Nilan VPL Active heat recovery and cooling (air/air)

Similar documents
> HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION. Available range. Unit description. Options. Accessories

ENERGY CONSERVATION STRATEGIES FOR HVAC SYSTEMS

ROOF TOP SPACE. SELF-CONTAINED REVERSIBLE AIR-AIR UNITS OF 23 TO 281 kw EVERY EFFICIENT SOLUTION FOR UNIVERSAL COMFORT NA C

Reducing running costs, whilst benefiting the environment and the future

Variable Speed Solutions Outstanding Performance For Heat Pump Applications

Set Free Modular FSXN. Engineering for tomorrow. And the tomorrow after that.

Rooftops High performance, proven reliability and easy installation

Largo & Allegro. Air Compressors. Largo & Allegro

YKN2open A R C 032 A B

Roof top. NEW SPACE Zen attitude NA O8.16B

High efficient heat reclaim with CO2

invite the beauty of nature inside

SMART BUILDINGS. Always the best climate for. Zehnder ComfoAir Q ventilation units

RS kw. Motor size: kw. All compressors available with frequency control! RENNER screw compressors

BUILDINGS & OFFICE SPACES INDUSTRIAL SOLUTIONS. Combined production of Heat and Power. Waste Heat Recovery Bottoming Cycle

PUHY-HP200YHM-A. City Multi Outdoor Product Information. Zubadan Y Series 8hp Outdoor Unit

Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies.

Variable Speed Solutions. Outstanding performance for residential applications

Rollair. Air Compressors ROLLAIR 150E AND ROLLAIR 150V-180V-240V

Optimize without compromise Take heat transfer solutions to a new level

Renewable Energy. to heat your home. thermia.com

Information Guide Long Term Efficiency. Issue 42

Rebel commercial packaged rooftop systems

Rebel commercial packaged rooftop systems

FLEXY EC HIGH EFFICIENCY ROOFTOP kw AIR COOLED COOLING ONLY/HEAT PUMP/ GAS/ DUAL FUEL

EES Energy Efficient Systems Rotary Screw Air Compressors kw Horsepower

indoor air quality and energy saving TECHNICAL DATA JD/JD ENTHALPIC HEAT RECOVERY VENTILATION UNITS for RESIDENTIAL BUILDINGS

Trane Water-Source Variable Refrigerant Flow

Air-cooled Chillers with High Speed Centrifugal Compressors

THE ALL-IN-ONE INLET AIR COOLING AND FILTRATION SOLUTION USING YOUR WASTE HEAT FREUDENBERG FILTRATION TECHNOLOGIES

SUPERB CLIMATE SOLUTION WITH A PROVEN RECORD

systems for turbomachinery Power Systems Camfil Farr - clean air solutions for turbomachinery

DANVEST POWER UNIT. with special Low Load Unit for wind-diesel power stations

AIRROLLAIR COMPRESSORS E

FTXM-K + RXM-L. Product catalogue 2015

Outdoor air treatment units

INDUSTRIALS GROUP. Screw Compressors. ESM Highly Efficient Fixed Speed Solutions

Control Products & Systems OEM siemens.com/buildingtechnologies-oem

shedding on any DYNACIAT unit. CMS RS 485 MODBUS/JBUS LONWORKS (option)

Reduce energy costs and create environmentally friendly hot water all year round

CARRIAGE OF INTEGRAL REFRIGERATED CONTAINERS ON BOARD SHIPS

VACUUM DISTILLATION SYSTEMS

Universal cooler in individual design BASELINE BL 006 BL Customized refrigeration technology Made in Germany

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

WINERY ENERGY SAVER TOOLKIT SUPPLIER CHECKLIST COMPRESSED AIR

Your partner for the right solution

Heat pumps. Oilon ChillHeat. Optimized cooling and heating performance

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 7 to 16 KW

Gitie. A CHOICE SMARTER than solar systems. Trivalent integrated outdoor package

Thermia Large capacity Heat pumps

plus pellet makes you independent

VRF V4+K Series 50Hz. Commercial Air Conditioners Commercial Air Conditioner Division Midea Group

Heat pumps. Oilon ChillHeat. Optimized cooling and heating performance

Flooded Type Water-Cooled Chillers. R134a

high-efficiency performance High Performance, Comfort, respect for the environment

Air Cooled Packaged Air Conditioning

IT S IN OUR NATURE NIBE.EU. Air/water heat pumps from NIBE

Building Commissioning, Energy Efficiency & Building Automation Systems

ACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features

Energy management. Record energy consumption Analyse energy consumption Save energy costs

Regenerative heat exchanger with ceramic core; high thermal efficiency (up to 90%). Telescopic pipe adaptable to the wall thickness.

