Control Strategies for PAA Wastewater Disinfection at WWTPs with Variable Effluent Quality

Similar documents
Disinfection of Secondary Effluent Using 22% Peracetic Acid at the M.C. Stiles Wastewater Treatment Facility

The Application and Measurement of Peracetic Acid for Wastewater Disinfection

Old City, New Ideas: Peracetic Acid in Wastewater Disinfection at St. Augustine

Session 311: Effects of TSS on Peracetic Acid Dosing for CSO Events

MUNICIPALITY OF WEST ELGIN RODNEY WASTEWATER TREATMENT PLANT

Using PAA as an Alternative WWTP Disinfection Method

11.0 EFFLUENT DISINFECTION

Georgia Power Plant Bowen NPDES Permit No. GA Ash Pond Dewatering Plan. Revised December 2017

CITY OF STEUBENVILLE, OHIO WASTEWATER TREATMENT FACILITY

CITY OF OXFORD WASTEWATER TREATMENT FACILITY ANNUAL PERFORMANCE REPORT FOR THE CALENDAR YEAR OF 2014

EWRI Pittsburgh Section Meeting October 30, U.S. EPA, Cincinnati, OH CB&I Federal Services LLC, Cincinnati, OH

Non Contact UV System at the Yakima Regional WWTP

With increasing risk management requirements. Wastewater UV Disinfection Systems Lessons Learned During Performance Testing

MUNICIPALITY OF WEST ELGIN WEST LORNE WASTEWATER TREATMENT PLANT

CITY OF OXFORD WASTEWATER TREATMENT FACILITY ANNUAL PERFORMANCE REPORT FOR THE CALENDAR YEAR OF 2018

FULL SCALE PILOT STUDY USING THE VTX PROCESS FOR THE REMOVAL OF SULFIDE AT THE VIRGINIA INITIATIVE PLANT

ENHANCING THE PERFORMANCE OF OXIDATION DITCHES. Larry W. Moore, Ph.D., P.E., DEE Professor of Environmental Engineering The University of Memphis

The Impact of VigorOx WWT II Wastewater Disinfection Technology on Endocrine Disruptors. ED Deactivation Bench Test Procedure

Module 5: Disinfection and Chlorination Answer Key

UV DISINFECTION OF LOW TRANSMITTANCE PHARMACEUTICAL WASTEWATER

Aquatic Toxicity and Fate of VigorOx WWT II

RE: Annual Report 2016 Wardsville Wastewater Treatment Plant and Collection System

At the Mercy of the Process Impacts of Nitrogen Removal Performance on WWTP Disinfection

CITY OF OXFORD WASTEWATER TREATMENT FACILITY ANNUAL PERFORMANCE REPORT FOR THE CALENDAR YEAR OF 2012

Analytical Instrumentation for Wastewater Monitoring

Facilities Plan. Technical Memorandum Nos. TM-CSO-11 and TM-WW-5 Disinfection Facilities

COMPARISON OF SBR AND CONTINUOUS FLOW ACTIVATED SLUDGE FOR NUTRIENT REMOVAL

NC-PC Industry Day Pretreatment 101. Industrial Waste Impacts on POTW Treatment Processes. Dawn Padgett Operations Manager Charlotte Water

BIOTECTOR TOC Analysers

Algae Removal from a Facultative Lagoon System Using Dissolved Air Flotation. J. Patrick Pierce, P.E. Environmental Treatment Systems, Inc.

WASTEWATER TREATMENT PLANT MASTER PLAN 6. BUSINESS CASE EVALUATION OF ALTERNATIVES

PROCESS OPTIMIZATION USING SPECTROPHOTOMETERS

Brightwater: The Design Challenges of a 39 mgd (150 MLD) Membrane Bioreactor

SIMPLE and FLEXIBLE ENERGY SAVINGS And PERFORMANCE ENHANCEMENT for OXIDATION DITCH UPGRADES

USPE Environmental Conference Nashville, TN March 10, 2011

Water Quality Permitting Program Monitoring Matrix 1,2,3

WEFTEC.06. Lake Okeechobee, Actiflo, peroxone, surface water, Cyanobacteria

AquaPASS. Aqua MixAir System. Phase Separator. System Features and Advantages. Anaerobic. Staged Aeration. Pre-Anoxic.

The following biological nutrient removal processes were evaluated in detail in the 2016 Liquid Processing Facilities Plan:

City of Paso Robles Uses Online Monitor to Detect Low-Level of THMs in Treated Wastewater

Actual Value: Monthly average amount of Flow, COD, and TSS contributed to the SROG system by each SROG city

Georgia Power Plant McDonough-Atkinson NPDES Permit No. GA Ash Pond Dewatering Plan. Revised May 2018

Case Study. BiOWiSH Aqua. Biological Help for the Human Race. Municipal Wastewater Bathurst Waste Water Treatment Works Australia.

Case Study. Biological Help for the Human Race. Bathurst Municipal Wastewater Treatment Works, New South Wales, Australia.

