THE STUDY OF ENERGY SAVING ON ACMV (AIR-CONDITIONING AND MECHANICAL VENTILATION) SYSTEM FOR FKM BUILDING ROSLI BIN CHE MAT

Similar documents
AIR-CONDITIONING & MECHANICAL VENTILATION AND LIGHTING RETROFIT THROUGH BUILDING SIMULATION CHEW CHIN ONG UNIVERSITI TEKNIKAL MALAYSIA MELAKA

ENERGY EFFICIENT RESIDENTIAL BUILDINGS ASSESSMENT USING BUILDING INFORMATION MODELING AMIN FAKHKHAR ZADEH

MASOUD GHEISARI A WEB BASED ENVIRONMENT FOR BUILDINGS LIFE CYCLE COST ANALYSIS 2007/2009

SIMULATION AND MEASUREMENT FOR INDOOR AIR FLOW LIM DA PING UNIVERSITI TEKNIKAL MALAYSIA MELAKA

FEASIBILITY STUDY ON EFFECTIVENESS LARGE SURFACE AREA OF ELECTRODE FOR EARTH BATTERY MUHAMMAD IZZUDDEEN BIN KHAZALI

MULTI-OBJECTIVES OPTIMIZATION OF POWER CONSUMPTION OF A BUILDING TOWARDS ENERGY SAVING MHD ISWANDI BIN KATUTU

COMBINED EMPIRICAL MODE DECOMPOSITION AND DYNAMIC REGRESSION MODEL FOR FORECASTING ELECTRICITY LOAD DEMAND NURAMIRAH BINTI AKROM

ENERGY AND THERMAL COMFORT ANALYSIS FOR UNIVERSITY LIBRARY. WONG PEEK HUI B BMCD

BUILDING PERFORMANCE ASSESSMENT IN TERMS OF ENERGY CONSUMPTION USING BUILDING INFORMATION MODELING MOJTABA VALINEJAD SHOUBI

ANALYSIS OF PREVENTIVE MAINTENANCE FOR PROCESSING PLANT ( GASSIFICATION PROCESS UNIT )

ASSESSMENT OF EARLY SUPPLIER INVOLVEMENT IN PRODUCT DEVELOPMENT IN MALAYSIA FOOD INDUSTRY YAP JESSICA

BORANG PENGESAHAN STATUS TESIS

THICKNESS EFFECT ON THE PERFORMANCE OF COMPOSITE TUBE ABDULLAH OMAR BIN ABDUL AZIZ UNIVERSITI MALAYSIA PAHANG

RELATIONSHIP BETWEEN INTERNATIONAL ROUGHNESS INDEX (IRI) AND PRESENT SERVICEABILITY INDEX (PSI)

DESIGN, ANALYSIS, AND FABRICATE OF LOW SPEED WATER TUNNEL AHMAD ZULFADHLI BIN MOHD KHALID UNIVERSITI MALAYSIA PAHANG

THE DESIGN AND CONSTRUCTION OF POST TENSIONED FLAT SLAB NURHIDAYAH BINTI ZAKARIA

TRANSITION OF ENGINE POWERED AIR-CONDITIONING SYSTEM TO THE SOLAR POWERED AIR- CONDITIONING SYSTEM IN A BUS: A FEASIBILITY STUDY

Performance evaluation of an actual building airconditioning

EXPERIMENTAL STUDY OF ACOUSTIC EMISSION TECHNIQUE FOR CONCRETE DEFECT DETECTION HEADER ALI A. UNIVERSITI TEKNOLOGI MALAYSIA

CHARACTERIZATION OF FIBER OPTIC SENSOR FOR LIQUID REFRACTIVE INDEX MONITORING DIANAY SHAFINA BINTI SHAFEI UNIVERSITI TEKNOLOGI MALAYSIA

DESIGN A LOW COST TABLE FAN USING DFMA ANALYSIS NURUL FARMIRA BINTI ZAKARIA UNIVERSITI TEKNIKAL MALAYSIA MELAKA

THE EFFECT OF AGING HEAT TREATMENT ON HARDNESS AND MECHANICAL PROPERTIES OF ALUMINIUM ALLOY NOOR MUHAMMAD JAMALLUDDIN BIN JUSOH

