Performance Analysis of Shell and Tube Heat Exchanger Using Miscible System

Similar documents
A COMPARATIVE STUDY OF HEAT EXCHANGER EFFECTIVENESS FOR DOUBLE HELICAL AND STRAIGHT CIRCULAR GEOMETRY

ICMIEE-PI Experimental and Numerical Investigation of an Air to Water Heat Exchanger

Address for Correspondence

Performance Analysis In Cross Flow Plate Fin Type Heat Exchanger

Solar Flat Plate Thermal Collector

Enhancement of Heat Transfer in Concentric Tube Heat Exchanger using Water Based Nano Fluid ( )

Effect of Corrugation Angle on Heat Transfer Studies of Viscous Fluids in Corrugated Plate Heat Exchangers

The effect of noncondensable gas on heat transfer in the preheater of the sewage sludge drying system

Optimization of Finned Tube Oil Cooler by Changing the Fin Material for Turbine Guide Bearing Applications

HORIZONTAL SHELL SIDE FLUIDIZED BED HEAT EXCHANGER, DESIGN CONSIDERATIONS AND EXPERIENCES FROM A PILOT UNIT

Validation of Deration of Heat Transfer Coefficient with Brine Usage

Thermal Design Optimization of Finned Shell and Tube Heat Exchanger Using Taguchi Approach

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

Design of heat recovery device to elevate coefficient of performance of water cooler by circulating drain water

Optimization on Scheduling for Cleaning Heat Exchangers in the Heat Exchanger Networks

TO CONDUCT THE PERFORMANCE TEST ON CHILLER UNIT BY USING NANOFLUID COOLED CONDENSER

Experimental investigation of single-phase and twophase closed thermosyphon solar water heater systems

The Experimental Study on Enhanged heat Transfer Performance in Plate Type Heat Exchanger

Experimental Investigation and Comparative Thermal Performance Analysis of Shell and Tube Heat Exchanger by Using CFD

Effect of Twisted Tape Inserts On Heat Transfer in A Concentric Tube Heat Exchanger

Delivery efficiency of the Jaga Low H 2 O heat exchanger in a Tempo enclosure

Design and development of an Earth Air Tube Heat Exchanger

Computational Modeling of Counter Flow Heat Exchanger for LMTD Analysis

1. To improve heat exchange between a gas & a liquid stream in a heat exchanger, it is decided to use fins. Correct the suitable option.

EXPERIMENT MODULE CHEMICAL ENGINEERING EDUCATION LABORATORY GAS GAS HEAT EXCHANGER (HXG)

ADVANCES in NATURAL and APPLIED SCIENCES

Modeling and Prediction of Shell and Tube Heat Exchanger Performance using ANN

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

CFD Simulation of Compact Type Mini Channel Heat Exchanger by Using of Water P.J.Pan 1 N.S.Patel 2

Performance Improvement on Water-cooled Cold-Plate

IJSRD - International Journal for Scientific Research & Development Vol. 1, Issue 12, 2014 ISSN (online):

International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:16 No:05 14

Efficiency improvement of steam power plants in Kuwait

INVESTIGATION OF FOULING EFFECT ON OVERALL PERFORMANCE OF SHELL AND TUBE HEAT EXCHANGER IN A UREA FERTILIZER PRODUCTION COMPANY IN NIGERIA

Performance Assessment of a Shell Tube Evaporator for a Model Organic Rankine Cycle for Use in Geothermal Power Plant

SteadyStateThermalAnalysisofShellandTubeTypeHeatExchangertoDemonstratetheHeatTransferCapabilitiesofVariousThermalMaterialsusingAnsys

Effect of geometrical parameters on heat transfer and pressure drop characteristics of plate fin and tube heat exchangers

Effect of Vibration on Heat Transfer Enhancement in a Rectangular Channel Heat Exchanger

ISOBUTANE GEOTHERMAL BINARY CYCLE SENSITIVITY ANALYSIS

Performance Evaluation of Solar Assisted Heat Pump Water Heating System

Performance Evaluation of Molten Salt Cavity Tubular Solar Central Receiver for Future Integration with Existing Power Plants in Iraq

