1 BUILDING INTEGRITY DEA SUMMARY REPORT SUPPLIER NAME UNITS AUDITED Opex Mills SSL2 Building 4X Generator Building 6X Generator Building Denim Generator Building Rope Denim Generator Building SSL Generator Building Generator Utility Building Diesel Generator Building Label Building SUPPLIER ADDRESS AUDIT DATE December 2014 AUDIT PERFORMED BY AUDIT TEAM Kanchipur,Narayangonj,Dhaka,Bangladesh Arko Consults Environment & Infrastructure Management Solution (EIMS) 4 Members including structural engineer. BUILDING OVERVIEW SSL 3 Garment Manufacturing RCC frame structure 2 story/ Sqft/floor. Floor Load Ground Floor: Spinning section, 1st floor: Spinning & Office. Isolated. Yes 4X GENERATOR BUILDING Utility Reinforced concrete structure Two storied / Total building area approx. 8,440 sft Ground floor: Generator 1st floor: Generator Main building part foundation is shallow foundation over 8" diameter sand pile. Extended part is over 18" diameter cast in situ single pile. BUILDING INTEGRITY DEA INSPECTION SUMMARY OPEX MILLS PAGE 1/10
2 6X GENERATOR BUILDING DENIM GENERATOR Utility Reinforced concrete structure Two storied / Total building area approx. 9,838 sft Ground floor: Generator 1st floor: Generator Footing on timber piles (6 in diameter according to the drawing) Utility RC beam column frame structure 3 story/ Sq.ft Ground floor : Boiler room and generator room 1 st floor: Substation, Power plant, Chiller room and store 2 nd floor : Compressor, Dryer and Store Roof: (4 Cooling Tower, Boiler silencer pipe and connecting pipe network for cooler. Cast -in-situ concrete pile. ROPE DENIM GENERATOR BUILDING Utility RC beam column frame structure 3 Story/13300 Sq.ft Ground floor : Generator room 1 st floor: Boiler and Chiller room 2 nd Floor: Compressor, Dryer and Control Panel Roof : Generator, Cooling Tower, 12 Chiller cooling tower and connecting pipe network for cooling tower. Cast -in-situ concrete pile. GENERATOR UTILITY BUILDING Garment Manufacturing BUILDING INTEGRITY DEA INSPECTION SUMMARY OPEX MILLS PAGE 2/10
3 RCC frame structure 2 story/ approx.3000 sq.ft/floor Ground Floor: Utility Maintenance Store, 1st floor: office Single and Combine footing DIESEL GENERATOR BUILDING Floor Load LABEL BUILDING Garment Manufacturing RC Frame structure 3 story/ approx.645 sq.ft/floor Ground Floor: Vacant, 1st Floor: Vacant, 2nd Floor: 01 Electric Control Panel Single and Combine footing Garments Label manufacturing Reinforced concrete beam-column frame structure Four storied / Total building area approx. 10,232 sft Ground & 1 st floor: label section 2 nd & 3 rd floor: compressors Individual footing on 6 dia, 23 to 25 long, Wooden Piles (as per drawing) BRIEF DESCRIPTION OF METHODOLOGY Detailed Engineering Analysis (DEA) as Bangladesh National Building Code (BNBC) BUILDING INTEGRITY DEA INSPECTION SUMMARY OPEX MILLS PAGE 3/10
4 DETAILED CONTENT Evaluation and Test... 4 Conclusion AND Recommendations..4 SSL3 Building 4&5 4X Generator Building 5 6X Generator Building 5 and 6 Denim Generator Building. 6&7 Rope Denim Generator Building 7 SSL Generator Building.. 7 and 8 Generator Utility Building. 8 Diesel Generator Building. 9 Label Building..9 DETAILED DESCRIPTION OF METHODOLOGY.10 EVALUATION AND TEST Destructive and Non Destructive Test o Evaluation of concrete strength from core test. o Verification of Rebar of structural members by Ferro Scanning Analysis of structural adequacy Assessment of Foundation Evaluation of Column Evaluation of Beams Evaluation of Slabs SSL 3: No diagonal cracks were observed in the partition walls due to differential settlement. Hence foundation is considered to be safe at prevailing load conditions. The columns are found safe in gravity loading for a live load of 5kN/sqmtr. For lateral (Earthquake and wind) load, members are found safe. Grade Beams are adequate under vertical load. Slabs interior panel are adequate. BUILDING INTEGRITY DEA INSPECTION SUMMARY OPEX MILLS PAGE 4/10
5 Recommendations: NIL 4X GENERATOR BUILDING: It was found that average concrete strength was 2080 psi and equivalent strength of concrete 1764 psi according to ACI 562. Considering both existing and BNBC recommended live load all the floor beams are adequate considering vertical load. However, most of the beams are overstressed due to lateral loading. Some grade beams are also overstressed. The slab is adequate for this loading condition. There is some crack observed in the ground floor roof slab which is may be due to the vibration of the equipment. Most of the columns are overstressed for gravity loading. Similarly, most of the columns are overstressed due to lateral loadings when both existing and BNBC recommended 63 psf is considered. Footings are adequate with factor of safety above 2.0 for existing loading and 63 psf live loading. All the pile capacity is adequate for existing loading and 63 psf live loading with factor of safety above 2.0. Recommendations: To ensure desired performance of the building structural members need to be retrofitted based on proper retrofitting design. Exterior beam and cracked portion of slab need to be repaired as per retrofit design. However during this rectification times equipment and electromechanical machineries need to be relocated or shut down for the safety of people at site 6X GENERATOR BUILDING It was found that average concrete strength was 2255 psi and equivalent strength of concrete 871 psi according to ACI 562. The slab is adequate for existing loading as well as for BNBC recommended 63 psf live load. BUILDING INTEGRITY DEA INSPECTION SUMMARY OPEX MILLS PAGE 5/10
