Document No Issue Date: May 15, 2012

Similar documents
UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

Huntsville Utilities Underground Residential Service Requirements

Addendum 1.0. For Lagrange Library Specification 1.0. Technology Consultants Fort Wayne, Indiana

Local Government District of Pinawa P.O. Box 100 PH: Pinawa, MB R0E 1L0 FX:

legend. #1 is a gas relief valve? If so does Enbridge supply with station?

The following sections are included in Division 27: Section : Underground Ducts and Raceways for Communication SysteMS 283

1 data PIC location (with 2 ports) typically asf for multiple staff members

ELECTRICAL SAFETY Information Bulletin

Communications Page 1 of 9

STREET LIGHTING. Springville City Power standard street lights will be installed in accordance with Springville City Power's Line Extension Policy.

INDEX. Page SECTION 1.0: SCOPE Toronto Hydro Requirements Ontario Electrical Safety Code 1 SECTION 2.0: PURPOSE 1

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

Section 2: Underground

UBC Technical Guidelines Section Edition Audio-Video Infrastructure Page 1 of 5

UNDERGROUND SERVICES SECONDARY

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0528 Pathways. Page 1 of 6

Basic Service. This Section provides information regarding a. Introduction

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

CHAPTER 11 CONDUITS AND FITTINGS

Please check with your local inspection authority for any additional requirements before installation.

TYPICAL INSTALLATION INSTRUCTIONS

CONDUITS AND FITTINGS

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal.

a) Line and load compartments must be separated by a stable barrier.

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL SECTION RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

TS 803 DUCTS DUCT INSTALLATION, PROTECTION AND MARKING WITHIN A TRENCH OPEN TRENCH DUCT INSTALLATION PROFILE

FORMAT Technical specifications content and numbering system shall be based on 2004 CSI MasterFormat.

[Type text] Heber Light & Power. Developers & Excavators. Electrical Service Requirements Manual

Residential Electric Policy

Homeowner electrical wiring guide. Including the 2015 Canadian Electrical Code amendments

Design Guidelines for Facilities Construction:

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

Student Services & Classroom Addition

SECTION HORIZONTAL CABLING

WIRING METHODS CHAPTER 38

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

Electric Service Handbook

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

Post Office Box 500 Carson, WA Phone (509) Fax (509) Toll Free (800)

New Conduit Specification

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

CONSTRUCTION SPECIFICATION FOR GROUNDING

nbn Lead-in Trenching Requirements

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

.2 The maximum length of horizontal cable shall not exceed 90 meters in any 360 degree direction.

TS 804 CABLES TABLE OF CONTENTS TRAFFIC SIGNAL EQUIPMENT POLE WIRING DIAGRAM LOCATIONS WITH CENTRE MEDIANS

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

Building Design Standards December 2009 SECTION COMMUNICATIONS HISTORY DRAWINGS

EFFECTIVE DATE: November 1, 2011, unless a later date is cited at the end of a section. [ NMAC - Rp,

PRIMARY LINE EXTENSION

GV 001 Equipment Bases and Enclosures General Information

SECTION ELECTRICAL CABLE. 1. Trench excavation, backfill, and compaction; Section

OVERHEAD SERVICES - SECONDARY

The University of Texas at Austin September 30, 2011

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

CITY OF UNION, OREGON TECHNICAL SPECIFICATIONS SECTION 9 UNDERGROUND UTILITIES

Procurement Services SVC East Fowler Avenue Tampa, Florida (813)

UNM IT/Telecommunications Guide Specification Communications Underground Ducts, Raceways and Structures /27/06

Request for Proposal. I. Background. Objectives. Summary Scope of Work. Park City Fire Service District Fiber Upgrade Duct Installation

UMass Amherst Information Technology. Design and Construction Guidelines

EFFECTIVE DATE: July 1, 2008, unless a later date is cited at the end of a section. [ NMAC - Rp,

EXTERIOR ASSIST PHONES REVISIONS Summary of Change Date 4/11/11 Blue Light Updated Manufacturer Information

DIVISION STRUCTURED CABLE

A/E Design Guide for Drawings and Spec Section Communications Infrastructure.

