SECTION COOLING TOWER

.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures.

SECTION FIELD ERECTED INDUCED DRAFT COOLING TOWER

FXV. Closed Circuit Cooling Towers. Closed Circuit Cooling Towers. Product Detail FXV - C 1. Engineering Data FXV Models... C2

TM Series Induced Draft Cooling Tower Specifications

Lenntech. Tel Fax / Marley MS Cooling Tower /

Compass Series Open Cooling Towers BAC AUSTRALIA

PREMIER Low Profile Induced Draft Cooling Tower Specifications

IMT Open Cooling Towers... B78. Benefits... B80. Construction Details... B82. Custom Features and Options... B83. Accessories...

Cooling Tower Depot, Inc. 651 Corporate Circle, Suite 206 Golden, CO Phone (720) Fax: (720)

Cooling Tower Depot, Inc. 651 Corporate Circle, Suite 206 Golden, CO Phone (720) Fax: (720)

ACF SERIES COUNTER FLOW COOLING TOWER ENGINEERING DATA

TM Series Cooling Tower Specification

Fiberglass Cooling Towers

FXT Open Cooling Towers... B46. Benefits... B48. Construction Details... B49. Custom Features and Options... B50. Accessories...

ACX Series Cross Flow Induced Draft Cooling Towers

Pioneer Forced Draft Cooling Tower Specifications

Pioneer Forced Draft Cooling Tower Specifications

SERIES COOLING TOWER 300, 400, 500 & 600 CLASS DIRTY WATER HIGH TEMPERATURE DURABILITY. Heavy Duty Crossflow Splash Filled Type

FXV Closed Circuit Cooling Tower Specification

SECTION WELDED STEEL WATER STORAGE TANKS

SECTION INDUCED DRAFT COOLING TOWERS

QuadraFlow cooling tower

Series V Cooling Tower

SPECIFICATIONS - DETAILED PROVISIONS Section Progressing Cavity Pump C O N T E N T S

/ Marley Series 10 Series 15 Cooling Tower /

Lenntech. Tel Fax / Marley Sigma Steel Cooling Tower /

1DIVISION 15- MECHANICAL Section Fire Pumps. A. Single Stage, Double Suction, 9100 Series Horizontal Splitcase Fire Pump (Base Mounted)

Water headers are made of reinforced plastic and the design of the spray tree ensures uniform water distribution.

SUGGESTED SPECIFICATIONS Pump Frames through 64132

SECTION MECHANICAL SPECIFICATION GRIT COLLECTION EQUIPMENT

SECTION INDUCED DRAFT COOLING TOWERS

Central Station Air Handler Specification

AMCOT COOLING TOWER CORPORATION LRC-H & LRC-LNS CROSS FLOW COOLING TOWER OPERATIONS AND MAINTAINENCE MANUAL

SUGGESTED SPECIFICATIONS

DIVISION 15- MECHANICAL Section Fire Pumps

OXF-30K INDUCED DRAUGHT CROSSFLOW FRP COOLING TOWER

SECTION ALUMINUM HANDRAIL SYSTEMS

VSS-2 ½ D HIGH HEAD SUMP PUMP FREE STANDING

Architect s Project Number of 5 Decentralized HVAC Equipment District Master Specs 2013 Edition

K. All mechanical rooms shall be designed with a minimum 3-1/2 dropped floor.

DELTA. Cooling Towers, Inc. Delta Cooling Towers. Leader in Non-Corrosive Cooling Tower Technology

SK50. Performance Data TOTAL HEAD IN FEET HEAD-METERS 6 SK50 SK Liters/Second Capacity-U.S. G.P.M.

OAKDALE CHILLED WATER PLANT CAPACITY UPGRADES UI PROJECT INSTALL CHILLERS SECTION COOLING TOWERS

SHEF40. Performance Data. Wholesale Products Page: Section: Performance Data Dated: April 2002 Supersedes: January 2001

Fiberglass Crossflow Field-Erected Cooling Towers

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

SECTION ALUMINUM GATES

SECTION SLUICE GATES

VANGUARD Packed Column Air Stripping Tower Specifications

SECTION PACKAGE BOOSTER PUMP STATIONS

HPGR200 2 HP. Capacity-U.S. G.P.M.

