UL, KUL, WG-KUL, ARK, ARK-1

Similar documents
Fire Protection Valves

Fire damper. Type FKS-EU. Installation and operating manual. GB/en. according to Declaration of Performance DoP / FKS-EU / DE / 003

Conergy SolarFamulus II

Fire damper. Type FKRS-EU. Installation and operating manual. GB/en. according to Declaration of Performance DoP / FKRS-EU / DE / 003

Operating and Installation Manual Fire Damper Type FKA-EU

CFFWA-XX-1-U. Rev. 1.2

Louvers and Dampers April Product Guide Specification SECTION SMOKE DAMPERS

Mechanically Fasten Duct Sections. Code Reference: 2013 Title 24, Part 6 Standards 120.4(a) Sealed Openings. Drawbands

ASSEMBLY & INSTALLATION INSTRUCTIONS

TRAPEZOIDAL SHEET METAL RAIL LIFT/VARIO for trapezoidal sheet metal roofs

Fixed Blade Weather Louvre

ifix INSTALLATION MANUAL PV flat roof installation system Version

Installation- and Operating Instructions Interroll End stop RM 8811

4/S1 VENTILATION LOUVRES FZ, AFZV, AFZM, RZ, ARZ, PZ, ZP. v 3.3 (en)

0160 Series Curtain Fire Dampers

This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.

Application & General Notes: Installation Supplements: Safety Warning: Other Installation References: Receiving & Handling: Electrical Guidelines:

Installation, Operation and Maintenance Manual

2500 Series Fire Smoke Dampers

Installation Instructions/Operation and Maintenance Manual. Models PLG-60 PLG-72. PS DOORS Contact Information. Website psdoors.

Operating and Installation Manual Fire damper Type FKR-EU

Declaration of Performance

RECEIVING AND HANDLING

Declaration of performance

VIA BOWLING. File No.: M COPYRIGHT 2005, VIA BOWLING PRODUCTS

1-300 SERIES Endover Rotator Operator s Manual for Morse End-Over-End Drum Rotators Series

KS EXTENSIONS FOR CLEAN ROOMS

MANUAL. landscape orientation. portrait orientation. metal roof mounting system for solar panels METAL ROOF MOUNTING SYSTEM. Rev

Z5033 E3 Ball joint adapter Mounting instructions

11/2 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD2, (D)IBD2SS AND IBDT FIRE DAMPERS

Instructions for the Use of the. SMB SOLAR MULTIBOARD (also referred to as SMB or board below) on Photovoltaic Arrays with Framed Modules

Documentation. Transient voltage suppressor - AX2090- TS Version: Date:

FSFCA (Ductless Direct Expansion Fan Coil) Rev. 1.1

INGLEBEAMS. Our Inglebeam range is available in either solid aggregate versions or hollow light weight version.

Z5043 MAX Horizontal bracket Mounting instructions

FD Damper Installation, Operating and Maintenance Instructions

20 Portable Saw Mill OWNER S MANUAL

24 Portable Saw Mill OWNER S MANUAL

INGLEBEAMS. Our Inglebeam range is available in either solid aggregate versions or hollow light weight version.

L505 VISUAL LEVEL INDICATOR. Dip-Tape Visual Level Indicator INSTALLATION AND OPERATIONS MANUAL

MODEL AS2 AS2 SPECIFICATIONS & COMPONENTS

Aluminium Single Deflection Grilles. Model Series 5100

MODEL 185R Kontrol-Karrier Operator s Manual for Morse Kontrol-Karrier

BASIC LOUVER INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

HELIOSTAR 252, 218 HORIZONTAL, FREE INSTALLATION

INGLEBEAMS. Our Inglebeam range is available in either solid aggregate versions or hollow light weight version.

3 HOUR UL CLASSIFIED CURTAIN TYPE (D)IBD230, (D)IBD430, and (D)IBD630 FIRE DAMPERS WITH INTEGRAL SLEEVES

On-roof system Tau Installation manual

1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations...