6 For both existing loading and for BNBC recommended 63 psf live load all the floor beams in typical floor are adequate without considering lateral loadings. Considering lateral loading a few numbers of floor beams and grade beams are overstressed. Most of the columns are overstressed due to existing and 63 psf live loading loadings condition and almost all the columns are overstressed due to lateral loadings. All the pile capacity is adequate for existing loading with factor of safety above 2.0 except two pile group. All the foundations are adequate for 63 psf live load with factor of safety above 2.0 except two (F.S above 1.5). Recommendations: Proper anchorage of boiler base need to ensure by casting pedestal of boiler. R.C.C. casting with rebar encasement can be used to avoid future cracks due to temperature change or movement. BUET recommendation for unreinforced masonry should be followed. Slenderness ratio of the columns is very high it needs to be addressed during selection of suitable retrofitting period. Performance of the non-durable timer piles need to be assessed. Here, detail liquefaction potential was not calculated due to unavailability of soil parameter from soil test data supplied by client. However during this rectification times equipment and electromechanical machineries need to be relocated or shut down for the safety of people at site DENIM GENERATOR BUILDING Average concrete strength was found 3425 psi and equivalent strength of concrete 2300 psi according to ACI 562. Considering the concrete strength suggested by ACI 562, all the columns, slabs are adequate (without considering any lateral load). The slab is adequate for existing loading. All the floor beams in typical floor are adequate considering lateral loadings. Some grade beams are overstressed. Considering BNBC 2006 with all its load combinations (i.e. gravity and lateral load) most of the columns are overstressed in the ground floor level where floor height is 21'-0". All the columns are adequate for gravity loading except six double height columns out of twenty five columns. However, most of the columns are overstressed due to lateral loadings BUILDING INTEGRITY DEA INSPECTION SUMMARY OPEX MILLS PAGE 6/10
7 All the pile capacity is adequate for existing loading with factor of safety above 2.0 except one pile group (F.S above 1.5). Considering 63 psf live load, all the foundations are adequate for factor of safety more than 2.0 except one pile group (F.S above 1.5). RECOMMENDATIONS We recommend rectify the overstressed structural members by proper retrofitting method. However during this rectification times equipment and electromechanical machineries need to be relocated or shut down for the safety of people at site. Stair is found to be adequate from analysis and comparing with design. BUET recommendation for unreinforced masonry should be followed. ROPE DENIM GENERATOR BUILDING Equivalent concrete strength was found 2600 psi. The equivalent concrete strength has been calculated according to ACI 562. The slab is adequate for existing loading condition and BNBC recommended loads. Some floor beams are not adequate considering lateral loadings. All the columns are adequate for gravity loadings but most of the columns are overstressed due to lateral loadings. Stairs are found to be adequate considering field investigation and analysis. All the foundations are adequate for existing loading with factor of safety above 2.0. By observing the soil stratification of Bore hole No 34 and 36 for Rope Denim Generator Building we found that the liquefaction potential is absent at the site. RECOMMENDATIONS Overstressed Columns should be strengthened by proper retrofitting. Overstressed Beams should be strengthened. Restriction should be imposed on vertical extension of any storey. Brick work need to be strengthened to prevent out-of-plane failure by providing vertical support or wrapping with FRP as per BEUT recommendation. SSL GENERATOR BUILDING BUILDING INTEGRITY DEA INSPECTION SUMMARY OPEX MILLS PAGE 7/10
8 It was found that the equivalent concrete strength for brick chips is 2,167 psi. The equivalent concrete strength has been calculated according to ACI 562. All beams are adequate for both existing and BNBC 2006 live loading which includes lateral load (i.e. earthquake and wind load). However, some beams at first floor are overstressed for torsion which can be neglected. All the columns are adequate for gravity loadings. However, some columns at ground floor are overstressed due to lateral load for both existing and BNBC 2006 live loading condition. The slab is adequate for all loading condition. However at first floor, deflection under compressor is a concern issue and significant vibration found due to compressor. Pile foundations are adequate for all loading conditions. RECOMMENDATIONS We recommend to strengthen the overstressed structural members with proper retrofitting design. Moreover, need to reduce load on first floor if possible and need to incorporate damping device with proper design under base of the compressor to reduce vibration. GENERATOR UTILITY BUILDING Structure was analyzed under actual present loading conditions and under BNBC 2006 loading conditions. Under vertical loading, for a live load of 3.0 kn/sqm, the building is found safe. Under lateral (earthquake & Wind) load, members are found safe. Foundation is considered safe at prevailing loading condition. Beams are adequate under vertical load & lateral load. No cracks were detected. Grade Beams are adequate under vertical load. Slabs interior panel are adequate. No significant deflections were detected. Recommendations: Nil BUILDING INTEGRITY DEA INSPECTION SUMMARY OPEX MILLS PAGE 8/10