Distillation Experiment--Flooding

Research Article. Kallalu Harika *, Tummala.Likhitha, Pulla Varsha Rani and R.Ramakanth. Abstract

Heat and Mass Transfer Studies on 134 A-DMAC Based Falling Film Absorbers for Absorption Refrigeration System

Parametric CFD analysis of an EMbaffle Heat Exchanger. EMbaffle B.V. The Netherlands

SINGLE-PASS SHELL & TUBE HEAT EXCHANGER MANUAL-SAMPLE. CNAT Doc. No.:

Heat transfer enhancement in fire tube boiler using hellically ribbed tubes

Modeling Techniques for Increased Accuracy

Experimental Investigation of Heat Transfer Enhancement of a Double Pipe Heat Exchanger with Helical Fins in the Annulus Side

Available online at ScienceDirect. Procedia Engineering 89 (2014 )

Performance of a counterflow heat exchanger with heat loss through the wall at the cold end

Energy Optimization Using Pinch Analysis

Evaluation of efficiency and collector time constant of a solar flat plate collector

International Journal of Mechanical Civil and Control Engineering. Vol. 1, Issue. 3, June 2015 ISSN (Online):

Application of COMSOL Pipe Flow Module to Develop a High Flux Isotope Reactor System Loop Model

Exergy analysis of a flat plate solar collector

Keywords: Fire tube Boiler, Water tube Boiler, Economizer

Improvement of Energy Efficiency using Porous Fins in heat Exchangers

APPENDIX C Optimization of Rectangular Offset-Strip, Plate-Fin Surfaces

Efficiency and heat losses of indirect water bath heater installed in natural gas pressure reduction station; evaluating a case study in Iran

Evaluating Performance of Steam Turbine using CFD

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

ISSN (ONLINE): , ISSN (PRINT):

Thermal Analysis and Modelling of Thermal Storage in Solar Water Heating Systems

Study on the heat transfer characteristics of an evaporative cooling tower B

M. TECH. BIOTECHNOLOGY (Evening) SEMESTER II

Department of Mechanical Engineering, IUPUI ME 414 Thermal-Fluid Systems Design Fall 2004 Project 2: Heat Exchanger Design

Numerical Investigation of Swirl's Effects in the Outer Annulus of a Reverse-flow Gas Turbine Combustor

Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008

Design Optimization of a Non-evacuated CPC Collector

Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant

Cleaning Schedule Operations in Heat Exchanger Networks

A Schematic Design and Analysis of a Pin Inserted U-Tube Heat Exchanger

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

A SIMULATION OF AN UNDERGROUND HEAT STORAGE SYSTEM USING MIDNIGHT ELECTRIC POWER AT PARK DOME KUMAMOTO

Profile LFR-56 HELIOS. KOREA Republic of. Molten lead-bismuth eutectic

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

SUPERCRITICAL HEAT TRANSFER AND HEAT EXCHANGER DESIGN FOR ORGANIC RANKINE APPLICATION

An Experimental Investigation of Heat Transfer Performance for Forced Convection of Water in a Horizontal pipe partially filled with a Porous Medium

Design and Analysis of Hydraulic Oil Cooler by Application of Heat Pipe

Design and Fabrication of Shell and Tube Heat Exchanger

Analysis of heat pipe solar collector using artificial neural network

Analysis of Longitudinal Fin Patterns in a Concentric Double Tube Heat Exchanger using LMTD and CFD Techniques

MODIFIED DESIG OF SHELL AND TUBE HEAT EXCHANGER AND CFD ANALYSIS J.Vijay Kumar 1, M.V.S.Pavan Kumar 2, J.Subash Kumar 3, T.N.V Ashok Kumar 4 1,2,3,4

