Prevention of Condensation on Conduits that Penetrate Insulated Metal Panel

Similar documents
Quality NBR Insulation

White Paper. By Jeffrey T. Kochelek and Adam H. Hilton V.1.0.0

TECH SOLUTIONS THERMAX Insulation in Low Humidity Metal Buildings

Insulation Terms, Definitions & Formula

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

Available online at ScienceDirect. Procedia Engineering 146 (2016 ) 60 68

Purdue e-pubs. Purdue University. Weiwei Zhu Oklahoma State University, United States of America,

CUSH-A-THERM VAPOR BARRIER PROTECTION

Insulation in Low Profile Cross Ventilated Freestall Facilities TAKE HOME MESSAGES

Technoform North America. Stainless and its use in Window Spacer Technology

SECTION HVAC INSULATION

Insulating Basements: Part 1 Fundamentals

Insulating Attics & Crawlspaces. Roger Morrison, PE, RRC NCFI Polyurethanes

Fire Barrier 3000 WT Intumescent Silicone Sealant

UBC Technical Guidelines Section Edition Thermal Insulation for Piping Page 1 of 5

HVAC INSULATION. A. General Requirements for Flexible Elastomeric Insulation: 3. Use pre-molded roll on pipe sizes 3.5" and below.

Water Quality Specification for Power Supplies

FireX Fire Stopping Mastic FM

079 Quick Installation Guide

FIRESTOP AND FIRE PROTECTION

Pipe Protection Tape System

STATE UNIVERPROGRAM DIRECTIVES

1.52mm 1.52mm. Exterior Siding Sheet: Fabricated from Z275 steel material conforming to ASTM A653M grade 230 steel

Study on Waterproof and Air Permeability of Inorganic Insulated Decorative Panel

Controlling Moisture.

TECH SOLUTIONS A Prescriptive Solution to Meet Air Barrier Energy Code Requirements in Metal Buildings

10 Steps to Save Energy in Your House

GENERAL GUIDELINE SikaMembran System / VERSION 1 / SIKA SERVICES AG

PERMATHERM PIPE INSULATION PRODUCTS

AIR HANDLING UNITS. Beyond Compare

Thermal Insulation of Buildings

A. Section Fire Procection, HVAC & Plumbing Penetration Firestopping. B. Section Interior Painting: Painting insulation jacket.

PRODUCT CATALOGUE PROFLEXR. Thermal Insulation. CFC free HCFC free Zero Ozone Depletion Potential (ODP) Taking care of energy and Environment

Condensation - Prevention and Control

SECTION DUCT INSULATION

SIGMA GLASS PACK The Sigma glass pack combines a warm-edge Super G glass spacer system with two panes of glass to achieve an R-value of 1.89.

INSTALL FIRE PROTECTION

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

INSTALLATION GUIDELINES for ISO-C1 POLYISOCYANURATE MECHANICAL INSULATION for CHILLED WATER SYSTEMS

GypLyner. GypLyner. Metal framed wall lining system. All our systems are covered by SpecSure when using genuine Gyproc and Isover products.

Smart Vapor Retarders

CAJ. Combos. C-AJ of 5. Through Penetrations Series. Concrete. 3Fire Protection Products

UBC Technical Guidelines Section Edition Insulation of Tanks, Steam and Condensate Piping Page 1 of 6

PROPERTIES OF MATERIALS PART HARDNESS

Polyolefin foams provide attractive solutions for thermal insulation of pipes in buildings

A. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials

This article will address the test methods used to determine R-values and their relative degree of accuracy.

Mechanical Insulation for Refrigeration Systems

ARMAFLEX SHEET AL / KY / AL-KY

Solution Provider. Implementing Innovative Ideas. Success Stories of Benchmarking & Proposals

Floors Walls Roofs. Jablite Premium board Jablite board. APPLICATION: Internally Lined Pitched Roof PRODUCTS: Vencel Resil Limited

New Opportunities For Spray Polyurethane Foam

Advanced technologies for enhancing the building envelope. 3M Building and Construction Market

D. Provide UL-approved assemblies for pipes and ducts passing through fire-rated floors, walls, or partitions as required.

TECHNICAL BULLETIN 0214 (update of 0111) PERFORMANCE/COST COMPARISON OF POLYISO vs. XPS PIPE INSULATION SYSTEMS

Insulated Composite Panels Designed for Brick Back-up

TECH NOTES INSULATING SOLUTIONS: THERMAX TILT WALL FIT OUT. THOMCO, Inc

Operable / Fixed Skylight Milgard Aluminum Window

Firebreak 66 Intumescent Pressure Sealant

A. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials

In alliance with. Green AppeAl

guarantee successful solutions. of which 7000 are covered, today Framec Truck is a through a wide range of highly sophisticated

