Modelling of Indirect Evaporative Air Coolers

Similar documents
A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS. Aaron Powers Johnson Controls, Inc.

Thermal and Exergy Analysis of Counter Flow Induced Draught Cooling Tower

QATAR UNIVERSITY. Graduate Studies. College of Engineering INVESTIGATION OF A REGENERATIVE INDIRECT EVAPORATIVE COOLING SYSTEM.

Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S. Patel 1 Hardik M.Patel 2

PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER

Development and Performance Evaluation of Indirect-Direct Evaporative Cooling System

CFD Modelling and Analysis of Different Plate Heat Exchangers

COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS

Sustaining thermal power plant production in low water supply regions using cooling towers

Energy Conversion and Management

INVESTIGATION OF THE THERMAL PERFORMANCE OF A CROSS-FLOW WATER COOLING TOWER WITH DIFFERENT PACKINGS

Performance Improvement of Mechanical Induced Draft Cooling Tower by Using Aluminum as Fill Medium

Energy and Buildings

Theoretical and computational analysis of closed wet cooling towers and its applications in cooling of buildings

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

Study on the heat transfer characteristics of an evaporative cooling tower B

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

Application of a cooling tower model for optimizing energy use

Performance Analysis of Cooling Tower

MODELLING AND SIMULATION OF A TYPICAL CROSS FLOW COOLING TOWER

Performance of a counterflow heat exchanger with heat loss through the wall at the cold end

INVESTIGATION ON THE OPTIMUM DESIGN OF HEAT EXCHANGERS IN A HYBRID CLOSED CIRCUIT COOLING TOWER

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Fresh air pre-cooling and energy recovery by using indirect evaporative cooling in hot and humid region a case study in Hong Kong

Critical exergy analysis of counterflow reversibly used cooling towers

Cooling Tower Operation

Modeling Techniques for Increased Accuracy

Sensitivity Studies of a Low Temperature Low Approach Direct Cooling Tower for Building Radiant Cooling Systems

Heat Rejection using Cooling Towers

Potential of passive design strategies using the free-running temperature

Heat Transfer Correlations for Low Approach Evaporative Cooling Systems in Buildings

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis

Heat and Mass Transfer in Convective Drying Processes

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS

The formation of oscillation marks in continuous casting of steel

M. Karagiorgas, M. Tsagouris, K. Galatis BONAIR Meletitiki, Greece. A. Botzios-Valaskakis CRES, Greece ABSTRACT

Performance Improvement on Water-cooled Cold-Plate

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET

Process intergration: Cooling water systems design

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

Modern CFD application on aerothermal engineering aspects of natural draft cooling towers

A cooling tower combined with chilled ceiling: system optimisation

Coupling Model and Solving Approach for Performance Evaluation of Natural Draft Counter-Flow Wet Cooling Towers

2. TECHNICAL DESCRIPTION OF THE PROJECT

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

1. To improve heat exchange between a gas & a liquid stream in a heat exchanger, it is decided to use fins. Correct the suitable option.

Thermal insulation of buildings and cooling demand

07059, Antalya / TURKEY ABSTRACT

Keywords: CFD; Cooling tower; Evaporative cooling; NTU; Spray water

Review on Numerical Simulation of frosting behavior on Ambient air vaporizer

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

Compound ejectors with improved off-design performance

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Solar Distillation System Based on Multiple-Effect Diffusion Type Still

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

An Investigation in Performance Enhancement of Induced Draft Counter Flow Wet Cooling Tower

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max.

COOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED CHILLER

MODELING AND EXPERIMENTAL VALIDATION IN PARTIALLY WET CONDITIONS OF AN AIR-TO-AIR HEAT RECOVERY EXCHANGER

Design Features of Combined Cycle Systems

PARAMETRIC STUDY OF GAS TURBINE CYCLE COUPLED WITH VAPOR COMPRESSION REFRIGERATION CYCLE FOR INTAKE AIR COOLING

Performance Evaluation of an Integrated Hybrid Photovoltaic/Thermal (PV/T) Greenhouse

Steam compression with inner evaporative spray cooling: a case study

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

Heat Exchangers. Introduction. Classification of heat Exchangers

Creating a New Model to Predict Cooling Tower Performance and Determining Energy Saving Opportunities through Economizer Operation