Performance prediction of a thermal system using Artificial Neural Networks

PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER

WATER COOLING OF PHOTOVOLTAIC PANELS FROM PASSIVE HOUSE LOCATED INSIDE THE UNIVERSITY POLITEHNICA OF BUCHAREST

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

Appendix B Heat-Exchanger Design

Boiler Efficiency Testing. To understand the operation of a fire tube boiler To determine the operating efficiency of the boiler

GAS COOLING HEAT TRANSFER AND PRESSURE DROP CHARATERICTICS OF CO 2 /OIL MIXTURE IN A MICROCHANNEL ABSTRACT

Evalauation Of Heat Transfer Characteristics Of Titanium Nitride And Titanium Carbide Nano Fluids In Shell & Tube Heat Exchanger

CFD Modelling and Analysis of Different Plate Heat Exchangers

Measurement and Modeling for the Mitigation of Organic Crystallization Fouling

APPLICATIONS OF A DYNAMIC THREE-DIMENSIONAL NUMERICAL MODEL FOR BOREHOLE HEAT EXCHANGERS. M. He, S.J. Rees, L. Shao

Fluid Mechanics, Heat Transfer, and Thermodynamics Fall Design Project. Production of Dimethyl Ether

Design and construction of a pilot scale heat exchanger-cooling tower system for scaling/deposition and inhibition studies

PAPER-I (Conventional)

MATHEMATICAL MODELING OF A DOUBLE PASS UNDERFLOOR HEATING SYSTEM

Transcription:

American Journal of Applied Sciences 5 (5): 548-552, 2008 ISSN 1546-9239 2008 Science Publications Performance Analysis of Shell and Tube Heat Exchanger Using Miscible System 1 M. Thirumarimurugan, 2 T.Kannadasan and 3 E.Ramasamy Department of Chemical Engineering, Coimbatore Institute of Technology, Coimbatore-641 014 Abstract: An experimental investigation on comparative heat transfer study on a solvent and solution were made using 1-1 Shell and Tube Heat Exchanger. Steam is the hot fluid, whereas Water and Acetic acid- Water miscible solution serves as cold fluid. A series of runs were made between steam and water, steam and Acetic acid solution. In addition to, the volume fraction of Acetic acid was varied and the experiment was held. The flow rate of the cold fluid is maintained from 120 to 720 lph and the volume fraction of Acetic acid is varied from 10-50%. Experimental results such as exchanger effectiveness, overall heat transfer coefficients were calculated. A mathematical model was developed for the outlet temperatures of both the Shell and Tube side fluids and was simulated using MATLAB program. The model was compared with the experimental findings and found to be valid. Key words: Heat exchanger design, simulated annealing, overall heat transfer coefficient INTRODUCTION A heat exchanger is a device in which energy is transferred from one fluid to another across a solid surface. Exchanger analysis and design therefore involve both convection and conduction. Two important problems in heat exchanger analysis are (1) rating existing heat exchangers and (ii) sizing heat exchangers for a particular application. Rating involves determination of the rate of heat transfer, the change in temperature of the two fluids and the pressure drop across the heat exchanger. Sizing involves selection of a specific heat exchanger from those currently available or determining the dimensions for the design of a new heat exchanger, given the required rate of heat transfer and allowable pressure drop. The LMTD method can be readily used when the inlet and outlet temperatures of both the hot and cold fluids are known. When the outlet temperatures are not known, the LMTD can only be used in an iterative scheme. In this case the effectiveness-ntu method can be used to simplify the analysis. The choice of heat exchanger type directly affects the process performance and also influences plant size, plant layout, length of pipe runs and the strength and size of supporting structures. The most commonly used type of heat exchanger is the shell-andtube heat exchanger, the optimal design of which is the main objective of this study. Computer software marketed by companies such as HTRI and HTFS are used extensively in the thermal design and rating of HEs. These packages incorporate various design options for the heat exchangers including the variations in the tube diameter, tube pitch, shell type, number of tube passes, baffle spacing, baffle cut, etc. A primary objective in the Heat Exchanger Design (HED) is the estimation of the minimum heat transfer area required for a given heat duty, as it governs the overall cost of the HE. But there is no concrete objective function that can be expressed explicitly as a function of the design variables and in fact many numbers of discrete combinations of the design variables are possible as is elaborated below. The tube diameter, tube length, shell types etc. are all standardized and are available only in certain sizes and geometry. And so the design of a shell-and-tube heat exchanger usually involves a trial and error procedure where for a certain combination of the design variables the heat transfer area is calculated and then another combination is tried to check if there is any possibility of reducing the heat transfer area. Since several discrete combinations of the design configurations are possible, the designer needs an efficient strategy to quickly locate the design configuration having the minimum heat exchanger cost. Thus the optimal design of heat exchanger can be posed as a large scale, discrete, combinatorial optimization problem [13]. Most of the traditional optimization techniques based on gradient methods have the possibility of getting trapped at local optimum depending upon the degree of non-linearity and initial guess. Hence, these traditional optimization techniques do not ensure global optimum and also have limited applications. In the recent past, some experts studied on Corresponding Author: M. Thirumarimurugan, Department of Chemical Engineering, Coimbatore Institute of Technology, Coimbatore-641 014 Tel: 91-9943549700 548