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

Best Practice On Insulation Of Process Installations

Design & Construction Standards, Revised January

Fixed Skylight / Fixed Multiple Skylight Milgard Aluminum Window

THE PROFESSIONAL HIGH PERFORMANCE INSULATION FOR LONG TERM ENERGY SAVING TRUSTED SINCE 40 YEARS

Light-Metal Roof Edge, Raised

PERMATHERM, INC. SPECIFICATION FOR COLD/CRYO PIPE INSULATION

PERMATHERM, INC. SPECIFICATION FOR COLD/CRYO PIPE INSULATION

SMART SOLUTIONS DOUBLE GLAZING SOLAR COMFORT TINTING GLASS ASK OUR SALES REPRESENTATIVES ABOUT. Reduce your 23% energy costs * by as much as

Cable Terminators COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS. Applications

Insulation manufacturer to submit dew point analysis free of charge for typical wall section. Analysis by:

Insight. Stress Relief. By Joseph W. Lstiburek, Ph.D., P.Eng., Fellow ASHRAE

NIA s 62nd Annual Convention Sheraton Grand at Wild Horse Pass March 29 April 1, Barry Schmitt of Value Engineered Products

PERMATHERM, INC. SPECIFICATION FOR CHILLED WATER PIPE INSULATION

When I started tiling, we didn t do our own shower pans that BATHS

TECH SOLUTIONS Hot Box Testing of Four Different Metal Building Roof Assemblies Determines Insulation Efficiency

3-Dimensional Thermal Analysis of Lenmak EnvaTherm and SpandrelTherm Backpan Assemblies

PLASTICS. Chapter 5. Materials of Construction-Plastics 1

RTV123. Technical Data Sheet RTV123

Rev. 08 9/15 Please Read Disclaimers:

Review of 2012 IECC & IRC for Attic Accesses

RTV128. Technical Data Sheet

CPD Seminar Handout: Roof Refurbishment: Choosing the Best Solution

NEW! THE FLEXIBLE PROFESSIONAL INSULATION WITH REVOLUTIONARY CHARACTERISTICS. even easier to use

ITW INSULATION SYSTEMS

Module 3 Slabbing, Skimming, Dry Lining and Floors UNIT: 2 Skimming to Plasterboard

THE PERFECT WALL IN COLD CLIMATES:

ITW INSULATION SYSTEMS

Multijacketed Tubing, Single-Jacketed Tubing, and Insulated Tubing

Assembly Instruction. wedi Fundo Primo Steam Shower System

cost trends insights on construction costs

Emperor Penguins and Efficient Buildings. Resisting frigid temps with thermal breaks.

PAROC FIRE PROTECTION SOLUTIONS FOR PIPE PENETRATIONS

Commercial Flashing Details

Thermal Bridging Solutions. Improving Building Envelope Performance

379 Quick Installation Guide

Product range ROMA INSULATION SYSTEMS. Everything you need to know about ROMA and our products in one document.

Crawl Spaces and Basements: Defining the Building Envelope

Transcription:

Scott T. McGlamery, P.E.; Bret T. Heckman, P.E. Department of Electrical Engineering, Hixson, Cincinnati, OH Abstract - Condensation is a concern in every food plant, because it can provide a breeding ground and serve as a vehicle for microbes. A particularly challenging application for condensation control are penetrations of insulated metal panels between warm and cold spaces. Hixson has conducted research to determine the most effective way to control condensation on conduits in this situation. I. Introduction Conduit penetrations through walls or ceilings of a food production facility are inevitable. When a conduit spans two rooms with a significant temperature difference, condensation can form on the inside and outside of a conduit. This unwanted water could provide a niche for microbial harborage. Condensation is usually a concern in any room conditioned below 40 F. For example, there is a walkable ceiling directly above a food processing room. The food processing room will be cooled to approximately 38 F, while the walkable ceiling could be exposed to ambient conditions. On a warm summer day, the walkable ceiling could reach temperatures above 80 F with high humidity. The only separation between these spaces would be a 4 insulated metal panel. A conduit between these spaces would be warm on one side and cold on the other. (See Figure 1.) Condensation occurs when the surface temperature of an object is below the dew point of the surrounding atmosphere. If the conduit spanning both spaces is not properly addressed, the temperature on the warm side can be less than the dew point. Much like a cold beverage sitting outside on a summer day, water will bead up on the surface and drip down the inside and outside of the conduit. Collection of this water can create a breeding ground for microbes. Hixson has made observations in the field regarding the condensation build up in and on conduits that run from a conditioned space to an unconditioned space. These situations happen most commonly when there is a temperature difference between spaces of at least 30 F. Figure 1: Heat transfer on a conduit through an insulated metal panel. Design, selection, and installation of conduit penetrations can help significantly reduce or eliminate the amount of condensation that occurs in a facility. II. Test Setup and Procedure An apparatus was constructed to simulate a cold environment separated from a hot environment. To segregate the spaces, 4 insulated metal panel was used and different conduit types were used to span the areas. To create the cold environment, a plastic bin was filled with a water/ice bath mixture. When covered with the 4 insulated metal panel, it created a space temperature around 35 F. Testing was conducted in an open area in August with temperatures ranging from 86 F to 93 F. Two pieces of insulated metal panel were penetrated with five conduits. The penetration was then sealed with silicone caulk. Conduits used for the experiment were 10 long and each made of a different material. These materials were stainless steel, Schedule 80 PVC, rigid steel, aluminum, and PVC coated rigid steel.