Analysis of Heat Gain in Computer Laboratory and Excellent Centre by using CLTD/CLF/SCL Method

POLYSILICON PROCESS DEVELOPMENT THE EFFECT OF PECVD PROCESS PARAMETERS ON THE FILM CHARACTERISTICS MUJAHIDUN BIN MASHURI

EFFECTS OF CHEMICAL MECHANICAL POLISHING (CMP) PARAMETERS ON NIP/AL SUBSTRATE SURFACE CHARACTERISTICS MOHD AIDIL BIN ROSLI

A SENSOR ARRAY BASED ON PLANAR ELECTROMAGNETIC SENSORS FOR AGRO-ENVIRONMENTAL MONITORING SYAHRUL HISHAM BIN ABD. RAHMAN

THE RELATIONSHIP BETWEEN JOB SATISFACTION AND EMPLOYEE LOYALTY IN THE MANUFACTURING INDUSTRY OF CHINA SHI HE

EXPLORING THE EFFECT OF PROMOTIONAL MIX ELEMENTS ON BRAND AWARENESS IN AIRLINE INDUSTRY

POLLUTION INVESTIGATION AND EMISSION INVENTORY FOR RESTAURANT IN MBMB REGION SHARMEEZAM BIN MAT UNIVERSITI TEKNIKAL MALAYSIA MELAKA

FACTORS INFLUENCING THE STRENGTH OF FOAMED BITUMEN STABILISED MIX MOHD YAZIP BIN MATORI UNIVERSITI TEKNOLOGI MALAYSIA

Signature :... Supervisor s Name :... Date :...

Level 1 Modules tdp-101 hvac industry overview tdp-103 concepts of air conditioning tdp-102 abcs of comfort

AN EFFICIENT MICROCONTROLLER-BASED ELECTRONIC BALLAST FOR HIGH PRESSURE SODIUM LAMPS USED IN STREET LIGHTING MOHD HAMIZAN BIN OMAR

UNIVERSITI TEKNIKAL MALAYSIA MELAKA

LAPORAN PROJEK SARJANA MUDA

WIND EFFECTS ON SYMMETRICAL MULTIPLE CORE WALL SYSTEM OF HIGH-RISE BUILDING HAZWANI BINTI SAMSUDIN

INVENTORY MANAGEMENT AND CONTROL AT AN IN-FLIGHT CATERING COMPANY NOR LIAWATI BINTI ABU OTHMAN

APPLICATION OF GRAPH-BASED METHOD FOR MANUFACTURING LAYOUT EVALUATION

ORGANIZATIONAL STRUCTURE IMPACTS ON PROJECT PERFORMANCE AMONG WORKER AT OIL AND GAS INDUSTRY

AN INTEGRATED ENERGY AND WATER FOOTPRINT FOR OFFICE BUILDING SUSTAINABLE GREEN MANAGEMENT SYSTEM AUGUSTINE AGHA OKO

CARBON EMISSION STRATEGY FOR MALAYSIA (GREEN BUILDING COMMERCIAL) TINA ZAHANI ZAINUDDIN

PARASITIC MOMENT EFFECT FOR THE THREE SPANS CONTINUOUS PRESTRESSED CONCRETE BRIDGE SITI SARAH SALIM

ELECTRICAL ENERGY SAVING POTENTIAL IN SRI LANKA OFFICE BUILDINGS - APPLICATION TO OFFICE BUILDINGS IN COLOMBO. L.H.W.K.S. Priyantha (108925E)

A STUDY ON ATTITUDE TOWARDS USAGE OF AUTOMATED PUSHER BOX TECHNOLOGY USE BEHAVIOR IN FELDA RUBBER INDUSTRY

Performance analysis of a new single effect hot water absorption chiller system

NATURAL GAS DEHYDRATION USING TRIETHYLENE GLYCOL (TEG) AHMAD SYAHRUL BIN MOHAMAD UNIVERSITI MALAYSIA PAHANG

EFFECT OF PRECIPITATE HARDENING TREATMENT ON MICROSTRUCTURE AND MECHANICAL PROPERTIES OF CAST ALUMINUM SILICON ALLOY (A356) BENJUNIOR BINDAMIN

