UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING. NAME: Communications Equipment Room ORIGINAL DATE:

Size: px
Start display at page:

Download "UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING. NAME: Communications Equipment Room ORIGINAL DATE:"

Transcription

1 UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING FACILITIES STANDARD PURPOSE: 1. The general purpose of each Facilities Standard is to provide minimal criteria for construction materials at University facilities regarding code compliance, warranty, approved products, execution and uniformity. 2. To protect the health and safety of patients, visitors, students, faculty and staff, in addition to protecting non-project UAB property, all construction must be in accordance with: NFPA 241 safeguarding construction, alteration and demolition operations; Standard Building Code, Chapter 33, regarding site work, demolition and construction; NFPA 101 Life Safety Code. 3. Construction safety is the responsibility of the contractor in accordance with the regulations and codes of the agency having jurisdiction, and according to the guidelines adapted by OSHA. 4. The Communications Equipment room Facilities Standard establishes a series of guidelines for specifying this particular item on any construction project at the University. This Facilities Standard is not to be regarded as a specification. GENERAL: 1. The Engineer shall furnish a section for Communications under the Electrical Specifications or under Division Contractor shall provide a Voice /Data Communication Equipment Room (CER) for each building level complete with equipment and finishes. The lowest level CER shall be used for Communication Service Entrance (CSER). Stack CER s where possible. Communication work shall be complete a number of days to be determined for each project, prior to the completion date of the project. 2. In general multiple CER s are required per floor if: Usable floor space exceeds 10,000 sq. ft. Cable length between CER and outlet, including slack, exceeds 295 ft., or conduit distance exceeds 240 ft (for the data signal only). PAGE NO

2 If a CER has more than 176 station drops, refer to UAB Communications Dept., Mr. Terry Weaver, If a CER serves multiple tenants or an office density of less than one work area per 100-sq. ft., larger areas may be served by a CER provided the cable length is met. 3. The following minimum size of CER is based on one outlet per 100-sq. ft. work area: Served Area CER at Least Up to 5,000 sq. ft. 8 X 10 >5,000 to 8,000 sq. ft. 10 X 12 >8,000 to 10,000 sq. ft. 12 X 14 Non-Hospital CSER 14 X16 Hospital CSER 16 X CER s shall be solely used for Communication Department equipment, H.S.I.S., and University Computing. Security backboard, fire alarm, intercom, CATV and other signal equipment shall be located in the electrical/mechanical rooms or in separate auxiliary or signaling rooms. 5. CER finishes shall be as follows: backboards covering all walls completely, 8 H X ¾ thick high-density commercial plywood, painted with two coats of fire retardant light gray paint. Sheetrock shall be wall painted. Flooring shall be static free asphalt/linoleum tile, with rubber base cove. Ceiling shall be drop layin type minimum 8-6 above floor with flush lighting. 6. Fluorescent lighting shall run parallel with long wall. Lighting intensity shall be at least 50-foot candles at 39 above floor. Emergency lighting shall be provided in each CER. Coordinate the lights location with UAB Telecommunications so that lights are not installed over the racks. 7. Door shall be lockable, minimum 36 wide and 80 high, opening out of room. 8. Fire Protection (if required by Codes): specify wire cages for sprinkler heads. Design drainage troughs to protect equipment from leakage in wet pipe systems. Consider using dry pipe system. 9. CER shall be provided with a controlled environment using a unit above ceiling to maintain a dust free area, 64 to 75 F, a 30 to 55% relative humidity, and a positive pressure with a minimum of one air change per hour, based on 4,500 BTU/hour heat load. PAGE NO

