Estimation of existing tall buildings pile foundations bearing capacity under seismic and wind loads. T.Davitashvili 1,a, I.

Similar documents
The Effects of Building Parameters on the Modal Displacement Shapes of Tall Buildings

MODAL PUSHOVER ANALYSIS OF RC FRAME BUILDING WITH STAIRCASE AND ELEVATOR CORE

Strengthening of infilled RC frames by CFRP

Structural Design of Super High Rise Buildings in High Seismic Intensity Area

International Journal of Advance Engineering and Research Development

Earthquake Damage Assessment of Reinforced Concrete Hotel Buildings in Hawaii

Miss. Sayli S Kamble. 1, Prof. Dr. D. N. Shinde 2 1 Department of civil Engineering, PVPIT Budhgaon, Shivaji university, Maharashtra, India.

Department of Civil Engineering, SKP Engg. College, Tiruvanamalai, TN, India

Seismic Performance of Residential Buildings with Staggered Walls

Seismic Behaviour of Multi-Storied RCMRF Buildings Resting on Sloping Ground

The use of micropiles as a form of underpinning of existing commercial buildings development of IKEA hall in Gdańsk

Earthquake Resistant Design for Low Rise Open Ground Storey Famed Building

Council on Tall Buildings

FOUNDATIONS. Foundations Copyright G G Schierle, 2006 Press Esc to end, for next, for previous slide 1

Effect of Openings in Shear Wall

EFFECT OF SOFT STOREY LEVEL VARIATION ON TORSIONAL ROTATION OF LEAD RUBBER BASE ISOLATED STRUCTURE

THE INTERNATIONAL JOURNAL OF SCIENCE & TECHNOLEDGE

SEISMIC BEHAVIOR OF MULTI-STORY STRUCTURE WITH DIFFERENT TYPES OF SLABS

Seismic Performance Of R C Flat-Slab Building Structural Systems

Lateral System Analysis and Confirmation Design

Experimental study on the seismic performance of RC moment resisting frames with precast-prestressed floor units.

Research on the Influence of Infill Walls on Seismic Performance of Masonry Buildings with Bottom Frame-Shear Walls

Effect of Change in Shear Wall Location with Uniform and Varying Thickness in High Rise Building

Case Study: Challenges of a Single-layer Reticulated Dome

LEARNING OF ETABS. 15 ft

Seismic Performance of Multistorey Building with Soft Storey at Different Level with RC Shear Wall

PEER Tall Building Seismic Design Guidelines

Earthquake behaviour of a reinforced concrete building constructed in 1933 before and after its repair

EQUIVALENT UNIFORM DAMPING RATIOS for Irregular in Height Concrete / Steel Structural systems

Keywords: Discrete Staggered Shear Wall, High-Rise Building, Response Spectrum Analysis, Storey Drift.

Effect of Building Height on Torsional Response of Lead Rubber Bearing Base Isolated Structures-A Study

Comparative Study of Equivalent Static Analysis and Response spectrum analysis on Flat Slab Using Etabs

SSRG International Journal of Civil Engineering ( SSRG IJCE ) Volume 4 Issue 6 June 2017

N.Nageswarao Department of Civil Engineering, Amara Institute of Engineering and Technology.

Literature survey on Analysis of Multistory Building considering Hybrid Structure

Invention: Seismic Retrofitting by Exterior Steel Brace Structural Building Jacketing System

Council on Tall Buildings. and Urban Habitat BACKGROUND SECTION STEEL REINFORCED CONCRETE SHEAR WALL STEEL PLATE COMPOSITE SHEAR WALL

Research on Design of High Rise Building Based on Seismic Design Theory

Optimum Position of Multi Outrigger Belt Truss in Tall Buildings Subjected to Earthquake and Wind Load

Civil Engineering Construction I (CBE5031)

Comparative Cost Analysis of Possible Seismic Retrofitting Schemes for Multi-Story Unreinforced Masonry Building

Comparative Study of Multi-storeyed RC Building With Open Ground Storey Having Different Type Infill Walls

Analysis and Design of a Multi-storey Reinforced Concrete Building

BUILDING INTEGRITY DEA SUMMARY REPORT

Study of seismic effect on buildings modified with shear wall

EARTHQUAKE ANALYSIS OF A G+12 STOREY BUILDING WITH AND WITHOUT INFILL FOR BHUJ AND KOYNA EARTHQUAKE FUNCTIONS

Detailed Seismic Assessment Report. Islington Substation August 2011

Strengthening or Retrofitting

Dynamic Analysis of Reinforced Concrete Framed Structures with Infill Wall Chethana M S Assistant Professor Department of Civil Engineering