the design, performance analysis and simulation studies on heat exchangers [12,13,15,16,18]. Modeling and Simulation of Shell and Tube Heat Exchangers Under Milk Fouling was carried out [15]. Dynamic Model for Shell and Tube Heat Exchangers was discussed [12]. Shell and Tube heat exchangers are applied where high temperature and pressure demands are significant and can be employed for a process requiring large quantities of fluid to be heated or cooled. Due to their design, these exchangers offer a large heat transfer area and provide high heat transfer efficiency in comparison with others. Modeling is a representation of physical or chemical process by a set of mathematical relationships that adequately describe the significant process behavior. Improving or understanding chemical process operation is a major objective for developing a process model. These models are often used for Process design, Safety system analysis and Process control. The simulation of an industrial system on a computer involves mathematical representation of the physical process undergone by the various components of the system, by a set of equations, which are in turn solved. Simulation is much cheaper than setting up big experiments or building prototypes of physical system and variables on the behavior of the system. A steady state model for the outlet temperature of both the cold and hot fluid of a shell and tube heat exchanger will be developed and simulated, which will be verified with the experiments conducted. Based on these observations correlations to find film heat transfer coefficients will be developed. MATERIALS AND METHODS Experimental Studies Experimental Set up: Experiments were conducted on a 1-1 Shell and Tube Heat Exchanger. The Fig. 1 shows the schematic diagram of the heat exchanger. Experimental procedure: The overhead tank was filled with water. The heater was switched on and temperature was set to 100 C. It was waited until the set temperature was reached. The pump was switched on and water was allowed into heating tank and the hot inlet valve to the Heat exchanger was opened. The cold fluid inlet valve was opened. It was waited until the steady state has been reached. At steady state, all the four temperatures and flow rates of cold and hot fluid do not change. The Rota meter reading and the flow Fig. 1: 1-1 Shell and Tube Heat Exchanger Table 1: Hot water-water system Fluid Temperatures (ºC) Volumetric Volumetric ----------------------------------------------- flow rate flow rate Cold Cold Hot Hot of cold of hot fluid fluid fluid fluid fluid (lpm) fluid (lpm) inlet outlet inlet outlet 2 0.88 29 59 100 76 3 0.88 29 56 100 72 4 0.88 29 52 100 70 5 0.88 29 49 100 68 6 0.88 29 47 100 65 7 0.88 29 45 100 62 8 0.88 29 41 100 59 9 0.88 29 38 100 56 10 0.88 29 36 100 53 11 0.88 29 33 100 50 Table 2: 10% Acetic acid-water solution Fluid Temperatures (ºC) Volumetric Volumetric ----------------------------------------------- flow rate flow rate Cold Cold Hot Hot of cold of hot fluid fluid fluid fluid fluid (lpm) fluid (lpm) inlet outlet inlet outlet 2 1.68 29 45.0 100 71.0 3 1.68 29 42.0 100 70.0 4 1.68 29 40.0 100 69.0 5 1.68 29 39.0 100 67.5 6 1.68 29 38.0 100 66.0 7 1.68 29 36.0 100 65.0 8 1.68 29 34.0 100 64.0 9 1.68 29 32.0 100 63.5 10 1.68 29 31.5 100 62.0 11 1.68 29 31.0 100 61.5 rate of hot fluid using collection tank was noted down. The flow rate of cold fluid was changed and waited for new steady state to be reached. The above step can be repeated Experimental observations: The Observations made for the Hot Water-Water system and the varying composition of Hot Water -10% Acetic acid solution system are given in the following Table 1 and 2. The composition was taken based on volume. 549