2200-Lb. Semi-Electric Stacker OWNER S MANUAL

OPERATOR S SAFETY MANUAL

SECTION AIR TERMINAL UNITS

SERVICE PEDESTAL FLOOR-MOUNTED SERVICE PEDESTAL. Installation Manual

Installation Instructions

SECTION AIR OUTLETS AND INLETS

Loading Arm Installation, Maintenance & Safety Manual

BLUEKIT VENTILATION FLAPS

Document Number FD & DFD 150X MODELS Hour Curtain Fire Dampers Vertical or Horizontal Mount

1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations...

SECTION AIR DISTRIBUTION

Architectural Louvre Panels. Manufactured in Great Britain. Aquarius. Louvre Panel Systems SOLINEAR. integration / imagination / innovation

Welding & Fabrication Tools Mini VaR Tool Kit

Installation Guide. IMPORTANT: Read all sections before starting. For the most up-to-date information, visit our website: leadvisioninternational.

Volume flow rate measuring units

Document number CURTAIN FIRE DAMPERS

geba fire damper WFK according to EN 15650

Industrial flue gas probes. Instruction manual

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5)

Z5010 (Version 2) TV spigot with fixing plate Mounting instructions

OPERATING MANUAL. Conveyor belts. CB-/B-Conveyor

PE45 AMAZON MONKEY BARS OWNER'S MANUAL

General Guidelines. Instructions for Part # WP Safety. It is the user s responsibility to read and follow all instructions.

AirBench EX Operation and Maintenance

Installation, Operation and Maintenance Manual

ASSEMBLY AND OPERATING MANUAL LTW SLIDE RAIL SYSTEM - Type PV

Agilent 16034E Test Fixture

Trimbox NO2 Filter. Product Manual. ventilation systems

Installation instructions for. Wall Mounting Frame C M298 - M311 - M313 - M314 - M316. Version: 1.0 Date:

PE21 AMBER DOUBLE SWING OWNER S MANUAL

1.02 Related Sections A. Section Heating, Ventilation and Air Conditioning (HVAC). C. Section Pneumatic and Electric Control HVAC.

PE57 HOLT 2 DOUBLE SWING OWNER S MANUAL

2-finger angular gripper SGB 32-50

USER S OPERATING AND INSTRUCTION MANUAL

Mounting systems for solar technology

PAINT BOOTHS GENERAL PURPOSE

RAPID-EPS PATENT PENDING

Agilent 16048D Test Leads

Agilent 16047D Test Fixture

INSTALLATION PROCEDURE

450 and 550 Series Pressure/Vacuum Relief Valve (ATEX Approved)

2200-Lb. Stacker. Fixed Straddle Leg OWNER S MANUAL

applications and fabric types fabric expansion joints

BRANZ FACTS RESILIENT NON-STRUCTURAL ELEMENTS SEISMICALLY RESILIENT NON-STRUCTURAL ELEMENTS # 3. Restraint systems

EHH-601D. Miami-Dade Qualified Wind-Driven Rain Louver

LVH-A Series Intumescent Fire Dampers Alternative Mounted Systems 1, 2 & 4 hour Fire Rating

Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment.

Installation, Operation and Maintenance Manual

LK15 PRESTIGE PLAY KITCHEN OWNER'S MANUAL

Instructions for installation and use PFEIFER LSV Lifting Loop

MOUNTING SYSTEM FOR PITCHED ROOF WITH TILES. mounting system for pitched roof with tiles for solar panels in landscape setup. Rev

Transcription:

Installation manual GB/en Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1 TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202265 E-mail: trox@trox.de http://www.troxtechnik.com Product overview A00000053072, 11/2017, TROX GmbH 2015 Fig. 1: Schematic illustration 1 Front frame, UL with L-sections, KUL with U- sections 2 Blades (closed) 3 Centre mullion (B 1000 mm) 4 Blades (open) 5 Blade restrictor 6 Seal 7 WG border 8 WG regular blades 9 10 11 12 13 14 15 16 WG bottom blade Crimped wire mesh, with or without insect screen Casing Blades Seal Linkage Travel stop (angle section) Adjustable blade restrictor Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1 1

