GIB Quiet Clip GIB CBI March Features and Benefits

Similar documents
Intertenancy Barrier Systems for Terrace Homes

Noise Control Systems

INTERTENANCY SYSTEMS 2018

Volume II FWPRDC PN Maximising impact sound resistance of timber framed floor/ceiling systems. Page 183

SECTION D Masonry Wall Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications.

GIB FIRE RATED SYSTEMS. Product. Scope. Building Regulations. Appraisal No. 289 [2018] Logo. Appraisal No. 289 (2018) BRANZ Appraisals

5.0 GIB PERFORMANCE SYSTEMS INSTALLATION

GIB FIRE RATED SYSTEMS. Product. Scope. Building Regulations. Fire Rated Systems Specification and Installation Manual GIB. Appraisal No.

Maximising impact sound resistance of timber framed floor/ ceiling systems Volume 3

SECTION E Ceiling Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications. Floor/Ceiling Systems

Acoustical Characteristics of Carpet

Reverberation Control Systems

Noise Control Systems Supplement

PROMATECT hour walls

LOXO CLADDING SOUND INSULATION PERFORMANCE. Opinion on Acoustic Performance of. Loxo Cladding Systems Utilising Aerated Concrete.

PROMAtect H 4 hour walls. progressivematerials.com.au


wet area systems Product BRANZ APPRAISAL No. 427 (2007) Scope Building Regulations

SECTION B Steel Frame Wall Systems. Contents. Steel Stud Selection Tables. Introduction. Design Considerations. Installation.

GIB EZYBRACE SYSTEMS 2011

Single frame acoustic separating wall system

PROMATECT 100 Solid Partitions

Experimental setup. Each design was constructed and tested

June Non - Residential New Build Partition walls

Status: Rev: Comments Date: Author: Reviewer:

June Non - Residential Refurbishment Separating floors

2.0 GIB PRODUCT RANGE

June Residential Refurbishment Separating floors

Contents. Timber framing to be installed in accordance with AS:1684 Metal framing to be installed in accordance with BCA Volume: 2

This page was. intentionally. left blank

Intertek Testing Services

FIRE RATING MATERIAL FIXING NOTES

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to URBAN SURFACES. Series/Model: Urban Surfaces Soundtec

Presented By: Jim O Neill. Acoustics

1. The subfloor must be structurally sound and able to withstand live and dead loads with a deflection limitation of L/360.

SubPrimo. subprimo. Acoustic insulation for timber & laminate flooring. Uniclass L5395:N372 EPIC E485:Y45. CI/SfB (43) T (P2)

SOUND INSULATION ASSESSMENT RANELAGH MULTI-DENOMINATIONAL SCHOOL, DUBLIN October 2014

METRA INTER- TENANCY WALL SYSTEM. Product. Scope. Appraisal No. 985 [2018] Appraisal No. 985 (2018) BRANZ Appraisals

Acoustic. . Absorbs sound reduces noise transmission between rooms for a quieter more relaxing home

Opinion on Acoustic Performance of. Rockcote Systems Utilising Integra Aerated Concrete. 08 December 2010

LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

PLYWOOD FLOATING FLOOR

SOUND INSULATION TESTING IN DWELLINGS

Acoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A August 2016 CONSTRUCTION

Metal Web Floor System

RESILIENT SOUND ISOLATION CLIPS

84 Symonds Street PO Box 5811 Wellesley Street Auckland 1141 New Zealand T: F:

KINETICS NOISE CONTROL TEST REPORT #AT001052

GenieClip. Sound Isolation Clips. It s not magic, it s engineering. Impact and Airborne Sound Control

Creating perfect living spaces. Shaping spaces for living, with internal lining solutions that enhance lifestyles. Creating perfect living spaces

FIRE PROTECTION. GTEC Shaftwall systems 244 GTEC Shaftwall Stairwell systems 248 GTEC Horizontal Shaftwall systems 249 GTEC Encasement systems 250

Please Note: PhoneStar was previously branded as Phonewell

Sound Control Solutions in Floor/Ceiling Assemblies

robustdetails E-FC-7 Separating Floor Concrete Separating Floors Concrete E-FC-7

Silencer Rubber Underlayment

Internal walls. Creating perfect living spaces. Technical Advice Centre Tel:

Selecting floors and ceilings

PREDICTING SOUND INSULATION PERFORMANCE

Building a Quieter Home

GypWall TM ROBUST 4.4. GypWall ROBUST. Durable impact resistant partition system. Key facts. Sector Guide

Specialists in Acoustic Flooring and House to Flat Conversions

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Forest rx

C06. S05. P02 P12 GypFloor silent

C06. S05. P02 P12 GypFloor silent

April Section 4.3. Separating Floors

rondo acoustic wall & ceiling systems manual

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES

Instruction and Safety Manual Resilient Sound Isolation Clips (SIC Clips)

SECTION GYPSUM BOARD SYSTEM

Flanking Transmission at Joints in Multi-Family Dwellings. Phase 1: Effects of Fire Stops at Floor/Wall Intersections

PinkWood Ltd. Revised September 29, 2017

RSIC-1 ACOUSTIC ASSEMBLY

Floor Insulation Underlayment Section Sound Control Matting

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10

LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO )

KINETICS NOISE CONTROL TEST REPORT # AT001084

RSIC-1 ACOUSTIC ASSEMBLY

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Expona

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4005

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4002

SECTION GYPSUM BOARD SYSTEM

FLOOR CEILING ASSEMBLY

ACOUSTICAL PERFORMANCE TEST REPORT

Part E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague,

Staggered stud acoustic partition system

SPECIFICATION: CLASSIC PROGRESSIVE MOVABLE WALL SYSTEM DEMOUNTABLE STEEL STUD AND GYPSUM BOARD PARTITIONS

FIRM-FILL SCM-400 can be installed under a FIRM-FILL Gypsum Concrete Floor Underlayment to produce an exceptional vibration isolation floor system.

LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO )

GypWall Secure Systems

A simplified approach to impact sound insulation rating without using a tapping machine

GypLyner (walls) Metal framed wall lining system. GypLyner.

HACKER SOUND MAT II, to create a quieter living environment while meeting demanding project specifications in multi-family construction.

acoustics 101 The following is a brief tutorial that describes the use of a flooring underlayment as an acoustic barrier.

Installation Guide and Safety Manual Resilient Sound Isolation Clips (SIC Clips)

ENKASONIC FLOOR UNDERLAYMENT 9110

Stark Truss Company, Inc. Revised December 14, 2018

Part E robustdetails. robustdetails. September 2015 Update Pack. Dear Colleague,

KINETICS NOISE CONTROL TEST REPORT #AT001067

Transcription:

CBI - 5113 March 2002 GIB Quiet Clip Features and Benefits No special flooring systems required Easy fit Installation Significantly improves low frequency sound transmission Significantly improves low frequency impact insulation Superior, cost effective noise control for floor/ceiling systems Fully tested for use with GIB Noise Control Systems A reduction in low frequency sound such as bass stereo and footfall noise is clearly noticeable when the is installed correctly. NZ Patent Application Number 506991

TECHNICAL INFORMATION PERFORMANCE COMPARISONS STC and IIC ratings The ability of a floor/ceiling to reduce noise is expressed as the Sound Transmission Class (STC) for airborne noise, and the Impact Insulation Class (IIC) for impact noise. Examples of airborne noise are people talking, the TV or stereo being played. Examples of impact noise are people walking, scratching chairs or items being dropped on a floor. STC The ISO 140-3 standard laboratory test for airborne noise exposes a specimen to noises over a frequency range between 100 and 3150 Hz. On the basis of the noise reduction achieved over this range, a single figure STC rating is calculated. This single figure STC rating does not provide any information about the system s performance when exposed to any particular frequency. The laboratory test also does not consider the performance in the frequency range below 100 Hz, where base thumping noises are most annoying. The The performance of the may not be immediately evident from the single figure STC rating. However, low frequency noises in the 50-500 Hz are dampened and will be experienced by occupants as much softer and more acceptable. Figure 1 compares the STC performance of the standard GIB Rondo Direct Fixed Clip with the. Airborne Sound Reduction 60.0 50.0 40.0 30.0 20.0 10.0 Standard GIB Clip 50 63 80 100 125 160 200 250 315 400 500 Frequency Hz Figure 1. Low frequency STC performance enhancement achieved by using the Notes for guidance The higher the bar, the better the performance a 3dB difference in any frequency is noticed by most people a 5dB difference is clearly noticeable IIC The ISO 140-6 standard laboratory test for impact noise uses a tapping machine exposing a specimen to impact frequencies ranging from 100 to 3150 Hz. On the basis of the noise reduction achieved over this range, a single figure IIC rating is calculated. This single figure IIC rating does not provide any information about the system s performance against any particular frequency. The laboratory test also does not consider the performance in the frequency range below 100 Hz where footfall impact noise (walking) is most annoying. The Again the performance of the is not immediately apparent from the single figure IIC rating. However, Figure 2 shows that low frequency impact noises are dampened significantly. Occupants will experience the loudness of footfall noise in the frequency range from 50-500 Hz as much softer and more acceptable. Impact Sound Received 76.0 74.0 72.0 70.0 68.0 66.0 64.0 62.0 60.0 58.0 56.0 Standard GIB Clip 50 63 80 100 125 160 200 250 315 400 500 Frequency Hz Figure 2. Low frequency IIC performance enhancement achieved by using the Notes for guidance The lower the bar, the better the performance a 3dB difference in any frequency is noticed by most people a 5dB difference is clearly noticeable