Overall Heat transfer coefficient, W / m2k Overall Heat transfer coefficient Vs Volumetric flow rate of cold fluid 160 140 120 100 80 60 40 20 0 0 2 4 6 8 10 12 Volumetric flow rate of Acetic acid, LPM Fig. 2: Overall Heat Transfer Coefficient Vs Vol. flow rate of Cold fluid and composition of cold fluid Modeling and simulation Physical modeling: The physical model equation was developed using dimensional analysis followed by least square curve fitting experimental data as follows: Nu = 0.4232(Re) 0.339 (Pr) 0.3412 (x) 0.003 Simulation: The models derived above are simulated using MATLAB. Simulation is done for various flow rates and for 10% Acetic acid and plotted in Fig. 2 along with the experimental values. RESULTS AND DISCUSSIONS The effect of different input variables on output variable are discussed in detail in the following sections. Heat exchanger effectiveness, the film coefficients for both hot and cold fluids and overall heat transfer coefficient calculations for the above observed readings are presented in the Table 3 and 4. Effect of flow rate of the cold fluid: Increase in the flow rate of cold fluid results in increase in the overall heat transfer coefficient as can be seen from tables. This is because increase in the flow rate increases the Reynolds number, which in turn increases the Stanton number and thereby the film heat transfer coefficient. The increase in film heat transfer coefficient will increase the overall heat transfer coefficient. This will also cause a decrease in the tube outlet temperature, as can be observed form tables. This is because increase in the volumetric flow rate increases the mass flow rate in a much faster rate than over all heat transfer coefficient or the heat energy transferred. Since the specific heat remains almost constant, tube outlet temperature should decrease to comply with law of conservation of energy. Am. J. Applied Sci., 5 (5): 548-552, 2008 Uexp Usim 550 As the flow rate of tube side fluid is increased, the tube side heat transfer coefficient increases, which in turn decreases fin effectiveness and surface effectiveness. The variation of fin effectiveness, surface effectiveness and exchanger effectiveness with flow rate for different compositions is shown in figures. Also the overall heat transfer coefficient increases, thereby NTU also increases and so exchanger effectiveness comes down. Effect of composition of the cold fluid: A decrease in composition of Acetic acid will increase the overall heat transfer coefficient as can be seen from tables. This is because increase in the concentration of water increases the heat capacity of the tube side fluid and hence the heat transferred. Decrease in composition decreases the tube outlet temperature because decrease in the concentration increases the specific heat value, which leads to decrease in tube outlet temperature. A decrease in composition of Acetic acid will increase the overall effectiveness and will decrease the surface and fin effectiveness. Fin effectiveness and surface effectiveness of hot side remains almost constant since the variation in composition of cold side fluid does not affect the hot side fluid. Fin effectiveness and surface effectiveness of cold side shows a slight increase with decrease in volume percentage of Acetic acid as evident from tables. This may be because of the slight decrease in film heat transfer coefficient with increase in composition of water. Surface effectiveness depends on film effectiveness and hence this also will increase. Overall effectiveness increase with decrease in composition of Acetic acid Overall heat transfer coefficient for S and T HE: As the volumetric flow rate of the tube side fluid is increased from 120 to 720 lph, the overall heat transfer coefficient increased from 126.167 to 150.15 W/(m 2 K). For the same volumetric flow rates, the simulated values varies from 121.805 to 148.605 W/m 2 K respectively, i.e., almost same as experimental values. Shell outlet temperature for S and T HE: For the flow rate increments from 120 to 720 lph, the outlet temperature of the shell side fluid varied from 45 to 31ºC, whereas the simulated values were 42 to 30ºC, respectively. Tube outlet temperature for S and T HE: For the flow rate increments from 120 lph to 720 lph, the outlet temperature of tube side fluid varied from 71 to 61.5ºC, whereas the simulated values were 68 to 60ºC respectively.