CSIRO Energy Centre Newcastle, New South Wales, Australia

Advanced Rooftop FLEXY II The packaged Air Handling Unit solution. Providing indoor climate comfort

HIGH EFFICIENCY SHOWERS WASTE WATER HEAT RECOVERY UNIT. Saved power 80kW. Showers waste water 9 C Power consumption 3,1kW. Showers waste water 31 C

Diagonal compact module. The intelligent solution for electronics cooling.

STERIVAPHP. Original without compromises. protecting human health. new line steam sterilizers

CO2 transmitters. Introduction 44. CO 2 transmitters 45. CO 2 and temperature transmitters 46. CO 2 transmitters for special applications 47-48

RL SERIES. Two Stage Light Oil Burners FIRING RATES LIGHT OIL

Centrifugal Air Compressors. MSG Centac C-Series 350-1,300 kw (500-1,750 hp)

European KEYMARK Scheme

AIRCOOL VENTILATORS FURTHER INFORMATION

Star. by Fläkt Woods. iq Star Astra Energy efficient chilled beam

NEW REQUIREMENTS NEW SOLUTIONS

Integrated Air Conditioning System

STERIVAP HP. Large Steam Sterilizer for Health Care for Original Without Compromises. protecting human health

FIRST LARGE-SCALE SOLAR SEASONAL BOREHOLE THERMAL ENERGY STORAGE IN CANADA

ESyCool green ESyCool classic. Sustainable energy systems for food retailing. Heating systems Industrial systems Refrigeration systems MF/1

Room automation for laboratories. Safety and a pleasant climate for life sciences and the healthcare sector.

European KEYMARK Scheme

Optimum Heat Renewable Energy Optimal Pellet Biomass Boiler Product Presentation

GHS VSD + series. Oil-sealed rotary screw vacuum pumps with Variable Speed Drive (VSD) technology

A class of its own JUMAG STEAM BOILER COMPACT INFORMATION STEAM BOILER WATER SUPPLY MODULES BLOW DOWN VESSEL COMPACT STEAM SYSTEM.

ROOF TOP PACKAGE UNITS

Wood Chip and Pellet Boilers

UltraGas. Technical Data Output range 15 to 2000 kw. Condensing Gas Boiler /02-07/15 Subject to modifications

Efficient Operation of Swimming Pools and Hydrotherapy Pools

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM

Report on thermal cooling system implementation and performance

Pressure Booster System. Hya-Eco VP. Type Series Booklet

Online data sheet MAC800 CUSTOMIZED ANALYZER SYSTEMS

EUROPE S LEADING CHP SPECIALIST. Dachs CHP RANGE GUIDE 2016

SECTION 3: SUSTAINABLE DESIGN CONTENTS

Building-Related Research at Herrick Laboratories: Past, Present, and Future

Installation Instructions

RETROFIT SOLUTIONS. For Gas Turbines And Rotating Machinery

i-chiller COMPACT 1 to 4 kw 0 C to 30 C ic03c to ic10c RELIABILITY:

FROST TOP - WF SERIES

CLIMACIAT TAILOR-MADE INDOOR AIR QUALITY CLIMACIAT CLIMACIAT CLIMACIAT. airclean. airtech. airaccess AIR HANDLING UNIT NA16.14A

HYDROCARBON REFRIGERANT CONVERSION REPORT FOR BOSCH SIEMENS HOME APPLIANCES CO CHUZHOU, CHINA.