SUBMERSIBLE SEWAGE EJECTOR

B. Polyethylene samples shall be submitted for Owner approval of color and quality.

G2D Series Performance Data Discharge: 1-1/4 Solids: 1/4. Wholesale Products Page: JP10075SSD-1 Section: Performance Data Dated: January, 2011

UNIFIED FACILITIES GUIDE SPECIFICATIONS

HIGH MAST CAMERA POLE ASSEMBLY GENERAL

SECTION GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT

G2DT Series Performance Data Discharge: 1-1/4 Solids: 1/4. Wholesale Products Page: JP10074SSD-1 Section: Performance Data Dated: January, 2011

SPL Evaporative Condensers

OVERSHOT GATE TECHNICAL DATA SHEET

1.02 RELATED SECTIONS: Water supply piping, water use piping, electrical, irrigation, foundations, site plans.

CONTENTS. 1 Product Introduction. 2 Unique Features. 4 XE Model Cooling Towers. 6 Series 3000: Induced Draft Crossflow Cooling Towers

SUGGESTED SPECIFICATIONS

HUP. Performance Data. Wholesale Products Page: Section: Performance Data Dated: January RPM: 1550 Discharge: 1" Solids: 1/8" GPM: TDH:

1.02 RELATED SECTIONS: Water supply piping, water use piping, electrical, irrigation, foundations, site plans.

K. ASTM F436- Standard Specification for Hardened Steel Washers; 2011.

Sigma CROSSFLOW COOLING TOWER

DESIGN PACKAGE. COMMONS PARK Twin Falls, Idaho

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.

SECTION HVAC GRAVITY VENTILATORS

SECTION FUEL-FIRED UNIT HEATERS

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System

1. Revision: The bid date has been postponed to July 18, 2012 at 1:30 PM.

Diffused Aeration Piping Equipment

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Galvanized System

PRASAR BHARATI (India s Public Service Broadcaster) OFFICE OF THE ADDL. DIRECTOR GENERAL (E)(EZ) ALL INDIA RADIO & TELEVISION, KOLKATA

"SRMZ" ROOFTOP PACKAGED MULTIZONE UNITS Self Contained Single Package Units 17.5 to 43 Ton Cooling Capacities

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers.

SECTION DECORATIVE METAL RAILINGS

Stainless Steel Aeration Equipment Specification

VANGUARD Packed Column Air Stripping Tower Specifications

Pump Specifications 450 Series 1/2 hp Submersible Sump Pump

SECTION EXHAUST FANS PART 1 GENERAL

RAOUL WALLENBERG HIGH SCHOOL SECURITY COILING GRILLE SFUSD PROJECT NO SAN FRANCISCO UNIFIED SCHOOL DISTRICT SECTION 08330

SUBMERSIBLE PUMPS FOR WASTEWATER (S-114)

SECTION MECHANICALLY ASSISTED MOBILE STORAGE SHELVING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

This guide can be used to prepare a specification for incorporating wall bracket jib cranes into a competitively bid construction project.

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

HYDROMATIC BV-40 SUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

SD/SW/VS50 SD50 SW50 VS50

SPX50/SPX50H. Performance Data. Wholesale Products Page: Section: Performance Data Dated: October 2007

/ Marley Sigma 1000/1200 Cooling Tower /

SECTION PLUMBING PIPING SYSTEM

INDUCED-DRAFT TWIN CROSSED-FLOW COOLING TOWER

special needs surface trajectory costs. High Efficiency 3. 4.

PC2 Evaporative Condenser F112 ENGINEERING DATA PC2 EVAPORATIVE CONDENSERS F136 STRUCTURAL SUPPORT F137 ALTERNATIVE STRUCTURAL SUPPORT

SECTION PACKAGED, SUBMERSIBLE SEWERAGE PUMP UNITS

333 North Main Street P. O. Box Alpharetta, Georgia Fernandina Beach, Florida

Transcription:

MESAN series MXL Engineering Guide Specifications The following document can be provided to an Engineer, Contractor, or Owner to allow them to properly specify MESAN s MXL series Cooling Towers. 15XXX- Field-Assembled Cooling Tower PART I-GENERAL A. General 1.0 Provide an induced draft, cross flow, induced-draft, modular type, low-profile, cooling tower conforming to all specifications, schedules and as shown on the plans. The tower shall be capable of cooling gpm of water from F to F with a F ambient air wet bulb temperature. Deviations from the design conditions in any respect are not acceptable. The tower shall not exceed the limiting dimensions of inches long x inches wide x inches high (not including the concrete foundations). The total connected horsepower of the tower fans shall not exceed HP (nominal motor nameplate horsepower) or HP per motor. The tower shall be equal to MESAN Model MXL- -_ or approved equal. Alternate cooling towers shall include whatever costs required for alterations to the electrical system, architectural enclosures, concrete foundations or structural steel required for different tower configurations or sizes. 1.1 The cooling tower performance shall be certified by the Cooling Tower Institute in accordance with CTI STD-201. Alternate towers that are not certified by CTI shall include in their bid cost for a third party certification test to be performed during the warranty period, as per CTI ATC-105. Manufacturer s performance warranty alone shall not be accepted.