Thermistors were then installed at incremental locations on each conduit. Below the insulated panel the thermistors were located at 8 below the bottom of the panel. Thermistors were also located above the panel up to 40. Figure 2: Conduits from left to right SST, Schedule 80 PVC, aluminum, rigid steel, and PVC coated rigid steel Once the thermistors were installed, closed cell rubber foam pipe insulation was fitted around each conduit. Several tests were conducted using ½ thick insulation and ¾ thick insulation at lengths of 12, 24 and 36 and with no insulation. The goal was to test each conduit under the same conditions to measure the heat transfer through the conduit by the use of thermistors and observations. Figure 3: 3/4 Insulation installed 36 above the insulated metal panel. III. Analysis The resistances of the thermistors were measured, documented and converted to temperature. For the experiment involving 36 of insulation, 29 thermistors were used over a 48 span of the conduit. Five of the thermistors were located below the insulated metal panel and the remaining 24 were located above. When readings were taken when no insulation was present, the thermal conductive properties of each material type became apparent. For clarity of results, the heat transfer of two uninsulated conduits can be found in Graph 1.

Graph 1: Heat Transfer on SST and Aluminum conduits. Distance zero represents the top of the insulated metal panel. The ambient temperature below the insulated metal panel inside the bucket is approximately 35 F. The ambient temperature above the insulated metal panel is approx. 93 F. Aluminum is ~15 F lower than stainless steel as it exits the insulated metal panel. Because the aluminum conduit has a lower temperature, it is more likely to be closer to the dew point of the space. This condition frequently leads to condensation on a conduit. (Graph 1 shows that aluminum is greatly impacted by the environment it is in and proves that the higher the thermal conductivity, the more influenced a conduit will be by the temperature of the environment.) See Table 1 for examples of materials and their thermal conductivity. Thermal Conductivity Material (W/m*K) Polystyrene (metal panel insulation) 0.03 Schedule 80 PVC 0.19 SST 16.3 PVC Coated Steel N/A Steel 50 Aluminum 247 Copper 398 Table 1: Thermal Conductivity of Materials Graph 2 represents temperature readings for each the different insulation configurations. The temperature points shown are from the thermistor located at point 0 or the top of the insulated metal panel. Graph 3 indicates that temperatures of conduits gradually rise as they reach the end of the insulation.

Graph 2: Temperature readings immediately above the insulated metal panel penetration. The length of the insulation is shown as 12, 24 or 36 and the thickness is 1/2", or 3/4". For no insulation, readings were taken as the conduits penetrated the insulated metal panel. Graph 3: Temperature readings immediately above the insulation. For no insulation, readings were taken as the conduits penetrated the insulated metal panel.

Graph 4: Temperature readings above the insulation for all 5 conduits with 36 long 3/4" thick and 12 long 1/2" thick insulation. For no insulation, readings were taken as the conduits penetrated the insulated metal panel. When reviewing the extremes of insulation coverage, a noticeable difference emerges. The temperature of the conduits covered with 36 of 3/4" insulation keeps the temperature of the conduits lower as they penetrate the insulated metal panel and reach the end of the insulation, whereas the 12 of 1/2" insulation allows the temperature of the conduits to rise closer to ambient conditions above the panel. Graph 4 proves that insulating the conduit too well will actually increase the chances of condensation forming. By using shorter, thinner insulation the heat from the warm side of the space is able to travel farther down the conduit. This allows the conduit to become warmer in a shorter distance. In the cases where there was insulation, no condensation was observed on any of the conduits above the insulation. During the no insulation test, condensation was observed on the aluminum conduit as it penetrated the insulated metal panel. IV. Conclusions Select materials with the lowest thermal conductivity possible that still meet corporate/facility standards for the environment they are located. Conduits with the lowest thermal conductivity provided a warmer conduit once it passed through the insulated metal panel from the cold side to the hot side. Using 1/2" insulation, insulate the first 12 of the conduit starting from the face of the insulated metal panel on the warm side of the penetration. This allows the temperature of the conduit to rise above the dew point while inside of the insulation. After 12, the conduit will be closer to the space temperature which lowers the probability of condensation forming. To prevent condensation from forming on the inside of the conduit, a vapor barrier should be put in place. In this case, an expanding polyurethane foam sealant provides the best vapor seal.

Figure 4: Conduit penetration detail to reduce the chance of condensation in a warm environment. Hixson White Paper: Conduit Seal Effectiveness References National Electric Code, 2014. National Fire Protection Agency, Inc. Quincy, MA, 2013. Hixson is pleased to present this and other white papers on issues important to the clients we serve. We focus on discovering the most effective solutions for a given situation, without bias. We do not sell or represent any of the products presented in these papers. Visit www.hixson-inc.com for the abstracts from other papers.