A WORK PROCESS SCHEDULE

1993 SPECIFICATIONS CSJ SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK

Primary Contact: Owner Customer Electrician Builder

UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING. NAME: Communications Equipment Room ORIGINAL DATE:

Telecommunications Design Guidelines University of Alberta Cabling Standards (version 2.1)

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 7/14/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 17 October 2013 ( ENCLOSURE 1)

OREGON UNIVERSITY SYSTEM STANDARD PUBLIC IMPROVEMENT CONTRACT BID FORM. FROM: Name of Contractor

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

ZG Scope. 2 Applicable Documents. 3 General. 4 Stock Item Numbers. Padvault Single-Phase Residential, 2.1 PacifiCorp Material Specifications

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

Specifications for Electrical Underground Residential Distribution Systems

SECTION GROUNDING

UNDERGROUND DROP CABLE CONDUIT INSTALLATION AND SPECIFICATION GUIDELINES FOR SINGLE DWELLING RESIDENTIAL APPLICATIONS

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 26 March 2013 ( ENCLOSURE 1)

RESEARCH AND TECHNOLOGY BUILDING RENOVATION MAY 18, 2009 SECTION COMMUNICATIONS

PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System

The Medical Center Company Electrical System Installation Requirements

Central Lincoln PUD Single-Family Residential Guidelines & Standards April 21, 2017

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

Electric Service Standards

Telecommunication Spaces

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section Data System Page 1 of 7

Merrimac Municipal Light Department. Commercial Developments Policy

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

Transcription:

Professional Engineer Authenticated TELUS Residential Service Conduit Requirements For Stand-Alone Homes and Duplexes in Fibre Only Communities Beginning in January 2010 TELUS began designing new subdivisions within the Top 48 population centres in Alberta and British Columbia using only fibre optic cable. This document explains the new conduit only servicing model that is used in fibre only communities, and it summarizes what the TELUS and builder responsibilities are within that model. For more information please contact the following TELUS personnel: 780 Area Code / Red Deer North Rick Fedirko 780-414-2411 rick.fedirko@telus.com 403 Area Code / Red Deer South Tony Walker 403-530-6244 tony.walker@telus.com General Entrance Requirements TELUS extends the 20mm (3/4 ) HDPE conduit which is stubbed at the property line to the service connection point on the side of the home. TELUS will use this HDPE or PVC conduit and the builder provided PVC conduit and LB to install fibre optic cable when a customer orders service. Note that TELUS no longer pre-installs cables to homes in fibre only communities, and that we are requesting an empty conduit within the house. If a coiled drop of cable is located at the property line then please follow the information included in the P630 located at: http://about.telus.com/community/english/about_us/for_our_customers/building_industry_consulting_services. Page 1 of 10

Fibre Only Conduit Service Diagram: TELUS Responsibility After the builder contacts Ledcor (see Builder Responsibilities below), a continuous section of 20mm (3/4 ) HDPE (high density polyethylene) SDR 13.5 orange or PVC service conduit will be extended from the property line to the side of the house at TELUS expense. At the base of the foundation wall the HDPE or PVC conduit will be fed through a TELUS supplied rigid sweeping 90 degree bend (to prevent HDPE kinking) and extended up the wall through the builder provided PVC conduit and LB. The HDPE conduit will be capped off within the LB. Builder Responsibilities TELUS requests the builder do the following in order to accommodate the HDPE or PVC conduit: 1. TRENCH: Provide a suitable trench from the property line to the service location at the side of the house as follows: Trench must be free of construction materials, rocks or stones. Trench must be sloped for grade changes. Stepped grade changes are not acceptable as this can cause pinching or constriction of the HDPE conduit. Page 2 of 10