3 REVISIONDATE: 10. CER power and grounding requirement: Wiremold 3000 surface metal raceway placed 6 from floor on all backboards, with 20amp duplex receptacles on 18 centers. Strip shall be served with 3-20 amp branch circuits from emergency power if available. In addition, 4 individual outlet 20 amp 120V branch circuits shall be specified and located next to the ground bus at 7-8 from floor. Specify a #2/0 green ground riser through all CER s terminated on a ground bus, Square D # LBC165212, to be mounted on top right corner of a backboard. 11. The Engineer shall design a conduit riser system (using single line diagram) through all CER s consisting of six (6) 4 empty conduits with pull cord, 3 for Voice and 3 for Data. Conduits shall be aligned so that all conduits are positioned next to the backboard on one side by the door of the CER (not in the middle of the room), and sequenced 1, 2, 3, 4, 5 and 6 from left to right. Conduits shall terminate in each CER with a bushing 6 above floor and 4 below ceiling. Support conduits around top and bottom edge of backboard with Unistrut channel. Main Riser Copper and Fiber Optic Cables, Racks and communications hardware will be designed and installed by the UAB Telecommunications Department. 12. The Engineer shall design a Cable Tray System on all floor over the corridors for communication stations wiring. Tray shall be steel ladder type with a minimum of 3 side-wall and a minimum of 12 wide. Size shall be designed for present and future communications capacity. Four (4) 4 conduits from tray to top of backboard in CER shall be designed, and supported as Item 11 above. Tray shall not pass through firewalls; four to six 4 conduits shall connect the tray sections through firewalls. Conduit penetrations shall be sealed per Codes. Ground continuity of the system shall be maintained. 13. For stations wiring refer to Communication Raceway/Cabling System Standard # PRODUCTS: 1. Cable Tray acceptable Manufacturers: a) B-line b) Cope c) PW Industries d) Mono-Systems, Inc. e) Flex-All PAGE NO

4 EXECUTION: 1. Engineer shall consult Mr. Terry Weaver, RCDD ( address: early in the design to verify the capacity and specific requirements for each project, and submit construction documents for review and approval. END OF STANDARD Prepared by: Revised by: Terry S. Weaver Telecommunications Engineering Manager Reviewed and PAGE NO

5 REVISIONDATE: Recommended by: Approved : Mark A. Goska Brooks H. Baker III Director, Architecture & Engineering Associate Vice President - Facilities PAGE NO

Standards and Procedures Security Room Construction/Renovations At University of North Carolina Wilmington

Standards and Procedures Security Room Construction/Renovations At University of North Carolina Wilmington Standards and Procedures Security Room Construction/Renovations At University of North Carolina Wilmington Rev 062017 Provided by UNCW Physical Security and Access OVERVIEW... 3 CABLE INSTALLATION... 3

More information

Telecommunication Spaces

Telecommunication Spaces Telecommunication Spaces October 19, 2016 Page 1 Revision History Telecommunication Spaces Standard Effective Date Email Version Contact Phone OIT-TS strevena@csustan.edu 1.0 Stan Trevena 209.667.3137

More information

1 data PIC location (with 2 ports) typically asf for multiple staff members

1 data PIC location (with 2 ports) typically asf for multiple staff members 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

TELECOMMUNICATIONS ROOMS. Table of Contents PART 1 GENERAL 2 A. LOCATION: 2 B. SIZE 2 C. STRUCTURAL 3 D. ENVIRONMENTAL 3 E. ELECTRICAL AND LIGHTING 3

TELECOMMUNICATIONS ROOMS. Table of Contents PART 1 GENERAL 2 A. LOCATION: 2 B. SIZE 2 C. STRUCTURAL 3 D. ENVIRONMENTAL 3 E. ELECTRICAL AND LIGHTING 3 UNIVERSITY CONTACT: Network Services (302) 831-3722 TELECOMMUNICATIONS ROOMS Table of Contents PART 1 GENERAL 2 A. LOCATION: 2 B. SIZE 2 C. STRUCTURAL 3 D. ENVIRONMENTAL 3 E. ELECTRICAL AND LIGHTING 3

More information

Communications Page 1 of 9

Communications Page 1 of 9 Page 1 of 9 Last Update: April 23 rd, 2014 Introduction Design In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a

More information

The University of Texas at Austin September 30, 2011

The University of Texas at Austin September 30, 2011 SECTION 27 11 00 COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes basic communications room requirements. Refer to T series drawings for specific communication

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0528 Pathways. Page 1 of 6

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0528 Pathways. Page 1 of 6 1 General 1.1 Scope of work 1.1.1 The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the completion of