DEFLECTION MONITORING OF CAST IN-SITU BALANCED CANTILEVER PRESTRESSED CONCRETE BOX GIRDER BRIDGE MOHD KHAIRUL AZMAN BIN HAMBALI

A MATHEMATICAL MODEL FOR WATER AND ENERGY NETWORKS MOHAMMAD REZA ABBASI UNIVERSITI TEKNOLOGI MALAYSIA

Signature :... Supervisor s Name: Mohd Saifuzam Bin Jamri. Date :...

I/We declare that had read this work and from my/our opinion this work is adequate from scope and quality aspect for award of Bachelor Degree of

SIMULATION ON EFFECTS OF DIFFERENT TYPES OF CHANNEL/DRAIN ENGINEERING STRUCTURE ON MOS DEVICE PERFORMANCE NORAZLINA BINTI MOHD AMIN

THE USAGE OF QUICK RESPONSE (QR) CODE AMONG THE SMARTPHONE S USER

MAINTENANCE MANAGEMENT ASSESSMENT IN A LOCAL MANUFACTURING COMPANY MOHAMMAD ANNUAR BIN MD SALLEH

Chapter 9: Applications of the Laws of Thermodynamics

PERFORMANCE OF SOLAR AIR-CONDITIONING SYSTEM USING HEAT PIPE EVACUATED TUBE COLLECTOR MAHENDRAN A/L MOORTHY

MANAGING GREENNESS IN FIRM MARKETING TO ENHANCE BUSINESS PERFORMANCE CHONG KAH JUAN UNIVERSITI TEKNIKAL MALAYSIA MELAKA

ESTIMATION IN SPOT WELDING PARAMETERS USING GENETIC ALGORITHM HAFIZI BIM LUKMAN

FLOOD DAMAGE ASSESSMENT MODEL USING COST-BENEFIT ANALYSIS NOR AZLIZA BINTI AKBAR

EFFECT OF DRY MACHINING ON TOOL WEAR MADIHAH BINTI ZUBIR

IMPACT OF WORK LIFE BALANCE ON EMPLOYEES LOYALTY, SATISFACTION, AND PRODUCTIVITY KADARKO ESTHER DIZAHO

DEVELOPMENT OF SILICON-ON-INSULATOR (SOI) TRAPEZOIDAL WAVEGUIDE USING ANISOTROPIC WET ETCHING KHAIRUL ANUWAR BIN ABU KASIM

SUPERVISOR CONFIRMATION NAME OF SUPERVISOR : DR MOHAMMED HARIRI BIN BAKRI DATE :

THE EFFECT OF SUBSTRATE TEMPERATURE OF TITANIUM ALUMINIUM NITRIDE COATING ON TITANIUM ALLOY (TI-6AL-4V) SUBSTRATE USING PVD METHOD HAMID BAHADOR

AHMAD KHAIRUL HAFIZI BIN WAHAB

INCENTIVE ESTIMATOR HVAC USER GUIDE CONTENTS FLORIDA CUSTOM INCENTIVE PROGRAM

DEVELOPMENT OF BRICK FROM MUD FLOOD: MECHANICAL PROPERTIES AND MORPHOLOGY CHANGES MUHAMMAD IRFAN BIN SHAHRIN

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.

PROPERTIES OF ASPHALTIC CONCRETE AC14 CONTAINING COCONUT SHELL AS COARSE AGGREGATE SITI NUR AMIERA BINTI JEFFRY

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.

