PERFORMANCE TEST REPORT. Rendered to: SIMTEK FENCE. TYPE: SimTek Privacy Fence System

Similar documents
TEST REPORT. Rendered to: ENDURIS EXTRUSIONS INC. For: 6' high by 8' wide Dog Ear Picket Shadow Box Privacy Fence Systems

TEST REPORT. Rendered to: COLLINS LIMITED, LLC. For:

TEST REPORT. Rendered to: KEYLINK FENCING & RAILING, INC. For: PRODUCT: Lancaster Series. TYPE: Aluminum Level Guardrail System

TEST REPORT. Rendered to: AFCO INDUSTRIES, INC. For: PRODUCT: Redi-Rail. TYPE: Aluminum Level Guardrail System

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: Solutions Aluminum Guardrail System with Glass Balustrades

STRUCTURAL PERFORMANCE TEST REPORT. Rendered to: DIGGER SPECIALITIES, INC. For: 8 ft by 42 in Westbury Style C10 Level Aluminum Guardrail Assembly

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door

WESTERN SPINDLE LLC TEST REPORT

PERFORMANCE EVALUATION TEST REPORT. Rendered to: CBT SUPPLY, INC. / D.B.A. SMARTDESKS

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly

ASTM D 4541 ADHESION STRENGTH PERFORMANCE TEST REPORT. Rendered to: BAUTEX SYSTEMS. PRODUCT: AMB 20-WN Liquid Applied Membrane

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

PERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight

SURFACE PROPERTY TEST REPORT. Rendered to: VANGUARD ADA SYSTEMS OF AMERICA. PRODUCT: Detectable Warning/ADA Non-Skid Coating

MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall

TEST REPORT. Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip

TEST REPORT. Report No.: C Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall)

TEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan

PERFORMANCE TEST REPORT. Rendered to: DOW CORNING CORPORATION. PRODUCTS: Dow Corning 790 Silicone

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC.

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1" FABRI TACK

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4" Fabri Trak

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results

calibrated gas flows from the room burner.

PERFORMANCE TEST REPORT. Rendered to: HILTI CORPORATION. PRODUCT: Extreme Weather Window & Door Insulating Foam Sealant

OSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: MGM INDUSTRIES. SERIES/MODEL: 4600 Picture Window

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO)

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star

MILLENNIUM METALS, INC TEST REPORT

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America LLC. SERIES/MODEL: FCM B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

Prepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web:

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless. TYPE: Stretch Fabric Wall System

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles

KNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT

Prepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web:

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to FABRITRAK SYSTEMS, INC. SERIES/MODEL: Fabri Flex Fabric with 6#

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to DFB SALES. Series/Model: DFB Artform Panel Wrapped in Carnegie Xorel

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window

FENCE STUNNING BEAUTY LIFETIME DURABILITY. (800)

LABORATORY TEST REPORT

TEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

PRODUCT CATALOG

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB. TYPE: Acoustical Wall Panel

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to VENEKLASEN ASSOCIATES

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to VENEKLASEN ASSOCIATES

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY. Series/Model: Whisper Mat CS

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

TEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania

Structural Performance Certification Authorization Report

Structural Performance Certification Authorization Report

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

PERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: MGM INDUSTRIES. SERIES/MODEL: 4600 Double Hung

TEST REPORT. Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois. AD Skylight without Guard

TEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Vinyl

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas. Cycles 2,000,000. Summary of Results

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

PERFORMANCE TEST REPORT. Rendered to: TERRACORE PANELS, LLC PACIFIC BEDROCK INDUSTRIAL CO. LTD.

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1

Transcription:

Architectural Testing PERFORMANCE TEST REPORT Rendered to: SIMTEK FENCE TYPE: SimTek Privacy Fence System Report No: Report Date: 12/13/07 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

PERFORMANCE TEST REPORT December 13, 2007 TABLE OF CONTENTS PERFORMANCE TEST REPORT... 1 1.0 General Information... 1 1.1 Product... 1 1.2 Project Description... 1 2.0 Wind Load Testing... 1 2.1 Test Specimen... 1 2.2 Equipment... 1 2.3 Test Setup... 2 2.4 Test Procedure... 2 2.5 Limitations of Test... 3 2.6 Wind Load Panel Test Results... 3 2.7 Wind Load Post Test Results... 5 3.0 Summary and Conclusions... 6 Revision Log... 8 Appendix A - Drawings Appendix B - Photographs

