An energy-saving control strategy for VRF and VAV combined air conditioning system in heating mode

Similar documents
Field Performance Measurements of VRF System with Subcooling Heat Exchanger

Performance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation

Opportunities and Limitations of Building Precooling

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

An Optimal Maintenance Scheduler

LCCP Analysis of Energy-Saving Effect of Defaulting to Recirculated Cabin Air in EV Mobile Air Conditioning System

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

The New Variable Refrigerant Flow System Models in EnergyPlus: Development, Implementation and Validation

Canada Published online: 28 Feb 2011.

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate

Reducing Operating Costs with Optimal Maintenance Scheduling

Online Optimal Control of The Central Chilling System in a Super High-Rise Commercial Building

Heat Pump With a Condenser Including Solid- Liquid Phase Change Material

Conversion Factors for Comparing the Performance of Variable Refrigerant Flow Systems

Investigation on A Ground Source Heat Pump System Integrated With Renewable Sources

Heating Performance with a Volume Ratio on 2-Stage Compressor

Fault diagnosis of refrigerant charge based on PCA and decision tree for variable refrigerant flow systems

Year-round Energy Saving Potential for a Stratum Ventilated Subtropical Office. C.K. Lee Zhang Lin K.F. Fong

Performance Evaluation under the Actual Operation Condition of a Ground Source Multiheat Pump System

Energy-saving Potential Study on Telecommunication Base Station Free Cooling With a Thermosyphon Heat Exchanger in China

Economic Model Predictive Control for Variable Refrigerant Systems

MODELING AND VALIDATION OF EXISTING VAV SYSTEM COMPONENTS

Normalized Effect Of Condenser Fouling And Refrigerant Charge On Performance Of Vapor Compression Air Conditioning Systems

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

OPTIMAL OPERATION OF VAV AIR-CONDITIONING SYSTEM

The Part-Load Efficiency Benefit of Oil-Free, High- Speed, Direct-Drive Centrifugal Compressors

The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy Power Recovery

Unitary Air Conditioner Field Performance

Performance Characteristics and Mapping for a Variable-Speed Ductless Heat Pump

Optimal Supervisory HVAC Control: Experiences in Australia

Evaluating Energy Performance and Improvement Potential of China Office Buildings in the Hot Humid Climate against US Reference Buildings

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Utilizing Heat Dump Capacity of a Small Pond Attached to Infloor Slab of a Net-Zero Energy House

CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING

Inverter Drive Control and Seasonal Performance Analysis of a Single Speed Unitary Air-Source Split-System Heat Pump

Meeting the Variable Needs of Energy- Efficient Mechanical Ventilation When and Where You Need It

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

Application Of Oil Flooded Compression With Regeneration To A Packaged Heat Pump System

Operation of Cool Thermal Energy Storage to Increase Renewable Energy Utilization

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

The impact of hot and cold storages on a solar absorption cooling system for an office building

Airflow Based Model to Estimate Commercial Building HVAC Energy Use: Analysis to determine principal factors for different climate zones

Experimental Study on Thermal Performance Improvement of Envelop Integrated with Phase Change Material in Air-conditioned Room

Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat Recovery VRF System)

INCENTIVE ESTIMATOR HVAC USER GUIDE CONTENTS FLORIDA CUSTOM INCENTIVE PROGRAM

Seasonal Energy Efficiency Rating Improvement Of Residential HVAC Systems Using A Low Power Inverter With A PSC Compressor

The Evaluation method of HVAC System s operation performance based on Energy Flow Analysis and DEA

Using Simulation Model to Reduce System Design Time and Cost

Heat Pump Assisted Solar Thermal System

Verification of Chiller Performance Promotion and Energy Saving

> HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION. Available range. Unit description. Options. Accessories

Performance Evaluation of a Passive Chilled Beam System and Comparison with a Conventional Air System

Research on Ground Source Heat Pump Design

Modelling of Phase Change Material Implemented Into Cold Storage Application

Design and development of a residential gas-fired heat pump

Building Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System)