Residential Noise Control Floor/Ceiling System Timber Joists - GIB Quiet Zone Specification Loadbearing STC RW IIC Fire Resistance Lining Number Capability Rating Rating N/A LB *50 *50 *64 (See IIC below) N/A 1 x 13mm GIB Standard Floor Framing Floor joists shall comply with NZ 3604, be spaced at 600mm centres and have a depth of 200mm minimum alternatively use either Origin I-beams or CHH Hybeam HJ series joists designed for strength and serviceability, no less than 240mm deep and spaced at no more than 600mm. Nogs fixed on the flat to receive edges of flooring material shall be 100mm x 50mm minimum. Consult the beam manufacturer regarding construction of the solid blocking contained in the floor/ceiling to wall junctions. Flooring Minimum flooring shall be nominal 20mm particle board or minimum 17mm thick structural plywood fixed to the manufacturers instructions. and Battens The shall be fastened to the joists at maximum 1200mm centres (and no less than 900mm centres) to support the. The battens shall be spaced at 600mm centres maximum. It is important that these specific brands of batten and clips are used when specifying and installing GIB Noise Control Systems. Site tests have shown that other brands can have STC performances up to 10 STC points lower. Installing the Use 3 x 32mm x 8g GIB Grabber wafer head screws. Insert the first screw into the middle rubber grommet, tighten enough to hold the in place, adjust the clip to the correct height, insert the remaining two screws and tighten. the grommet is crushed. The screws should be tightened enough to allow the flexibility to remain in the connection between the grommet and the joists. Sound Control Infill Ceiling overlaid with R1.8 (75mm) pink Fibreglass batts. Alternatively, Autex R1.8 Greenstuf 95mm battens. Sheet are touch fitted. Ceiling Lining 1 layer of 13mm GIB Standard fixed at right angles to the steel battens. All sheet end butt joints shall occur on the battens. Sheet are touch fitted. Fastening the Lining Fasteners 25mm x 6g GIB Grabber Scavenger Head Drywall Self Tapping Screws Fasteners centres 200mm centres along each batten and along sheet end butt joints. Place fasteners no closer than 12mm to the sheet edges. Acoustic Sealant A bead of GIB Soundseal acoustic sealant is required around the ceiling perimeter. the grommet is crushed 1 x 13mm GIB Standard 1 x 13mm GIB Standard Light Fittings Use surface mounted light fittings. The penetration for the electric cable shall be packed with an acoustic sealant. Wall/Ceiling Junctions The internal angle between the ceiling and the walls are protected by GIB Cove adhered with GIB Cove adhesive or boxed corners (square stopped) filled and taped in accordance with the publication entitled GIB Living Solutions Site Guide. Jointing All fasteners heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled GIB Living Solutions Site Guide. Impact Insulation Class (IIC) A performance of IIC 39 is achieved by a bare floor A performance of IIC 40 is achieved with a 2mm thick cushion backed vinyl on particle board or structural plywood. A performance of IIC 64 is achieved with a 48oz hard twisted wool hessian backed carpet over a rubberwaffle underlay. * Note Estimated STC and IIC Performance and