ANALYSIS AND EVALUATION OF STRUCTURAL SYSTEMS WITH BRACING AND SHEAR WALL

SEISMIC RESPONSE OF A MID RISE RCC BUILDING WITH SOFT STOREY AT GROUND FLOOR

Alexis Pacella Structural Option Dr. Schneider Lexington II, Washington D.C. Technical Report #3 November 21,

Optimization in the Selection of Structural Systems for the Design of Reinforced Concrete High-rise Buildings in Resisting Seismic Forces

Comparison and Optimization of 8 Storeys Ordinary Moment Resisting Frame and Special Moment Resisting Frame Building


S. Gandhi *1, Syed Rizwan 2

Seismic Analysis and Design of Vertically Irregular RC Building Frames

An Experimental Study on the Effect of Opening on Confined Masonry Wall under Cyclic Lateral Loading

Sonnet Textile Industries Ltd.

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):

Static and Dynamic Behavior of Reinforced Concrete Framed Building: A Comparative Study

COMPARATIVE ANALYSIS OF A MULTISTORY BUILDING BY RESPONSE SPECTRUM METHOD AND SEISMIC COEFFICIENT METHOD

A seismic engineer s note book

DYNAMIC ANALYSIS OF MULTI STOREY STRUCTURE FOR DIFFERENT SHAPES. K.Upendra Reddy 1,Dr.E.Arunakanthi 2

Conventional formwork & mivan formwork structure A comparative study &analysis

Effects of opening in shear walls of 30- storey building

IS 1893 and IS Codal Changes

Analysis the Behavior of Building with Different Soft Story

Concept of Earthquake Resistant Design

1. INTRODUCTION 1.1 FLAT SLAB. 275 P a g e

Seismic Analysis Of Multi Storied Irregular Building Using Flat Slab And Grid Slab In Zone III & V

Construction Technology B (CON4313)

Note on the assessment:

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

DETAILED ANALYSIS AND DESIGN OF SLAB-WALL SYSTEM AND COLUMN-BEAM SYSTEM IN CONCRETE BUILDING

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online):

Comparative Study of Seismic Analysis between Conventional RC Frame and Flat Slab with Drop Muniraju K.S 1 Subramanya K.G. 2

Analysis of RC building in different seismic zones by moment resisting frame using IS 1893:2002

ANALYTICAL STUDY ON SEISMIC RESPONSE WITH AND WITHOUT SOFT STOREYS IN MULTISTOREY RC BUILDING

Comparison of Eurocode 8 and Turkish Earthquake Code 2007 for Residential RC Buildings in Cyprus

Seismic retrofitting of Pombalino frontal walls

MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS

MID-STORY SEISMIC ISOLATION FOR STRENGTHENING OF A MULTI-STORY BUILDING

NONLINEAR PERFORMANCE OF A TEN-STORY REINFORCED CONCRETE SPECIAL MOMENT RESISTING FRAME (SMRF)

Structural Engineering, Mechanics, and Materials. Preliminary Exam - Structural Design

The Wind and Seismic Analysis on Different Heights of Building by Using ETABS

International Journal of Intellectual Advancements and Research in Engineering Computations

Seismic Response of RC Frame Buildings with Soft Storeys

Experience of design and analysis of multistory buildings

STUDY ON THE BEHAVIOR OF BUILDING UNDER DIFFERENT SOIL CONDITIONS

Comparative Study of Flat Slab and Conventional Slab using Software Aid

Evaluation of Response Reduction Factor and Ductility Factor of RC Braced Frame

Computer Aided Design of Modern High-Rise Building

Simplified Finite Element Modelling of Multi-storey Buildings: The Use of Equivalent Cubes

Nonlinear Dynamic Analysis of Base Isolated Reinforced Concrete Building

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 09, 2015 ISSN (online):

Effect of Mass and Stiffness of Vertically Irregular RC Structure

Seismic Assessment of an RC Building Using Pushover Analysis

CHAPTER 2 SPECIMEN DETAILS, TEST SETUP AND TESTING PROCEDURE

Effects of configurations of shear walls on system behavior under seismic load

Transcription:

Estimation of existing tall buildings pile foundations bearing capacity under seismic and wind loads T.Davitashvili 1,a, I.Timchenko 2,b 1 Capto Group, 67, D.Aghmashenebeli ave., 0102 Tbilisi, Georgia 2 Hill International Ltd.;Transproject Ltd., 47, Shartava st. 0160 Tbilisi, Georgia a temodavi@yahoo.com, marsitexx@yahoo.com, b igortimchenko@hillintl.com, igortimchenko@gmail.com Keywords: soil, pile, structural optimization, seismic, wind load ABSTRACT In the paper two ways of justification of building's height increasing possibility are discussed - strengthening of foundations in order to improve their bearing capacity and numerical investigations of existing structure in order to identify its reserve of capacity. Results of structural analyses of a high-rise residential building are presented, performed in order to increase its height from 16- to 21 with minimized intervention level to the originally designed structure. At the period of investigations 11 floors of the building have been erected. The positive results of analyses allowed to reject proposed by designers method of strengthening of existing pile foundation and sub-grade soils using bore-injection piles. Introduction Increase of the buildings' height all over the world becomes a real factor in spite of all design and construction complexities. Especially, it's important for large cities in conditions of expensive and limited construction areas. Typically investors encourage investigations related to optimal use of the capacity reserve of structures since this allows to increase the number of floors and therefore to increase effectiveness of investments. And usually the idea of structural optimization comes when foundations and part of the structure are already completed. This creates additional difficulties providing minimal necessary reinforcement of upper structure when existing foundation already has some limit of bearing capacity and its reinforcement requires more serious investments and intervention to the foundation sometimes causes large technical and financial problems. Therefore, modifications to the structure in order to improve effectiveness of investment are often limited by the bearing capacity of existing originally designed foundations. Preliminary the owner of the building ordered design of 16-story multi-story residential structure. Therefore, when the frame was erected up to 11 stories, according to the project of Tbilisi Mayor`s Office New Life of Old Tbilisi it was recommended to increase the building's height with 5 additional stories. New design project considered strengthening of existing structures columns and inclusion of additional diaphragms of stiffness. But the question of the reinforced concrete piles strengthening remained undecided. Some technical proposals regarding reinforcement of the original foundation structure have been not applicable technically and required not acceptable additional investments. 4-14

Proposed methods to solve the problem Reinforcement of Foundations. The main problem related with the pile foundations is consisted in the method of strengthening, recommended by designers. Briefly, these recommendations include the following steps: 1. To drill boreholes at the depths 10.5-22.7m in the places of those indicated in the project (Fig.1. Foundation slab and location of existing piles); fastening of piles in bedrock at the depth not less than 1.0m is necessary. 2. At drilling works of foundation slab not to damage reinforcing bars of the slab. 3. In the drilled borehole to be installed d=127mm steel perforated pipe with a length of 3000 mm, which will remain into the body of pile after concreting. Then, reinforcing bars Ø32 A-III will be installed in the borehole preliminarily painted with two layers of anticorrosion paint. The mixture supply to the bore hole to be done under the pressure 10 atmosphere. Total length of 694 bore-injection piles 12151m. Fig. 1. Location of existing piles under the slab (from design model) 4. From the point of view of the technology the concreting of the cementation bore -injection piles is performed from the bottom level to the top. 5. Required amount of materials for the injection works: concrete volume - 162m 3 ; steel pipes - 25.3t and steel bars - 76t. Implementation of these works required unjustified charges and more than 2.0 million dollars. Technically this method was unrealizable as well. Unrealizable because of height of the first floorcar park H=2.12-2.44 m. No drilling facilities can work in this space area and drill about 12.0 km bore-holes. Ineffective, since the cementation process is uncontrolled and the results of strengthening are not predictable. In addition, drilling process of the bottom concrete slab by oneself caused many damaged of reinforcement of existing slab. Thus, due to technical and financial reasons this method of improvement of the foundation capacity has been rejected. 4-15