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels


Liquid-Solid Phase Change Modeling Using Fluent. Anirudh and Joseph Lam 2002 Fluent Users Group Meeting

Energy towers A renewable energy technology for producing electricity and desalinated water in arid climates

Adsorption Air Conditioner for Electric Vehicle Applications

COUPLED FEM MODEL FOR CONCRETE EXPOSED TO FIRE LOADING

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014)

Contents. Part I Design: Theory and Practice 1

Experimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in Buildings

The 3-D Numerical Simulation of a Walking Beam Type Slab Heating Furnace with Regenerative Burners

INDUSTRIAL COOLING TOWER DESIGN AND OPERATION IN THE MODERATE-CONTINENTAL CLIMATE CONDITIONS

THERMAL ANALYSIS OF WELDING IN T-JOINT PLATES USING FINITE ELEMENT ANALYSIS

on a Run-Around Membrane Energy Exchanger Saskatoon

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

Heat Transfer Correlations for Low Approach Evaporative Cooling Systems in Buildings

Parameters of the Atmospheric Air in the Dimensioning of Industrial Cooling Tower

II. SYSTEM DESCRIPTION AND MATHEMATICAL MODELING

Wastewater Pretreatment by Normal Freezing Cool Thermal Storage Process with Convective Heat Transfer Mechanism

Modelling and Simulation of Thermodynamic Processes of Vertical Shaft Kiln in Magnesia Plant Using CFD Code Fluent

Improving the Energy Performance of HVAC Systems in Operating Theatres by Using Heat Recovery Devices

Introduction. Objective

The Effect of High Temperature Feedwater on the Performance of an Evaporative Cooler Installed in a Gas Turbine Combustion Air Inlet System

The Performance of Compression-absorption Heat Pump System Using Low-temperature Geothermal Tail Water

A STEADY STATE MODEL FOR THE HEAT PIPE-ENCAPSULATED NUCLEAR HEAT SOURCE

Two-Phase Distribution of R-134a in a Header of a Parallel Flow Heat Exchanger

THE ITER HEAT REJECTION CHALLENGE.

Study of a high efficiency residential split water-cooled air conditioner

Effect of Drying Condition on Natural Block Rubber: Simulation and Experiments

LAHU Heat Recovery System Optimal Operation and Control Schedules

Transcription:

416 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and Modelling of Indirect Evaporative Air Coolers Gh. Heidarinejad Building and Housing Research Centre (BHRC), Iran M. Bozorgmehr University of Tarbiat Modares, Iran ABSTRACT In this paper, indirect evaporative cooling in an air cooler has been modeled. This model has been obtained from the governing equations of heat and mass transfer in primary and secondary air and water flows. Factors affecting on evaporative cooling performance such as mass flow rates, geometry and flow configuration has been investigated. Results show that cooling efficiency considerably depends on mass flow rates ratios of primary and secondary air flows and spacing between plates of wet and dry passages. The performance of this cooling system for typical conditions of some Iranian cities has been investigated. Using a first stage indirect evaporative cooling prior to conventional direct evaporative cooling systems in most regions of Iran will provide cooling comfort conditions as a low energy consumer alternative. 1. INTRODUCTION Evaporative air conditioning is an environmentally friendly and energy efficient method for cooling buildings. Two main different methods are used, the direct and the indirect one. In the direct method air passes through a wetted media in an adiabatic saturation process. In the indirect method, two distinct air flows pass through a wet surface heat exchanger, primary flow in the dry channels and secondary flow in the wet channels. In this case without adding water to the primary air, it is cooled and secondary air carries away the heat energy from it as water evaporates in wet channels, so the indirect stage sensibly cools the primary air. Secondary air could be supplied from outdoor or room exhaust which is so-called recovery. Also it may be extracted from primary air outlet which is referred to regenerative and in this case secondary air passes two times through the heat exchanger. Heat and mass transfer occur simultaneously in an indirect evaporative heat exchanger. Maclaine-cross and Banks (1983) analyzed the evaporative heat transfer in an indirect cooler. They suggested a simplified analysis model assuming that water film is stationary and continuously replenished with water at the same temperature and saturation line is a linear func- tion of temperature. The resulting decoupled equations describing the wet and the dry passages of the cooler were solved by defining a new independent variable: wet bulb depression which is the difference between dry bulb and wet bulb temperatures. This model could be used to predict the cooler performance by analogy to dry surface heat exchangers. Hsu et al. (1989) investigated three basic types of wet surface heat exchangers. They found that cooling effectiveness of each configuration increases with increasing dry channel NTU (Number of Transfer Units) and reaches maximum values asymptotically at some large values of NTU. They assumed that the non-circulating water is locally replenished and its local temperature was calculated from the mass and energy balance equations. They took into account the effect of longitudinal plate conduction. Their results showed that it has almost no effect on the cocurrent and counter-current configurations and its degrading effect on efficiency of cross flow is accelerated when the dry-passage length to that of the wet passage is large. Pescod (1979) proposed a simple design method for indirect evaporative cooler using parallel plastic plates with small protrusions. Although the thermal conductivity of plastic is very low, the heat transfer resistance across a thin plastic plate would be less than of the thermal resistance between the air and plate in dry side. Predictions of the efficiencies of Pescod s wet surface plate heat exchanger were found to be higher than the experimental data. Thus incomplete wetting of plate surfaces was suspected. Kettleborough and Hsieh (1983) described a counterflow indirect evaporative cooler with configuration of upward flow of the primary air and downward flows of secondary air and water. Numerical analysis was utilized to study the thermal performance of the unit. By applying wetting factor better agreement between calculated and measured performance data qualitatively was achieved. Erens and Dreyer (1993) reviewed three different models describing evaporative indirect cooler: (1) Poppe modelconsidering a variable Lewis factor, spray water evaporation rate and modeling over saturation in the secondary air; (2) Merkel model- can be derived from Poppe model by assuming a Lewis factor of unity and negligible effect of spray water evaporation and assuming that the sec- PALENC 2007 - Vol 1.indd 416 3/9/2007 1:25:07 µµ