Residential Noise Control Floor/Ceiling System Timber Joists - GIB Quiet Zone Upgrade Specification Loadbearing STC RW IIC Fire Resistance Lining Number Capability Rating Rating GBDFA 30c LB 53 53 71 (See IIC below) 30/30/30 2 x 13mm GIB Standard Floor Framing Floor joists shall comply with NZ 3604, be spaced at 600mm centres and have a depth of 200mm minimum. Alternative Floor Framing Use either Origin I-beams or CHH Hybeam HJ series joists designed for strength and serviceability, no less than 240mm deep and spaced at no more than 600mm. Nogs fixed on the flat to receive edges of flooring material shall be 100mm x 50mm minimum. Consult the beam manufacturer regarding construction of the solid blocking contained in the floor/ceiling to wall junctions. Flooring Minimum flooring shall be nominal 20mm particle board or minimum 17mm thick structural plywood fixed to the manufacturers instructions. Note: To ensure the FRR is achieved, nogs are required behind tongue or adhesive fixed flooring sheet joints and Battens The shall be fastened to the joists at maximum 1200mm centres (and no less than 900mm centres) to support the. The battens shall be spaced at 600mm centres maximum. It is important that these specific brands of batten and clips are used when specifying and installing GIB Noise Control Systems. Site tests have shown that other brands can have STC performances up to 10 STC points lower. Installing the Use 3 x 32mm x 8g GIB Grabber wafer head screws. Insert the first screw into the middle rubber grommet, tighten enough to hold the in place, adjust the clip to the correct height, insert the remaining two screws and tighten. the grommet is crushed. The screws should be tightened enough to allow the flexibility to remain in the connection between the grommet and the joists. Sound Control Infill Ceiling overlaid with R1.8 (75mm) pink Fibreglass batts. Alternatively, Autex R1.8 Greenstuf 95mm battens. Sheet are touch fitted. Ceiling Lining 2 layers of 13mm GIB Standard fixed at right angles to the battens. Offset the joints of the outer layer by 600mm from those of the inner layer. All sheet end butt joints shall occur on the battens and are offset between the first and second layers. Sheets are touch fitted. Fastening the Lining Fasteners Inner layer - 25mm x 6g GIB Grabber Scavenger Head Drywall Self Tapping Screws Outer layer - 41mm x 6g screws as above Fasteners centres 200mm centres along each batten and along sheet end butt joints. Place fasteners no closer than 12mm to the sheet edges. the grommet is crushed 2 x 13mm GIB Standard and Joist 2 x 13mm GIB Standard Acoustic Sealant A bead of GIB Soundseal acoustic sealant is required around the ceiling perimeter. The outer lining is then bedded onto the bead. Light Fittings Use surface mounted light fittings. The penetration for the electric cable shall be packed with a fire rated sealant. Wall/Ceiling Junctions The internal angle between the ceiling and the walls are protected by GIB Cove adhered with GIB Cove adhesive or boxed corners (square stopped) filled and taped in accordance with the publication entitled GIB Living Solutions Site Guide. Jointing Inner unstopped Outer layer - all sheet fasteners heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled GIB Living Solutions Site Guide. Impact Insulation Class (IIC) A performance of IIC 46 is achieved by a bare floor A performance of IIC 47 is achieved with a 2mm thick cushion backed vinyl on particle board or structural plywood. A performance of IIC 71 is achieved with a 48oz hard twisted wool hessian backed carpet over a rubberwaffle underlay.