WEAR DEBRIS DETECTION AND ANALYSIS OF AUTOMOTIVE ENGINE LUBRICATING OIL

THEORETICAL ANALYSIS OF SOLAR WATER HEATING SYSTEM AHMAD ASYRAF BIN RAMLI BACHELOR OF ENGINEERING UNIVERSITI MALAYSIA PAHANG

ENHANCE THE CUSTOMER BUYING BEHAVIOR THROUGH MARKETING STRATEGY ON PURCHASING A HOUSE : SRI PENGKALAN BINAAN IN MELAKA MUHAMMAD KHIDHR BIN MOHD FAUZI

THE EFFECT OF MARKETING MIX ON GUEST SATISFACTION AND GUEST RETENTION IN FIVE STAR HOTELS RONAK RAEESI

THE ROLE AND IMPACT OF INFORMATION TECHNOLOGY TOWARDS THE UNEMPLOYMENT RATE OF HUMAN RESOURCE MANAGEMENT

ENERGY CONSERVATION STRATEGIES FOR HVAC SYSTEMS

THE RELATIONSHIP BETWEEN INNOVATION CAPABILITY AND INNOVATION PERFORMANCE IN SERVICE FIRMS AMIR PARNIAN UNIVERSITI TEKNOLOGI MALAYSIA

ashrae) VENTILATING PRINCIPLES AIR CONDITIONING OF HEATING AND 7th Edition A Textbook with Design Data Based on the 2013 ASHRAE Handbook Fundamentals

QUANTITY SURVEYOR S LIABILITY DURING PRE TENDER STAGE ASMAH ALIA BT MOHAMAD BOHARI UNIVERSITI TEKNOLOGI MALAYSIA

Panel name : MISS SITINOR WARDATULAINA BT. MOHD YUSSOF

ANALYSIS OF QUALITY PRODUCT BY USING QFD METHOD AND SATISFACTION CRITERIA ON CONSUMER PRODUCT

OPTIMUM UTILIZATION OF QUARRY DUST AS PARTIAL REPLACEMENT OF SAND IN GREEN CONCRETE

UNIVERSITI TEKNIKAL MALAYSIA MELAKA

AVAILABLE TRANSFER CAPABILITY BASED ON RANDOMLY GENERATED PROBABILISTIC DISTRIBUTION FUNCTION OF WIND SPEED USING MONTE CARLO SIMULATION

SUPERVISOR VALIDATION

TABLE OF CONTENTS DECLARATION DEDICATION ACKNOWLEDGEMENTS ABSTRACT

ACCURACY ASSESSMENT OF HEIGHT COORDINATE USING UNMANNED AERIAL VEHICLE IMAGES BASED ON ORTHOMETRIC HEIGHT SYAMSUL ANUAR BIN ABU KASIM

Heat Load Calculation for Air Conditioning System

PARAMETER OPTIMIZATION SIMULATION OF HIGH POWER YTTERBIUM DOPED DOUBLE-CLAD FIBER LASER KHAIROL BARIYAH BINTI MAAMUR

1 Exam Prep Manual J Residential Load Calculation 8 th Edition Tabs and Highlights

LIFE CYCLE ASSESSMENT OF AN INTEGRATED SOLID WASTE MANAGEMENT SYSTEM IN JOHOR BAHRU SITI NADZIRAH BINTI OTHMAN UNIVERSITI TEKNOLOGI MALAYSIA

STUDY ON EFFECT OF WINDOW GRILLES FOR SAFETY PURPOSES ON HEAT TRANSFER IN A BUILDING. Amirul Ariffin Bin Kassim

HUMAN POWERED LED TORCH QARTIKA ESLYNA BT OTHMAN

PRODUCT DESIGN IMPROVEMENT THROUGH DESIGN FOR MANUFACTURE AND ASSEMBLY (DFMA) AND THEORY OF INVENTIVE PROBLEM SOLVING (TRIZ) AFZAN BINTI ROZALI

STRUCTURAL SYSTEM ANALYSIS AND DESIGN FOR SAFE HOUSE. Mohammad Rezaeianpakizeh

TDPs provide you with new technical training materials designed to help your contractors, engineers, and designers to effectively design, specify,

SHEAR STRENGTH PARAMETERS OF IMPROVED ORGANIC SOIL BY CALCIUM BASE STABILIZER NORLIZAWATI HASSAN

EFFECTIVENESS OF CRM SYSTEM FOR CUSTOMER SERVICE REPRESENTATIVES (CSR) TRAINING AT TELEKOM MALAYSIA

Grunenwald Science and Technology Building

ACMV Energy Analysis for Academic Building: A Case Study

Transcription:

THE STUDY OF ENERGY SAVING ON ACMV (AIR-CONDITIONING AND MECHANICAL VENTILATION) SYSTEM FOR FKM BUILDING ROSLI BIN CHE MAT This report is submitted in partial fulfilment of requirement for the award of Bachelor of Mechanical Engineering (Design and Innovation) Faculty of Mechanical Engineering Universiti Teknikal Malaysia Melaka June 2012

2 SUPERVISOR DECLARATION I hereby that I read this dissertation and found its content and form to meet acceptable presentation standards of scholarly work for the award of Bachelor of Mechanical Engineering (Design and Innovation) with honours Signature Supervisor Date :.. : Dr. Reduan Bin Mat Dan :..

i DECLARATION I hereby, declare this project entitled the study of energy saving on acmv (airconditioning and mechanical ventilation) system for fkm building is the result of my own research except as cited in the reference. Signature: Authors name: Rosli Bin Che Mat Date: 31 May 2012

For my beloved parents, siblings and friends ii

iii ACKNOWLEDGEMENT First of all, thanks to ALLAH SWT for HIS mercy and guidance in giving me full strength to complete the PSM ( Projek Sarjana Muda ) project and report about the study of energy saving on ACMV (air- conditioning and mechanical ventilation) system for FKM building A lot of thank to my project supervisor, Dr. Reduan Bin Mat Dan for his support, guidance and advise me in this project and help me to complete the technical report of PSM. This project was tested my abilities mentally and physically and also my skill in the Mechanical Engineering. Furthermore, I would like to thank to my PSM panels for my presentation, En. Faizil Wasbari and En. Abdul Rafeq that willing to evaluate my PSM project. Not forgot to second reader, En. Faizil Wasbari for PSM1 and Pn. Mahanum for PSM2. I would like to thank to other lecturers that help me direct or indirect in this PSM project. Lastly, I would like to thanks to my parents, Mr Che Mat B. Che Kob and Mrs Siah Bt Sulaiman that support me mentally and physically not even in this project also for my study. Also to my course mate especially Mohd Azhar Ahmad, Muhammad Azhari and others who ever never give-up in giving their support to me in to accomplish this PSM project. Thank you very much, I will never forget all of your kindness.

iv ABSTRACT This project presents the energy consumption and ACMV (air- conditioning and mechanical ventilation) system of the FKM building. ACMV refers to the equipment, distribution network, and terminals that provide either collectively or individually the mechanical ventilating or air conditioning process to a building. The main objectives of this study are to investigate the relationship between building energy consumption and ACMV system and evaluate the building ACMV system performance through physical measurement. Improvement methods in ACMV system is later being proposed to reduce building energy consumption. This study is also tend to provide a baseline estimate of current energy use which can be used for calculation of the energy saving impact of various options for reducing energy usage. In doing this project, physical measurement is being conducted involving air velocity, temperature and air change rate. Window area and the building wall area measured to obtain the OTTV (Overall Thermal Transfer Value). The lower OTTV value is better for a building. Included proposals to reduce energy consumption and reduce the OTTV in this report. The analysis conducted consists of building cooling loads, energy saving estimates and costing for the building.