9 DIESEL GENERATOR BUILDING Structure was analyzed under actual present loading conditions and under BNBC 2006 loading conditions. Under vertical loading, for a live load of 2.0 kn/sqm, the building is found safe. Under lateral (earthquake & Wind) load, some members are found overstressed. Foundation is considered safe at prevailing loading condition. Beams are adequate under vertical load & lateral load. No cracks were detected. Grade Beams are adequate under vertical load. Slabs interior panel are adequate. No significant deflection were detected. Recommendations: Recommended to retrofitting of lateral load (Earthquake and Wind) within 9 months. LABEL BUILDING Stone chips was used in ground floor and brick chips was used from 1 st floor. We found equivalent concrete strength for stone chips is 2210psi and 2945 psi for brick chip. The equivalent concrete strength has been calculated according to ACI 562. The two way beam supported slab is adequate for both existing loading condition considering both existing and BNBC recommended 63 psf live load. All the grade beams section sizes are adequate. However, provided reinforcement at support is less than the required amount at most of the positions. For existing all the columns are adequate except 10 for gravity loading condition. However, most of the columns are overstressed due to lateral loadings. For 63 psf live load most all the columns are overstressed both in gravity loading and lateral loadings. All the foundations are adequate for existing loadings with factor of safety above 1.5 except six. Recommendations: We recommend to strengthening the overstressed structural members with proper retrofitting design. BUILDING INTEGRITY DEA INSPECTION SUMMARY OPEX MILLS PAGE 9/10
10 DETAILED DESCRIPTION OF METHODOLOGY Specification for Detail Structural Assessment Structural Analysis will be carried on according to BNBC (1993) and ACI code. I. Testing of Materials: Sub-soil Investigation Core/Pullout/CAPO Test (Destructive Test) for Concrete Strength UPV (Ultrasonic Pulse Velocity) Test (Non-destructive Test) for Concrete Strength Ferro-Scanning in Column, Beam and Slab for Rebar Detection. II. Investigation of Foundations Foundation Explorations III. Structural Evaluation (Design check): Analysis of sub-soil investigations report Development of computer simulated model Checking of structural stability and geometry Checking adequacy of foundation i.e. pile & pile cap or footing/raft Checking of lateral load resistance capacity of the Building BUILDING INTEGRITY DEA INSPECTION SUMMARY OPEX MILLS PAGE 10/10
BUILDING INTEGRITY SUMMARY REPORT
BUILDING INTEGRITY SUMMARY REPORT SUPPLIER NAME UNITS AUDITED Opex Mills 4X 6X Denim Rope Denim SSL SSL3 Utility Diesel SUPPLIER ADDRESS AUDIT DATE January 2014 AUDIT PERFORMED BY AUDIT TEAM Kanchpur,
More informationBUILDING INTEGRITY SUMMARY REPORT
BUILDING INTEGRITY SUMMARY REPORT SUPPLIER NAME SUPPLIER ADDRESS AUDIT DATE January 2014 AUDIT PERFORMED BY Cosmopolitan Industries Pvt Ltd Khejur Bagan, Bara Ashulia, Savar, Dhaka, Bangladesh Department
More informationINITIAL STRUCTURAL INTEGRITY ASSESSMENT REPORT (SIAR)
INITIAL STRUCTURAL INTEGRITY ASSESSMENT REPORT (SIAR) Factory Name: Karardi, Shibpur, Narsingdi, Narsingdi Dhaka Bangladesh 10 May 2013 The Alliance for Bangladesh Worker Safety Page 1/15 10 May 2013 Introduction
More informationStructural Inspection Report
Revision: Issue 2 Date: 23 rd June 2014 Cherry Pvt. Ltd. Florence Fashions Ltd. Ultimate Ltd. Chandand Fashion Ltd. Joy Fashion Ltd. Structural Inspection Report Authors: Adrian Ryan, Cathal Mac an tsearraigh
More informationABA Fashions Ltd. Plot #9, Block F, Tongi, Gazipur-1710 ( N, E) 08 MARCH 2014
ABA Fashions Ltd. Plot #9, Block F, Tongi, Gazipur-1710 (23.885176N, 90.399821E) 08 MARCH 2014 1 2 Observations 3 Highly stressed columns Cursory calculations indicate column at a high working stress.
More informationApparel Gallery Ltd.
Apparel Gallery Ltd. 147-148, Norshinghpur, Asulia, Savar, Dhaka (23.929985N,90.304914E) 23 March 2014 1 2 Observations Building 1 Heavy loading due to raised floor area on Ground Floor 3 Building 1 Raised
More information111 MORGAN ST. Ryan Friis
Technical Report No. 1 September 30, 2002 Executive Summary: 111 Morgan St. is a 9 story cast-in-place concrete condominium building being constructed in Chicago, Illinois. The building s floor system
More informationAbanti Color Tex Ltd. Plot-S, A-646, Shashongaon Enayetnager, Fatullah, Narayangonj ( E, N) 28 June 2014
1 Abanti Color Tex Ltd. Plot-S, A-646, Shashongaon Enayetnager, Fatullah, Narayangonj (90.476444E, 23.622806N) 28 June 2014 2 Preliminary calculations suggest columns in Units 1 and 2 are highly stressed
More informationTechnical Report 3. Alyssa Stangl Structural Option Advisor Dr. Linda Hanagan L A J O L L A C O M M O N S P H A S E I I O F F I C E T O W E R
Technical Report 3 Alyssa Stangl Structural Option Advisor Dr. Linda Hanagan L A J O L L A C O M M O N S P H A S E I I O F F I C E T O W E R Site and Location La Jolla Commons, San Diego, California General
More informationVolume 1. HOW TO MAKE A DREAM HOUSE EARTHQUAKE RESISTANT Contents
Preparation of Seismic Design Manuals for Earthquake Disaster Mitigation Volume 1 HOW TO MAKE A DREAM HOUSE EARTHQUAKE RESISTANT Contents Part I: A house and its behavior during earthquake A House? How
More informationmortarless Design Manual Part 1 (AS 3600:2009) Section 1 Page 1 AS 3600:2009 PLAIN AND REINFORCED CONCRETE - CODE OF PRACTICE
SECTION 1. mortarless Design Manual Part 1 (AS 3600:2009) Section 1 Page 1 AS 3600:2009 PLAIN AND REINFORCED CONCRETE - CODE OF PRACTICE 1.1 Overview of AS 3600:2009 AS 3600:2009 is the latest Australian
More informationCE 3150 Reinforced Concrete Design Design Project
Problem Description For this design project you will work in your project groups to complete a partial design of an office building. Specifically, you will design and fully detail three components: 1.