Important notes Important notes Information on the installation manual This manual enables operating or service personnel to correctly install the product described below and to use it safely and efficiently. It is essential that these individuals read and fully understand this manual before starting any work. The basic prerequisite for safe working is to comply with the safety notes and all instructions in this manual. The local regulations for health and safety at work and general safety regulations also apply. Qualified staff The work described in this manual has to be carried out by individuals with the qualification, training, knowledge and experience described below: HVAC technician HVAC technicians are individuals who have sufficient professional or technical training in the field they are working in to enable them to carry out their assigned duties at the level of responsibility allocated to them and in compliance with the relevant guidelines, safety regulations and instructions. HVAC technicians are individuals who have indepth knowledge and skills related to HVAC systems; they are also responsible for the professional completion of the work under consideration. HVAC technicians are individuals who have sufficient professional or technical training, knowledge and actual experience to enable them to work on HVAC systems, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved. Limitation of liability The information in this manual has been compiled with reference to the applicable standards and guidelines, the state of the art, and our expertise and experience of many years. The manufacturer does not accept any liability for damages resulting from: Non-compliance with this manual Incorrect use Operation or handling by untrained individuals Unauthorised modifications The actual scope of delivery may differ from the information in this manual for special constructions, additional order options or as a result of recent technical changes. Copyright This document, including all illustrations, photos, etc., is protected by copyright. Any use of this document without the written consent of the manufacturer is an infringement of copyright; this applies in particular to disclosing this document to third parties, to publishing, copying, microcopying, or translating content, and to saving content on electronic systems or modifying it. Violators will be held liable for any damage. The right to further claims remains reserved. Personal protective equipment Personal protective equipment must be worn for any work in order to reduce health or safety hazards to the minimum. The appropriate protective equipment for a job must be worn for as long as the job takes. Correct use Non-return dampers are used to prevent air from flowing against the intended airflow direction. They open and close automatically and are used for supply air or extract air in ventilation and air conditioning systems. 2 Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1

Transport and packaging Incorrect use WARNING! Storage temperature: 10 to 50 C Relative humidity: 95 % max., non-condensing Danger due to incorrect use! Incorrect use of the damper can lead to dangerous situations. Never use the damper: in areas with potentially explosive atmospheres for process air outdoors without sufficient protection against the effects of weather in humid rooms in rooms with aggressive or dust-laden air Transport and packaging Transport CAUTION! Danger of injury from sharp edges, sharp corners and thin sheet metal parts! Sharp edges, sharp corners and thin sheet metal parts may cause cuts or grazes. Be careful when carrying out any work. Wear protective gloves, safety shoes and a hard hat. Use only lifting and transport gear designed for the required load. Always secure the load against tipping and falling. Upon delivery, carefully remove the packaging and check the damper for transport damage and completeness. Storage Please note: Store the unit only in its original packaging Protect the unit from the effects of weather Protect the unit from humidity, dust and contamination Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1 3

Installation Installation General safety notes General installation information CAUTION! Danger of injury from sharp edges, sharp corners and thin sheet metal parts! Sharp edges, sharp corners and thin sheet metal parts may cause cuts or grazes. Be careful when carrying out any work. Wear protective gloves, safety shoes and a hard hat. Personnel: HVAC technician NOTICE! Contamination or damage will impair the function of the damper. Protect the damper from contamination and damage. Please note: Installation should be vertical and without torsion Installation only into horizontal ducts, with the blades horizontal Installation in vertical ducts only with the damper opening against gravity (extract air ducts) Note the airflow direction Duct connection on one side or on both sides (with UL only on one side) Dampers that are not screw-fixed to the wall or ceiling slab require suspensions. The function of the damper must be checked before installation. Fig. 2: Installation types 1 2 3 4 Ducts on both sides (only with KUL, ARK-1) Without duct (air transfer) Duct on one side (air outlet) Duct on one side (air inlet) The non-return dampers are installed away from walls (in ducts), or adjacent to or on the face of walls and ceiling slabs. Installation on the discharge side of a fan (only UL, KUL) Fig. 3: Upstream section Turbulence on the discharge side of a fan may damage the blades of the non-return damper. A straight upstream section >B+H is hence required on the discharge side of a fan. 4 Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1