VERIFICATION OF OPTIMUM OPERATION METHOD BY SIMULATION FOR THE HVAC SYSTEM WITH A THERMAL STORAGE TANK IN AN ACTUAL BUILDING

The Impact of Evaporator Fouling on the Performance of Packaged Air Conditioners

2. The requirements of Sections 502, 503, 504 and 505. In addition, commercial buildings shall comply with either Section 506.2, or

Component-Based Vapor Compression Simulation Tool With Integrated Multi-Objective Optimization Routines

Design of integrated control system for indoor environment*

Measurement and Simulation of Startup and Shut Down of Heat Pumps

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

Laboratory Assessment of a Demand Response Controller for Rooftop Units

Using Annual Building Energy Analysis for the Sizing of Cooling Tower for Optimal Chiller-Cooling Tower Energy Performance

A Comparative Study of Energy Consumption for Residential HVAC Systems Using EnergyPlus

Trane Water-Source Variable Refrigerant Flow

Modelica-based Heat Pump Model for Transient and Steady-State Simulation Using Low-GWP Refrigerants

Evaluation of an Extremum Seeking Control Based Optimization and Sequencing Strategy for a Chilled-water Plant

COPs, EERs, and SEERs

A Study on Engineering Application of Solar Heating System Assisted by Heat Pump

A Method for On-Going Commissioning of VRV Package Systems Using a. Simulation Model

Comparative Study On Simulation Tools Of Annual Heat Load For Energy Management Y. Takahashi 1 *, G. Yoon 1, M. Yoshinaga 2, and R. Chiba 3 1 Graduate

Study on Energy Saving Control of Electrical System in Office Building

Compressor Performance Comparison When Using R134 and R1234YF as Working Fluids

IMPROVING IAQ AND ENERGY EFFICIENCY FOR BUILDINGS USING VAV AIR CONDITIONING SYSTEM BASED ON FUZZY LOGIC

Final Report. Technical Subtopic 2.1: Modeling Variable Refrigerant Flow Heat Pump and Heat Recovery Equipment in EnergyPlus.

Air distribution and temperature control in classrooms

Energy Performance Evaluation and Development of Control Strategies for the Air-conditioning System of a Building at Construction Stage

Experimental Study of a CO2 Thermal Battery for Simultaneous Cooling and Heating Applications

Air Cooled Packaged Air Conditioning

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

DEVELOPMENT OF NEW SELF-COMPARISON TEST SUITES FOR ENERGYPLUS

Solar-Assisted Space Heating of a Highly Insulated Energy Efficient House

Experimental Studies on a Solar Assisted Heat Pump Working with R22: An Exergy Point of View

A SIMULATION BASED APPROACH FOR IMPACT ASSESSMENT OF PHYSICAL FAULTS: LARGE COMMERCIAL BUILDING HVAC CASE STUDY

The Influence of Operation Modes, Room Temperature Set Point and Curtain Styles on Energy Consumption of Room Air Conditioner

Improving the Energy Performance of HVAC Systems in Operating Theatres by Using Heat Recovery Devices

Impact Of Solar Irradiance Data On MPC Performance Of Multizone Buildings

THE USE OF HEAT RECOVERY DEVICES FOR REDUCING ENERGY CONSUMPTION OF TREATING VENTILATION AIR IN A TROPICAL OPERATING THEATRE

Whole Building Energy Performance Evaluation through. Similar Control Strategies

EnergyPro Building Energy Analysis. Single-story School Building

Performance enhancement of a photovoltaic thermal (PVT) and ground-source heat pump system

Selection of 3X400 Ton Centrifugal Water Chillers for Central AIC Plant --- A Case Study

Development of high efficiency VRF systems under partial heat load for commercial buildings