More informationRestoration and Rehabilitation FRP Wrapping
Restoration and Rehabilitation FRP Wrapping (Rehabilitation of a Power Plant Structures Affected by Earthquake & Tsunami at Port Blair, Andaman) M.Karthikeyan, B.E., M.B.A., F.I.E, K.Thiagaraj B.E., 156
More informationInvestigation on Behaviour of Reinforced Concrete Beam Column Joints Retrofitted with FRP Wrapping
International Journal of Civil Engineering Research. ISSN 2278-3652 Volume 5, Number 3 (2014), pp. 289-294 Research India Publications http://www.ripublication.com/ijcer.htm Investigation on Behaviour
More informationShear Wall Analysis. Introduction. The Medical Office Building Malvern, PA 7
The Medical Office Building Malvern, PA 7 Shear Wall Analysis Introduction The current lateral system in the Medical Office Building consists of cast-in-place (CIP) concrete moment frames and torsion beams.
More informationPRELIMINARY STRUCTURAL INVESTIGATION REPORT
124 E. Broadway Tucson, AZ Prepared for: CBRE Brokerage Services 3719 N. Campbell Ave. Tucson, AZ 85719 BACKGROUND: The Tucson Veterans of Foreign Wars building, located at 124 E. Broadway, Tucson, AZ
More informationThe Structural Redesign of Boyds Bear Country and its Related Systems. Boyds Bear Country, Pigeon Forge, Tennessee
The Structural Redesign of Boyds Bear Country and its Related Systems Included in this Presentation: Background and Existing System Proposal Problem / Solution Structural System Redesigns Pre-cast Concrete
More informationEARTHQUAKE DESIGN CONSIDERATIONS OF BUILDINGS. By Ir. Heng Tang Hai
EARTHQUAKE DESIGN CONSIDERATIONS OF BUILDINGS By Ir. Heng Tang Hai SYPNOSIS 1. Earthquake-Induced Motions 2. Building Configurations 3. Effectiveness Of Shear Walls 4. Enhancement Of Ductility In Buildings
More informationA/E REVIEW CHECKLIST STRUCTURAL
A/E REVIEW CHECKLIST STRUCTURAL Reviewers should - Use Checklists when reviewing any type of VA construction project for the following disciplines: Site and Landscape, Architectural, Structural, Plumbing,
More informationThe designer shall also submit additional information required by the University as described and underlined below.
I. Structural Engineering Submissions The designer shall submit all information required by the State Construction Office (SCO) as described in the State Construction Manual Chapter 300 - Project Design
More informationDESIGN CRITERIA. Allowable Stress Design (ASD) AISC-1999.
DESIGN CRITERIA 1. INTRODUCTION This appendix summarizes the codes, standards, criteria, and practices that are generally used in the design and construction structural engineering system for the Sarker
More information3.5 Tier 1 Analysis Overview Seismic Shear Forces
Chapter 3.0 - Screening Phase (Tier ) 3.5 Tier Analysis 3.5. Overview Analyses performed as part of Tier of the Evaluation Process are limited to Quick Checks. Quick Checks shall be used to calculate the
More informationFranklin Square Hospital Center Patient Tower
Thomas Weaver Structural Option Franklin Square Hospital Center Patient Tower Baltimore, MD Thomas Weaver Structural Option AE 481W Senior Thesis Consultant: Professor M. Kevin Parfitt 12/14/2009 Page
More informationMinimum Guidelines for the Design and Use of Underpins When Performing Foundation Stabilization and/or Supplementation UP-08
Minimum Guidelines for the Design and Use of Underpins When Performing Foundation Stabilization and/or Supplementation UP-08 Table of Contents 1. Title 2. Designation 3. List of Figures 4. Scope 5. Referenced
More informationFEMA P-593 STEP-BY STEP PRESCRIPTIVE RETROFIT FOR CRIPPLE WALL BRACING & ANCHORAGE TO FOUNDATION
INTRODUCTION Objective of provisions: The provisions of IEBC Appendix Chapter A3 are intended to reduce hazard of earthquake-induced damage (IEBC A301.1). These provisions are not intended to eliminate
More informationfifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance
APPLIED ARCHITECTURAL STRUCTURES: STRUCTURAL ANALYSIS AND SYSTEMS DR. ANNE NICHOLS FALL 2014 lecture fifteen design for lateral loads Lateral Load Resistance stability important for any height basic mechanisms
More informationCouncil on Tall Buildings
Structure Design of Sino Steel (Tianjin) International Plaza Xueyi Fu, Group Chief Engineer, China Construction Design International 1 1 Brief of Project 2 Location: Tianjin Xiangluowan Business District
More information90% Design Submittal Structural Calculations Parking Garage CDRL
NORTH METRO RAIL LINE PROJECT Thornton Crossroads at 104 th Avenue Station 90% Design Submittal Structural Calculations Parking Garage CDRL 03-037.11.06 June 2, 2017 Prepared by: Regional Rail Partners
More informationTHE FORENSIC MEDICAL CENTER
THE FORENSIC MEDICAL CENTER Image courtesy of Gaudreau, Inc. TECHNICAL REPORT #2 OCTOBER 26, 2007 KEENAN YOHE STRUCTURAL OPTION DR. MEMARI FACULTY ADVISOR EXECUTIVE SUMMARY Image courtesy of Gaudreau,
More informationStructural Redesign Gravity System
Redesign Gravity System Design Considerations A composite floor system was used for this design to maximize the efficiency of the material being used. This type of system requires less material and provides
More information4.6 Procedures for Connections
4.6 Procedures for Connections This section provides Tier 2 evaluation procedures that apply to structural connections: anchorage for normal forces, shear transfer, vertical components, interconnection
More informationAnchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi
STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel
More informationLOAD TEST EVALUATION OF FRP-STRENGTHENED STRUCTURES
The 7 th International Conference on FRP Composites in Civil Engineering International Institute for FRP in Construction LOAD TEST EVALUATION OF FRP-STRENGTHENED STRUCTURES Nestore GALATI Senior Design
More informationSEAU 5 th Annual Education Conference 1. ASCE Concrete Provisions. Concrete Provisions. Concrete Strengths. Robert Pekelnicky, PE, SE
ASCE 41-13 Concrete Provisions Robert Pekelnicky, PE, SE Principal, Degenkolb Engineers Chair, ASCE 41 Committee* *The view expressed represent those of the author, not the standard s committee as a whole.
