, 2010

CITY OF ODESSA SPECIAL SPECIFICATIONS ITEM 1000 GLASS-FIBER REINFORCED POLYESTER (FRP) REHAB/REPLACEMENT MANHOLE

OTEC 2017 Spray Applied Pipe Liner Supplemental Specifications 833 Calculations for the Resin Based Liner Presented by Peter Blais, PE

OTEC 2015 Conduit Renewal

Lateral Thinking The Key To Meeting Sewer Infiltration Reduction Targets & Lowering Operating Costs

Project Specifications

STIFPIPE : INTRODUCING A NEW HONEYCOMB-FRP PIPE

Fold & Form PVC Liners Sewer & Culvert Rehabilitation

SECTION SANITARY UTILITY SEWERAGE PIPING

Chemical Grouting to Maintain and Sustain Municipal Sewers By: Marc A Anctil Logiball Inc.

Fiber Reinforced Cured-in-Place Rehabilitation Under an Interstate

Pipe User Group. Tuesday March 14, Walnut Creek, CA. Matt Wassam

Wastewater Capital Projects Management Standard Construction Specification

SPECIAL SPECIFICATIONS UV CURED IN-PLACE SPIRAL WOUND FIBERGLASSS PIPE LINING

CEDAR RAPIDS METROPOLITAN AREA STANDARD SPECIFICATIONS FOR PUBLIC IMPROVEMENTS May 2014 SECTION SEWER LINERS

Specification Guidelines for Testing and Sealing Lateral Connections and Lateral Service Lines in Sanitary Sewer Systems

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

SECTION STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY 1.2 SUBMITTALS 1.3 PROJECT CONDITIONS

Process Specification. Structural Rehabilitation & Corrosion Protection for Circular Structures in Wastewater Collection and Potable Water Systems

CURED-IN-PLACE PIPE LINING

Structural Lining of Water Mains. City of St. John s, Water and Wastewater Division

Overview. Advanced Dual Wall Profile Construction. Superior Polypropylene Material

SECTION 027 SPECIFICATIONS - PIPE MATERIALS FOR SEWERS

CHAPTER 6 - SANITARY SEWER

STANDARD SPECIFICATIONS SECTION SEWER MAINS AND LATERAL REHABILITATION BY LINING

A. This Section includes subdrainage systems for foundations and underslab areas. A. Product Data: For each type of drainage panel indicated.

A. Gravity-Flow, Nonpressure, Drainage-Piping Pressure Rating: 10-foot head of water (30 kpa).

EVALUATION SUBJECT: PERMA-LATERAL PULLED- IN-PLACE CURED-IN-PLACE PIPE LINING SYSTEM

SANITARY SEWERS. B. Construct or relocate building sanitary sewer services, stubs, and connections.

A. This Section includes sanitary waste and vent piping inside the building and to locations indicated.

STANDARD SPECIFICATIONS FOR CONSTRUCTING SANITARY SEWER FACILITIES DIVISION III - CONSTRUCTION SPECIFICATIONS SECTION 4

A. This Section includes gravity-flow, nonpressure storm drainage outside the building, with the following components:

BMEC AUTHORIZATION:

SECTION 806 MANHOLE REHABILITATION

SECTION 063 SPECIFICATIONS - CURED-IN-PLACE PIPE

1 Revised: 2019 Edition

SECTION SANITARY SEWER SYSTEM

SANITARY WASTE AND VENT PIPING

City of Middletown WATER & SEWER DEPARTMENT 82 Berlin Street Middletown, CT TEL: (860) FAX: (860)

SaniTite. HP Sewer Pipe 300 mm 750 mm

Daytona Beach Pier Building Renovation Jun 2010

TRENCHLESS TECHNOLOGY. Department of Civil Engineering.

Transcription:

Product Submittal Document Information CIPP Lateral Renewal Connection System ManEntry Lapel Liner Updated 6/12/14