PERFORMANCE TEST REPORT Rendered to: SIMTEK FENCE 1301 West 400 North Orem, Utah 84057 Report No: Test Dates: 05/31/07 Through: 10/30/07 Report Date: 12/13/07 1.0 General Information 1.1 Product 6 ft by 6 ft SimTek Privacy Fence Systems 1.2 Project Description Architectural Testing, Inc. was contracted by SimTek Fence to perform dynamic wind load tests on their 6 ft by 6 ft privacy fence systems. This report includes comprehensive written and photographic documentation of the testing performed. 2.0 Wind Load Testing 2.1 Test Specimen Three (3) fence sections measuring approximately 6 ft wide by 6 ft tall and three (3) 102" posts were tested. SimTek Fence provided all test materials to Architectural Testing, Inc. See drawings in Appendix A for detailed descriptions of assembly and components. 2.2 Equipment The wind generator consists of an engine driven vane axial fan. The fan blades were fixed at a 5-1/2 pitch as marked on the fan. The plenum has an outlet of 8 ft wide by 4 ft high with eight 2 ft by 2 ft baffled outlets. Deflections were measured with linear transducers accurate to 0.01". Wind speeds were calibrated according to Section 7 of Miami-Dade's Protocol TAS 100-95 (reference Architectural Testing, Inc. Report No. 72064.02-119-16). 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

Page 2 of 8 2.3 Test Setup Wind Loading on Panels A steel test fixture was designed and fabricated to simulate a rigid post embedment. The bottom of the bottom rail was positioned 1" above the top of the test fixture. An additional panel section was added and anchored to the ground to simulate field installation conditions. The wind generator outlet was located 4 ft from the face of the specimen (see photographs in Appendix B). Linear transducers were fixed on the top rail, middle of the in-fill area, and bottom rail for deflection measurements. Wind Loading on Post A steel test fixture was designed and fabricated to simulate a rigid post embedment. The post was positioned in the center of the fixture and connected to one panel section with threaded rods. The wind generator outlet was located 4 ft from the face of the specimen (see photographs in Appendix B). Linear transducers were fixed on the top rail, middle of the in-fill area, and bottom rail for deflection measurements. 2.4 Test Procedure Panel and Post Testing Procedure Wind load testing was performed at 75 mph and held for duration of 50 seconds followed by a relaxation period of one to two minutes. Following the relaxation period the fence was subjected to a wind load of 110 mph for 35 seconds or until failure. Duration of wind load at each increment was determined by using the following equation: t = 3600 / V fm (Equation 1) where: t = duration, seconds, and V fm = "fastest mile" wind speed, mph. Wind speeds used in testing correlate with "fastest mile" wind speeds (V fm ) for reference to codes and design standards. Maximum deflections were recorded at each load level. Three (3) panel specimens and three (3) post specimens were tested using this sequence of loading.

Page 3 of 8 2.5 Limitations of Test Test setup and procedure provides information for evaluation of the fence assembly to resist sustained wind speeds indicated in the test results. This evaluation includes the transfer of wind loads to the fence panels, rails, and support posts. 2.6 Wind Load Panel Test Results See drawings in Appendix A for assembly details and photographs in Appendix B for specimen orientation respective to wind direction. Specimen Description: 6 ft x 6 ft SimTek Privacy Fence System Grade to Bottom Rail Height: 1" Rails: Two 18 gauge by 1-1/2" by 70-1/4" long rectangular galvanized stiffeners Panels: One 71-3/4" by 69-1/2" Linear Low Density Polyethylene Shell (LLDPE) Post: Two 5" by 5" in-line "I" shaped-lldpe shell with polyethylene foam core with 18 gauge galvanized reinforcing "Z" insert and one 5" by 5" end post with LLDPE shell and polyethylene foam core with 16 gauge galvanized reinforcing "C" insert. Rail Attachment: The panel was attached through the grooved channels on the post. No fasteners were used to secure the panels. The brackets were attached to the composite posts using three #10 by 2-1/2" stainless steel screws. Wind Speed Duration Specimen #1 Test Date: 5/31/07 Maximum Deflection (inches) Top Mid Bottom 75 mph 50 sec 2.17 3.32 0.58 0 mph Permanent set 1.11 0.94 0.27 110 mph 35 sec 2.24 3.72 1.18 0 mph Permanent set 2.03 1.59 0.39 Maximum Sustained Wind, V fm = 110 mph (equivalent V 3s = 130 mph)