More information151 First Side. Technical Assignment 2 November 16 th, William J. Buchko. AE 481w Senior Thesis The Pennsylvania State University
November 16 th, 2007 William J. Buchko AE 481w Senior Thesis The Pennsylvania State University Thesis Advisor: Kevin Parfitt Table of Contents Executive Summary... 3 Structural System Overview Foundation...
More informationSabah Shawkat Cabinet of Structural Engineering 2017
3.1-1 Continuous beams Every building, whether it is large or small, must have a structural system capable of carrying all kinds of loads - vertical, horizontal, temperature, etc. In principle, the entire
More informationEstimation of existing tall buildings pile foundations bearing capacity under seismic and wind loads. T.Davitashvili 1,a, I.
Estimation of existing tall buildings pile foundations bearing capacity under seismic and wind loads T.Davitashvili 1,a, I.Timchenko 2,b 1 Capto Group, 67, D.Aghmashenebeli ave., 0102 Tbilisi, Georgia
More informationGround + 4 floor RCC frame structure in Goa Floor to floor height is 3.0m Plan dimension, 24.0 m x 13.5 m SBC = 20 t/sqm, hard Strata is consider for
Ground + 4 floor RCC frame structure in Goa Floor to floor height is 3.0m Plan dimension, 24.0 m x 13.5 m SBC = 20 t/sqm, hard Strata is consider for seismic analysis Analysis done using structural designing
More informationIJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):
IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online): 2321-0613 Seismic analysis of RC Building Frame with Different Bracing Systems Mohammed Ali Khan
More informationLintel Tables Design Notes and Limitations
LINTEL TABLES Lintel Tables Design Notes and Limitations 1. These tables apply to one and two family residential structures only that conform to the requirements of the 2006, 2009 or 2012 International
More informationTable of Contents.2. Introduction...3 Gravity Loading and Deflections..4. Existing Structural System..8
WISCONSIN PLACE RESIDENTIAL TECHNICAL ASSIGNMENT 2 OCTOBER 29, 2007 KURT KRASAVAGE THE PENNSYLVANIA STATE UNIVERSITY STRUCTURAL OPTION FACULTY ADVISOR: DR. ALI MEMARI 1 Table of Contents Table of Contents.2
More informationBrent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan
Executive Summary: 200 Minuteman Park currently stands as a three story commercial building. The original design was limited to three stories by an industrial zoning law in Andover, Massachusetts. If this
More information5.0 Elevating Your Home
5.0 Elevating Your Home One of the most common retrofitting methods for homes is elevation. When a home is properly elevated, the living area should be above most flood levels. Several elevation techniques
More informationSeismic Rehabilitation of Selby Condominium Complex, Montreal (Quebec), Canada
Seismic Rehabilitation of Selby Condominium Complex, Montreal (Quebec), Canada M. Zarrabi & R. Bartosh BCA Consultants, Montreal, Quebec, Canada A. Pall Pall Dynamics Limited, Montreal, Canada SUMMARY
More informationITEM 404 DRIVING STEEL PILING
AFTER MARCH 1, 2012 ITEM 404 DRIVING STEEL PILING 404.1 Description. This Item shall govern the driving of steel piling. The piling shall be of the size and weight shown on the plans and shall be in accordance
More informationLIFE SCIENCES BUILDING STRUCTURAL CONCEPTS AND EXISTING CONDITIONS
Structural Technical Report 1 LIFE SCIENCES BUILDING STRUCTURAL CONCEPTS AND EXISTING CONDITIONS Prepared for: Dr. Aly M. Said Dr. Thomas Boothby Professor Kevin Parfitt Dr. Charles D. Cox Prepared by:
More informationGeotechnical Investigation Reports and Foundation Recommendations -Present status in India -Examples
Geotechnical Investigation Reports and Foundation Recommendations -Present status in India -Examples Prof. V.S.Raju (Formerly: Director, IIT Delhi & Professor and Dean, IIT Madras) Email: rajuvs_b@yahoo.com
More informationBuilding Systems and Design Elements included in SliDeRulE
Building Systems and Design Elements included in SliDeRulE No. System Subsystem Design Element 1.1.1 Foundation Deep Foundation Steel H-pile 1.1.2 Foundation Deep Foundation Steel pipe pile 1.1.3 Foundation
More informationComparative Study of R.C.C and Steel Concrete Composite Structures
RESEARCH ARTICLE OPEN ACCESS Comparative Study of R.C.C and Steel Concrete Composite Structures Shweta A. Wagh*, Dr. U. P. Waghe** *(Post Graduate Student in Structural Engineering, Y.C.C.E, Nagpur 441
More informationSEISMIC ANALYSIS OF SIX STOREYED RC FRAMED BUILDING WITH BRACING SYSTEMS
SEISMIC ANALYSIS OF SIX STOREYED RC FRAMED BUILDING WITH BRACING SYSTEMS ABSTRACT Megha Kalra Assistant Professor, The North Cap University, Gurgaon(India) Multistoreyed buildings are most affected by
More informationTechnical Assignment 1 10/8/03
Executive Summary Technical Assignment 1 10/8/03 The is 55 story high-rise condominium being built off the northern Miami coast. The structural design presented in this building is a direct result of its