2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and 417 ondary air never becomes over saturated; (3) Simplified model- assuming that the water temperature is constant through out the cooler. They applied these models to a cross flow indirect cooler and simplified model was recommended for small units and for initial design purpose. Chengqin and Hongxing (2006) developed an analytical model for the indirect evaporative cooling with parallel/ counter flow configurations. Similar to any other analytical model, humidity ratio of air in equilibrium with water surface was assumed to be a linear function of the surface temperature. Effects of spray water evaporation, spray water temperature variation along the heat exchanger, non unity surface wetability and Lewis factor were considered in the model. Results of analytical solutions were found to be in good agreement with those of numerical integrations. Review of the previous researches show that there are two main approaches to model indirect evaporative cooler: 1-Numerical integration; 2-Analytical model. Analytical models are limited to co-current and counter-current configurations with some simplifications and linear assumption for the saturation curve. In this paper using a numerical integration approach, three different configurations i.e. parallel, counter and cross flow are analyzed to determine the configuration that optimizes the performance. As can be seen from Figure 1 each repeated section of the cooler consists of a half of dry channel, plate wall and a half of wet channel. Figure 2 shows this section and a differential element. 2. MODELLING 2.1 Physical description of indirect cooler Indirect evaporative cooler consists of a series of parallel plates in which one is open for primary air flow and the other one is open for water and secondary air flows. Circulation water is sprayed onto the top of the heat exchanger and flows downward along wall surfaces of wet channels. Primary air flows in the alternative channels. A typical indirect cooler with counter flow configuration can be shown schematically in Figure 1. Figure 2: (a) Model section and its adjacent section, (b) Differential element. Sp: Dry channel spacing, Sa: Wet channel spacing. The following assumptions here are considered: There is no diffusion in the flow direction; Cooler is insulated from the surrounding; Specific heats are constant; Heat and mass transfer coefficients are constant and Lewis factor is unity; Plate wall, bulk water and air/water interface have the same temperature; Spray water is circulated. 2.2 Governing equations of heat and mass transfer For a differential element as shown in Figure 2b, by applying principles of mass and energy conservation, a set of differential equations can be obtained as follows. 2.2.1 Energy balance Energy balance equation for the primary air Figure 1: Typical indirect evaporative cooler with counter flow configuration. (1) PALENC 2007 - Vol 1.indd 417 3/9/2007 1:25:07 µµ