More information

THOMAS JEFFERSON UNIVERSITY HOSPITAL STANDARD OPERATING PROCEDURE FOR THE BUILD OUT OF TELECOMMUNICATIONS ROOMS AND ASSOCIATED SPACES

THOMAS JEFFERSON UNIVERSITY HOSPITAL STANDARD OPERATING PROCEDURE FOR THE BUILD OUT OF TELECOMMUNICATIONS ROOMS AND ASSOCIATED SPACES THOMAS JEFFERSON UNIVERSITY HOSPITAL STANDARD OPERATING PROCEDURE FOR THE BUILD OUT OF TELECOMMUNICATIONS ROOMS AND ASSOCIATED SPACES PREPARED BYBALA CONSULTING ENGINEERS, INC FOR THOMAS JEFFERSON UNIVERSITY

More information

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 26 March 2013 ( ENCLOSURE 1)

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 26 March 2013 ( ENCLOSURE 1) CELRL-PM-R March ARCOS BULLETIN - SUBJECT: IT Design. REFERENCE: a. UFC --0, Army Reserve Facilities b. Army Reserve IT Manual, Change c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC

More information

FORMAT Technical specifications content and numbering system shall be based on 2004 CSI MasterFormat.

FORMAT Technical specifications content and numbering system shall be based on 2004 CSI MasterFormat. DIVISION 27 00 00 COMMUNICATIONS FORMAT Technical specifications content and numbering system shall be based on 2004 CSI MasterFormat. BASIS OF DESIGN Design guidelines supplement building, fire, and other

More information

UBC Technical Guidelines Section Edition Audio-Video Infrastructure Page 1 of 5

UBC Technical Guidelines Section Edition Audio-Video Infrastructure Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 UBC Learning Space Acoustical Guidelines.2 UBC Learning Space Design Guidelines 1.2 Coordination Requirements.1 UBC IT Audio Visual 1.3 Description.1

More information

Third Party Design, Construction and Operations on FIU Campuses

Third Party Design, Construction and Operations on FIU Campuses Third Party Design, Construction and Operations on FIU Campuses A. List of Applicable Requirements: DIVISION OF INFORMATION TECHNOLOGY http://it.fiu.edu/ Contact Person: Robert Grillo Vice President and

More information

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails. SECTION 16714 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails. SECTION 27 11 00 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 11 00 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

COMMUNICATIONS EQUIPMENT ROOM FITTINGS

COMMUNICATIONS EQUIPMENT ROOM FITTINGS SECTION 271100 - COMMUNICATIONS EQUIPMENT ROOMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 17 October 2013 ( ENCLOSURE 1)

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 17 October 2013 ( ENCLOSURE 1) CELRL-PM-R October ARCOS BULLETIN - SUBJECT: IT Design Criteria Updates. REFERENCE: a. UFC --0, Army Reserve Facilities b. Army Reserve IT Manual, Change c. Army Reserve Design Process Submittal Requirements

More information

UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING

UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING FACILITIES STANDARD PURPOSE: 1. The general purpose of each Facilities Standard is to provide minimal criteria for construction materials

More information

UMass Amherst Information Technology. Design and Construction Guidelines

UMass Amherst Information Technology. Design and Construction Guidelines UMass Amherst Information Technology Design and Construction Guidelines December 2018 2.13 INFORMATION TECHNOLOGY AND COMMUNICATIONS 2.13.1. General A. UMass IT/ Cable Engineering Services (CES) is here

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract apply to this Section. 1.2 SUMMARY A. This Section

More information

DIVISION STRUCTURED CABLE

DIVISION STRUCTURED CABLE FORMAT 1. Technical specifications content and numbering system shall be based on the most current CSI Master Format. BASIS OF DESIGN 1. Design guidelines supplement building, fire, and other health, safety

More information

RESEARCH AND TECHNOLOGY BUILDING RENOVATION MAY 18, 2009 SECTION COMMUNICATIONS

RESEARCH AND TECHNOLOGY BUILDING RENOVATION MAY 18, 2009 SECTION COMMUNICATIONS SECTION 27 00 00 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following items for wiring systems used as signal pathways for voice and highspeed data transmission: 1. Communication outlets.