Installation Installing UL NOTICE! Risk of damage due to incorrect use. Do not use the UL non-return damper in external walls or as an exhaust air or fresh air damper. For external walls use only WG-KUL (with factory mounted external weather louvre). Fig. 4: Wall installation UL1 Extract opening UL2 Supply opening Note the airflow direction (blade opening direction) Installation opening H 1 B 1 Without installation subframe With installation subframe H + 15 B + 15 H + 35 B + 35 Fix the damper with suitable screws (by others); flange holes 9 mm. Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1 5

Installation Installing KUL / WG-KUL Fix the damper with suitable screws (by others); flange holes 9.5 mm. NOTICE! Risk of damage due to incorrect use. Do not use the KUL non-return damper in external walls or as an exhaust air or fresh air damper. For external walls use only WG-KUL (with factory mounted external weather louvre). Fig. 7: Installation with installation subframe (WG- KUL-1 shown) 1 2 3 Threaded stud Fixing tab Installation subframe Items 1 to 3 are included in the installation subframe supply package Installation opening H1 B1 Without installation subframe With installation subframe H + 95 B + 95 H + 115 B + 115 Fig. 5: Wall installation without installation subframe (KUL-1 shown) Fig. 6: Duct installation (KUL-1 shown) 6 Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1

Installation Installing ARK-1 NOTICE! Risk of damage due to incorrect use. Do not use the ARK-1 non-return damper in external walls or as an exhaust air or fresh air damper. Fig. 8: Horizontal airflow Fig. 10: Wall installation without installation subframe (ARK-1 shown) 1 Blade movement area must be kept clear Fig. 9: Vertical airflow Fig. 11: Duct installation (ARK-1 shown) 1 Blade movement area must be kept clear Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1 7

Installation Fix the damper with suitable screws (by others); flange holes (only KUL-G) 9.5 mm. 4 5 6 7 Fixing tab Hexagon head screw Installation subframe Damper casing Fig. 12: Wall installation with installation subframe (steel/stainless steel construction) 1 2 3 Threaded stud Fixing tab Installation subframe Items 1 to 3 are included in the installation subframe supply package Installing the installation subframe Fig. 14: Bend and spread the fixing tabs before installation Connecting the duct Use screws to attach the damper to the ducting. The damper casing has flange holes for duct connection. Seal the joint between the casing flange and the duct in order to avoid pressure loss. Use sealing tape, for example, and clamps or additional screws, if necessary. The movement of the damper blades must not be obstructed by any attachment. Fig. 13: Installation subframe and damper assembly 1 2 3 Threaded stud Washer Hexagon nut 8 Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1

Commissioning and maintenance Commissioning and maintenance Commissioning Personnel: HVAC technician As part of commissioning, the non-return damper must be tested for correct functioning. NOTICE! Start-up of fans with UL/KUL Ensure a gradual start-up of fans to avoid a sudden pressure increase. NOTICE! ARK-1 blade restrictors Type ARK-1 non-return dampers have adjustable blade restrictors, which can be adjusted as part of commissioning. Maintenance Non-return dampers are maintenance-free with regard to wear but must still be included in the regular cleaning of the ventilation system. Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1 9

Technical data Technical data UL/KUL Data Value Unit Max. pressure 100 Pa Operating temperature -20 80 C Total differential pressure at 2.5 m/s 25 Pa WG-KUL Data Value Unit Max. pressure 100 Pa Operating temperature -20 80 C Total differential pressure exhaust air at 2.5 m/s 55 Pa Total differential pressure fresh air at 2.5 m/s 60 Pa ARK-1 Data Value Unit Max. pressure 5000 Pa Operating temperature (galvanised steel) 0 80 C Operating pressure (galvanised steel with optional Viton seal) 0 120 C Operating pressure (stainless steel with optional Viton seal) 0 200 C Total differential pressure at 10 m/s (horizontal airflow) 115 Pa Differential pressure at 2 m/s (vertical airflow) 135 Pa Differential pressure at 10 m/s (vertical airflow) 45 Pa Closed blade air leakage (against the intended airflow direction) to EN 1751 (class) Casing air leakage to EN 1751 (class) 4 C For more technical data see the technical leaflet. 10 Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1

Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1 11

12 Non-return dampers Types UL, KUL, WG-KUL, ARK, ARK-1