Product Submittal Review ITEM 1. Manufacturer Company Name: LMK Technologies, LLC Contact Individual(s) Rick Gage Street Address: 1779 Chessie Lane City, State, Zip Code: Ottawa, IL 61350 Telephone: 815.433.1275 ext105 Facsimile: 815.433.0107 Product Submittal: Installation Practice For Rehabilitation Of A Sewer Service Lateral Using A One-Piece Main Lapel/Brim, Hydrophilic Gasket And Lateral Cured-In-Place Liner Assembly Via Man- Entry Into Large 30 Inch Diameter And Larger Mainline Pipes. Only Certified Licensed Installers by LMK are authorized to install the LMK ManEntry Lapel Liner in 30 mainline pipes or larger. ITEM 2. INTENT: This specification covers material requirements, installation practices, and methods for the reconstruction of a sewer service lateral pipe and the main connection without excavation. The pipe renovation shall be accomplished by insertion and inflation of a resin impregnated, single-piece lateral and main, gasket sealed connection liner assembly. The main connection and hydrophilic gasket are fastened in place and the lateral liner is pressed against the lateral pipe by inflation and held under pressure until the thermo-set resin has cured. The lapel portion is pressed against the mainline pipe and then fastened to the host pipe with a stainless steel compression ring using standard concrete fasteners. When cured, the liner extends over a predetermined length of the service lateral and a portion of the main pipe at the connection and forms a continuous, singlepiece, tight fitting, corrosion resistant and verifiable non-leaking Main/Lateral cured in-place pipe (CIPP) outfitted with a gasket seal. ITEM 3. Company Information: Larry Kiest, Jr. President/Founder. Inventor of more than 110 issued patents teaching methods and apparatuses for the Rehabilitation of Underground Pipes, Conduits and similar Structures. Mr. Kiest is a Licensed Plumber in the State of Illinois, Advisory Board Member of Trenchless Technology Center Louisiana Tech University, Member of ASCE/ PINS Lateral Committee, served 2-terms Board Member of NASSCO (2008-2012), Original chairman that initiated the NASSCO Lateral Committee, Active Board Member NASTT (2012-current), Member of No-Dig Planning Committee, Member of AWWA Standards Committee, Member of WEF, Member WEF Collections Committee, V.P. and active board member 2010-current) of MSTT, Member of ASTM, and Chairman of Task Committee F17, subcommittee 17.67 standard practice for rehabilitation of a sewer service lateral using a one piece main and lateral cured-in-place liner installed by means of air inversion. Mr. Kiest has conducted business in the field of Trenchless

Pipe Renewal Systems since 1985. ITEM 4. 4.0 The Technique The Man-Entry Lapel Liner repair renews the main/lateral connections and extends up into the lateral pipe for a designated length. The repair consist of a one-piece, continuous main and lateral lining that is vacuum impregnated with thermo-set resin; hereby referred to as a Lapel Liner. 4.1 A brief description of the operation and technique; including materials and methods of installation. 4.2 Intended use: Structural Repair Crack/Joint Sealing of Root Intrusion and Water Infiltration 4.3 EXISTING SEWER (Main and Lateral) 4.4 Diameter Ranges Lateral: 3 24 inch diameters. Main: 30 inch and greater. The reconstruction will be accomplished using a non-woven fabric tube of particular length and a thermo-set resin with physical and chemical properties appropriate for the application. The mainline lapel/brim and lateral tube are vacuum impregnated with the resin and then placed inside the lateral pipe via man-entry into the mainline. The liner is then placed inside of the lateral and the brim pressed against the mainline. The brim and hydrophilic gasket are held in place with an appropriately sized stainless steel compression ring which is anchored into place. The lateral tube is pressed against the lateral pipe wall by using a rubber inflation device. The liner is then cured ambiently. Once cured, the lateral inflation device is removed. The end result is a one-piece structural lateral lining and mechanically fastened connection to the main that provides a verifiable non-leaking connection with all mainline pipe types by incorporating a compression connection gasket at the connection. The cured finished materials as described above will, upon installation inside the host pipe, exceed the minimum test standards specified by the American Society for Testing Methods F1216-07. Minimum Test Standards for CIPP ASTM F1216 Appendix X1 FLEXURAL STRENGTH -ASTM D-790 4,500 PSI FLEXURAL MODULUS -ASTM D-790 250,000 PSI The system is designed for fully deteriorated pipe conditions. Typical installations are a direct result of ground water infiltration, root intrusion and structural defects such as open joints, offset joints, broken or missing pipe sections and hammer taps. The new pipe exhibits a smoothbore interior that typically increases flow rates. The system is compatible with most all types of pipes; V.C.P., Concrete, Cast Iron, P.V.C and existing main pipes that have been renewed by a CIPP process. Typically, full-length lining systems utilize an inner coating or film. Films may range from PVC, PU to PE. The system is compatible with all pipe materials due to the use of a mechanically fastened hydrophilic sealing connection compression gasket at the mainline/lateral connection.