v ABSTRAK Projek ini membentangkan penggunaan tenaga dan ACMV (penghawa dingin dan pengudaraan mekanikal) sistem bangunan di Fakulti Kejuruteraan Mekanikal (FKM). ACMV merujuk kepada peralatan, rangkaian pengedaran dan terminal yang menyediakan sama ada secara kolektif atau individu pengalihudaraan mekanikal atau proses penyaman udara untuk bangunan. Objektif utama kajian ini adalah untuk mengkaji hubungan antara penggunaan tenaga elektrik bangunan dan sistem ACMV dan menilai prestasi sistem bangunan ACMV melalui pengukuran fizikal. Kemudiannya, kaedah penambahbaikkan dalam sistem ACMV yang dicadangkan untuk mengurangkan penggunaan tenaga bangunan. Kajian ini juga cenderung untuk menyediakan suatu anggaran asas penggunaan tenaga semasa yang boleh digunakan untuk pengiraan kesan penjimatan tenaga pelbagai pilihan untuk mengurangkan penggunaan tenaga. Dalam melakukan projek ini, ukuran fizikal dijalankan yang melibatkan halaju udara, suhu dan kadar perubahan udara. Luas tingkap serta luas dinding bangunan diukur untuk mendapatkan nilai OTTV( nilai keseluruhan pemindahan haba). Semakin rendah nilai OTTV semakin bagus untuk sesuatu bangunan. Disertakan cadangan untuk mengurangkan penggunaan tenaga serta mengurangkan nilai OTTV. Analisis yang dijalankan terdiri daripada membina beban penyejukan, anggaran penjimatan tenaga dan kos penggunaan ACMV untuk bangunan.

vi TABLE OF CONTENTS DECLARATION.... i ABSTRACT... iv ABSTRAK... v TABLE OF CONTENTS... vi List of tables... x List of figures... xi List of symbols and abbreviation... xiii List of appendixs... xv CHAPTER 1 INTRODUCTION... 1 1.0 BACKGROUND... 1 1.1 OBJECTIVES... 2 1.2 SCOPES OF PROJECT... 2 1.3 PROBLEMS STATEMENT AND SOLUTIONS... 3 CHAPTER 2 LITERATURE REVIEW... 4 2.0 INTRODUCTION... 4 2.1 AIR- CONDITIONING AND MECHANICAL VENTILATION (ACMV) SYSTEM... 5 2.1.1 Air- Conditioning... 6 2.1.2 Mechanical Ventilation... 7 2.2 GREEN BUILDING... 7 2.2.1 Green Building Index (GBI)... 9 2.2.2 How Does GBI Work... 10

vii 2.3 THERMAL CONDUCTIVITY... 11 2.4 RADIATION... 13 2.5 OVERALL THERMAL TRANSFER VALUE (OTTV)... 15 2.5.1 Concept 0f OTTV... 16 2.6 GUIDELINES FOR ENERGY EFFICIENCY IN DESIGN OF AIR CONDITIONING INSTALLATIONS... 18 2.6.1 Design Considerations... 18 2.6.2 Load Calculation and Sizing for AC System... 18 2.6.3 Air Side System Design Criteria... 19 2.6.4 Water Side Distribution System... 20 2.6.5 Off Hours Control... 20 2.6.6 Energy Saving Systems... 21 2.7 ENERGY MANAGEMENT SYSTEM (EMS)... 23 2.7.1 Energy Consuming Areas... 23 2.7.2 Application of EMS to ACMV system... 23 2.8 BENEFITS OF LOW ENERGY BUILDINGS... 24 CHAPTER 3: METHODOLOGY... 25 3.0 INTRODUCTION... 25 3.1 FLOW CHART OF THE PROJECT... 26 3.2 STRATEGY TO REDUCE ENERGY CONSUMPTION OF ACMV... 29 3.3 DETERMINE OTTV( OVERALL THERMAL TRANSFER VALUE)... 31 3.3.1 Building Specifications... 31 3.3.2 OTTV Formula... 34 3.3.3 Malaysian Standard MS 1525:2007... 34 3.4 determine cooling load... 35 3.4.1 External Load... 35 3.4.2 Internal Load... 37 CHAPTER 4...

viii RESULT... 40 4.0 INTRODUCTION... 40 4.1 Result for OTTV calculation... 40 4.1.1 Sample calculation OTTV... 43 4.2 Result of cooling load calculation... 46 4.2.1 Sample calculation of cooling load... 48 4.3 Electricity costing for FKM building... 54 4.4 Guidelines for maintenance an air conditioning systems... 55 4.4.1 Schedule of maintenance... 56 4.4.2 Monthly Routine Service and Repair... 57 CHAPTER 5 (DISCUSSION)... 63 5.1 Current OTTV... 63 5.2 Proposed OTTV... 64 5.3 Background To MS ( Malaysia Standard ) 1525 : 2007... 65 5.4 Building Envelope, Window Design And OTTV... 65 5.5 Ways To Improve OTTV (Reduce OTTV)... 66 5.6 Building cooling load estimation... 66 5.6.1 How to keep cooling loads low... 67 5.7 Electricity costing for FKM building... 68 5.8 Services and maintenance... 68 CHAPTER 6 CONCLUSION AND RECOMMENDATION... 69 6.1 Achievement of objective one... 69 6.2 Achievement of objective two... 69 6.3 Achievement of objective three... 70 6.4 Recommendations for future work... 71 6.4.1 To optimize the design of ACMV system in term of sizing. It should be balance between cost of optimization and saving.... 71 6.4.2 To study individual component energy saving... 71