418 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and q: Rate of heat transfer (W) : Mass flow rate (kg/ s) c p : Specific heat at constant pressure (J/kg K) t: Temperature (ºC) : Overall heat transfer coefficient (W/m 2 K) A: Area (m 2 ) Subscripts p and w stand for primary air and spray water respectively. Energy balance equation for the secondary air (2) i: Enthalpy of moist air (J/kg dry air) K: Mass transfer coefficient (kg/m 2 s) Subscripts asw and a stand for saturated air at water temperature and secondary air, respectively. This equation is a result of the assumption of Lewis number being unity (Hassan, 2005). Another approach considers the effect of variable Lewis number. Erens and Dreyer (1993) implemented the two methods on a cross flow wet liquid cooler. Their calculation showed insignificant differences between the results by these two methods. Energy balance equation for the three streams flowing inside the element With the assumption of constant water flow rate, energy balance equation for the streams flowing inside the element shown in Figure 2b is: Equation (4) sets the condition for inlet and outlet water temperature and this temperature has to be found iteratively. Equation (5) can be solved separately after once solution of the set of equations (1)-(3) has been found, because water temperature is necessary to solve this equation. The solution procedure depends on the configuration of the cooler. Three main configurations could be considered which are parallel, counter and cross flow. These configurations are shown schematically in Figure 3. The main purpose of this paper is to study the cooling performance of these configurations. For parallel flow the integration starts from the top with known conditions of primary and secondary air flows and a guessed inlet water temperature. Integration for each element proceeds from top to the bottom. At the bottom obtained value for the outlet water temperature is compared with guessed inlet value and is corrected until both inlet and outlet water temperatures would be the same. For the counter flow, because of scattered inlet conditions at the top and bottom of the heat exchanger, another iteration to find the outlet enthalpy of secondary air is added. Each time at the bottom, calculated enthalpy at the inlet and inlet enthalpy of the secondary air are compared until they would be equal. For cross flow configuration, because primary air and secondary air flow in perpendicular direction, the heat exchanger is divided into a series of two-dimensional elements. Integration starts from the upmost element in the inlet of primary air and proceeds downward. (3) Spray water temperature varies inside the heat exchanger. Because of water circulation, the inlet spray water temperature will equal the outlet spray water temperature. (4) 2.2.2 Mass balance The mass balance for the element gives the rate of spray water evaporation (kg/s) (5) w: Humidity ratio of air (kg water/ kg dry air) Equations (1)-(5) govern heat and mass transfer in an indirect evaporative cooler. 2.3 Numerical integration procedure Equations (1)-(3) form a set of coupled ordinary differential equations which can be solved simultaneously, using a multi step numerical integration procedure. Figure 3: Three flow configurations, (a) parallel, (b) counter, (c) cross. P: primary air, W: spray water, S: Secondary air. Inlet, Outlet 3. RESULTS AND DISCUSSION Results for typical temperature profiles in various configurations of indirect cooler have been shown in Figure 4. The size of cooler is assumed 1 1 1 m 3. For the sake of comparison between different configurations, values for mass transfer coefficient and overall heat transfer coefficient has been considered equal. Outdoor air tem- PALENC 2007 - Vol 1.indd 418 3/9/2007 1:25:07 µµ