Disinfection of Combined Sewer Overflows with Sodium Hypochlorite and Peracetic Acid

A Sustainable Nitrogen Removal Program using Nitrack Automation at Tyson Foods. Mehran Andalib David Redinger Lee Kleckner Kathryn Chadwick

HIGH RATE TREATMENT AS PART OF THE SOLUTION FOR WET WEATHER FLOWS JUNE

TABLE OF CONTENTS. SECTION 1 INTRODUCTION 1.1 Background Purpose and Scope

Optimizing Water Reclamation Systems by Automation using Continuous Water Quality Analysis

Review of WEFTEC 2016 Challenge & Overview of 2017 Event. Malcolm Fabiyi, PhD, MBA Spencer Snowling, PhD. P.Eng

Dundalk Wastewater Treatment Plant

REMOVAL OF SELENIUM FROM REFINERY WASTEWATER USING THE HONEYWELL UOP XCEED BIOREACTOR SYSTEM

2017 Annual Performance Report

ENHANCED TECHNICAL ASSISTANCE EVALUATION

NEW BIOLOGICAL PHOSPHORUS REMOVAL CONCEPT SUCCESSFULLY APPLIED IN A T-DITCH PROCESS WASTEWATER TREATMENT PLANT

Georgia Power Plant McManus NPDES Permit No. GA Ash Pond Dewatering Plan. Revised April 2018

6.2.1 Intermediate Pumping Overview

UV Disinfection for a Municipal Wastewater Lagoon Effluent No Prior Filtration Needed? Wayne Wong, M.A.Sc., P.Eng., PMP

BEING GOOD STEWARDS: IMPROVING EFFLUENT QUALITY ON A BARRIER ISLAND. 1.0 Executive Summary

Operation and Control of Multiple BNR Processes in One WWTP

Baltimore City Department of Public Works

The City of West Palm Beach (City)

BRACEBRIDGE WASTEWATER TREATMENT 2016 SUMMARY REPORT

On-Line Nutrient Monitoring-Operator s Job Got Easier

ULTRAVIOLET DISINFECTION 2013 Municipal Markets.

Treatability Study and Reverse Osmosis Pilot Study of Industrial Wastewater at a Wood Products Mill

City of Leadwood Wastewater System Engineering Report

EHS SMART-Treat Onsite Moving Media Treatment System

75 th STREET WASTEWATER TREATMENT PLANT UPGRADES PROJECT

Wastewater Treatment. Where does wastewater go when it leaves your house?

A COMPARATIVE PERFORMANCE STUDY OF TWO TYPES OF CLOTH FILTER MEDIA APPLIED IN MUNICIPAL WASTEWATER TREATMENT

Anderson Water Pollution Control Plant

Altoona Westerly Wastewater Treatment Facility BNR Conversion with Wet Weather Accommodation

NPDES COMPLIANCE OF COOLING TOWERS BLOWDOWN AT POWER PLANTS WITH RECLAIMED WATER AS SOURCE WATER

National Pollutant Discharge Elimination System; Determination of Sampling Frequency Formula for Industrial Waste Discharges

WEFTEC.06. **Cobb County Water System, Marietta, Georgia

Non-Chemical Disinfection & Dechlorination to Protect RO and Demineralizer Treated Boiler Make-up Water

ECO Smart Aerobic Waste Water Treatment System. Optimising the re-use and recycling of waste water

Hānai Ai / The Food Provider September October November 2014

Chlorination/Dechlorination: An Environmental Solution

Iroquois Wastewater Treatment Plant 2016 Annual Performance Report

2017 Performance Report for Bobcaygeon Waste Water Treatment Facility

City of Andover, Kansas Energy Assessment-Wastewater Treatment Plant

City of Elk River Wastewater Treatment Facility Improvements. Achieving Wastewater Treatment Goals

Marcos Elizondo Vice President, Landfill Operations & Engineering

VC Series Wastewater. Vertical Open Channel Ultraviolet Disinfection

AMPC Wastewater Management Fact Sheet Series Page 1

AMPC Wastewater Management Fact Sheet Series Page 1

Case Study. BioMagic. Variable Dosing Yields Economy and Results CITY OF CARLSBAD. Pump station odor and hydrogen sulfide control

Taylor Creek Treatment Plant. Metropolitan Sewer District of Greater Cincinnati

Clean Water 2020 Program

EQUIPMENT AND SERVICE COMPANY, INCORPORATED FX- 300 ISE Ammonia, Nitrate, Nitrite Measurement

Copies: Mark Hildebrand (NCA) ARCADIS Project No.: April 10, Task A 3100

NEW SOLUTION FOR PRIMARY WASTEWATER TREATMENT; CLOTH MEDIA FILTRATION

Post-Aerobic Digester with Bioaugmentation Pilot Study City of Meridian, ID WWTP PNCWA 2010

Aeration Blower Requirements. Tom Jenkins 06/15/2016

Bracebridge Wastewater Treatment 2017 Summary Report

Stonecrest Estates Sewage Treatment Plant 2017 Annual Report

Membrane BioReactor: Technology for Waste Water Reclamation

Transcription:

Control Strategies for PAA Wastewater Disinfection at WWTPs with Variable Effluent Quality Philip Block 1*, Scott Morgan 2, Kati Bell 3, Sarah Stewart 4 1 PeroxyChem, Philadelphia, PA 2 City of Memphis, TN 3 CDM Smith, Nashville, TN 4 CDM Smith, Houston, TX ABSTRACT The dose of peracetic acid that is required to control microbial concentration in wastewaters will depend on a number of factors, including: target microorganism, the disinfection contact time, and the characteristic quality of the wastewater effluent. Wastewater characteristics that impact peracetic acid oxidant demand, and hence disinfection performance, may include natural organic matter, reduced metals, biological oxygen demand, chemical oxygen demand and total suspended solids. For most treated municipal wastewater effluent, the quality of the wastewater is such that the peracetic initial oxidant demand is relatively low and stable over time. This allows PAA dose to be controlled using simple flow-pacing, once the oxidant demand is known. With recent advances in on-line, continuous PAA monitoring probes, feedback control based on effluent PAA residual could also be combined with flow pacing to provide robust and reliable PAA dose control. However, there are situations where wastewater effluent quality is highly variable, due to any number of factors, such as intermittent industrial discharges to the wastewater treatment plant. Changing effluent conditions can result in variable PAA demand; thus, more active control on PAA dosing may be required to optimize PAA performance in an effort to minimize operational costs. KEYWORDS: peracetic acid, disinfection, process control, water quality INTRODUCTION While chlorination is still the most commonly used disinfection technology for municipal wastewater in the US, formation of chlorinated disinfection by-products (DBPs) has become a concern, and is one of the major drivers for wastewater utilities to consider alternative disinfection technologies. In recent years, peracetic acid (PAA) has gained momentum as an alternative disinfection technology to chlorine 1-3 due to its lack of DBP formation, its lower aquatic toxicity profile, and its lower oxidant demand. Upon reaction with bacteria and viruses,

natural organic matter, reduced metals and suspended solids, PAA decomposes to oxygen, water and acetic acid. As a result, chlorinated by-products are not formed. In addition, PAA does not persist in the environment once discharged, so quenching, which would be the analogous process to de-chlorination, is typically not required. Peracetic acid is delivered as an equilibrium solution comprised of peracetic acid, hydrogen peroxide, acetic acid (vinegar) and water, and has been used in a variety of industries, including the medical and food safety markets, as a disinfectant and sterilizing agent. While its use as a wastewater disinfectant is relatively new in the US municipal market, its effectiveness on controlling bacterial microorganisms is well-known 4. The effective dose of peracetic acid will depend on a number of factors, including: the target microorganism, disinfection contact time, and the quality of the wastewater effluent. Wastewater characteristics that impact PAA oxidant demand, and hence performance, may include natural organic matter, reduced metals, biological oxygen demand, chemical oxygen demand and total suspended solids. For many wastewater treatment facilities, the quality of the wastewater is such that the PAA oxidant demand is relatively low and stable over long periods, and may only show seasonal variability. In addition, the demand on the PAA is generally very rapid, occurring within the first few minutes of contact time. As a result, once the initial PAA dose is determined through jar or pilot testing, meeting a specific microbial reduction requirement becomes a matter of maintaining a constant PAA dose. This allows for PAA dosing to be controlled using simple flow-pacing. With advances in on-line, continuous PAA monitoring probes, feedback control based on effluent PAA residual can also be combined with flow pacing. However, there are treatment facilities where wastewater effluents have characteristics that are highly variable, with water quality fluctuating weekly, sometimes even daily. This may be due to any number of factors; one example is where wastewater is impacted by industrial discharges that may have compositional changes arising from operational and production scheduling. These changing influent conditions can result in a variable PAA demand. This variable demand may result in either an under-dosing of the PAA, if the residual feedback control cannot keep up with the fluctuating demand changes, or an over-dosing of PAA, if an initial PAA dose is set to cover the worst-case oxidant demand of the wastewater. In such cases, more active control of the PAA dosing is required to optimize PAA performance and achieve reliable microbial control, while minimizing chemical consumption costs. An alternative control scheme is to use influent water quality parameters as input variables to drive a feed-forward control algorithm. This requires an understanding of how specific water quality parameters impact PAA demand over the full range of temporal water quality; and it is important to obtain sufficient data to fit an algebraic formula on which process control can be based.

BACKGROUND The City of Memphis M.C. Stiles Wastewater Treatment Plant (WWTP) processes a combined municipal and industrial waste stream. The industrial component of the wastewater is highly variable across a range of industries. As a result, the treated effluent can still contain nonbiodegradable molecules that contribute to chemical oxygen demand, but not biochemical oxygen demand (see Figure 1). When considering disinfection technologies to meet effluent discharge standards at this WWTP, the compounds that impart color to the wastewater effluent render use of UV disinfection impractical due to low UV transmittance (< 10-percent) and represent a significant demand on chemical oxidants such as chlorine and peracetic acid. This demand represents a substantial operating cost for oxidative disinfectants. Additionally, the timedependent nature of the industrial discharges induce a time variable in the oxidant demand, making simple flow-paced disinfectant dosing schemes not practical or cost effective. The high oxidant demand of the effluent and long contact time that is already available at the Stiles WWTP in an existing contact basin also make simple residual, feed-back dosing schemes not cost effective. Figure 1 Variability of color in effluent from the M.C. Stiles WWTP Recent work 5 investigating oxidative disinfectants and the impact of water quality on disinfection efficacy at the Stiles WWTP at the pilot reactor scale; results showed that peracetic acid 6 had a more favorable oxidant demand profile compared to chlorine chemistry. It was also shown that one or more water quality parameters, such as color, chemical oxygen demand (COD) or oxidation-reduction potential (ORP) could be used as a feed-forward control parameter for oxidant dosing. FULL-SCALE PAA TRIAL TO DEVELOP PAA DOSE CONTROL A full-scale, six-month trial of PAA disinfection was conducted at the Stiles WWTP to demonstrate the ability to use a feed-forward control scheme to consistently meet the target