More information

Addendum 1.0. For Lagrange Library Specification 1.0. Technology Consultants Fort Wayne, Indiana

Addendum 1.0. For Lagrange Library Specification 1.0. Technology Consultants Fort Wayne, Indiana Addendum 1.0 For Lagrange Library Specification 1.0 Technology Consultants Fort Wayne, Indiana TECHNICAL SPECIFICATIONS FOR TELECOMMUNICATION DISTRIBUTION FACILITIES AND INSTALLATION PROCEDURES For Lagrange

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

Portland State University OIT Networking & Telecommunications Services

Portland State University OIT Networking & Telecommunications Services Portland State University OIT Networking & Telecommunications Services TELECOMMUNICATIONS CABLING/WIRING INSTALLATION & RELATED FACILITIES STANDARDS 2009-2011 Introduction The Office of Information Technology/

More information

1. Section , Gas and Vacuum systems for Laboratory and Healthcare Facilities

1. Section , Gas and Vacuum systems for Laboratory and Healthcare Facilities PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Pre-Fabricated Modular Futrus Headwall System a. Futrus Headwall as detailed on the drawings, including related components and accessories required

More information

Telecommunications Design Guidelines University of Alberta Cabling Standards (version 2.1)

Telecommunications Design Guidelines University of Alberta Cabling Standards (version 2.1) February 7, 2008 Telecommunications Design Guidelines University of Alberta Cabling Standards (version 2.1) Introduction: For all planned building projects on the U of A campus, Facilities Management,

More information

It is acceptable to place all required information in the main element (such as D5010) and delete the sub-elements provided in this template.

It is acceptable to place all required information in the main element (such as D5010) and delete the sub-elements provided in this template. 6. ENGINEERING SYSTEMS REQUIREMENTS D50 ELECTRICAL SYSTEMS REQUIREMENTS ELECTRICAL TEMPLATE 02/18 Instructions for using this template: There are template files for each UNIFORMAT Level 2 Group Elements.

More information

1.0 GENERAL 1.1 DOCUMENTS

1.0 GENERAL 1.1 DOCUMENTS 1.0 GENERAL 1.1 DOCUMENTS.1 This section of the Specification forms part of the Contract Documents and is to be read, interpreted, and coordinated with all other parts. 1.2 SUMMARY.1 Section Includes:

More information

TENANT CRITERIA MANUAL INSERT PHOTO HERE

TENANT CRITERIA MANUAL INSERT PHOTO HERE G TENANT CRITERIA MANUAL GREENWOOD MALL INSERT PHOTO HERE General Growth Properties, Inc. 110 N. Wacker Drive Chicago, IL 60606 (312)-960-5000 Tenant shall supply and install an electrical meter

More information

SECTION GROUNDING

SECTION GROUNDING SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment

More information

A/E Design Guide for Drawings and Spec Section Communications Infrastructure.

A/E Design Guide for Drawings and Spec Section Communications Infrastructure. Instructions to A/E: Communications Infrastructure specification 27 17 51 shall be included and coordinated with the master specifications unless directed otherwise by the University Project Manager. All

More information

Alamo Colleges. Telecommunications Infrastructure Standards. For. New Facility Construction or Renovations. Version

Alamo Colleges. Telecommunications Infrastructure Standards. For. New Facility Construction or Renovations. Version For New Facility Construction or Renovations Version 2010.8.5 Prepared By: COMBS Consulting Group I.T. design & consulting 11550 IH-10 West, Suite 270 San Antonio, Texas 78230 Voice: 210-698-7887 Fax:

More information

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).

3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC). SECTION 16111 CONDUITS PART 1 - GENERAL 1.01 DESCRIPTION A. General: Provide conduits, complete, as shown, specified or required per Contract Documents. Principal items include: 1. Rigid aluminum conduit.