Energy Efficiency in Building Active Design Part II

EnergyPro Building Energy Analysis. Nine-story Office Building

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 An energy-saving control strategy for VRF and VAV combined air conditioning system in heating mode Yonghua Zhu Shanghai Jiao Tong University, China, People's Republic of, zhuyonghua88@sjtu.edu.cn Xinqiao Jin Shanghai Jiao Tong University, China, People's Republic of, xqjin@sjtu.edu.cn Zhimin Du Shanghai Jiao Tong University, China, People's Republic of, duzhimin@sjtu.edu.cn Xing Fang Shanghai Jiao Tong University, China, People's Republic of, windofreeds@sjtu.edu.cn Bo Fan Shanghai Jiao Tong University, China, People's Republic of, fanbo1025@sjtu.edu.cn Follow this and additional works at: http://docs.lib.purdue.edu/iracc Zhu, Yonghua; Jin, Xinqiao; Du, Zhimin; Fang, Xing; and Fan, Bo, "An energy-saving control strategy for VRF and VAV combined air conditioning system in heating mode" (2014). International Refrigeration and Air Conditioning Conference. Paper 1365. http://docs.lib.purdue.edu/iracc/1365 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2125, Page 1 An energy-saving control strategy for VRF and VAV combined air conditioning system in heating mode Yonghua ZHU 1, Xinqiao JIN 1 *, Zhimin DU 1, Xing FANG 1, Bo FAN 1 1 School of Mechanical Engineering, Shanghai Jiao Tong University Shanghai 200240, P. R. China Tel/fax: +86 21 34206774 * Corresponding Author ABSTRACT Although variable refrigerant flow (VRF) systems have become attractive due to good energy performances in part load conditions, the shortcoming of no outdoor air intake has not been solved thoroughly. A VRF and VAV combined air conditioning system is proposed to solve this problem. VAV part of the combined system consists of an outdoor air processing (OAP) unit and VAV boxes. Generally the VRF unit operates to maintain indoor temperature and the OAP unit operates to process the outdoor air. A control strategy for the combined system aiming at reducing energy consumption is presented in this paper. When both VRF unit and OAP unit are operating, a load allocation optimization module is executed to find the best load allocation between them to minimize the energy consumption of the combined system. When the allocated load of the OAP unit is very small, the proposed control strategy stops the OAP unit, leaving only the VRF unit to operate to improve the overall energy efficiency of the combined system. When load requirements are met, the OAP unit is restarted and the load allocation optimization module is executed again. The proposed control strategy is evaluated based on the developed simulation platform. Results show that the proposed control strategy can effectively decrease the energy consumption of the combined system. 1. INTRODUCTION The variable refrigerant flow (VRF) system has earned wide popularity due to high energy efficiency under part load conditions (Zhou et al., 2007; Liu et al., 2010; Aynur et al., 2009). However, the shortcoming that the VRF system has no outdoor air (OA) intake has not been solved thoroughly. On the other hand, many studies have demonstrated that ventilation has great impacts on health outcomes, absence rates and productivity (Seppanen et al., 1999; Wargocki et al., 2002). Ventilation is also an energy use contributor for processing and delivering the air especially in highly occupied spaces. When one considers these factors together -the importance of ventilation on occupants, the sufficiency of ventilation in VRF systems, and the energy consumption of ventilation, it is very clear that there is urgent need to develop and promote better energy efficient systems for providing ventilation while simultaneously taking advantages of the VRF systems. In our previous studies (Zhu et al., 2014a; Zhu et al., 2014b), a VRF and VAV combined air conditioning system aiming at taking advantages of both parts was proposed and simulated. VAV part of the combined system mainly consists of an outdoor air processing (OAP) unit and VAV boxes. Previous studies found that the combined system could maintain all the air conditioning zones at their specific set-points no matter their set-points are the same or different, and no matter the number of operating indoor units changes or not. It can effectively solve the ventilation sufficiency problem of the VRF systems. In addition, the combined system was found having potential to decrease energy consumption without compromising thermal comfort and indoor air quality by intelligent (optimal) control from the system point of view. This paper mainly presents a control strategy for the combined system in heating conditions aiming at decreasing the energy consumption. Remainder of this paper is organized as follows. Section 2 introduces the