More informationStructural Requirements
Structural (for the design Engineer of Record) Presented by: Lindsay Anderson Consultant Structural Plan Examiner and Dixit Patel Structural Plan Examiner 1 Overview 1. Department Clarification Memorandums
More informationStructural Technical Report 1 Structural Concepts / Existing Conditions
Chris Shelow Structural Advisor: M. Kevin Parfitt Koshland Integrated Natural Science Center 10/05/05 AE 481W Structural Technical Report 1 Structural Concepts / Existing Conditions Executive Summary The
More informationStructural Comparison between Pan Joist Concrete and Steel Frame Systems for UMCP Student Housing Building B
Structural Comparison between Pan Joist Concrete and Steel Frame Systems for UMCP Student Housing Executive Summary The proposed thesis will include an investigation of two different alternative structural
More informationResearch on the Influence of Infill Walls on Seismic Performance of Masonry Buildings with Bottom Frame-Shear Walls
AMSE JOURNALS-AMSE IIETA publication-7-series: Modelling B; Vol. 8; N ; pp - Submitted Jan. 7; Revised March, 7, Accepted April, 7 Research on the Influence of Infill Walls on Seismic Performance of Masonry
More informationREINFORCING TABLES INSTALLATION MANUAL
REINFORCING TABLES 201 REINFORCING TABLES Design Limitations Introduction The structural wall reinforcing and lintel design tables contained within the Appendix of NUDURA s Installation Manual have been
More informationReinforced Concrete Design. Lecture no. 1
Reinforced Concrete Design Lecture no. 1 Mechanics of RC Concrete is strong in compression but week in tension. Therefore, steel bars in RC members resist the tension forces. RC Members Reinforced concrete
More informationStructural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity
System Codes and Criteria Design Codes and Standards The design code used is the Wisconsin Administrative Code along with the State of Wisconsin Department of Commerce-Safety & Buildings Chapters Comm
More informationA Guide for the Interpretation of Structural Design Options for Residential Concrete Structures
CFA Technical Note: 008-2010 A Guide for the Interpretation of Structural Design Options for Residential Concrete Structures CFA Technical This CFA Technical Note is intended to serve as a guide to assist
More informationStructural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)
Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction
More informationSee the IRC for additional information. See CPD-DS Information Bulletin 100 for Requirements for 1 & 2 Family Dwelling plan submittals.
As a customer service initiative, the Kansas City, Missouri, City Planning and Development Department/Development Services, in cooperation with the Greater Kansas City Home Builders Association, has developed
More informationProject Findings: Appendix 2
NSF Final Report CMMI-1034874 Project Findings: Appendix 2 Selected Damage Photos of Engineered Buildings PART 2. Teleco Office Tower Civil Engineering and Engineering Mechanics Department University of
More informationTHE FORENSIC MEDICAL CENTER
THE FORENSIC MEDICAL CENTER Image courtesy of Gaudreau, Inc. TECHNICAL REPORT #1 OCTOBER 5, 2007 KEENAN YOHE STRUCTURAL OPTION DR. MEMARI FACULTY ADVISOR EXECUTIVE SUMMARY Image courtesy of Gaudreau, Inc.
More informationStructural Inspection
General: Background: An inspection and structural analysis have been performed for the purpose of evaluating the buildings structural systems and components. A full set of structural drawings was utilized
More informationEffect of Edge Beam and Shear Wall on the Structural Behavior of Flat Plate Multistoried Building: A Computing Modeling for lateral load Analysis
Effect of Edge Beam and Shear Wall on the Structural Behavior of Flat Plate Multistoried Building: A Computing Modeling for lateral load Analysis Zasiah Tafheem 1, A.S.M Rubaiat Nahid 2, Tanzeelur Rahman
More informationShoring and Reshoring Fundamentals
Shoring and Reshoring Fundamentals by Mary Bordner Tanck, PE SHORING AND RESHORING FUNDAMENTALS Because it has such a significant impact on schedule and material movements, it is important for everyone
More informationProject Findings: Appendix 2
NSF Final Report CMMI-1034874 Project Findings: Appendix 2 Selected Damage Photos of Engineered Buildings PART 1. St. Louis Gonzague Cafeteria Building Civil Engineering and Engineering Mechanics Department
More informationSEISMIC PERFORMANCE OF LOW-RISE PRE-ENGINEERING BUILDINGS WITH TILT-UP AND MASONRY FAÇADE WALLS DURING THE CANTERBURY EARTHQUAKES IN NEW ZEALAND
10NCEE Tenth U.S. National Conference on Earthquake Engineering Frontiers of Earthquake Engineering July 21-25, 2014 Anchorage, Alaska SEISMIC PERFORMANCE OF LOW-RISE PRE-ENGINEERING BUILDINGS WITH TILT-UP
More informationMinimum slab thickness of RC slab to prevent undesirable floor vibration. Technology, Dhaka-1000, Bangladesh. 2.