More information

The following sections are included in Division 27: Section : Underground Ducts and Raceways for Communication SysteMS 283

The following sections are included in Division 27: Section : Underground Ducts and Raceways for Communication SysteMS 283 P a r t IV: De s i g n St a n d a r d s 279 Division 27: Communications Ge n e ra l Professionals shall verify that all applicable portions of these standards are incorporated into the final construction

More information

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS

SECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS SECTION 16711-27 05 28.33 PART 1 - GENERAL 1.01 SUMMARY A. This section includes Labor, materials and equipment necessary to complete the installation required for the items specified under this Section,

More information

City and County of San Francisco CONTRACT No A SFO - Data Center, Building 60 SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

City and County of San Francisco CONTRACT No A SFO - Data Center, Building 60 SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Cable Trays for Communications Cabling 1. Cable Trays 2. Cable Runways 3. Basket Tray B. Cable Tray Support

More information

METERING INSTALLATION

METERING INSTALLATION 4.01 METERING SPECIFICATIONS METERING INSTALLATION Metering specifications will be issued to the customer by OPPD. Metering specifications are required before any work is started on all new wiring or additions

More information

Building Design Standards December 2009 SECTION COMMUNICATIONS HISTORY DRAWINGS

Building Design Standards December 2009 SECTION COMMUNICATIONS HISTORY DRAWINGS SECTION 27 00 00 COMMUNICATIONS HISTORY The University Technology Services (UTS) Building Design Specification is a collection of requirements which architects and engineering consultants must adhere to

More information

186 TH AIR REFUELING WING KEY FIELD, MERIDIAN, MS ADDENDUM #1 PERFORMANCE WORK STATEMENT

186 TH AIR REFUELING WING KEY FIELD, MERIDIAN, MS ADDENDUM #1 PERFORMANCE WORK STATEMENT 186 TH AIR REFUELING WING KEY FIELD, MERIDIAN, MS PROJECT NUMBER MDVL092051 Renovate Vehicle Maintenance Facility Bldg 200 23 June 2017 ADDENDUM #1 PERFORMANCE WORK STATEMENT 1.0 SCOPE. This addendum to

More information

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 - GENERAL 1.1 SECTION

More information

Building Permit Application

Building Permit Application Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: ARCHITECT/ENGINEER ADDRESS:

More information

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING 2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING E3305.3: now reads The space equal to the width and depth of the panelboard and extending

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.

A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein. 16470 PANELBOARDS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 16 An optional keynote to

More information

DIVISION 27: COMMUNICATIONS AND TECHNOLOGY DESIGN STANDARDS TABLE OF CONTENTS

DIVISION 27: COMMUNICATIONS AND TECHNOLOGY DESIGN STANDARDS TABLE OF CONTENTS I. PURPOSE DIVISION 27: COMMUNICATIONS AND TECHNOLOGY DESIGN STANDARDS TABLE OF CONTENTS II. III. GENERAL A. STANDARDS B. DESIGN REQUIREMENTS C. TOPOLOGY 1. Voice 2. Data Connections 3. Voice over IP (VoIP)

More information

ELECTRON BEAM DUMP - ROOM DATA SHEET

ELECTRON BEAM DUMP - ROOM DATA SHEET ROOM DATA SHEETS WBS and System Managers: Eric Bong/R.Bionta/Dave Schultz FACILITY COMPONENT ELECTRON BEAM DUMP - ROOM DATA SHEET Name of Building Organization or Department SLAC, Stanford University Net

More information

S CHEDULE G - D OCUMENTS S UBMITTAL R EQUIREMENTS

S CHEDULE G - D OCUMENTS S UBMITTAL R EQUIREMENTS S CHEDULE G - D OCUMENTS S UBMITTAL R EQUIREMENTS This Attachment lists the items to be provided by the Architect in accordance with Owner/Architect Agreement. This list is not all-inclusive, nor is it

More information

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS SECTION 27 05 00 COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

LACCD INFORMATION TECHNOLOGY STANDARD

LACCD INFORMATION TECHNOLOGY STANDARD Page 1 of 20 TABLE OF CONTENTS I. Instructions... 2 II. Purpose... 2 III. Scope... 2 IV. Key Terms... 2 V. Standards... 3 1. 2. 3. 4. 6. 7. 8. Section 1: Entrance Facility (EF) Design Criteria... 3 1.1

More information

INFRASTRUCTURE STANDARD

INFRASTRUCTURE STANDARD Telecommunications and Network Services INFRASTRUCTURE STANDARD December 18, 2017 Revision 1.6 Download PDF at: www.uvm.edu/telcom UNIVERSITY OF VERMONT TELECOMMUNICATIONS INFRASTRUCTURE STANDARD January

More information

Pre-installation checklist. 3. Project manager has read specifications, and specs to be on-site during work.