microbial reduction required by the WWTP s National Pollutant Discharge Elimination NPDES permit. The objectives of the trial included: Characterization the impact of water quality on peracetic acid (PAA) demand over time, Identification of key water quality parameters for use in feed-forward control of PAA dosing, Development of a PAA dose control algorithm, Determination of the optimal PAA dose to achieve the required Escherichia coli (E. coli) concentration for discharge under the NPDES permit, and Demonstration and verification of continuous PAA control for disinfection compliance. Trial Site Description The Stiles WWTP is owned and operated by the City of Memphis and uses contact-stabilization to meet treatment objectives. Figure 2 shows the general layout of the Stiles WWTP and Table 1 provides an overview of the historical plant performance along with permit limits. Disinfection Contact Tanks Final Clarifiers Contact Stabilization Tanks Screening & Grit Chambers Final Clarifiers Figure 2. Overview of the Stiles WWTP The single grab daily maximum limit for E. coli is 487 cfu/100 ml, with a monthly geometric mean limit of 126 cfu/100 ml. To determine whether PAA could be used to consistently meet these limits, a full-scale PAA trial was conducted at the facility.

Table 1. Historical effluent water quality characteristics at the Stiles WWTP. Parameter Minimum observed Daily Performance Data Average or mean 1 Maximum observed Daily (minimum; maximum) Draft NPDES Limit Weekly maximum Monthly maximum Daily Flow 2 (MGD) 58 94 232 135 -- -- BOD 3 (mg/l) 5 34 144 86.1 64.7 43.1 TSS 3 (mg/l) 1 22 103 104 78 52 ph 4 (s.u.) 6.5 7.2 8.1 6.0 9.0 -- -- E. coli 5 (cfu/100ml) 1.3 x 10 4 (4.4 x 10 5 as 6.0 x 10 5 geomean) 1.1 x 10 7 487.. 126 as geomean Apparent color 6 (PtCo units) 29 749 2084 -- -- -- True color 6 (PtCo units) 24 619 2000 -- -- -- Apparent UVT 6 (%) 0 9.3 36 -- -- -- Filtered UVT 6 (%) 0.6 16 71.9 -- -- -- 1 arithmetic means were reported for all values except E. coli which is also reported as a geometric mean 2 average daily influent flow values, period of record: 9/1/09 5/31/13 3 daily values taken from composite effluent samples, period of record: 9/1/09 5/31/13 4 daily values taken from grab effluent samples, period of record: 9/1/09 12/31/12 5 daily values taken from grab effluent samples, period of record: 1/17/08-7/11/13 6 daily values taken from composite effluent samples, period of record: 8/11/11 5/21/13 The Stiles WWTP was originally constructed to provide chlorine disinfection; however, due to concerns over disinfection by-products and their impact on aquatic organisms in the receiving waterbody, the practice was never implemented. Thus, the WWTP has an existing contact chamber (Figure 3); it is a typical two train serpentine configuration designed provide plug flow for 15 minutes at the peak hour flow of 250 million gallons per day (MGD). Flows from the north and south sides of the plant are combined in a mixing chamber at the head of the disinfection contact tank; flow then splits into the north and south channels. It was assumed throughout the PAA trial that flow was completely mixed with respect to flow, water quality and E. coli concentrations in the mixing chamber prior to flow splitting into each of the two channels. At the end of each channel, treated effluent flows over a weir, and combines in a common pipe before being discharged to the Mississippi River.

North Effluent weir EC Out PAA 3 BFM PAA 2 PAA 1 DP Influent Effluent Effluent weir EC IN Color COD UVT ph/t Mixing Chamber South Figure 3. Stiles WWTP disinfection contact chamber DP PAA dosing point PAA 1 position of PAA probe 1 PAA 2 position of PAA probe 2 PAA 3 position of PAA probe 3 EC in location of influent E. coli sampling EC out location of effluent E. coli sampling Color location of color probe COD, UVT location of COD / UVT probe ph / T location of ph and temperature probe BFM position of the bubbler flow meter Full-scale Trial Approach The PAA field trial was conducted in five phases, between December 2014 and April 2015. During the trial, PAA was dosed into the north side of the disinfection chamber and the south side was used as a control, with no PAA addition. Influent water quality was measured at the head of the south side chamber and disinfected samples were collected at the weir on the north side of the contact tank. Phase 1 was conducted over a two week period during which PAA was flow paced, and water quality parameters were continuously monitored using on-line analyzers: color, chemical oxygen demand (COD), oxidation-reduction potential (ORP), percent UV transmittance at 254 nm