Where communications services and power services share a common trench, Canadian Electrical Code rule 60-602 must be followed. 2. PVC CONDUIT & LB: Supply and install a 32mm (1-1/4 ) LB and a 32mm (1-1/4 ) schedule 40 PVC conduit along the outside of the house from the LB to a minimum of 300mm below the finished grade. The TELUS provided HDPE or PVC conduit pathway will be installed inside the PVC conduit and LB, and. *Note that if the HDPE is installed before the builder supplied PVC conduit, then the builder should slide the schedule 40 PVC conduit over the TELUS supplied HDPE leaving the top of the HDPE conduit accessible inside the LB. Provide the following separations between services on the outside of the house: Between Electrical service and TELUS service: 200mm (8 ) minimum separation Between Cable TV service and TELUS service: 250mm (10 ) minimum separation 3. ARRANGE TELUS CONDUIT: After excavation of the trench and installation of the schedule 40 PVC conduit and LB, the builder shall contact the TELUS contractor (Ledcor Technical Services, LTS) to arrange for extension of the HDPE conduit from the property line to the side of the house at TELUS expense. Note that LTS will arrange to install the HDPE or PVC conduit with 72 hours of being contacted, so do not back-fill the trench until the conduit extension has been completed. LTS contact information as follows: Phone 310-0218 (toll free, no area code required) Email to ltsconduitextension@ledcor.com and provide address and contact information 4. INTERNAL CONDUIT PATHWAY: Supply and install a 25mm (1 ) non-metallic conduit from the LB to the central wiring location inside the home, to provide TELUS with a continuous pathway from our pedestal to the central wiring point within the house. This conduit should have a maximum of four sweeping 90 degree bends, and should have a pull string installed. Providing an internal conduit pathway means that no external splice box is required which makes the external installation more visually appealing and matches the typical installation method of other service providers. *Note that this empty conduit is instead of the previously supplied 4 pair 24 gauge telephone wire and the 6 gauge insulated ground conductor. 5. BACKFILL: Backfill the service trench after the TELUS HDPE or PVC service conduit is installed. Ensure the trench is free of construction material and the service conduit is placed so that kinking or pinching will be avoided. Use only native loose packed fill directly on the service conduit and avoid large rocks or frozen soil which could damage the conduit. Ensure there is 500mm (20 ) of fill coverage on top of the service conduit before tamping. 6. NO INTERNAL CONDUIT PATHWAY: If the builder decides not to provide a non-metallic conduit between the LB and the central wiring point inside the home, then TELUS requires the builder to supply and install a bend insensitive fibre (ITU-T-G657 compliant, indoor or outdoor rated) a 4 pair 24 gauge telephone wire and the 6 gauge insulated ground conductor between the external LB and the internal central wiring point leaving 2m of slack at each end. This will result in an additional splice box installed on the LB on the outside of the house. This wiring is required because TELUS cannot guarantee that fibre could be installed between the LB and the central wiring point through a finished basement at some time in the future. Page 3 of 10

Normal Conduit Routing to Central Wiring Location: TELUS' primary requirement is to have a clear and unobstructed raceway from the outside wall to the panel location. TELUS' conduit must come above grade at the side of the house and cannot be placed as a continuous underground run with direct entry into the basement for two specific reasons: In the event that the street or pedestal location was too flooded the conduit could act as a direct route for the water to enter into the house. In the event the duct is damaged on private property TELUS would have no direct access into the house to provide temporary services. Internal Conduit Routing Options for a Centralized Panel Extend conduit through the basement floor: Alternative Routing for Centralized Panel Builder Supplied: 1 ¼ Schedule 40 Rigid Conduit to 300mm below grade 6 x 6 or Approximate Transition Box with Cover in place of STB 1 Schedule 40 Rigid duct to sweeping 90 extended through footing to Centralized Panel Location Minimum 900mm Coverage To Property Line Line of Grade 1 ¼ Sched 40 Rigid Conduit Min 300mm Below grade Extend Pull rope 1 Sched 40 Rigid Conduit To Centralized Panel Foundation Wall TELUS Supplied: Continuous 20mm HDPE SDR 13.5 Conduit 2 Sweeping 90 PVC Schedule 40 *Note all bends must be Sweeping* Page 4 of 10