TECHNICAL INFORMATION PERFORMANCE COMPARISONS Inter-tenancy Noise Control Floor/Ceiling System Timber Joists Specification Loadbearing STC RW IIC Fire Resistance Lining Number Capability Rating Rating GBDFA 60c GBCJA 60a LB 56 56 72 (See IIC below) Floor Framing Floor joists shall comply with NZ 3604, be spaced at 600mm centres and have a depth of 200mm minimum. Alternative Floor Framing Use either Origin I-beams or CHH Hybeam HJ series joists designed for strength and serviceability, no less than 240mm deep and spaced at no more than 600mm. Nogs fixed on the flat to receive edges of flooring material shall be 100mm x 50mm minimum. Consult the beam manufacturer regarding construction of the solid blocking contained in the floor/ceiling to wall junctions. Flooring Minimum flooring shall be nominal 20mm particle board or minimum 17mm thick structural plywood fixed to the manufacturers instructions. Note: To ensure the FRR is achieved, nogs are required behind tongue or adhesive fixed flooring sheet joints and Battens The shall be fastened to the joists at maximum 1200mm centres (and no less than 900mm centres) to support the. The battens shall be spaced at 600mm centres maximum. It is important that these specific brands of batten and clips are used when specifying and installing GIB Noise Control Systems. Site tests have shown that other brands can have STC performances up to 10 STC points lower. Installing the Use 3 x 32mm x 8g GIB Grabber wafer head screws. Insert the first screw into the middle rubber grommet, tighten enough to hold the in place, adjust the clip to the correct height, insert the remaining two screws and tighten. the grommet is crushed. The screws should be tightened enough to allow the flexibility to remain in the connection between the grommet and the joists. Sound Control Infill Ceiling overlaid with R1.8 (75mm) pink Fibreglass batts. Alternatively, Autex R1.8 Greenstuf 95mm battens. Sheet are touch fitted. Ceiling Lining 2 layers of 13mm GIB Noiseline fixed at right angles to the battens. Offset the joints of the outer layer by 600mm from those of the inner layer. All sheet end butt joints shall occur on the battens and are offset between the first and second layers. Sheets are touch fitted. Fastening the Lining Fasteners Inner layer - 25mm x 6g GIB Grabber Scavenger Head Drywall Self Tapping Screws Outer layer - 41mm x 6g screws as above Fasteners centres 200mm centres along each batten and along sheet end butt joints. Place fasteners no closer than 12mm to the sheet edges. 60/60/60 2 x 13mm GIB Noiseline the grommet is crushed 2 x 13mm GIB Noiseline and Joist 2 x 13mm GIB Noiseline Acoustic Sealant A bead of GIB Soundseal acoustic sealant is required around the ceiling perimeter. The outer lining is then bedded onto the bead. Light Fittings Use surface mounted light fittings. The penetration for the electric cable shall be packed with a fire rated sealant. Wall/Ceiling Junctions The internal angle between the ceiling and the walls are protected by GIB Cove adhered with GIB Cove adhesive or boxed corners (square stopped) filled and taped in accordance with the publication entitled GIB Living Solutions Site Guide. Jointing Inner unstopped Outer layer - all sheet fasteners heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled GIB Living Solutions Site Guide. Impact Insulation Class (IIC) A performance of IIC 47 is achieved by a bare floor A performance of IIC 50 is achieved with a 2mm thick cushion backed vinyl on particle board or structural plywood. A performance of IIC 72 is achieved with a 48oz hard twisted wool hessian backed carpet over a rubberwaffle underlay.

Installation Guide Lines and GIB Rondo Battens The shall be fastened to the joist at maximum 1200mm centres (and no less than 900mm centres) to support the GIB Rondo batten. The battens shall be spaced at 600mm centres maximum for linings 13mm thick, and at 450mm centres maximum for linings 10mm thick. the grommet is crushed. and It is important that these specific brands of batten and clips are used when specifying and installing GIB Noise Control Systems. Site tests have shown that other brands of metal clips and battens can perform up to 10 STC points below the tested brands above. Installing the Using 3 x 32mm x 8g GIB Grabber wafer head screws. Insert the first screw into the middle rubber grommet, tighten enough to hold the in place, adjust to the clip correct height and insert the remaining two screws and tighten up. GIB Noiseline Joist the grommet is crushed. The screws should be tightened enough to allow the flexibility to remain in the connection between the grommet and the joists. Substitution GIB Systems for Sound Control are not generic. GIB Noiseline It is important that only GIB branded components are used when specifying and installing GIB Sound Control Systems. Substitution is not in accordance with GIB Systems recommendations and must be at the risk of the owner, specifier or builder. If you wish to substitute then you must first ensure that the alternative proprietary brand supplier can provide documentary evidence of NZBC compliance, including structural, noise control IIC and STC durability and hazardous material. For further systems detail please refer to Winstone Wallboards Ltd. Please phone the GIB information Helpline 0800 100 442