(UVT), ph and temperature. Grab samples were collected to evaluate E. coli concentrations at the influent and effluent of the disinfection contact tank. PAA residuals were measured at three locations throughout the contact tank using online monitoring probes. The Phase 1 data were analyzed, and correlations between each water quality parameter, PAA demand and E. coli reduction were performed. The two best parameters were selected based on the highest r 2 value from a least-squares fit of the data to PAA demand, and the greatest sensitivity of that parameter to PAA demand (greatest slope in the change of the quality parameter versus change in the PAA demand). Using the selected parameters, a feed-forward algorithm, coupled with flow pacing, was developed to control PAA dose based on each parameter. Phase 2 was conducted over a two week period, utilizing the dose algorithm developed from Phase 1 data for color. Disinfection performance was evaluated over a wide range of effluent color concentrations and flows. Phase 3 was conducted similarly to Phase 2, except the dose algorithm was based on COD. After Phase 3, the algorithm providing the greatest performance with respect to microbial reductions and PAA use rates was identified for additional testing. Phase 4 was a month long assessment of disinfection performance using the PAA dose algorithm based on color, selected after Phase 3. During this phase, adjustment of the algorithm and base PAA dose was conducted to maximize disinfection performance while minimizing the dose required. Final verification and qualification of the VigorOx WWTII control algorithm was assessed during the final month-long Phase 5. The refined PAA dose algorithm, as determined during Phase 4 was implemented and disinfection performance was monitored. Instrumentation for Monitoring Water Quality Peracetic acid was measured in situ via the Prominent Dulcotest CTE sensor. The sensor is a membrane-capped amperometric, two electrode sensor for the measurement of PAA in aqueous solution. It has a platinum working electrode and a silver halide coated counter or reference electrode. PAA contained in the sample water diffuses through the membrane, causing a potential difference between electrodes. Three PAA submersible probes were placed into the disinfection contact tank (north side, PAA dosing): a 10 ppm PAA probe one quarter of the distance down the contact tank (Probe 1, P1), a 10 ppm PAA probe one half the distance down the contact tank (Probe 2, P2), and a 2 ppm PAA probe located at the effluent weir (Probe 3, P3) (see Figure 3). Wastewater color was measured on-line utilizing a ChemScan UV-3151 Series Analyzer with a flow-through sensor. The analyzer draws a sample of wastewater from the untreated side of the disinfection channel, representative of the influent wastewater, to the main unit, located in a control house adjacent to the disinfection contact tank. Periodic grab samples were collected and measured using a portable HANNA Instruments (HI96127) color meter. Calibration of the ChemScan unit was performed if greater than a 10-percent difference was observed between results from the two instruments. The color analyzer was stable through the course of the trial, requiring minor daily cleaning of an internal filter as its maintenance profile. Wastewater COD and UV transmittance (UVT at 254 nm) was measured online using a submersible YSI CarboVis model 701. Periodic grab samples were collected and measured using a benchtop HACH DRB200 COD analyzer and a bench scale HACH DR5000 spectrophotometer. Calibration of the YSI CarboVis was performed if greater than 10-percent

difference between COD or UVT was observed between the online and benchtop instruments. The COD and UVT analyzers remained stable throughout the trial, with cleaning every two to three days. Measurements were made in the control side of the disinfection contact tank. ORP, ph and temperature were measured using a SensoLyt multi-probe. The probes required little maintenance, except for occasional cleaning. Two McCrometer SPI Mag Model 282L Single Point Insertion Electromagnetic Flow Meters (IFM) were inserted, one each, into the north and south side wastewater conduit pipe prior to entering the mixing chamber of the contact tank. The IFM proved to be significantly interfered with by organic solid material within the wastewater. This introduced error into the measured flow, and impacted the target PAA dose concentration via the flow-pacing algorithm. As a result, the IFM were replaced for Phase 4 and 5 with a Teledyne ISCO Signature bubbler-type flow meter (BFM), which was inserted into the disinfection channel right before the outflow weir. The BFM was shown to be highly stable and reproduced accurately the wastewater flow rate as determined upstream by the plant. As the BFM only measures flow through the north side of the disinfection channel, total plant flow was determined as twice the BFM measurement. Disinfection Performance Sampling Grab samples were collected Monday through Friday at the influent, effluent and midpoint of the disinfection contact tank for E. coli (see Figure 3). In Phases 1, 2 and 3, samples were obtained three times a day (at approximately 8 am, 10 am and 2 pm) at the three locations. During Phase 4, samples were collected three times a day, but only at the influent and effluent of the disinfection contact tank. For Phase 5, samples were collected once a day, at 10 am, for both the influent and effluent. Upon collection, the wastewater samples were stabilized using sodium thiosulfate that was provided in the sample containers to quench PAA so that disinfection did not continue during sample transport. E. coli analysis were performed by a third-party laboratory. RESULTS AND DISCUSSION Results of the full-scale trial are presented in the following sections by Phase, with key observations from each Phase being noted. Phase 1: Assessment of Influent Water Quality Parameters The first phase was a ten day trial designed to assess undisinfected wastewater quality (color, COD, UVT and ORP) and the impact on PAA demand. PAA dosing for Phase 1 was initially set at 10 ppm; due to relatively low wastewater flow in later stages of Phase I, very low PAA dose pump speeds caused PAA to be delivered in a discontinuous, pulse-like fashion. To overcome this operational issue, the PAA dose was increased to 15 ppm. Results of effluent color and COD collected during Phase 1 are provided in Figure 4; results of UVT and color and ORP are provided in Figure 5. Wastewater color ranged from a maximum of 1950 to a minimum of 400 color units and COD ranged from 82 to 355 mg/l during this Phase. The high color and COD data were correlated to periods when particularly industrial users were discharging; when these users stopped production, wastewater color decreased substantially.