Pre-installation checklist. 3. Project manager has read specifications, and specs to be on-site during work. Pre-installation checklist 1. Contractor qualifications verified. 2. Project manager is Belden/CDT installer certified. 3. Project manager has read specifications, and specs to be on-site during work.

More information

COMMUNICATIONS CABLING SECTION COMMUNICATIONS CABLING PART 1 - GENERAL

COMMUNICATIONS CABLING SECTION COMMUNICATIONS CABLING PART 1 - GENERAL 13686.00 COMMUNICATIONS CABLING 271513-1 1.1 RELATED SECTIONS SECTION 27 1513 COMMUNICATIONS CABLING PART 1 - GENERAL A. Drawings and general provisions of the Contract, including General and Supplementary

More information

REQUEST FOR QUOTATION Carroll Hall Alterations Addendum #2 Dated Jan 11, 2016

REQUEST FOR QUOTATION Carroll Hall Alterations Addendum #2 Dated Jan 11, 2016 Contents of Addendum 2 Answers to questions submitted Additional Items Revised Drawings QUESTIONS AND ANSWERS (1 30) REQUEST FOR QUOTATION 2016-25 Carroll Hall Alterations Addendum #2 Dated Jan 11, 2016

More information

1. Voice and data telecommunications for campus are managed by the Office of Information Technology (OIT) located in Gordon Palmer Hall.

1. Voice and data telecommunications for campus are managed by the Office of Information Technology (OIT) located in Gordon Palmer Hall. Section includes various guidelines for the operation and maintenance of communication systems, common work results, structured cabling, data communications, and audio-video communications. This design

More information

CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST

CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST Check off each item that is included within the submitted Contract Documents Review Package. Provide a written explanation for any omissions. The following items,

More information

TABLE OF CONTENTS Public Safety Building

TABLE OF CONTENTS Public Safety Building DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary

More information

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 05 28 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES...

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES... DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General Requirements

More information

A. This Section includes steel cable trays and accessories.

A. This Section includes steel cable trays and accessories. SECTION 26 05 36 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6 Page 1 of 6 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General

More information

SECTION COMMON WORK RESULTS FOR ELECTRICAL

SECTION COMMON WORK RESULTS FOR ELECTRICAL PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

B. Provide a complete conduit system with associated couplings, connectors, and fittings.

B. Provide a complete conduit system with associated couplings, connectors, and fittings. SECTION 26 05 33 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 260500. B. Provide a complete conduit system with associated couplings, connectors, and fittings. 1.02 RELATED

More information

University of Florida Telecommunication Standards April 2005

University of Florida Telecommunication Standards April 2005 University of Florida Telecommunication Standards April 2005 This document is designed to assist certified designers such as Professional Engineers and RCDD s in the preparation of telecommunications documents

More information

SEISMIC RESTRAINT SYSTEM

SEISMIC RESTRAINT SYSTEM 1. GENERAL 1.1. Description: SECTION 16012 SEISMIC RESTRAINT SYSTEM 1.1.1. This specification covers design and installation of seismic bracing and anchorage required for conduit, cable tray, bus duct,

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

DALLAS-FORT WORTH INTERNATIONAL AIRPORT

DALLAS-FORT WORTH INTERNATIONAL AIRPORT DALLAS-FORT WORTH INTERNATIONAL AIRPORT ADDENDUM NO. 2 TO THE REQUEST FOR BIDS Contract No. 9500445 Restroom Rehabilitation at Terminal B (Phase 3 & 4) December 20, 2010 THE REQUEST FOR BIDS (RFB) FOR

More information

Engineering Specifications for the CXI Room of the FEH LUSI Document # ESD SP

Engineering Specifications for the CXI Room of the FEH LUSI Document # ESD SP LCLS Engineering Specifications Document # 1.9-114 LUSI, CF, XES Revision 0 Engineering Specifications for the CXI Room of the FEH LUSI Document # ESD SP-391-001-37 Aymeric Robert Author, LUSI Scientist