1.2 The cooling tower manufacturer shall have a Quality Management System certified by an accredited institution as complying with the requirements of ISO-9001 2008, in order to ensure consistent quality of its products and services. Cooling tower manufacturers that are not ISO-9001 certified shall not be accepted. 1.3 Cooling tower manufacturer shall provide comprehensive field-assembly instructions in video format (DVD format), in addition to written instructions. Written instructions alone shall not be accepted (applies to MXL-01 to MXL-07) 1.4 Cooling tower shall be delivered in up to 4 factory-pre-assembled modules to be stacked and joined / bolted together on site. Cooling towers delivered in knocked down condition shall not be accepted, unless the supplier covers the cost of assembling and supervision labor on-site at local union rates. (applies to MXL-08 to MXL-10) PART II- PRODUCTS 2.1 Tower Structure 2.1.a The construction of the cooling tower(s) shall be of RTM (high-density FRP) with UVresistant white gelcoat, The FRP casing panels shall be made of high-density fiberglass, designed in a way to be joined using flanged edges and nut/bolts and with a minimum number of steel parts inside the tower Towers assembled using self-tapping screws shall not be accepted. Drive assembly support brackets and cross members shall be made of Hot Dipped Galvanized Steel (HDGS) (alternatively HDGS, SS-304 or SS-316, please indicate).

2.1.b The cold water basin shall be constructed of FRP with UV-resistant white gel coat. (optional HDGS, SS-316 or SS-304). The basin sections underneath the fill area shall be sloped toward the center to ease cleaning. Cold water basin shall be fitted with ANSI-125 flanges (3 diameter and above) for field piping connections (SS304 flanges also available as an alternative) or NPT female threaded ports (2-1/2 diameter and below). A brass float valve with stainless steel float shall be provided. Make-up and overflow piping connections shall be NPT threaded type. 2.1.c The hot water distribution system shall be open gravity type, with fixed calibrated orifices and without nozzles, removable nozzles shall not be accepted. The hot water basin and basin covers shall be constructed of FRP with UV-resistant gel coat (alternatively HDGS, SS-304 or SS-316, please indicate).. The fan deck and hot water basin covers shall be designed to withstand a 50 psf live load or a 200 pound concentrated load. FRP strainers shall be provided for each hot-water basin (alternatively HDGS, SS-304 or SS-316, please indicate)., and fitted with anti-splash devices made of FRP. The distribution fill shall be made of vacuum formed PVC designed to ensure the even distribution of water over the wet deck surface. Fill shall be arranged in several staggered layers over the height of the air intake opening. Single sheet fills shall not be accepted. Fill sheets shall have built-in 45 air intake louvers. Removable nozzles shall not be accepted. 2.1.d Fill shall be film type of thickness not less than 0.27 mm or 10 mils (measured after vacuum forming) rated for temperatures up to 45 o C. (optional ASTM fire retardant fill and also high-temperature CPVC fill, please indicate) 2.1. e. Separate drift eliminators with at least three changes of direction made of PVC and at least 5.5 thick shall be provided. Integral drift eliminators as part of the fill sheets shall not be

accepted. 2.1.f The fan deck and fan cylinder shall be FRP with UV-resistant gelcoat. The top of the fan cylinder shall be equipped with a removable fan guard made of hot dip galvanized steel (SS-304 or SS-316 also available, choose one) with openings not larger than 1.25 x 1.25. 2.2 Mechanical Equipment 2.2.a Fan shall be axial type with airfoil blades made of extruded aluminum with adjustable pitch. Fan blades made of sheet-metal shall not be accepted. 2.2.b Fan hub to be made of a single billet steel piece, CNC machined to integrate the blade shafts cradles, with conical shaft hole (tapered lock type) to ensure perfect centering of the complete assembly. Fan hubs with welded or bolted-on cradles shall not be accepted. Aluminum fan hubs shall not be accepted. Fan hub shall attach to the fan shaft through a tapered-lock joint (conical). Fan hubs using set screws to attach to the fan shaft shall not be accepted 2.2.c Fan motor(s) shall be totally-enclosed, air-over (TEAO), reversible, cage, ball bearing type, designed specifically for cooling tower service. The motor shall be furnished with special moisture protection on winding, shafts and bearings, shall comply with IP55 enclosure and insulation class F standard. Maximum motor size shall not exceed HP per cell. (Alternatively, Inverter-duty and/or NEMA-Premium motors, please indicate) 2.2.d (Optional, please delete if not desired) The fan(s), fan shaft(s), bearings, speed reducer and fan motor shall be warranted against defects in materials and workmanship for a period of five (5) years from date of shipment, FOB point of delivery of original order