Page 4 of 8 2.6 Wind Load Panel Test Results: (Continued) Wind Speed Duration Specimen #2 Test Date: 05/31/07 Maximum Deflection (inches) Top Mid Bottom 75 mph 50 sec 1.92 3.32 0.57 0 mph Permanent set -- -- 0.22 110 mph 35 sec -- -- 0.76 0 mph Permanent set -- -- 0.13 -- Indicates no data point recorded Maximum Sustained Wind, V fm = 110 mph (equivalent V 3s = 130 mph) Wind Speed Duration Specimen #3 Test Date: 05/31/07 Maximum Deflection (inches) Top Mid Bottom 75 mph 50 sec -- 4.57 0.64 0 mph Permanent set -- 1.09 0.19 110 mph 35 sec -- 10.05 1.40 0 mph Permanent set -- -- -- -- Indicates no data point recorded. Maximum Sustained Wind, V fm = 110 mph (equivalent V 3s = 130 mph)

Page 5 of 8 2.7 Wind Load Post Test Results See drawings in Appendix A for assembly details and photographs in Appendix B for specimen orientation respective to wind direction. Specimen Description: 6 ft x 6 ft SimTek Privacy Fence System Grade to Bottom Rail Height: 1" Rails: Two 18 gauge by 1-1/2" by 70-1/4" long rectangular galvanized stiffeners Panels: One 71-3/4" by 69-1/2" Linear Low Density Polyethylene Shell (LLDPE) Post: One 5" by 5" in-line "I" shaped-lldpe shell with polyethylene foam core with 18 gauge (0.54 minimum thickness) galvanized reinforcing "Z" insert made with HSLAS (high strength, low alloy steel) Grade 60, Class 2. Post Attachment: The post was attached to the center of the panel with threaded rods and anchored to the test fixture with steel angles. Wind Speed Duration Specimen #1 Test Date: 10/29/07 Maximum Deflection (inches) Top Mid Bottom 75 mph 50 sec -- -- -- 0 mph Permanent set -- -- -- 110 mph 35 sec -- -- -- 0 mph Permanent set -- -- -- -- Indicates no data point recorded. Maximum Sustained Wind, V fm = 110 mph (equivalent V 3s = 130 mph) Wind Speed Duration Specimen #2 Test Date: 10/30/07 Maximum Deflection (inches) Top Mid Bottom 75 mph 50 sec 2.17 1.19 0.27 0 mph Permanent set 0.58 0.38 0.15 110 mph 35 sec 5.89 3.21 0.74 0 mph Permanent set 1.38 0.83 0.32 Maximum Sustained Wind, V fm = 110 mph (equivalent V 3s = 130 mph)

Page 6 of 8 2.7 Wind Load Post Test Results: (Continued) Wind Speed Duration Specimen #3 Test Date: 10/30/07 Maximum Deflection (inches) Top Mid Bottom 75 mph 50 sec 1.59 0.89 0.23 0 mph Permanent set 0.46 0.31 0.16 110 mph 35 sec 4.98 2.73 0.68 0 mph Permanent set 1.35 0.82 0.33 Maximum Sustained Wind, V fm = 110 mph (equivalent V 3s = 130 mph) 2.8 Summary and Conclusions The tested samples of SimTek Privacy Fence withstood a 110 mph sustained wind corresponding to "fastest mile wind speed", V fm. Equivalent 3-second gust wind speed (V 3S ) is 130 mph.

Page 7 of 8 Detailed drawings, data sheets, representative samples of test specimens, a copy of this test report, and all other supporting evidence will be retained by Architectural Testing, Inc. for a period of four years from the original test date. At the end of this retention period, said materials shall be discarded without notice, and the service life of this report by Architectural Testing, Inc. shall expire. Results obtained are tested values and were secured using the designated test methods. This report neither constitutes certification of this product nor expresses an opinion or endorsement by this laboratory; it is the exclusive property of the client so named herein and relates only to the tested specimens. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC: Matthew C. Holloway Technician Travis A. Hoover Project Engineer MCH:mch/alb Attachments (pages) Appendix A - Drawings (6) Appendix B - Photographs (3)

Page 8 of 8 Revision Log Rev. # Date Page(s) Revision(s) 0 12/13/07 N/A Original report issue

APPENDIX A Drawings

APPENDIX B Photographs

Photo No. 1 Wind Load Panel Test Setup Photo No. 2 Specimen #1 - at 110 mph Wind Speed

Photo No. 3 Specimen #2 during Wind Load Panel Test Photo No. 4 Wind Load Post Setup

Photo No. 5 Specimen during Testing of Post Photo No. 6 Specimen during Testing of Post