More information

SEISMIC PROTECTION SYSTEMS Bracing Products for Racks & Cabinets

SEISMIC PROTECTION SYSTEMS Bracing Products for Racks & Cabinets SEISMIC PROTECTION SYSTEMS Bracing Products for Racks & Cabinets Seismic Frame Two-Post Rack Page 11-3 Seismic Protection Products - Racks Page 11-6 Seismic Protection Products - Runway Page 11-8 Seismic

More information

Power Electronics, Inc. Packaged Equipment Center Standard Construction and Design Features

Power Electronics, Inc. Packaged Equipment Center Standard Construction and Design Features DESIGN CRITERIA FOR STANDARD CONSTRUCTION: These standard design elements of the P.E.I. Power Equipment Center are utilized to meet the following design criteria per ASCE 7-05 as adopted by the IBC (International

More information

1. General Telecommunications Design Considerations

1. General Telecommunications Design Considerations 1. General Telecommunications Design Considerations 1.1. Entrance Point and Main Telecommunications Room Design 1.1.1. Conduit entrances typically consist of three 4 conduits. Conduit quantities are determined

More information

HUNTINGTON STATION POWER FLOOR PLAN

HUNTINGTON STATION POWER FLOOR PLAN 0/09/5 ADDENDUM 0/09/5 ADDENDUM TIME CLOCK SWITCH KEYED NOTES: EXISTING PANEL "SS2" 2 PROVIDE 2 CIRCUIT ASTRONOMICAL TIME CLOCK SWITCH FOR CANOPY LIGHTING CONTROL. CONNECT CANOPY LIGHTING THROUGH TIME

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D

BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D HOSKINS ARCHITECTURE, LLC 1827 1 ST AVENUE NORTH, SUITE 104 BIRMINGHAM, ALABAMA 35203 205.321.4122 ADDENDUM NO. 3 PROJECT: BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D HOSKINS

More information

R Scale: 3/32 = 1-0. Scale: 3/32 = 1-0

R Scale: 3/32 = 1-0. Scale: 3/32 = 1-0 145-0 SIGN SCHEDULE A1 A2 A3 B C D E F G B G F A1 INTERNALLY ILLUMINATED CHANNEL LETTERS INTERNALLY ILLUMINATED CHANNEL LETTERS INTERNALLY ILLUMINATED CHANNEL LETTERS D/F INTERNALLY ILLUMINATED MONUMENT

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

AIRWAYS CROSSING PHASE II BUILDING INFORMATION 5305 McCall Way N.E. T2E 7N7

AIRWAYS CROSSING PHASE II BUILDING INFORMATION 5305 McCall Way N.E. T2E 7N7 AIRWAYS CROSSING PHASE II BUILDING INFORMATION 5305 McCall Way N.E. T2E 7N7 www.airwayscrossing.ca Excellent access to Barlow Trail/McKnight Blvd. Bays starting at 4,000 sq. ft. Surface loading T5 lighting

More information

SECTION PART 1 GENERAL

SECTION PART 1 GENERAL SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Grounding of electrical systems and equipment and basic requirements for ground for equipment, circuits, and systems.

More information

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS SECTION 270528 PATHWAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Communications equipment coordination and installation. 2. Sleeves for pathways and cables. 3. Raceway

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 25 05 26 GROUNDING AND BONDING A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

INSTALLATION MANUAL. FOOTWALL/SINKWALL (floor mount)

INSTALLATION MANUAL. FOOTWALL/SINKWALL (floor mount) INSTALLATION MANUAL FOOTWALL/SINKWALL (floor mount) OVERVIEW The Form is a UL-listed configurable footwall/sinkwall system. This system can include any combination of base cabinets, upper cabinets, wardrobes,

More information

Section HIGH-TENSION Stretched-Fabric Wall Systems SoftWalls, Inc.