4.5 Circular and/or Non- The system can accommodate pipe ovality up to -20%. Circular Capability 4.6 Material Limitations This system is designed for gravity sewers and low pressure piping. 4.7 Lining Material Composition and Construction Needle punched felt or proprietary knitted tubes coated with a chemically resistant impervious film. The tube is stitched using Nomex, high-temp, high-strength thread. The tube is air-tight and flexible in design to reduce inversion pressures. 4.8 Main/Lateral Jointing System The lining material is constructed as a one-piece lapel/brim shaped Main/Lateral fitting. The main lapel and lateral lining tube is stitched with high-temp Nomex thread. Therefore, there is no joining of two separate liners during the installation process. The end product is a one-piece brim style main to lateral cured-in place pipe with the use of a hydrophilic gasket seal. 4.9 Resin System Resin Systems include: LMK656 Non Filled ISO Polyester Resin LMK656EN Filled ISO Polyester Resin LMK770 Series Ambient Cured Epoxy Resin LMK100 Series VOC Free Vinyl Ester Resin 4.10 Mechanical Properties Excess resin migrates into pipe defects allowing a mechanical anchoring. Concrete anchors (1/4" x 2 1/4") by Tapcon are used to secure the stainless steel compression ring, cured-in-place lapel portion and hydrophilic hat style gasket. 4.11 Physical Properties Flexural Strength 4,500-PSI Minimum Test Method: ASTM 790 Flexural Modulus 250,000-PSI Minimum Test Method: ASTM 790 4.12 Corrosion attack Chemical Resistance Testing. Test Method: ASTM D5813 and F1216 See Independent Laboratory Testing: Microbac Corrosion Test. 4.13 Resin Saturation The lapel liner is vacuum impregnated with a thermo-set resin. Method 4.14 Gasket Sealing The mainline connection shall include a seamless molded flange shaped gasket. 4.15 Effects of Line and There are no effects caused by grade changes since air pressure is Grade used to pressurize the liner against the host pipe until cured. 4.16 Protruding Lateral Pipes It is recommended protrusions into the main pipe are cut flush to the host pipe. 4.17 Reduction in Pipe Diameter, and its Effect The lateral liner exhibits a slick and typically smooth interior with a co-efficient that increases flow-rate. Minor wrinkling may occur and some wrinkling may occur based on actual inner pipe diameter, inner surface, pipe configuration and conditions. 4.18 Homeowner Impact Homeowners and building occupants at a minimum will receive a door knob notice bulletin 48 hours prior to the scheduled work and personal contact is attempted to be made the day of the scheduled work. The notice bulletin summarizes the scope of work, tentative time of service disruption and home/building owner cooperation for non-use of water/sewer for a 2-hour period or less. A brief explanation of Dry Fixture Traps is also included. ITEM 5.

5.0 Sewer preparation involves cleaning and a flow stoppage or diversion period. 5.1 Mainline Service 5.2 Specific Requirements The main and the laterals are cleaned utilizing high-pressure water and mechanical cleaning tools. Pressures may range from 2,000 to 4,000 PSI removing all roots, debris and obstructions. Cleaning of the lateral is performed from the main pipe. Any protruding service connections will be removed prior to liner insertion. The current condition of the pipe will be compared to the original designed condition to verify that design parameters have not changed. Normal mainline flows are plugged or by-passed during the process, depending on flow. Typical time for plugging the mainline is three-hours (3) or less. In some cases by-pass pumping will be required and used. Access to the upstream and downstream manholes is mandatory. 5.3 Cleanout System Lateral lengths 3.0-feet and less are renewed without the need for a cleanout. Lengths greater than 3.0-feet require a TEE shape, or back to back WYE shaped cleanout fittings located a minimum of two-feet (2 ) upstream from the terminal end of the lateral CIPP liner. 5.4 Installation Crew and Equipment 5.5 Handling Sewer Access (i.e., existing manholes) A typical crew consists of (3 to 4) technicians. A mobile wet out unit is required for onsite vacuum impregnated of the liner. Traffic disruption is minimal. The installation process is typically quick, efficient and non-disruptive with no need for surface restoration when compared to open cut replacement methods. Licensed and Trained Technicians remotely carry out the installation. Entry into a manhole is absolutely required. If confined entry is required, Federal, State and local laws apply. 5.6 Inflation Method Air pressure is applied to the rubber inflation device causing the lateral tube to inflate. 5.7 Maximum Length Maximum length for a continuous lateral lining is 18 inches for main to lateral connection where no cleanout exists. 5.8 Curing Method The Resin/Catalyst packages are proprietary to LMK Technologies. The resin systems are either cured at ambient temperatures or steam cured. Polyester/Vinyl-ester Ambient: One hour pot time/one hour cure time. 5.9 Removal of Inflation Device The inflation device is removed after curing. 5.10 Equipment Removal Once cured, the equipment is removed from the mainline pipe. 5.11 Document Final Video and Testing Procedures A final video inspection is performed from the main.

5.12 Design Life 50-Year Design Life based on assumption described in ASTM F1216 for the lateral liner. Appendix X1 and long-term creep as described in ASTM D2990. ITEM 6. Advanced Materials: Liner Assembly Lapel Liner Man-entry Lapel Liner Vacuum Impregnation Installed from the main pipe up into the lateral 10,000 hour CIPP chemical resistance testing ASTM D2990 Flexible construction Gasket Sealing Technology (hydrophilic and/or compression gaskets) 10,000 hour hydration/dehydration gasket sealing test Respectfully Submitted By: Larry Kiest, Jr. Larry Kiest, Jr. President LMK Technologies, LLC.