Table 3: Water-water system Cold fluid (Water) Hot fluid (water) ---------------------------------- ---------------------------------- Fluid Mass flow Fluid Mass flow Heat transfer coefficient (W/m 2 K) Temperature rate Temperature rate ------------------------------------------- Effectiveness (ºC) (Kg h 1 ) (ºC) (Kg h 1 ) Tube side Shell side Overall (%) --------------- ----------- ---------------- ----------- ----------- ----------- ---------- ---------------- t i t o m c T i T o m h h i h o U C* NTU 29 59 118.764 100 76 51.012 178.579 478.810 110.742 0.432 1.772 74.8 29 56 178.272 100 72 51.084 178.468 664.850 118.343 0.288 1.892 80.0 29 52 237.960 100 70 51.109 178.314 710.663 119.617 0.216 1.912 81.0 29 49 297.648 100 68 51.141 178.194 786.183 121.067 0.172 1.934 81.5 29 47 357.336 100 65 51.185 178.027 849.143 122.850 0.144 1.961 83.2 29 45 416.880 100 62 51.228 177.833 930.835 124.378 0.123 1.984 84.5 29 41 477.000 100 59 51.264 177.672 1029.525 125.786 0.108 2.005 85.5 29 38 536.976 100 56 51.300 177.492 1091.340 126.582 0.096 2.017 86.7 29 36 596.880 100 53 51.336 177.295 1114.810 126.903 0.086 2.021 87.0 29 33 656.892 100 50 51.372 177.130 1166.408 127.388 0.078 2.028 87.6 Table 4: 10% Acetic acid-water solution Cold fluid (Water) Hot fluid (water) ---------------------------------- ---------------------------------- Fluid Mass flow Fluid Mass flow Heat transfer coefficient (W/m 2 K) Temperature rate Temperature rate ------------------------------------------- Effectiveness (ºC) (Kg h 1 ) (ºC) (Kg h 1 ) Tube side Shell side Overall (%) --------------- ----------- ---------------- ----------- ----------- ----------- ---------- ---------------- t i t o m c T i T o m h h i h o U R c NTU 29 45.0 120.179 100 71.0 97.548 222.070 460.254 126.167 0.862 1.056 53.00 29 42.0 180.482 100 70.0 97.577 221.995 578.965 133.689 0.574 1.120 58.50 29 40.0 240.832 100 69.0 97.606 221.969 734.423 140.647 0.430 1.177 63.00 29 39.0 301.158 100 37.5 97.648 221.870 766.641 141.643 0.344 1.205 66.00 29 38.0 361.461 100 66.0 97.690 221.768 847.226 144.092 0.287 1.222 65.30 29 36.0 422.199 100 65.0 97.718 221.679 920.641 146.198 0.245 1.228 67.50 29 34.0 482.408 100 64.0 97.745 221.587 952.571 146.843 0.215 1.233 68.20 29 32.0 543.182 100 63.5 97.759 221.567 985.977 147.493 0.191 1.251 69.00 29 31.5 603.675 100 62.0 97.799 221.451 1086.990 149.701 0.172 1.252 72.50 29 31.0 664.114 100 61.5 97.812 221.438 1116.180 150.150 0.156 1.254 74.08 The results for the other compositions were similar to that obtained from the one considered here as the reference. From the above comparisons it can be said that the mathematical model developed for the system is very close. CONCLUSION Experiments were conducted on a 1-1 Shell and Tube heat exchanger with different cold side flow rates and different compositions of cold fluid. The effect of these parameters on the shell outlet temperature, tube outlet temperature and overall heat transfer coefficients were studied. It was found that cold fluid outlet temperature decreases and the overall heat transfer coefficient increases with increase in flow rate of cold fluid. Also the outlet temperature of cold fluid decreases and overall heat transfer coefficient increases with increase in composition of water. The overall effectiveness of heat exchanger was found to increase with decrease in composition of water. It was 551 found that the Cross Flow Heat Exchanger is the most effective compared with the Shell and Tube Heat Exchanger. A mathematical model of this system is developed, simulated using MATLAB and compared with the experimental values. Finally a correlation for the calculation of film heat transfer coefficient is developed using dimensional analysis for tube side. NOMENCLATURE T i = Inlet temperature of hot fluid (ºC) T o = Outlet temperature of hot fluid (ºC) t i = Inlet temperature of cold fluid (ºC) t o = Outlet temperature of cold fluid (ºC) Re = Reynolds No. Pr = Prandtl No. Nu = Nusselt No. St = Stanton No. NTU = No. of heat transfer units of an exchanger lpm = Litres per minute