Section HIGH-TENSION Stretched-Fabric Wall Systems SoftWalls, Inc. P a g e 1 PART I. GENERAL 1.01 Scope A. Furnish and install SoftWalls HIGH-TENSION Acoustical & Tackable Stretch Fabric Systems B. Related Work Specified Elsewhere: 1.Preparation of a smooth, flat and

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:

More information

Geometrik Manufacturing Inc.

Geometrik Manufacturing Inc. PRODUCT: GEOSQUARE WOOD TILES Page 1 PART I GENERAL 1.1 SECTION INCLUDES 1. GeoSquare wood [acoustical] ceiling tiles. 2. Coordination with other trades that have parts attached to, penetrate through or

More information

FORM FOOTWALL. FORM FOOTWALL (floating) (floating) Installation Manual

FORM FOOTWALL. FORM FOOTWALL (floating) (floating) Installation Manual FORM FOOTWALL (floating) Installation Manual FORM FOOTWALL (floating) OVERVIEW The Form is a UL-listed configurable footwall system. This system can include any combination of base cabinets, upper cabinets,

More information

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows: SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.

More information

SECTION PATIENT BED SERVICE WALLS

SECTION PATIENT BED SERVICE WALLS PART 1 GENERAL 1.1 DESCRIPTION: SECTION 10 25 13 PATIENT BED SERVICE WALLS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Due to the very specialized nature of Patient Wall

More information

PROJ. NO SECTION WIRING DEVICES

PROJ. NO SECTION WIRING DEVICES SECTION 26 27 26 WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Request for Proposal

Request for Proposal Request for Proposal Dillon School District Three Telecommunications Cabling for Latta Middle School Contact: Robert McIntyre, Director of Technology (843) 752-7101 office phone (843)752-2081 office fax

More information

15. EVERY BRANCH CIRCUIT SHALL BE PROVIDED WITH A SEPARATE, DEDICATED NEUTRAL IN ACCORDANCE WITH NEC, WETHER SHOWN ON DRAWINGS OR NOT.

15. EVERY BRANCH CIRCUIT SHALL BE PROVIDED WITH A SEPARATE, DEDICATED NEUTRAL IN ACCORDANCE WITH NEC, WETHER SHOWN ON DRAWINGS OR NOT. ELECTRICAL LEGEND ELECTRICAL NOTES DEMOLITION NOTES: J NF US E.C. EM T NL WP - 20 AMP, 120 VOLT DUPLEX RECEPTACLE - DUPLEX RECEPTACLE WITH (2) USB PORTS - MANUAL MOTOR STARTER - VOICE/DATA OUTLET WITH

More information

University of Florida Telecommunication Standards JANUARY 2010

University of Florida Telecommunication Standards JANUARY 2010 University of Florida Telecommunication Standards JANUARY 2010 This document is designed to assist certified Information Transport System (ITS) designers such as Professional Engineers and Registered Communications

More information

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

1510 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

1510 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS SECTION 260533-RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Section includes conduit raceways, and tubing, surface raceways, wireways, outlet boxes, pull and junction boxes, and

More information

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS

MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS DAIMLERCHRYSLER MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS ISSUE DATE: 5/1/90 EFFECTIVE DATE: 2/4/92 REVIEW DATE:

More information

Huntsville Utilities Underground Residential Service Requirements

Huntsville Utilities Underground Residential Service Requirements Huntsville Utilities Underground Residential Service Requirements Sections: Scope General Conduit Installation Conduit Termination at Riser Pole Conduit Termination at Padmount Transformer or Secondary

More information

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 14 - CONVEYING EQUIPMENT DESIGN STANDARDS SECTION

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 14 - CONVEYING EQUIPMENT DESIGN STANDARDS SECTION PART 1 - GENERAL 1.01 Elevator manufacturer to provide equipment and installation warranty and maintenance services for at least one year after acceptance. This requires routine monthly inspection, emergency

More information

Village of Gurnee Construction Documents Submittal Requirements

Village of Gurnee Construction Documents Submittal Requirements Commercial New Construction 4 sets of complete plans Commercial Alterations 2 sets of complete plans Residential New Construction, Remodel and/or Addition 2 sets of complete plans DETAILED PLAN REQUIREMENTS

More information

Kaf-Tech Product Specification

Kaf-Tech Product Specification Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-LUMINARY CABLE

More information