ix REFERENCES... 72 APPENDIX A... 77 APPENDIX B... 79 APPENDIX C... 82

x LIST OF TABLES TABLE TITLE 2.1 Thermal conductivities of some materials at room temperature (Source: Cengel, Y.A, 2003) 2.2 Emissivity s of some materials at 300K (Source: Cengel, Y.A, 2003) PAGE 13 14 3.1 Properties of green glazed wall 33 3.2 Properties of pre-cast concrete wall 33 4.1 Summary of current OTTV 41 4.2 Summary of proposed OTTV 42 4.3 Summary of current cooling load 46 4.4 Summary of proposed cooling load 47 4.5 Solar Cooling Load (SCL) at 12 pm 49 4.6 5.1 Schedule Of Maintenance Total OTTV for each facade elevation 56 63

xi LIST OF FIGURES FIGURE TITLE PAGE 2.1 PusatTenaga Malaysia 8 2.2 Diamond Building Putrajaya 8 2.3 A simple experiment setup to determine the thermal conductivity of a material (Source: Cengel, Y.A, 2003) 2.4 Radiation heat transfer between a surface and the surfaces surrounding it (Source: Cengel, Y.A, 2002) 2.5 Radiation heat transfer between a surface and the surfaces surrounding it (Source: Cengel, Y.A, 2003) 12 14 15 3.1 Final Year Project Flow Chart 28 3.2 Strategy To Reduce Energy Consumption Of ACMV 29 3.3 Top View With Actual Orientation 31 3.4 West Wall 31 3.5 South Wall 32 3.6 East Wall 32 3.7 North Wall 32 4.1 Refrigerant Compressors 57 4.2 Water Chillers 58 4.3 Cooling Towers 59

xii 4.4 Cooling Chiller Pump 60 4.5 Water Pumpset 60 4.6 Air Filter At Air Handling Unit 64 4.7 Air Handling Unit 64 4.8 Ducting System 64 4.9 Piping System 64

xiii LIST OF SYMBOLS AND ABBREVIATION A U TD CLTD CLTDc Q SHGF SC CLF RT LM K α ω m T area heat transfer coefficient temperature difference cooling load temperature difference corrected cooling load temperature difference cooling load solar heat gain factor shading coefficient cooling load vactor refrigerant ton correction for latitude and month Thermal Conductivity Thermal absorptivity Specific Humidity Specific mass flow rate Relative humidity Absolute Temperature

xiv h Enthalpy h ' Enthalpy of vaporization fg Q L Q S Q W COP OTTV ACMV PSM Latent heat transfer Sensible heat transfer Heat transfer rate Work Coefficient of Performance overall thermal transfer value air conditioning mechanical ventilation projek sarjana muda

xv LIST OF APPENDIXS APPENDIX TITLE A Gantt chart B Table which used for calculation C Plan floor of FKM building( MARS)