30 DIGITAL SERIES CLIMATEMASTER GEOTHERMAL HEATING AND COOLING

Transcription:

M a r k e t l e a d i n g c o m m e r c i a l a n d d o m e s t i c v e n t i l at i o n w i t h h e at r e c o v e r y Nilan 31-125 Active heat recovery and cooling (air/air)

Nilan 31-125 Commercial ventilation with heat recovery and cooling (air/air) The 31-125 units are tested heat recovery units with cooling developed for industrial and comfort ventilation for air requirements of up to 12,000 m³/h. About indoor climate The Danish Working Environment Authority says: A poor indoor climate in the workplace can and must be prevented. Several rules, norms and standards have been set out for indoor climate conditions. A poor indoor climate can e.g. result in employees not feeling well, experiencing irritated mucous membranes, headaches and lethargy. These are symptoms which reduce employees quality of life and increase absence due to illness. Function The Nilan 31-125 units are active heat recovery units with cooling that extract warm, damp air and inject temperate air. This means that particles, odours and dampness are removed and a comfortable indoor climate achieved. The energy in the exhaust air is recovered and transferred to the intake air through a combination of passive heat recovery and a heat pump which extracts energy directly from the air. The unit is supplied as standard with a reversible cooling/heating system which controls the cooling & heat recovery output modulated from 50% to 100%. Nilan 31-125 comprises two fans for intake and exhaust air respectively as well as a heat pump with a compressor. Heating surface and controls can be fitted externally. The units are compact and easy to service as all components are gathered in a single place. The 31-125 units can produce up to 12,000 m³/h (at 250 pascal). The units are controlled using the electronic CTS 6000 control system. NILAN CTS 6000 is a newly developed and tested control system with monitoring, regulating and control options from any place in the world via an IP address. CTS 6000 also provides the option of registering and reporting back on error messages from the control system by e-mail. Advantages All the required sensors, fire thermostats, etc. are as far as possible built in and connected internally in the unit. Any pressure transmitters and heat surface components are fitted externally. This means that the electrical installation is simple and quick for a qualified engineer to carry out in accordance with the enclosed electrical diagrams. As no separate cooling authorisation is required for installation, the installation fee is reduced. The is prepared from the factory for outdoor installation which means that further preparation is unnecessary. is supplied as a single unit. The NILAN filter unit FU is a unit produced for location in front of the heat recovery unit. The unit comprises an outdoor air filter and an exhaust air filter as well as a heat pipe which works as a passive pre-heat exchanger. Two motorized dampers are installed from the factory in the outdoor air and exhaust air sections. All sensors for pressure, temperature and baffle positions are internally connected to multiple plugs. Multiple plugs are used for the connection of each ventilation module. This ensures that incorrect installation cannot take place and reduces installation costs significantly. The whole unit is located behind a door for easy service access. 2

Options 31: Renews up to 1,800 m³/h (at 250 Pa). Temperature efficiency of 82%. 0.89 kw (-12 C, 50% RH) 1.59 kw (25 C, 50% RH) 35: Renews up to 2,500 m³/h (at 250 Pa). Temperature efficiency of 84%. 1.42 kw (-12 C, 50% RH) 2.40 kw (25 C, 50% RH) 45: Renews up to 3,500 m³/h (at 250 Pa). Temperature efficiency of 77%. 1.83 kw (-12 C, 50% RH) 3.31 kw (25 C, 50% RH) 55: Renews up to 4,500 m³/h (at 250 Pa). Temperature efficiency of 85%. 3.33 kw (-12 C, 50% RH) 4.97 kw (25 C, 50% RH) 65: Renews up to 5,500 m³/h (at 250 Pa). Temperature efficiency of 83%. 4.22 kw (-12 C, 50% RH) 6.47 kw (25 C, 50% RH) 75: Renews up to 8,000 m³/h (at 250 Pa). Temperature efficiency of 81%. 4.60 kw (-12 C, 50% RH) 7.59 kw (25 C, 50% RH) 85: Renews up to 10,000 m³/h (at 250 Pa). Temperature efficiency of 77%. 6.63 kw (-12 C, 50% RH) 9.91 kw (25 C, 50% RH) 125: Renews up to 12,000 m³/h (at 250 Pa). Temperature efficiency of 74%. 8.47 kw (-12 C, 50% RH) 13.06 kw (25 C, 50% RH) Temperature efficiency calculated at nominal air volume, outside air 4 C and 0% RH Facts: Cooling function Heat recovery Renews up to 12,000 m³ per hour (at 250 Pa) Intake air and exhaust air Temperature efficiency up to 85% Option of supplementary heat using water or electrical heating surface Advantages: No damp problems or odours Fresh air supply and extraction of contaminated air High recovery Low operational consumption and cost due to heat pipe FU + heat pipe Fan section 3