2125, Page 2 combined system and the testing facility. Section 3 discusses the proposed control strategy in details. Cases studies and evaluation of the proposed control strategy are carried out in Section 4. And Section 5 concludes this study. 2. DESCRIPTION AND SIMULATION OF THE COMBINED SYSTEM Fig. 1 shows the schematic of the combined system. The VRF part consists of an outdoor unit and several indoor units. The VRF unit maintains the zone temperature at the set-point by varying refrigerant flow rate with the help of variable speed compressor and electronic expansion valves (EEVs). In each branch supply duct, there is a VAV box to modulate the OA flow in response to the zones demand. Five types of control loops, the so-called VRF (DX) capacity control, zone temperature control, VAV box control, supply fan control and EEV opening control, as shown in Fig. 1 as well, are designed for the combined system for getting good thermal comfort and indoor air quality, and for reliable operation of the compressors. Demand-controlled ventilation (DCV) strategy is adopted to regulate the adequate amount of outdoor airflow. Fig. 2 shows the typical floor pan of a conceptual office building for accommodating the combined system. The building has six floors in total above ground. Each floor of the building is divided into six conditioned thermal zones, corresponding to four outdoor exposures (east, west, south and north), an interior zone (including a ring-shaped corridor) and a center core. A summary of the key parameters of the building is listed in Table 1 of (Zhu et al., 2014a). The air conditioned zones are numbered from zone 1 to zone 25 for conveniently identifying their locations. The test facility (i.e. the simulation platform) is developed based on TRNSYS (Klein, 2009). The combined system is modeled and simulated by integrating the individual component or sub-system models into a complete system (Zhu et al., 2014a; Zhu et al., 2013). Models of other typical components, such as VAV box, supply fan, sensor, controller and actuator, can be found in authors previous works (Jin et al., 2005; Wang and Jin, 2000). Figure 1: Schematic and control designing of the combined system

2125, Page 3 Figure 2: Typical floor plan of the conceptual building 3. THE PROPOSED CONTROL STRATEGY 3.1 Logic of the proposed control strategy The objective of the proposed control strategy is to minimize the total energy consumption of the combined system (a sum of those of the VRF unit, the OAP unit and the fans) without compromising to thermal comfort and indoor air quality. It is found that variation of the OA supply temperature will lead to a reciprocal relationship of cooling/heating capacity as well as energy consumption between the VRF unit and the OAP unit (Zhu et al., 2014b). In the proposed control strategy (Fig. 3), when both the VRF unit and the OAP unit are operating, the load allocation optimization module (Fig. 4) will be executed to find the best load allocation to minimize the energy consumption of the entire combined system (Zhu et al., 2014c). The best load allocation is realized by optimizing the control variable, i.e., the OA supply temperature set-point. On the other hand, if the allocated load of the OAP unit is quite small, or the OAP unit operates at very low energy efficiency, the proposed control strategy will stop the OAP unit, leaving only the VRF unit to operate to improve the energy efficiency of the combined system. The VRF unit which is basically designed for maintaining the indoor air temperature should not be stopped. When requirements are met, the OAP unit is restarted and the load allocation optimization module is executed again.

2125, Page 4 Figure 3: Logic of the proposed control strategy

2125, Page 5 3.2 Modeling of the load allocation optimization Figure 4: Logic of the load allocation optimization module 3.2.1 Energy consumption predicting model. The VRF unit includes an outdoor unit and several indoor units as shown in Fig.1. Each indoor unit consists of a DX coil and a supply fan. The OAP unit can also be simply treated as combination of a DX coil and a supply fan. Without loss of generality, all the DX coils are assumed to be of the same type and have similar characteristics. Similar to the modeling methodology illustrated in literatures (Zhou et al., 2008), the overall energy consumption of a VRF unit is estimated by the following equations. W Wcomp Wfan (1) W Q( RTF)( EIR) (2) comp n Q Qi W fan i 1 n W i 1 fan, i PLR RTF PLF (5) 1 EIR ( EIRT)( EIR f ) COP (6) rated Where, W comp and W fan denote energy consumption of the compressor and the supply fan respectively, Q and Q i denote actual cooling capacity of total and single DX coil at operation condition respectively, RTF denotes run-time fraction and EIR for energy input ratio, PLR denotes part load ratio, a ratio of the practical cooling load divided by the rated design load (Zhang et al., 2006), PLF expresses degradation of efficiency for on-off switching of the compressor (Henderson et al., 1999), COP rated denotes rated COP of the VRF unit, EIR T denotes temperature modifier of EIR, and EIR f denotes air flow rate modifier of EIR(treated constant in this paper). b c d e f T T T T n c e db, OA db, avg EIRT a T c, ref T e, ref T db, ref T db, ref n ref n T T Q / Q (8) db, avg db, i i i 1 (3) (4) (7)