Structural Analyses. Alternatively, the numerical analyses of the building capacity have been proposed with adjusted input data. First of all, the existing engineering-geology investigation report ( Autodesignroad Ltd, dated 2005) has been analyzed. The results of this investigation showed that the soil bearing capacity value (1.70MPa for bedrock) could be adjusted. Characteristics of the base rock with alternation of the inter thin layers of argillites and loamy sandstones seemed inadequate and it was decided to perform the new engineering-geology investigations. This job was implemented by Georgian Institute for Regional and Urban Planning AKHALI SAKKALAKMSHENPROEKTI LTD (Report #11-18/45, 12/10/2011). Description of the Building Multi-storey apartment house #34a, Al. Kazbegi ave., in the central part of Tbilisi is characterized by overall dimensions in plan - 24.4x60.0m. Structural system of the building - monolithic reinforced concrete frame with RC diaphragms and pumice concrete blocks for infill external walls and partitions. The total height of the building including car park is 65m. The building is not regular, the column mesh is different - 6.6x6.6m; 6.0x6.6; 6.6x4.4 and 6.0x4.4m. Location of diaphragms is shown below: Fig. 2. Design numerical model, location of RC diaphragms The soil conditions on the site area and the basic soil lithologic sections are presented by four engineering geology elements (EGE): EGE - 1. Filled soil with thickness up to 1.4m; EGE - 2. Sandy loam with inter layers of sand and loam, small degree of water saturation and layers of the average degree of water saturation, solid, unsettled, depth from 1.4 to 18.5m; EGE - 3. Crushed material of base rock with loam filling, unsettled, depth from 18.5 to 22.0m; EGE - 4. Base rock with alternation of inter thin layers of argillite and loamy sandstones, slightly weathered, unsettled with depth from 22.0 to 25.0m. The established level of underground water for the period of investigations (03.10.2011) was fixed in sandy loams at the depth of 1.4-1.6m from the surface. The end-bearing piles with d=1.2m are fixed into this type of soil. 4-16

Input Data for Numerical Analyses For numerical analyses of the building the following important adjustments and modifications have been done: - Adjustments to the existing design model (originally developed by KONEX Ltd) related to geometry, physical-mechanical parameters of materials have been implemented. - Soil reaction parameters were adjusted based on last geological investigations. - Wind load cases with pulse component added. - Time history seismic load cases added. Several accelerograms have been applied- records of the Tbilisi 25 April 2002 epicentral earthquake, artificial accelerograms calculated for the construction area soil conditions. All records were scaled for 0.2g. One of artificial accelerograms is presented in Fig. 3. 4-17

Fig. 3. Artificial accelerogram #2, velocity, displacement functions, response spectra - Dead and imposed loads were adjusted as well. - Considering that the building is not regular in plan and rotational effects could take place, the diagonal directions of seismic excitation have been analized as well. All numerical analyses have been performed using structural software LIRA-Windows (developed in NIIASS- Kiev, Ukraine). Main Results of Analyses Results of numerical analyses contain full information on stress-strain state of the building's elements, their reinforcement, dynamic parameters of the building, vibration modes, horizontal displacements at design load combinations and other data. Maximum horizontal displacements in all directions under wind and seismic excitation are within code limits (Fig. 4, 5): Fig. 4. Maximum horizontal seismic displacements don't exceed 36cm (H/200) 4-18

Fig. 5. Maximum horizontal wind displacements don't exceed 13cm (including 6.1cm from pulse component) i.e. H/500 Calculated bearing capacity of piles [2] is defined as F d = c RA= 1*2166*1.131=2450t, where R R l c, n d 15, =1300/1.4*(1/1.2+1.5)=2166 t/m 2 g d f 1982<2450t with 20% reserve. Where 1982 t- maximum normal force in the element at the bottom level of the most loaded pile at design load combinations. 1300 t/m 2 - soil bearing capacity based on the engineering-geology investigations. Conclusions and Recommendations Based on analyses of results the main conclusions and recommendations have been developed: 1. The calculated bearing capacity of piles at design load combinations is sufficient for 21-story building with additional reserve of 20%. Minimal reserve of the load bearing capacity is 20 %. Reinforcement of piles 24Ø32=192cm 2 exceeds required reinforcement - 165cm 2 for A500 steel. No strengthening works of the pile foundation is required. 2. Horizontal displacements of the building due to seismic and wind loads are in the range of the construction rules and regulations requirements: seismic displacement is H/200 (H height of the building); wind displacement including pulse component is H/500 (13cm). 3. External infill walls and partitions to be erected with pumice blocks, that was taken into account in the project and in structural calculations. References [1] SNIP II-7-81*. Code of Construction. Construction in the Seismic Regions. Moscow, 1986. [2] SNiP 2.02.03-85. Code of Construction. Pile Foundations. Moscow, 1995. 4-19