PAA residual at Probe 1 was observed to increase when color decreased; COD also decreased and UV transmittance showed a general increase during this period. The PAA residuals at the midpoint (P2) and end of the contact tank (P3) at the effluent weir were near the detection limit of the analyzer throughout the phase and are not shown; as a result, the analysis of Phase 1 data is based on the residuals reported at the analyzer located nearest the PAA application point (P1). PAA residuals at Probe 1 are shown in Figure 6 along with E. coli results. As shown in Figure 6, when the PAA residual at Probe 1 is 4 ppm or higher, the disinfected E. coli concentration was 126 cfu/100 ml or lower. Figure 4. Color and COD measurements during Phase 1.

Figure 5. UVT and ORP measurements during Phase 1 Figure 6. PAA residual at P1 and E. coli measurements during Phase 1.

While successful PAA dosing can be achieved by a flow-pacing regime at many WWTPs, the time-dependent water quality demand on PAA at the Stiles WWTP observed during Phase 1 of this trial clearly demonstrates the need to implement feed-forward dosing scheme. This will provide proper dosing of PAA needed to achieve the target microbial reduction in a proactive, instead of reactive mode. The feed-forward dose control algorithm is based on Equation 1. PAA dose = PAA set + PAA demand Equation 1 PAA dose is then flow-paced to using a flow signal. The PAA residual at Probe 1 is thus dependent on two factors: the PAA demand associated with oxidation of non-target compounds in the effluent and flow. Flow impacts the apparent PAA demand due to the time-dependent nature of the demand kinetics and PAA auto-decomposition. Additionally, flow impacts the hydraulics of the disinfection channel, resulting in non-ideal flow for some flow regimes. For each water quality parameter, PAA demand is assessed through statistical analysis of PAA residual as a function of the wastewater quality parameter and flow. Based on the statistical analyses, wastewater color (r 2 = 0.70) and COD (r 2 = 0.66) were selected for building dose control algorithms further testing. The UVT of the effluent was too low (< 5- percent) to provide adequate sensitivity for dose control; ORP did not provide a sufficient fit (low r 2 ) to be selected as a parameter for control. Phase 2: Effluent Color for Feed-forward Dose Control During Phase 2, color was used as a feed-forward control parameter for PAA dosing. The first E. coli sample point was moved to a position coincident with PAA Probe 1 because there was only a very small difference between the E. coli concentrations halfway through the contact tank and those at the end of the basin, collected at the effluent weir. PAA demand was determined as a function of wastewater color, based on Phase 1 data. Color was continuously monitored, and PAA demand was calculated from the measured color value. During Phase 2, low and high PAA set values were evaluated and PAA dose was paced using a signal from the flow meter. Data for PAA dose were plotted along with effluent color, and PAA residual at Probe 1, and are provided in Figure 7; during this phase ranged from 590 to 2000 PtCo units. Again, the PAA residuals at P2 and P3 were near the detection limit of the analyzer throughout the phase and are not shown; as a result, the analysis of data for the rest of the study is based on the residuals reported at P1, which are shown in Figure 8 along with E. coli results.

Figure 7. Color and PAA residual measurements during Phase 2. Figure 8. E. coli results and PAA residual measurements at Probe 1 during Phase 2.

It is of note that during Phase 2, the data logger stopped recording from January 8, 2015, 9:10 am to January 9, 2015, 1:00 pm; while the cause of this was not determined, it does not alter the conclusions drawn from Phase 2. Additionally, in Figure 2, an increase in PAA dose is noted on January 12, 2015; this was the planned increase in PAA dose halfway through the study. Results of E. coli testing showed that color was a good feed forward parameter for managing disinfection process control. All E. coli samples were below the maximum daily limit of 487 cfu/100ml and, all but two samples were below the monthly geometric mean limit of 126 cfu/100 ml which would easily meet disinfection compliance requirements. The E. coli data at Probe 1 shows that in most cases, the majority of the disinfection is accomplished in the first few minutes of contact; however, it is necessary to provide additional contact time to achieve disinfection to meet permit requirements. In addition to the online color data collected on the undisinfected effluent, grab samples were also collected at the influent (at the location of the water quality probes) and at the effluent of the contact basin (near Probe 3) for laboratory measurements of apparent and true color. Apparent color is the direct color reading of the sample, while true color represents the results of the filtered sample. Data for these daily grab samples is summarized in Table 2. It is of note that on average, throughout the treatment in Phase 2 of testing, that the PAA reduced the color of the effluent by approximately 100 Platinum-Cobalt (PtCo) units. It was not anticipated that PAA would have a significant impact on effluent color; this is a secondary benefit of PAA for disinfection at the Stiles WWTP. Table 2. Summary of daily apparent and true color data collected from grab samples Date Apparent Color (PtCo units) True (filtered) Color (PtCo units) Untreated flow PAA treated flow Difference Untreated flow PAA treated flow Difference 01/08/15 467 394-73 336 269-67 01/09/15 908 844-64 802 624-178 01/10/15 1264 1124-140 870 696-174 01/11/15 1208 1148-60 824 696-128 01/12/15 960 760-200 508 396-112 01/13/15 1000 872-128 520 460-60 01/14/15 1252 1056-196 770 624-146 01/15/15 850 626-224 354 255-99 01/16/15 572 550-22 1392 1220-172 01/17/15 686 646-40 151 133-18 01/18/15 500 498-2 149 112-37 Average Color Reduction -104-108 Phase 3: Effluent COD for Feed-forward Dose Control Phase 3 was conducted over a ten day period using COD as the feed-forward control in the PAA dosing algorithm. PAA demand was determined as a function of wastewater COD based on Phase 1 data. COD was continuously monitored, and PAA demand was calculated from the measured COD value. During Phase 3, a high and a low PAA set value was tested with PAA dose being paced