2125, Page 6 Where, a to f are model parameters to be identified using the operation data collected in present time-step and recursive least square estimation technique (Ma and Wang, 2011; Nassif et al., 2008). T c denotes condensing temperature of VRF unit, T e denotes evaporating temperature of VRF unit, T db,oa denotes dry bulb temperature of OA, T db,avg denotes weighted average dry bulb temperature of the air entering the heating coils, n denotes the compressor speed. The subscript ref denotes referenced value of the corresponding variable. 3.2.2 Load allocation optimization. The objective function is the total energy consumption (W total ) of the combined system, which is a sum of that of the VRF unit and the OAP unit (calculated using Eqs. (1)~(8)). Assuming the OAP unit takes LR of the total load (noted as Q load ) of the combined system, theoretical cooling/heating capacity of the OAP unit is Q load LR, and that of the VRF unit is Q load (1-LR) as a result. The value of Q load should be determined at first. In this study, it is assumed that the load conditions are not significantly changed between current and last time step. Q load can be estimated using operation conditions of the VRF unit and the OAP unit in last time step by recursive least square estimation technique. According to Eq.(1), the total energy consumption is then given by Qload (1 LR) Wtotal Qload (1 LR)( EIRVRF ) Wfan, VRF Qrated, VRF (9) Qload LR Qload LR( EIROAP ) Wfan, OAP Qrated, OAP 2 Wtotal ( k1 k2) LR 2k2LR k3 (10) Where 2 Qload k 1 EIROAPQ (11) rated, OAP 2 Qload k 2 EIRVRFQ (12) rated, VRF k3 k2 Wfan, VRF Wfan, OAP (13) 3.2.3 Logic of determining OA supply temperature set-point. For the combined system in heating mode, the higher the LR is, the more loads the OAP unit takes and the higher OA supply temperature should be. Therefore, the LR can be transformed and used for the OA supply temperature control by rules depicted as follows. Where subscript meas indicates current measurement. T Q LR T (14) load OA, set OA, meas QOAP, meas 4. EVALUATION OF THE PROPOSED CONTROL STRATEGY 4.1 Conditions setting Six zones, zone 7 to 12, of the typical floor as shown in Fig. 2 are selected for accommodating a combined system. Heat gains of light and equipment are set the same for each zone, but heat gains of occupants vary in different zones, which are simulated by multiplying the base occupant density by an occupant factor of each office. The set-points of the six zones are 22.The corridor adjacent to these zones is assumed to have an independent air conditioner, which has a thermostat set to 22 C. Rated capacity of the VRF unit is 25.6 kw, and that of the OAP unit is 11.8 kw. One day in January, which is the coldest month in Shanghai, is selected for the evaluation of the proposed control strategy. Fig. 5 shows the ambient temperature and relative humidity variation of the test day. The temperature rises as high as 16 in the late afternoon. The combined system operates from 8:00 to 20:00. The proposed control strategy starts from 8:30 to eliminate the impacts of system dynamics during the startup period. Besides the proposed control strategy, a benchmark strategy which has a fixed OA supply temperature set-point of 22 is also evaluated for comparison purpose.