Online control and monitoring of Nilan 31-125 CTS 6000 enables Nilan industrial units to be controlled and monitored online using a PC located anywhere in the world. CTS 6000 has been designed to meet future requirements for optimising the economy of ventilation units as well as detailed adaptation to the requirements of individual buildings. Control Optimum control of ventilation units assumes simple and user-friendly operation of the most important functions. Using a weekly or annual programme, units can be set for automatic operation to allow for the setting of operating times, room temperatures, ventilation speeds, alarms, etc. The weekly programme can be customised, and extended operation is possible beyond the weekly programme s operating periods. When the unit s functions and weekly programme have been set, it will run automatically without any further need for adjustment. An annual programme also permits programming for public holidays when the unit does not need to operate. Using graphic history diagrams it is possible to collect information about the unit s operation and subsequent adjustment and optimisation. Automatic, intelligent control provides optimal operating economy of the unit and ensures a comfortable indoor climate. Monitoring With CTS 6000 the ventilation unit can be monitored over the Internet from a PC located anywhere in the world. The unit can also be hooked up to the building s internal network or have its own dedicated Internet connection. Current operation can be followed by using trend diagrams. CTS 6000 ensures optimum monitoring of the unit s operating status as all forms of operational failures, alarms and maintenance notifications are sent automatically by e-mail or SMS to the right users. Immediate action can then be taken in the event of operational failure. This also allows for optimum maintenance and service visit planning. CTS 6000 also provides the company s service partners with the option of remote control and diagnosis of any faults. Start-up and adjustment of Nilan automation Start-up and adjustment of Nilan automation is an optional extra. This service includes: functional testing of the installation checking the heat pump circuit for defects that may have occurred during transport checking air volume (on measurement across evaporator) adjustment of CTS in accordance with customer requirements. When booking start-up and adjustment of automated functions, installation must be complete, including ducts, baffles and valves. Internal and external electrical work, including control panel, must have been completed as must any plumbing work related to water surfaces. Start-up must be booked with Nilan s service dept. approx. 14 days before required start-up. 4 On-site control panel Nilan CTS 6000 is a newly designed, thoroughly tested control and monitoring programme. With CTS 6000, Nilan industrial units can be controlled either online over the Internet or on-site using a control panel. CTS 6000 also provides the option of registering and reporting back on error messages from the control system by e-mail.

Calculating operational economy A precise analysis of weather conditions and geographical location are decisive when choosing the most efficient and economically viable ventilation system. Nilan has developed Nilan Calculator, a unique calculation software, which allows realistic and extremely precise calculations that take every factor into account. Achieve precise calculation of operating economy Whereas traditional calculation methods only take into account an installation's efficiency under extreme temperatures, Nilan Calculator is based on data that present a straightforward, precise picture of the climatic norms in which the installation is to function. The programme uses so-called DRY data based on extensive meteorological measurements for the locality in which the installation will be used. Variables such as day and week plans and holidays can be entered to provide a detailed picture of when and how the installation will be used. Nilan's new calculation software ensures a precise, accurate basis for decisionmaking when it comes to choosing the most economical ventilation system. The programme has been thoroughly tested to achieve the greatest possible userfriendliness, and its development will continue in consultation with users. We greatly appreciate feedback so that we can ensure optimum development of future versions of the software. To order Calculator send Du kan an bestille e-mail to Nilan Calculator ved calkulator@nilan.dk at sende en mail til calculator@nilan.dk 5

