ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

Similar documents
Structural Performance Certification Authorization Report

Dennis Fassnacht Jr :59:35-04'00'

Structural Performance Certification Authorization Report

TEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio

TEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO)

AAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania

Structural Performance Certification Authorization Report

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee

Structural Performance Certification Authorization Report

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

TEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC.

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window

TEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A AAMA TEST REPORT SUMMARY

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

Architectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310

TEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS:

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

PERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT SUMMARY. Rendered to:

INTERNATIONAL WINDOW TEST REPORT

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Polyvinyl Chloride (PVC)

ETC Laboratories Measuring Up To Your Standards And More

OSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Vinyl

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4. TYPE: Single Hung Window

SECTION VINYL (PVC) WINDOWS

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut


ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door

Construction Consulting Laboratory, International

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

PERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

AAMA/WDMA/CSA 101/I.S.2/A440-08

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door

MARLIN WINDOWS, INC 3500 HC SERIES 3 3 8" SLIDING WINDOW PAGE 1

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America LLC. SERIES/MODEL: FCM B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window

SECTION SERIES 200 DOUBLE-HUNG VINYL WINDOWS

STRUCTURAL PERFORMANCE TEST REPORT. Series Casement (Rep/Impact/AAMA) C-C70 940mm x 1930mm (37 x 76 )

AAMA/WDMA/CSA 101/I.S.2/A440-08

TEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: MGM INDUSTRIES. SERIES/MODEL: 4600 Double Hung

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: CUSTOM VINYL PRODUCTS, LLC

TEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina

General Specifications COMPLETE PRODUCT LINE

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

Milgard Quiet Line Series Vinyl Windows 3-Part Specification

SECTION VINYL WINDOWS AND DOORS. 2.2 Slider Windows Classic Series (Standard sizes) and Thermo-Fit Series (Custom sizes)

United Window & Door - Series 5500 New Construction Double Hung Windows Specifications

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

Architectural Single-Hung Aluminum Window Series L701T SH-AW130 GUIDE SPECIFICATION

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

2000/2100/2200 Series Heavy Commercial Sliding Patio Doors

INVITATION TO BID. Fire Restoration at Nike Manor, 3549 S. 239th St., Kent, WA ADDENDUM NO. 1

SILVER LINE BUILDING PRODUCTS

SECTION ALUMINUM STORM WINDOWS

Series 4900 Vinyl Single Hung Windows R50/R45/R35/R30 Performance for New Construction

Series SX45 Horizontal Slider Series FX45 Fixed 4 1/2" High Performance Thermal, Architectural Grade Windows

SECTION ALUMINUM WINDOWS

Series 3500 Thermal Series 3900 Fixed Thermal Architectural Grade Horizontal Sliding Window

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia

Sliding Patio Doors Brickmould Vinyl

OSHA Title 8 General Industry Safety Orders Floor Openings, Floor Holes, Skylights and Roofs

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia

SECTION ALL ULTREX DOUBLE HUNG WINDOW

Series 2900 Vinyl Single Hung Windows R50/R45/R35/R30 Performance for New Construction

Transcription:

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT Rendered to: MASTER WINDOW SYSTEMS, INC. SERIES/MODEL: Master 1000 Sliding Window PRODUCT: PVC Horizontal Sliding Window Summary of Results Title Test Specimen #1 Test Specimen #2 Test Specimen #3 Specimen Configuration XO XOX 1/3, 1/3, 1/3 XOX 1/4, 1/2, 1/4 Rating HS-R30 69 x 48 HS-R20 104 x 48 HS-R25 104 x 48 Operating Force N/A N/A N/A Air Infiltration N/A N/A N/A Water Resistance Test Pressure N/A N/A N/A Uniform Load Deflection Test Pressure ±35.0 psf ±20.0 psf ±25.0 psf Uniform Load Structural Test Pressure ±52.5 psf ±30.0 psf ±37.5 psf Forced Entry Resistance N/A N/A N/A Reference should be made to ATI Report No. for complete test specimen description and data. 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT Rendered to: MASTER WINDOW SYSTEMS, INC. 2060 DeFoor Hills Road, N.W. Atlanta, Georgia 30318 Report No.: Test Dates: 10/19/06 And: 11/01/06 Report Date: 09/13/07 Expiration Date: 09/26/09 Project Summary: Architectural Testing, Inc. (ATI) was contracted by Veka, Inc. to witness testing on three Series/Model SS27WW, PVC horizontal sliding windows at their test facility located in Fombell, Pennsylvania. The samples tested successfully met the performance requirements for the following ratings: Test Specimen #1: HS-R30 69 x 48; Test Specimen #2: HS-R20 104 x 48; Test Specimen #3: HS-R25 104 x 48. This report is a reissue of the original Report No. 68612.01-501-47. This report is reissued in the name of Master Window Systems, Inc. through written authorization of Veka, Inc. Test specimen description and results are reported herein. Reference ATI Report Number 59931.01-501-47 for gateway performance test results. Test Specification: The test specimens were evaluated in accordance with ANSI/AAMA/NWWDA 101/I.S.2-97, Voluntary Specifications for Aluminum, Vinyl (PVC) and Wood Windows and Glass Doors. Test Specimen Description: Series/Model: Master 1000 Sliding Window Product Type: Poly Vinyl Chloride (PVC) Horizontal Sliding Window Test Specimen #1: HS-R30 69 x 48 Overall Size: 5' 9" wide by 4' 0" high Operable Sash Size: 2' 10-1/4" wide by 3' 9-1/4" high Fixed Daylight Opening Size: 2' 6-5/8" wide by 3' 6-3/4" high Overall Area: 23.0 ft 2 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

Page 2 of 7 Test Specimen Description: (Continued) Test Specimen #1: HS-R30 69 x 48 (Continued) Installation: The unit was installed in a wood buck constructed of Spruce-Pine-Fir construction lumber and sealed at the exterior nail fin perimeter with a silicone sealant. The unit was secured to the buck through the nail fin with #8 x 1-1/4" long dry wall screws, spaced approximately 9" on center. A nominal 1/8" space was maintained at the perimeter between the buck and window frame. Test Specimen #2: HS-R20 104 x 48 Overall Size: 8' 8" wide by 4' 0" high Operable Sash Size (2): 2' 10-1/4" wide by 3' 9-1/4" high Fixed Daylight Opening Size: 2' 7-3/4" wide by 3' 6-3/4" high Overall Area: 34.7 ft 2 Installation: The unit was installed in a wood buck constructed of Spruce-Pine-Fir construction lumber and sealed at the exterior nail fin perimeter with a silicone sealant. The unit was secured to the buck through the nail fin with #8 x 1-1/4" long dry wall screws, spaced approximately 4-1/2" on center. A nominal 1/8" space was maintained at the perimeter between the buck and window frame. Test Specimen #3: HS-R25 104 x 48 Overall Size: 8' 8" wide by 4' 0" high Operable Sash Size (2): 2' 2" wide by 3' 9-1/4" high Fixed Daylight Opening Size: 4' 0-3/4" wide by 3' 6-3/4" high Overall Area: 34.7 ft 2 Installation: The unit was installed in a wood buck constructed of Spruce-Pine-Fir construction lumber and sealed at the exterior nail fin perimeter with a silicone sealant. The unit was secured to the buck through the nail fin with #8 x 1-1/4" long dry wall screws, spaced approximately 4-1/2" on center. A nominal 1/8" space was maintained at the perimeter between the buck and window frame.

Page 3 of 7 Test Specimen Description: (Continued) Finish: All vinyl was white. The following descriptions apply to all specimens. Glazing Details: The sash was exterior and the fixed lite was interior glazed with 3/4" thick, sealed insulating glass, fabricated from two sheets of 3/32" (1/8" in fixed lite of 1/4, 1/2, 1/4 unit) clear annealed glass and a butyl spacer material with stainless steel substrate, single sealed. Each insulating glass unit was set against a double-sided adhesive tape and secured with rigid vinyl glazing beads. Weatherstripping: Description Quantity Location 0.187" backed by 0.260" 2 Rows Top and bottom rails high pile with center fin 0.187" backed by 0.260" 1 Row Jamb stile, lock stile high pile with center fin 0.187" backed by 0.280" 1 Row Head, sill, jambs high pile with center fin Frame Construction: The PVC frame was constructed using mitered and welded corner construction. The fixed meeting stile was coped and fastened through the head and sill with two #8 x 3" long screws per end. A rigid PVC roller track was applied to the sill. Sash Construction: The PVC sash was assembled using mitered and welded corner construction. Screen Construction: The screen was constructed from formed aluminum. The corners were square-cut and secured with plastic corner keys. Fiber mesh screen cloth was held-in-place with a flexible spline.