2.2.e The fan drive shall be V-belt type with tapered lock pulleys designed for 150% of the motor nameplate HP rating (Amarillo or Sumitomo gear reducers also available, please indicate) The belt material shall be neoprene reinforced with polyester cord and specifically designed for cooling tower service. Fan sheaves shall be cast iron construction with corrosion protective coating. Aluminum pulleys shall not be accepted. The fan and fan pulleys shall be mounted on the shaft with special tapered bushing to provide maximum torque and centering and prevent wobbling. Fan assemblies using set screws shall not be accepted. Bearings must be NSK brand or equivalent rated for L10 80,000 hours of service life, sealed type, permanently lubricated and enclosed inside a steel cylinder with bolted on caps to isolate them from the airstream. Pillow bearings shall not be accepted. Bearings exposed to the airstream, shall not be accepted, Bearings requiring periodic lubrication shall not be accepted. 2.2.f For towers equipped with gear drives (optional), the motor, drive and transmission shaft shall be factory assembled, laser-aligned and shipped as a single piece. Disassembled drives requiring field alignment and field assembly shall not be accepted. 2.3 Water Outlet 2.3.a The cooling tower basin shall be provided with an ANSI-125 flanged connection on the side of the cold water basin s water sump box. The outlet shall be provided with large area removable FRP strainer and an anti vortex device to prevent air entrainment. The strainer shall match the materials of construction of the cold water basin. Tower manufacturers that do not supply integral strainers in their cold water basins shall include in their pricing an additional full flow basket strainer to be installed in the condenser water piping. 2.3.b. For multiple cell applications, an equalizing pipe connection shall be provided for each tower, installed on one side of the water sump, fitted with ANSI-125 flange and with the same diameter as the outlet pipe connection. Flume boxes shall not be accepted

2.5 Access and maintenance. To extend the lifespan of the tower by easing the accessibility and maintenance of the tower the following must be provided and shall not be excluded by any cooling tower manufacturer. Exclusions to this section shall not be considered as equal. 2.5.a An access ladder made of hot dip galvanized steel (SS-304 or SS-316 also available) shall be provided for access to the fan deck. Ladder shall be equipped with a safety cage which shall comply with OSHA standards. 2.5.b. Two hinged access doors per each cell shall be provided, dimensions of each door not to be less than 39 high x 25 wide each for easy access of maintenance personnel 2.5.b. An internal walkway made of FRP and HGDS structure (SS-304 or SS-316 also available), with anti-skid surface shall be provided. Internal walkways with open spaces shall not be accepted. All working surfaces shall be designed to withstand 50 psf or 200 lbs live load. Other components of the cooling tower, i.e. basin floor and fill/drift eliminators, shall not be considered an internal working surface. Cooling tower manufacturers that require that these surfaces be used, as a working platform shall provide a two year extended warranty to repair any damage to these surfaces caused by routine maintenance. 2.5.c An internal ladder with secondary catwalk shall be provided at a height that allows maintenance personnel to work on the fan assembly without the use of any other methods of access to such height. These to be made of HDGS (SS-304 or SS-316 also available)

2.5.d A 1" hot dip galvanized steel (SS-304 or SS-316 also available) pipe handrail shall be provided around the perimeter of the cooling tower. The handrails shall be provided with knee and toe rails. All the components shall comply with OSHA standards. 2.6 Cooling Tower Accessories 2.6.a (Optional) Vibration Cutout Switch: Provide electronic vibration switch with contact for BAS monitoring. Wiring shall be by the installing contractor. The electronic vibration cut out switch will be guaranteed to trip at a point so as not to cause damage to the cooling tower to ensure this the trip point will be 0.6 in/sec. 2.6.b Standard Warranty shall cover manufacturing defects for a period of 12 months from start-up date, or 18 months from invoice date, whichever occurs first. Warranty covers parts replacement only FOB port of origin of the original order. Manufacturer reserves the right to request the return of any defective parts for analysis before validating the warranty. Any freight costs associated with returned defective parts to be covered by the customer. An exception to this policy are those moving components (motor, speed reducer, bearings and pulleys) covered by an extended 5-year warranty, for which the delivery point, FOB terms and freight costs coverage remain the same as for the standard warranty. END OF SECTION