Extend conduit through the floor joists: Builder Supplied: 1 ¼ LB 1 ¼ Schedule 40 Rigid Conduit 1 Conduit with Pull Rope to Central Panel location Alternative Routing for Centralized Panel Extend Pull Rope *Note all bends must be Sweeping* Joist To Centralized Panel 1 ¼ LB Joist 1 ¼ Sched 40 Rigid Conduit Line of Grade 1 Sched 40 Rigid or Flexible Non-metallic Conduit Minimum 900mm Coverage Min 300mm Below grade Foundation Wall TELUS Supplied: Continuous 20mm HDPE SDR 13.5 Conduit 2 Sweeping 90 PVC Schedule 40 Page 5 of 10

Outside To Inside Transition Pre-Wire and Panel/Backboard Area Central Wiring Requirements The inside wiring should be done in a star configuration where the individual set runs from each telephone jack and TV location collect at a common location within the home (see Figure 2). The centre of the star is to be in a heated environment where there is no risk of the ambient air temperature falling below 0º (zero) Celsius. A garage is NOT a suitable location Builder/Owner will provide One (1) duplex 15A non-switched power receptacle dedicated to home networking, communication and entertainment equipment, installed in a multi media enclosure at this location (the use of a Multi Media enclosure or Smart Panel is not mandatory although it is recommended). Total space required for the mounting of the Fibre Equipment and Multi Media enclosure will be a minimum of 600mm (24 ) x 900mm (36 ). Owner/Builder will provide patch panels for Voice / DATA / Coax. Refer to Figure 2 and Figure 3 for more information Page 6 of 10

Figure 2 1 Inch Rigid or Flex Conduit LB Grade Central Wiring Location Space of 24 x 36 inches Required for mounting of Equipment Detailed View see Figure 3 Page 7 of 10

Inside Wiring and Equipment Layout (Figure 3) 24 X 36 area of wall space required to accommodate all equipment. If a Multimedia enclosure is not used the same layout will apply on a securely fastened ¾ plywood backboard. Page 8 of 10

Inside Wiring Instructions The builder/owner shall supply telephone cabling and terminate as follows: Voice, Data and Coax Patch Panel Style Termination strips at the backboard location. All CAT5e inside wire to each location where the Home Builder/Owner would like Voice, DATA and TV (i.e.: if all 3 services are required in one location, then 3 CAT5e would be required at this location). Voice set runs to have W/BL, W/O AND W/GR terminated on RJ11 wall outlets and all 4 pairs terminated at the backboard location on the voice module. Data & TV runs to be terminated on RJ45 wall outlets and all 4 pairs terminated at the backboard location on the Data module according to the TIA-568A standard and labeled at both ends. Verification testing to be completed on all set runs. TELUS prefers using CAT5e cable for TV but can use coax cables. Please call 310-2255 for more information about products and services offered by TELUS or visit telus.com/bics Page 9 of 10

Professional Engineer Authenticated Title: TOPPS Documentation Engineering Review Process Original date of issue: 2011-05-17 Reviewed by: Tony Walker APEGGA APEGBC Title: Professional Engineer Signed 2011-05-17 2011-05-17 Document history: Date of Revision Description of Revision Revised by Reviewed by Certified by 1 2011-05-17 Original Rick Fedirko Tony Walker 2 2011-06-09 Changed wording on picture on page 2 from STB to LB Rick Fedirko Eddie Alfonso 3 2011-07-06 Changed wording on picture on page 2 and added verbiage on page 6 Rick Fedirko Eddie Alfonso 4 2012-05-15 Added PVC and removed pull string from pedestal to LB Rick Fedirko Eddie Alfonso 5 This document is the property of TELUS and contains proprietary and confidential information which must not be duplicated, used or disclosed without prior consent of TELUS. To verify and certify signature please add the certificate to your list of trusted identities by http://webakab.tsl.telus.com/psdtl/topps/topps/certexchangetonywalker.fdf To verify and certify signature please add the certificate to your list of trusted identities by http://webakab.tsl.telus.com/psdtl/topps/topps/certexchangeeddiealfonso.fdf Page 10 of 10