using a flow signal. Phase 3 data for PAA dose was plotted along with effluent COD, and PAA residual measured at Probe 1 in Figure 9. Figure 9. COD and PAA residual measurements during Phase 3. In reviewing Phase 3 data, there were two disruptions in data collection. The first occurred from January 22, 2015 at 8:20 am to 6:30 pm when the PLC control became inoperative due to a spurious signal being sent to the control algorithm; this programming issue was corrected. The second disruption occurred during a loss of power to the plant from January 22, 2015 at 9:40 pm to January 23, 2015 at 7:30 am. The loss of plant power caused a fault in the PAA dosing pump, which required a manual restart which did not occur until the morning of January 23rd. Both disruptions caused a loss in monitoring data and a disruption of PAA addition to the disinfection channel, however, this loss of data does not significantly impact the conclusions drawn from Phase 3. Considering process implications from the trial, the design team will include both process and power redundancy in the final design of the system to prevent loss of PAA addition that would result in loss of microbial control. During Phase 3, effluent COD ranged from 128 to 413 mg/l, representing a range of wastewater quality (Figure 9). Figure 10 shows undisinfected E. coli concentrations along with treated samples at PAA Probe 1 and at the effluent weir at the contact tank. In Figure 10, the dashed red line indicates the daily maximum of 487 cfu/100ml and the solid red line is the monthly

geomean of 126 cfu/100ml. When PAA set was set at a high value, E. coli at the effluent weir were below 487 cfu/100ml, but many exceeded the 126 cfu/100ml geometric mean limit. When the PAA set value was decreased, the test demonstrated the point of compliance failure, i.e., where many of the effluent E. coli concentrations were above the maximum daily limit. This testing to failure helps identify the minimum PAA set needed to achieve consistent E. coli control. Figure 10. E. coli results and PAA residual measurements at Probe 1 during Phase 3. Phase 1 demonstrated that color and COD were the best quality parameters for use in the feedforward PAA dose control. Phases 2 and 3 showed that the PAA dose can be adequately controlled using either wastewater color or COD. However, wastewater color was selected as the best water quality parameter for process control based on the following findings: While both the color and COD probes proved to be reliable throughout the field trial, the color probe required less maintenance, approximately 5 10 minutes of cleaning the inline filter per day, resulting in less change in measured color before and after maintenance. The COD probe required 30 45 minutes of cleaning (scrubbing the organic residue from the surface) every fourth day. The sensitivity of the color measurement with respect to PAA dosage was higher than that for the COD measurement ( PAA dose/ water quality parameter), allowing for finer control of PAA dosing with the color parameter.

Phase 4: Adjustment of Algorithm Using Color for Feed-forward Dose Control Based on analysis of the Phase 2 and Phase 3 results, PAA set was programmed to 7 ppm for Phase 4, which was designed to allow for additional minor adjustments to the dosing algorithm to optimize chemical use. During Phase 4, severe weather impacted the delivery of chemicals to the temporary trial system. Thus, a conservation program was initiated part way through Phase 4 to reduce the amount of chemical used when critical data was not being collected. The conservation program consisted of reducing the dosage of PAA into the disinfection contact tank to a flow-paced 2 ppm, during periods when E. coli sampling did not occur (weekends and weekday evening hours). It was shown that this reduction in off-hour PAA usage did not negatively interfere with E. coli control during the weekday sampling periods and did not impact the demonstration of the PAA efficacy. The PAA residual at Probe 1 is plotted along with undisinfected and effluent weir E. coli data collected in Figure 12. Figure 11. Color, PAA dose and PAA residual measurements during Phase 4. Figure 11 shows the PAA dose based on the control algorithm and the measured color values. It is of note that during the latter part of Phase 4, the PAA conservation mode was put into effect and did not impact the monitoring that was used to develop an assessment of the process as shown in Figure 12, which provides the undisinfected and effluent weir E. coli concentrations along with the PAA residuals at Probe 1. The dashed and solid red lines in Figure 12 represent the daily maximum concentration of 487 cfu/100ml and the monthly geometric mean of 126 cfu/ml, respectively.