2125, Page 7 Figure 5: Temperature and relative humidity of the test day 4.2 Results and discussion Fig. 6 shows a comparison of the zone temperature variation under the two control strategies. It can be seen from this figure that the zone temperature can be maintained at the set-point very well with both control strategies. Fig. 7 shows the total load and the load allocation of the OAP unit under the proposed control strategy. The total load varies with the load conditions, and it gradually decreases from the morning to the early afternoon. The OAP allocated load also decreases during this time, and it meets the stopping requirement at about 13:15. The OAP unit is stopped at this time as a result. After the total load is high enough that the restarting requirement is met at about 18:45, the OAP unit is restarted, and the load allocation optimizing is executed again after this time. Figure 6: Zone temperature variation under two control strategies (Zone 7)

2125, Page 8 Figure 7: Load allocation results under the proposed control strategy Table 1 lists the heating capacity and energy consumption of the combined system under the two control strategies. As seen in the table, the total heating capacity of the combined system, which is a sum of the VRF unit and the OAP unit, is almost the same under the two control strategies. However, the energy consumption of the combined system is different greatly. When the proposed control strategy is executed, about 5.17 % of energy can be saved, which indicates the superiority of the proposed control strategy over the fixed set-point control strategy. Table 1: Heating capacity and energy consumption of the combined system Item Control strategy Benchmark Proposed Heating capacity (10 3 kj) VRF 354.82 371.96 OAP 135.26 117.92 Total 490.08 489.88 Energy consumption (kwh) VRF 27.60 27.68 OAP 11.68 9.51 Supply fan 1.15 1.15 Total 40.43 38.34 Energy saving (%) - 5.17 The ratio of the allocated load to the rated capacity of the OAP unit determines when the OAP unit is stopped. It also affects the energy performance of the combined system. Table 2 lists the energy consumption of the combined system under different ratios. Table 2: Energy consumption of the combined system under different ratios of allocated load to rated capacity of the OAP unit

2125, Page 9 Control strategy Benchmark Proposed ratio=1/10 ratio=1/8 ratio=1/6 ratio=1/5 Energy consumption (kwh) 40.43 38.42 38.35 38.34 38.25 Energy Saving (%) - 4.97 5.14 5.17 5.39 It can be seen from Table 2 that the changing ratio of the allocated load to the rated capacity of the OAP unit results in different energy performance of the combined system. The energy saving of the combined system under the proposed control strategy increases as the ratio does in the test day. However, too large ratio will lead to frequent on-off switching of the OAP unit when the restarting load is not very high. In other words, the ratio should not be too large for the reliable operation of the OAP unit despite of the much larger energy saving percentage. 5. CONCLUSIONS An energy-saving control strategy is proposed and evaluated for the VRF and VAV combined air conditioning system in heating conditions. The proposed control strategy combines load allocation optimization and on-off switching logic to make a coordinating control of the VRF unit and the OAP unit. When both the VRF unit and the OAP unit are operating, the load allocation optimization module will be executed. When the load is quite small, the OAP unit will be stopped for efficient operation of the combined system. Once requirements are met, the OAP unit is restarted and the load allocation optimization module is executed again. Results showed that the proposed control strategy is feasible and superior to conventional fixed set-point control strategy. It could efficiently decrease the energy consumption of the combined system in heating conditions. The method can be easily extended to cooing conditions as well. NOMENCLATURE VRF VAV OAP DX OA EEV Variable refrigerant flow Variable air volume Outdoor air processing Direct expansion Outdoor air Electronic expansion valve PLR Part load ratio (W W -1 ) RTF PLF Run time fraction Part load factor EIR Energy input ratio (W W -1 ) LR Load ratio (W W -1 ) T Temperature ( C) n Compressor speed (rpm) W Input power (W)