2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and 419 perature is assumed 25ºC and has a relative humidity of 50%. Results show that counter configuration has the highest cooling efficiency. In cross configuration, averaged temperature of primary air in outlet is close to that in counter configuration. Figure 6: Effect of ratio of primary to secondary air mass flow rate on temperature for cross configuration. (mass flow rate of secondary air, ms=2.0 kg/s) Figure 4: Profiles of primary air temperature in various configurations along the flow direction. In some simplified methods, water temperature is considered constant throughout the cooler because of its circulation. Figure 5 shows the water temperature profiles along the water flow direction for various configurations. As it can be seen only for parallel flow it is expected to be constant and for counter and cross configuration it somehow varies in opposite manner. It should be noted that temperatures for cross configuration are averaged in each section because they shape a two dimensional distribution. Ratio of mass flow rates of primary and secondary air is a design parameter and its effect on cooling performance just for cross configuration is illustrated in Figure 6. Figure 5: Profiles of water temperature in various configurations along the flow direction. It can be seen from Figure 6, higher cooling efficiency is obtained as mass flow rate ratio decreases. For evaporative air conditioning, cooling capacity is defined which is determined from supply air temperature and mass flow rate. However lower primary air temperature is obtainable as mass flow rate ratio is decreased, but an optimum value for this ratio can be found from viewpoint of cooling capacity. Minimum spacing between channels should be considered while minimizing the total pressure drop (dry and wet passages). Figure 7 shows the effect of channel width on primary air temperature. In a fixed cooler volume, decreasing spacing between plates means increasing number of channels and therefore more area for heat and mass transfer. The efficiency of an evaporative cooler is defined as follows: (6) : Dry bulb temperature of primary air inlet : Dry bulb temperature of primary air outlet : Wet bulb temperature of secondary air inlet From Figure 4 it can be seen that for cross configuration a cooling efficiency of 80% is predicted which agrees with expected values for modern plate type indirect evaporative cooler (Watt, 1997). Pescod (1979) measured temperature cooling efficiency between 69 and 82 percent, while Maclaine-cross (1983) calculated 78 to 98 percent as possible in a theoretical model based upon cross-flow cooling tower theory. Excess water flow down the wet passages seemed to be the reason of difference between measured and calculated efficiencies, because mathematical model assumed stationary water layer which for finite water mass flow rate is not true. In the present work water is not stationary and it is PALENC 2007 - Vol 1.indd 419 3/9/2007 1:25:08 µµ

420 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and circulated. For perfect surface wetting, circulation water mass flow should be several times of that evaporate. However excess water flow deteriorates cooling efficiency and should be kept as minimum as possible. 5. CONCLUSIONS Main results of modelling indirect cooler for three main configurations are as follows. Counter configuration has the highest cooling efficiency. Increasing ratio of primary to secondary air mass flow and heat exchanger plates spacing decreases cooling efficiency. Using a pre cooling indirect stage prior to a direct stage provides comfort conditions in major cities of Iran as a clean and energy efficient alternative for conventional systems. REFERENCES Figure 7: Effect of channel width on primary air temperature profile for cross configuration. 4. COMFORT PERFORMANCE Iran has a wide variety of climatic conditions. In most hot and dry regions direct evaporative cooler is a common cooling system providing comfort for residential buildings. In regions or conditions with high wet-bulb temperature that the direct systems do not provide comfort conditions, vapour-compression cooling systems are used. If a first indirect stage is added to a second direct stage, a two stage indirect/direct cooler is obtained which could provide comfort conditions for a number of cities. Commonly 65% indirect stage efficiency (performance factor) and 85% direct stage efficiency is reached. Table 1 illustrates 2.5% design conditions in four major cities of Iran. Chengqin, R., Hongxing, Y. (2006). An analytical model for the heat and mass transfer processes in indirect evaporative cooling with parallel/counter flow configurations. Heat Mass Transfer 49 617-627. Erens, P. J., Dreyer, A. A. (1993). Modeling of indirect evaporative air cooler. Heat Mass Transfer 36 17-26. Hasan, A. A. (2005). Performance analysis of heat transfer processes from wet and dry surfaces: cooling towers and heat exchangers. Doctoral dissertation. Helsinki University of technology. Hsu, S. T., Lavan, Z., Worek, W.M. (1989). Optimization of wet surface heat exchangers. Energy 14 757-770. Kettleborough, C. F., Hsieh, C. S. (1983). The thermal performance of the wet surface plastic plate heat exchanger used as an indirect evaporative cooler. ASME J. Heat Transfer 105 366-373. Maclaine-cross, I. L., Banks, P. J. (1983). A general theory of wet surface heat exchangers and its application to regenerative cooling. ASME J. Heat Transfer 103 579-585. Pescod, D. (1979). A heat exchanger for energy saving in an air conditioning plant. Trans. ASHRAE 85 238-251. Watt, J. R., Brown, W. K. (1997). Evaporative air conditioning handbook. Lilburn: Fairmont Press. Figure 8: shows that room air comfort condition is achieved with indirect/direct cooling systems for major cities of Iran. For each city the process consists of indirect stage cooling, direct stage cooling and room air conditioning. PALENC 2007 - Vol 1.indd 420 3/9/2007 1:25:08 µµ