Page 4 of 7 Test Specimen Description: (Continued) Drainage: Description Quantity Location 1" wide by 1/4" high 2 Exterior base of the sill, weepslot (with flap) one at each end 1" wide by 1/4" 2 Intermediate sill wall, one at each high weepslot 1/2" long by track width 2 Sill roller track cut short at each end weep notch Hardware: Description Quantity Location Metal cam lock 2 (4) Lock stile, one 8" in from ends, and keeper with mating keeper on the fixed stile Single metal roller with 2 (4) Bottom rail, one at each end plastic housing Reinforcement: The fixed meeting stile contained an extruded aluminum reinforcement measuring 1.000" by 0.924" by 0.125", reference Drawing No. RFSH204AOM. The lock stile, and handle stile contained an extruded aluminum reinforcement measuring 0.870" by 0.846" by 0.135", reference Drawing No. RFSE1347AOM.

Page 5 of 7 Test Results: The results are tabulated as follows: Paragraph Title of Test - Test Method Results Allowed Test Specimen #1: HS-R30 69 x 48 Optional Performance 2.1.4.1 Uniform Load Deflection per ASTM E 330 (Deflections reported were taken on the exterior meeting stile) 35.0 psf (positive) 0.41" See Note #1 35.0 psf (negative) 0.64" See Note #1 Note #1: The Uniform Load Deflection test is not a requirement of ANSI/AAMA/NWWDA 101/I.S.2-97 for this product designation. The deflection data is recorded in this report for special code compliance and information only. 2.1.4.2 Uniform Load Structural per ASTM E 330 (Permanent sets reported were taken on the exterior meeting stile) 52.5 psf (positive) 0.17" 0.18" max. 52.5 psf (negative) 0.18" 0.18" max. Test Specimen #2: HS-R20 104 x 48 Optional Performance 2.1.4.1 Uniform Load Deflection per ASTM E 330 (Deflections reported were taken on the exterior meeting stile) 20.0 psf (positive) 0.22" See Note #1 20.0 psf (negative) 0.12" See Note #1 2.1.4.2 Uniform Load Structural per ASTM E 330 (Permanent sets reported were taken on the exterior meeting stile) 30.0 psf (positive) 0.01" 0.178" max. 30.0 psf (negative) 0.04" 0.178" max.

Page 6 of 7 Test Results: (Continued) Paragraph Title of Test - Test Method Results Allowed Test Specimen #3: HS-R25 104 x 48 Optional Performance 2.1.4.1 Uniform Load Deflection per ASTM E 330 (Deflections reported were taken on the exterior meeting stile) 25.0 psf (positive) 0.35" See Note #1 25.0 psf (negative) 0.39" See Note #1 2.1.4.2 Uniform Load Structural per ASTM E 330 (Permanent sets reported were taken on the exterior meeting stile) 37.5 psf (positive) 0.01" 0.178" max. 37.5 psf (negative) 0.02" 0.178" max. This report is reissued in the name of Master Window Systems, Inc. through written authorization of Veka, Inc. to whom the original report was rendered. The original Veka, Inc. Report No. is 68612.01-501-47. Detailed drawings, representative samples of the test specimen, and a copy of this report will be retained by Architectural Testing, Inc. for a period of four years from the original test date. The results herein were secured by using the designated test methods and they indicate compliance with the performance requirements of the referenced specification. This report does not constitute certification of this product, which may only be granted by the certification program administrator. This report may not be reproduced, except in full, without the approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC.: Lynn George Project Manager Michael L. Mackereth Director - Operations LG:jld Attachments (pages): Appendix-A: Alteration Addendum (1)

Page 7 of 7 Revision Log Rev. # Date Page(s) Revision(s) 0 09/13/07 N/A Original report issue - Reissue of Report No. 68612.01-501-47 in the name of Master Window Systems, Inc.

Appendix A Alteration Addendum Note: No alterations were required.