Technical specifications 31 35 45 55 65 75 85 125 Air volume m³/h 900-1,800 1,300-2,500 2,000-3,500 3,000-4,500 4,000-5,500 5,500-8,000 7,500-10,000 9,500-12,000 Nominal air volume m³/h 1,800 2,800 3,500 4,500 5,500 8,000 10,000 12,000 Main dimensions excl. connection pieces and base, LxWxH mm 1,350x 710x 1,400 1,350x 710x 1,400 1,350x 710x 1,400 1,500x 910x 1.400 1,500x 910x 1,400 2,000x 1,260x 1,770 2,000x 1,260x 1,770 2,250x 1,260x 2,000 Total weight without packaging kg 320 325 330 420 430 590 640 860 Power supply A 3x16 3x20 3x25 3x35 3x35 3x50 3x63 3x63 Voltage V 400 400 400 400 400 400 400 400 Compressor Number 1 1 1 1 1 2 2 2 Refrigerant type R 407 C R 407 C R 407 C R 407 C R 407 C R 407 C R 407 C R 407 C Quantity refrigerant g 4,300 4,300 4,300 7,200 7,200 11,000 11,000 12,500 Condenser/ evaporator HxW mm 400x 400 400x 400 400x 400 600x 600 600x 600 800x 900 800x 800 900x 900 Standard fan: Double inlet centrifugal fan Condensing capacity l/h 5,2 7,0 8,7 12,0 17,5 24,5 31,5 38,5 Condensation outlet: PVC pipe mm Ø 20 Ø 20 Ø 20 Ø 20 Ø 20 Ø 20 Ø 20 Ø 20 6

Ventilation promotes performance in the workplace Heat output Heat output is based on an extraction temperature of 20 C and a nominal air volume of 1,800, 2,500, 3,500, 4,500, 5,500, 8,000, 10,000 and 12,000 m³/h Heat output [kw] 90 80 70 60 50 40 30 20 10 0-12 -7-2 3 8 13 18 Outdoor temperature, ºC, RH 50% 31 + HP 35 + HP 45 + HP 55 + HP 65 + HP 75 + HP 85 + HP 125 + HP Operating economy The heat pipe (Nilan HP) is a closed evaporator/condensation circuit which transfers energy from the extracted air to the injected air without mixing the two air flows. The transfer of energy takes place by the cooling medium evaporating when heat is added. The steam condensates into a liquid at the cold end of the circuit after which the liquid returns to the evaporation phase. Cooling output Cooling output is based on an extraction temperature of 25ºC/50% and a nominal air volume of 1,800, 2,500, 3,500, 4,500, 5,500, 8,000, 10,000 and 12,000 m³/h (total cooling performance) Cooling output [kw] 45 36 27 18 9 The cycle continues as long as the exhaust air is warmer than the outside air. The greater the difference in temperature between the exhaust air and the outside air, the more effective the heat pipe will be. The cooling medium in Nilan HP is CO ² which does not affect the ozone layer and contribute to global warming in the way that HFC gases do. 0 20 25 30 Outdoor temperature, ºC, RH 50% 31 35 45 55 65 75 85 125 Evaporator Condenser 7

About Nilan Nilan A/S was set up in 1974 as a natural consequence of the oil crisis. As we started to insulate and seal our buildings to save energy, a need arose for good and healthy indoor climate solutions. This became the foundation of what is now Nilan A/S one of the world s leading ventilation and heat pump technology companies. We are currently represented in all the Scandinavian countries, Germany, Austria, Switzerland, Holland and North America either through subsidiaries or dealers. Nilan A/S Nilanvej 2 DK-8722 Hedensted Tel: +45 76 75 25 00 Fax: +45 76 75 25 25 nilan@nilan.dk www.nilan.dk At the cutting edge of developments Climate change and the world's excessive use of energy are at the top of the global agenda. Nilan is at the cutting edge of these developments and has manufactured heat pumps and ventilation systems for passive houses and low energy construction all over the world for many years. We are currently one of the leading suppliers in the low-energy market. It is a good example of how we always set great store by innovation and product development. All our products have also been tested and certified by TI. Made in Denmark Torben Andersen is the founder of Nilan A/S and managing director of the company. The company is located in Hedensted in a building with an area of 10,000 m2 housing both production and offices. As one of the only companies in the industry in Denmark, we manufacture and develop all our products in Denmark, and all our control systems and automation are developed and manufactured in close partnership with our Danish subcontractors. Our production uses state-of-the-art technology and is based on a sustainable approach focusing on the use of green materials, recycling and minimising waste. Dealer: g r c. d k. 3 0 0 0. 0 8. 2 0 1 0. 4 2 2 6 8