REFERENCES 1. Hesselgreaves, J.E., 2002. An approach to fouling allowances in the design of compact heat exchangers. Applied Therm. Eng., 22. 2. Holman, J.P., 1997. Heat Transfer. 8th Edn., McGraw-Hill Book Company, New York. 3. Zealsing, P., 2004. Heat exchanger design for good process performance, Chemical product finder 4. Robert, H.P. and D.W. Green, 1997. Perry s Chemical Engineering Hand Book, 7th Edn., McGraw-Hill Company, New York 5. Rohsenow, W.M., J.P. Hartnett and E.N. Ganic, 1985. Hand Book of Heat transfer Applications, 2nd Edn., McGraw-Hill Company, New York. 6. Donald, Q.K., 2000. Process Heat Transfer, Tata Mc Graw Hill Edition. 7. Warren, L. McCabe, J.C. Smith and P. Harriott, Unit Operations of Chemical Engineering, 5th Edn., Mc Graw Hill International Edition. 8. Babu, B.V., 2004. Process Plant Simulation, Oxford University Press. 9. Kothandaraman, C.P. and S. Subramanyan, 2000. Heat and Mass Transfer Data Book, Tata McGraw Hill Edition. 10. William, L.L., 1990. Process Modeling, Simulation And Control for Chemical Engineers, 2nd Edi., McGraw Hill International Edition. 11. Rudra, P., Getting Started with MATLAB(Version 6.0,7.0), Oxford University Press. 12. Aghareed, M.T., M.A. El-Rifai, Y.A. El-Tawil and R.M. Abdel-Monen, 1991. A New Dynamic Model for Shell and Tube Heat Exchangers. Energy Conservat. Manage., 32: 439-446. 13. David, B., 2002. Design of Shell and Tube Heat Exchangers When the Fouling Depends on Local Temperature and Velocity, Applied Thermal Eng., 22: 789-801. 14. Sparrow, E.M. and L.G. Reifschneider, 1986. Effect of Inner Baffle Spacing on Heat Transfer and Pressure Drop in Shell and Tube Heat Exchanger. Int. J. Heat Mass Transfer, 29: 1617-1628 15. Michael, C.G., G.E. Rotstein and S. Miccheietto, 1998. Modeling and simulation of shell and tube heat exchangers under milk fouling. AIChE J., 44: 959-971. 16. Mandavgane, S.A., M.A. Siddique, A. Dubey and S.I. Pandharipande, 2004. Modeling of Heat Exchangers Using Artificial Neural Net Work. Chem. Eng. World, pp: 75-80. 17. Anantharaman, S., 1997. Design and construction of shell and tube heat exchangers. Chem. Ind. Dev. Incorporat. Chem. Process. Eng., 11: 15-21. 18. Yusuf, A.K. and O. Guraras, 2004. A computer program for designing of shell and tube heat exchangers. Applied Therm. Eng., 24: 1797-1805. 552