Figure 12. E. coli results and PAA residual measurements at Probe 1 during Phase 4. In addition to the conservation mode that was implemented during the latter part of Phase 4 (as shown by the PAA residual oscillations in Figure 12), one other operational issue should be noted in interpretation of the data from this phase of work. On the evening of February 19 th and the morning of February 20 th, extremely cold weather caused the sample line to the color analyzer to freeze, resulting in a loss PAA dose control. During that event, the PAA dose was automatically set to the PAA set, which was a constant 7 ppm. This default operating condition did not provide a high enough PAA dose to meet the demand associated with the highly colored effluent, negatively impacting disinfection performance. As shown in Figure 12, the effluent E. coli on the morning of February 20 th exceeded the daily maximum limit. While this would have been a non-compliance event in the final, permitted system, this event also highlighted design considerations that would need to be addressed in the final system design. While there was a single non-compliance event as a result of operational issues, the remaining tests demonstrated excellent results over several cycles of wastewater

quality and flows; effluent color ranged from 450 to 3000 color units and flows varied from below 45 mgd up to 135 mgd. Phase 5: Validation of the Peracetic Acid Dosing System The operational and programming challenges that were identified in the previous phases were reconciled and the final dosing control algorithm was set for Phase 5, which was a demonstration of the ability of the system to meet compliance over a one month period. Validation of the system and verification of a success trial demonstration was defined as meeting the permit limits for E. coli throughout Phase 5 based on daily samples. The PAA set for Phase 5 was 7 ppm; additionally, the PAA conservation program was also continued during Phase 5, and consisted of reducing the dosage of PAA into the disinfection contact tank to a flow-paced 2 ppm, during periods when E. coli sampling did not occur (weekends and evenings). Results of the online monitoring for effluent color, PAA dose and PAA residual at Probe 1 are shown in Figure 13. E. coli were measured at the influent and effluent weir over the course of the thirty day Phase 5 trial with one sampling period per day as shown in Figure 14. Figure 13. Color, PAA dose and PAA residual measurements at Probe 1 during Phase 5. During Phase 5 flow ranged from 75 to 130 MGD which included the highest flow through the plant observed during the six month trial; these high flows represented the shortest contact times observed. Effluent color was generally high throughout Phase 5, ranging from 1000 to 3000 PtCo

units. Based on the set dose of 7 ppm and the demand from the color, the PAA dose concentration ranged from approximately 12 to 16 ppm during this phase. During Phase 5, some of the highest undisinfected E. coli concentrations in the trial were observed, with concentrations exceeding 1.2 million cfu/100ml. In all samples, the effluent weir E. coli concentrations were below the daily maximum of 487 cfu/100ml, with only one sample exceeding the monthly geometric mean of 126 cfu/100 ml at a concentration of 204 cfu/100ml, on March 19 th. The geometric mean of the E. coli data collected during the thirty-day period was 4 cfu/100 ml, this included non-detect values to be calculated as 0.9 cfu/100 ml. Additionally, the PAA dose algorithm was able to provide excellent treatment performance at very high color and high undisinfected E. coli concentrations. Figure 13. Color, PAA dose and PAA residual measurements at Probe 1 during Phase 5. CONCLUSIONS The six-month full scale trial successfully demonstrated the ability to use a dose pacing plus feed forward algorithm to provide continuous disinfection at the Stiles WWTP. This process control strategy allows the City of Memphis to address the bacteria limits in their NPDES permit while minimizing the chemical costs associated with implementing PAA disinfection. Disinfection performance was demonstrated over a broad range of water quality and flows; thus, in addition to

achieving a monthly geometric mean E. coli concentration of less than the NPDES permit limit of 126 cfu/100ml, the system was demonstrated under conditions of high wastewater color (high PAA demand), high wastewater flow rate (short contact time) and high influent E. coli concentrations. The trial also allowed demonstration of the functionality and stability of water quality monitoring and PAA residual probes, when proper maintenance is conducted. Finally, the full-scale trial allowed engineers to gain insight into important factors for final design of the permanent, full-scale PAA disinfection system. This permanent system will be designed to meet a peak hour flow of up to 250 MGD will be the largest full-scale PAA disinfection system in the US. REFERENCES 1. B. Keogh and M. Tran (2011). Old City, New Ideas: Peracetic Acid in Wastewater Disinfection at St. Augustine. Florida Water Resources Journal, April issue. 2. Bell, K.Y. and Archer, T.A. (2013a). Design and Operation Considerations for PAA Disinfection Systems. WEF Disinfection Conference, Indianapolis, IN, invited speaker. 3. Bell, K.Y., and Archer, T. (2013b). PAA An Alternative for Wastewater Disinfection: Engineering and Cost Considerations. WEF Technology and Exhibition Conference, Chicago, IL. 4. S. Rossi, M. Antonelli, V. Mezzanotte and C. Nurrizo (2007). Peracetic Acid Disinfection: An Alternative to Wastewater Chlorination. Water Env Res, 79, p 341 350. 5. K. Bell, S. Stewart, S. Morgan, J. Goldman. PAA as a Disinfection Alternative for Challenging Municipal Effluent: MC Stiles WWTP, Memphis, TN. WEFTEC 2014, New Orleans. 6. PeroxyChem s VigorOx WWT II peracetic acid (15% peracetic acid / 23% hydrogen peroxide formulation). The VigorOx WWT II peracetic acid SDS can be found at www.peroxychem.com.