Minimum slab thickness of RC slab to prevent undesirable floor vibration Mohammad Rakibul Islam Khan 1, *Zafrul Hakim Khan 2,Mohammad Fahim Raiyan 3 and Khan Mahmud Amanat 4 1, 2, 3, 4 Department of Civil
More informationPERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140)
PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140) *A. Ahmed 1, K. H. Tan 1 1 Department of Civil and Environmental Engineering National University of Singapore, Singapore,
More informationTotaling approximately 617,000
Totaling approximately 617,000 sq. ft, the mixed-use Embassy Suites hotel development is among the largest of several newly built hotels in the business district adjoining New York s bustling Wall Street
More information"Impact of New IS 1893 & Related Codes on Design of tall Buildings, Including Trend Setting Structures
"Impact of New IS 1893 & Related Codes on Design of tall Buildings, Including Trend Setting Structures Conference on Planning and Design of Tall Buildings including Earthquake and Wind Effects By S. C.
More informationCEN/TC 250- Published standards
CEN/TC 250- Published standards Standard reference Title Citation in OJ Directive EN 13391:2004 Mechanical tests for post-tensioning systems EN 1990:2002 Eurocode - Basis of structural design EN 1990:2002/A1:2005
More informationSupport Action for Strengthening PAlestine capabilities for seismic Risk Mitigation SASPARM 2.0 Deliverable D.C.1
Support Action for Strengthening PAlestine capabilities for seismic Risk Mitigation SASPARM 2.0 Deliverable D.C.1 Report on the identification of retrofit measures Deliverable contributors Institute for
More informationNorth Mountain IMS Medical Office Building
North Mountain IMS Medical Office Building Phoenix, Arizona Michael Hopple Technical Assignment 1 October 5 th, 2007 AE 481W-Senior Thesis The Pennsylvania State University Faculty Adviser: Dr. Ali Memari,
More informationKa Wahine Trust Halfway House PRO 2538 Detailed Engineering Evaluation Quantitative Assessment Report
Christchurch City Council Ka Wahine Trust Halfway House PRO 2538 Detailed Engineering Evaluation Quantitative Assessment Report Christchurch City Council Ka Wahine Trust Halfway House Quantitative Assessment
More informationA Research on Comparison of R.C.C and Post Tensioned Flat Slab with or Without Drop Using Software
2016 IJSRSET Volume 2 Issue 2 Print ISSN : 2395-1990 Online ISSN : 2394-4099 Themed Section: Engineering and Technology A Research on Comparison of R.C.C and Post Tensioned Flat Slab with or Without Drop
More informationOn Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)
TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 Light Gauge Steel Engineers Association Washington, D.C. 20005 Toll Free (866) 465-4732 www.lgsea.com DESIGN OF BY-PASS SLIP CONNECTORS IN COLD-FORMED
More informationAnalytical Study on Seismic Performance of Hybrid (DUAL) Structural System Subjected To Earthquake
Vol.2, Issue.4, July-Aug. 2012 pp-2358-2363 ISSN: 2249-6645 Analytical Study on Seismic Performance of Hybrid (DUAL) Structural System Subjected To Earthquake Nabin Raj.C 1, S.Elavenil 2 Department of
More informationFDA CDRH Laboratory Silver Spring, Maryland. Executive Summary: Timothy Mueller Structural Option Walter Schneider
Executive Summary: The FDA-CDRH Laboratory is currently being built on the Food and Drug Administration s White Oak Consolidation Campus. It is a four story building with a full below grade ground floor
More informationPossible solution to past CM exam question. Question 2 July New city centre office block. by Rajavel Inbarajan
Possible solution to past CM exam question Question 2 July 2015 New city centre office block by Rajavel Inbarajan The information provided should be seen as an interpretation of the brief and a possible
More informationAdministrative Changes
Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings
More informationCOMPARATIVE STUDY ON DESIGN RESULTS OF A MULTI-STORIED BUILDING USING STAAD PRO AND ETABS FOR REGULAR AND IRREGULAR PLAN CONFIGURATION
COMPARATIVE STUDY ON DESIGN RESULTS OF A MULTI-STORIED BUILDING USING STAAD PRO AND ETABS FOR REGULAR AND IRREGULAR PLAN CONFIGURATION K VENU MANIKANTA 1*, Dr. DUMPA VENKATESWARLU 2* 1. Student, Dept of
More informationAPPENDIX 6 (not yet reviewed by UCCS) STRUCTURAL ANALYSIS/VIBRATION CRITERIA
APPENDIX 6 (not yet reviewed by UCCS) STRUCTURAL ANALYSIS/VIBRATION CRITERIA GENERAL The purpose of this standard is to identify structural submittal requirements, as well as identify vibration design