2125, Page 10 a~f k 1 ~k 3 coefficients coefficients Subscript com fan sys i s c e db wb meas set ref rated compressors supply fan combined system ith air conditioned zone supply air condensing evaporating dry bulb wet bulb measurement set-point reference value rated value REFERENCES Aynur, T.N., Hwang Y., Radermacher, R., 2009, Simulation comparison of VAV and VRF air conditioning systems in an existing building for the cooling season, Energ. Build., vol. 41, no. 11: p. 1143-1150. Henderson, H., Huang, Y.J., Parker, D., 1999, Residential Equipment Part Load Curves for Use in DOE-2, LBL report, 42145. Jin, X.Q., Ren, H.G., Xiao, X.K., 2005, Prediction-based online proposed control of OA of multi-zone VAV air conditioning systems, Energ. Build., vol. 37, no. 9: p. 939-944. Klein, S.A., 2009, TRNSYS-A Transient Simulation Program, User Manual version 17.0, Solar Energy Laborataory, University of Wisconsin--Madison. Liu, X.B., Hong, T.Z., 2010, Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems, Energ. Build., vol. 42, no. 5: p. 584-589. Ma, Z.J., Wang, S.W., 2011, Supervisory and proposed control of central chiller plants using simplified adaptive models and genetic algorithm, Appl. Energ.,vol. 88, no. 1: p. 198-211. Nassif, N., Moujaes, S., Zaheer-uddin, M., 2008, Self-tuning dynamic models of HVAC system components, Energ. Build., vol. 40, no. 9: p. 1709-1720. Seppanen, O.A., Fisk, W.J., Mendell, M.J., 1999, Association of ventilation rates and CO2 concentrations with health and other responses in commercial and institutional buildings, Indoor Air, vol. 9, no. 4: p. 226-252. Wang, S.W., Jin, X.Q., 2000, Model-based proposed control of VAV air-conditioning system using genetic algorithm, Build. Environ., vol. 35, no. 6: p. 471-487.

2125, Page 11 Wargocki, P., Lagercrantz, L., Witterseh, T., Sundell, J., Wyon, D.P., Fanger, P.O., 2002, Subjective perceptions, symptom intensity, and performance. a comparison of two independent studies, both changing similarly the pollution load in an office, Indoor Air, vol. 12, no. 2: p. 74-80. Zhang, X., Xu, G., Chan, K.T., Yi, X., 2006, A novel energy-saving method for air-cooled chiller plant by parallel connection, Appl. Therm. Eng., vol. 26, no.16: p. 2012-2019. Zhou, Y.P., Wu, J.Y., Wang, R.Z., Shiochi, S., 2007, Energy simulation in the variable refrigerant flow airconditioning system under cooling conditions, Energ. Build., vol. 39, no. 2: p. 212-220. Zhou, Y.P., Wu, J.Y., Wang, R.Z., Shiochi, S., 2008, Simulation and experimental validation of the variablerefrigerant-volume (VRV) air-conditioning system in EnergyPlus. Energ. Build., vol. 40, no. 6: p. 1041-1047. Zhu, Y.H., Jin, X.Q., Du, Z.M., Fan, B., Fu, S.J., 2013, Generic simulation model of multi-evaporator variable refrigerant flow air conditioning system for control analysis, Int. J. Refrig., vol. 36, no. 6: p. 1602-1615. Zhu, Y.H., Jin, X.Q., Du, Z.M., Fan, B., Fang, X., 2014a, Simulation of variable refrigerant flow air conditioning system in heating mode combined with outdoor air processing unit, Energ. Build., vol. 68, no. 1: p. 571-579. Zhu, Y.H., Jin, X.Q., Du, Z.M., Fang, X., Fan, B., 2014b, Control and energy simulation of variable refrigerant flow air conditioning system combined with outdoor air processing unit. Appl. Therm. Eng., vol.64, no. 1-2: 385-395. Zhu, Y.H., Jin, X.Q., Fang, X., Du, Z.M., 2014c, Optimal control of combined air conditioning system with variable refrigerant flow and variable air volume for energy saving. Int. J. Refrig., DOI:10.1016/j.ijrefrig.2014.02.006. ACKNOWLEDGEMENT The research work presented in this paper was financially supported by National Natural Science Foundation of China (No. 51376125) and National Natural Science Foundation of China (No. 51376126).