More informationCBC SECTION/TABLE NUMBER NEW -CHANGE COMMENTARY. X Flexible and Rigid definitions removed and found in ASCE 7-10
2016 Chapter 16 Structural Design- Changes include new plan content requirements for Photovoltaic Panel Systems as well as guidance on how to determine the dead and live loads. For mid- and high-rise designs
More informationSEISMIC BEHAVIOUR OF RC BUILDING RESTING ON PLAIN AND SLOPING GROUND WITH BRACINGS AND SHEAR WALL
SEISMIC BEHAVIOUR OF RC BUILDING RESTING ON PLAIN AND SLOPING GROUND WITH BRACINGS AND SHEAR WALL Yashaswini R 1, Dr. Mahesh Kumar G 2 1M.Tech Student, CAD Structures, Shridevi Institute of Engineering
More informationDESIGN SPECIFICATION FOR FOUNDATIONS
FOR HINDUSTAN PETROLEUM CORPORATION LTD. VISAKH REFINERY DHT PROJECT JOB NO. : 6261 DOCUMENT NO. : A-6261-110-006 TOTAL NO. OF PAGES: 11 (INCLUDING THIS PAGE) 0 16-11-2009 FOR APPROVAL
More informationSeismic Analysis And Design of a Commercial Buildings (G+5)
Seismic Analysis And Design of a Commercial Buildings (G+5) Koritala Sindhua, PG student, Department of Civil Engineering, AM Reddy Engineering College,Narasaraopeta,Guntur Dist, Ap, JNTUK ABSTRACT The
More informationPioneering China s Tallest: Form and Structure of the Ping An Finance Ce nter
Pioneering China s Tallest: Form and Structure of the Ping An Finance Center David Malott, Director, KPF Dennis Poon, Vice Chairman, Thornton Tomasetti 领先中国之巅 : 平安金融中心的形式与结构 David Malott, Director, KPF
More informationB BASF MasterFlow MasterFlow MasterFlow MasterFlow C CGM Grout...8
B BASF MasterFlow 100...2 MasterFlow 648...5 MasterFlow 885...4 MasterFlow 928...3 C CGM...8 F FIVE STAR GROUT...7 G GROUT Five Star Non Shrink...7 General Purpose...6 Masterflow 100...2 Masterflow 648...5
More informationBUILDING CODES Presented by CORUM ENGINEERING
BUILDING CODES Presented by CORUM ENGINEERING AGENDA I. The Basics of Foundations A. Footer Designs B. Foundation Walls 1. Non-Backfilled Walls 2. Backfilled Walls (Retaining Walls) C. Slabs vs. Crawl
More informationSEISMIC RETROFIT OF BEAM-COLUMN JOINTS WITH FRP SHEETS
B-4 ADVANCED COMPOSITE MATERIALS IN BRIDGES AND STRUCTURES MATÉRIAUX COMPOSITES D'AVANT GARDE POUR PONTS ET CHARPENTES Winnipeg, Manitoba, Canada, September 22 24, 28 / 22, 23 et 24 septembre 28 SEISMIC
More informationJanuary 14, 2006 Structural Thesis Proposal: Structural and Breadth Redesign Options
River Tower at Christina Landing Wilmington, DE Joseph Bednarz Structural Option Faculty Advisor: Dr. Boothby Executive Summary January 14, 2006 Structural Thesis Proposal: Structural and Breadth Redesign
More informationone structural behavior, systems and design Course Description Course Description Syllabus & Student Understandings statics mechanics of materials
ARCHITECTURAL STRUCTURES: FORM, BEHAVIOR, AND DESIGN DR. ANNE NICHOLS SUMMER 2014 lecture one Syllabus & Student Understandings structural behavior, systems and design Introduction 1 Architectural Structures
More informationUSE OF 500 GRADE STEEL IN THE DESIGN OF REINFORCED CONCRETE SLAB. Prof. M. Shafiul Bari, Ph.D Department of Civil Engg., BUET
1.0 Introduction USE OF 500 GRADE STEEL IN THE DESIGN OF REINFORCED CONCRETE SLAB Prof. M. Shafiul Bari, Ph.D Department of Civil Engg., BUET There is growing interest within the reinforced concrete industry
More informationPlan Check No. Checked by: An Appointment Is Required for Verification
SUPPLEMENTAL CORRECTION SHEET UNREINFORCED MASONRY (URM) RETROFIT ( 2002 LABC ) Plan Check No. Checked by: Permit Appl. # An Appointment Is Required for Verification Job Address: For appt. call: APPLICATION
More informationADAPT Floor Pro 2009/2010 Tutorial Export Design Strip to ADAPT PT or ADAPT RC
ADAPT Floor Pro 2009/2010 Tutorial Export Design Strip to ADAPT PT or ADAPT RC Update: May 2010 Copyright ADAPT Corporation all rights reserved ADAPT PT 2010/RC 2010 to ADAPT Floor Pro 2009/2010 Strip
More informationHilton Baltimore Convention Center Hotel Western Podium
Hilton Baltimore Convention Center Hotel Western Podium CHRIS SIMMONS Structural Option Faculty Consultant: Dr. Ali M. Memari Thesis Proposal TABLE OF CONTENTS EXECUTIVE SUMMARY. Page 3 INTRODUCTION..
More informationEVALUATION & REPAIR OF CORROSION DAMAGED ROOF LIFT SLAB WITH WIRE POST-TENSIONING SYSTEM (BUTTON HEADS)
EVALUATION & REPAIR OF CORROSION DAMAGED ROOF LIFT SLAB WITH WIRE POST-TENSIONING SYSTEM (BUTTON HEADS) (C) COPYRIGHT POST-TENSIONING INSTITUTE, ALL RIGHT RESERVED 1 of 23 The following presentation discusses
More information