CHAPTER 1 INTRODUCTION 1.0 BACKGROUND The project tries to find ways on reducing the energy consumption of the ACMV (air- conditioning and mechanical ventilation) system of the FKM building. Air Conditioning is the control of the humidity of air by either increasing or decreasing its moisture content. Added to the control of the humidity is the control of temperature by either heating or cooling the air, the purification of the air by washing or filtering the air and the control of the air motion and ventilation. Ventilation refers to the process of supplying and removing air by natural or mechanical means to and from any space, Such air may or may not be conditioned. Building energy standards or codes are becoming more and more important in energy efficiency policies [1]. These standards can help raise concern and awareness of building energy conservation, promote energy efficient designs in buildings, encourage the development of energy efficient building products, and form a basis for assessing building energy performance and developing energy efficiency programmers [2]. Many countries in the world are now developing or upgrading their building energy standards in order to achieve the energy efficiency goals. In response to broad concerns regarding the environment and climate change, Green Buildings are becoming much more common and are increasingly in demand by building owners and occupiers [3]. As a result, they are featuring more prominently in the portfolios of most building developers, architects and engineering consultants. The current green trends are quickly becoming the new standard.

2 1.1 OBJECTIVES The objectives of this study are: i. To reduce OTTV (Overall Thermal Transfer Value) of FKM building and complying requirement of MS (Malaysia Standard) 1525. ii. iii. To propose methods on ACMV system maintenance and operation that can reduce building energy consumption. To estimate saving energy consumption for FKM building by calculate cooling load. 1.2 SCOPES OF PROJECT The scopes of this study are: i. Building load calculation including OTTV (overall thermal transfer value). ii. Practical measurements involving temperature, humidity and air change rate. iii. Standard guidelines of procedures for building maintenance based on the study.

3 1.3 PROBLEMS STATEMENT AND SOLUTIONS One of the biggest energy consumption for a non-residential building is the AMCV system. Any saving made on the energy consumption at this system will give significant impact to the cost of running and maintaining the building. Critical analysis and study need to be conducted on which component of the total ACMV system uses the highest energy and innovation and critical thinking is required on how to reduce these consumptions. Present OTTV value need to be determined and new expected OTTV value need to be projected in order to bring about the saving into the system. These are the solution for this problem: i. Redesign the building properties especially the window and the walls. ii. iii. iv. Research and find types of air conditioner and the systems of ACMV. Determine cooling load. Conduct the measurements including the OTTV, present energy consumption by the ACMV and temperature mapping. v. Propose Energy estimates, costing and saving.

CHAPTER 2 LITERATURE REVIEW 2.0 INTRODUCTION This literature review is based on term on related topic that was study and has been discussed by a professional and has given a complete explanation on how the things of study work out. The stated review below is important hint in study of saving energy consumption of ACMV (air-conditioning and mechanical ventilation) system relates on GBI (green building index). ACMV represent Air-conditioning and mechanical ventilation systems. It fills the fundamental principles and systems in a manner that is technically accurate, yet of practical use in the real working world [4]. Today s really, which mandates time and cost effectiveness in ACMV work, dictates this principles approach. By doing this project, some research and observation needed to know energy consumption saving and ACMV systems report [21]. i. Research the energy consumption of air- conditioning and mechanical ventilation, ACMV by the journal by previous study, journal, article, etc. ii. Research the system of ACMV and their equipment. iii. Research the green building index Malaysia, MS1525:2007 about energy management system of ACMV. iv. Research the concept OTTV (overall thermal transfer value) review.

5 2.1 AIR- CONDITIONING AND MECHANICAL VENTILATION (ACMV) SYSTEM ACMV stands for air conditioning and mechanical ventilation and refers to the equipment, distribution network and terminals used either collectively or individually to provide fresh filtered air, heating, cooling and humidity control in a building. A facility can have any combination of heat operated (absorption) and cooling mode to supply the ACMV system. For heating a facility, a gas-or oil-fired boiler or furnace, heat pump, rooftop unit, new technology such as infrared radiation, or electric heat could be employed. Common cooling sources include rooftop units, chillers, heat pumps, air conditioner or some sort of off-peak cooling system. For the purpose of this part, ACMV system is considered to be of three basic types: a. Central air- distribution systems In this type, either ACMV system equipment or an engineered and field-assembled combination of ACMV system components, receives recirculated room air (plus outside air as required) from a central duct system, performs the required ventilating or air-conditioning functions, and delivers the conditioned air to the central duct system, for final delivery to the conditioned space of the building. b. Central circulating water systems In this type, a centrifugal, rotary, screw, scroll or reciprocating, compression refrigeration or absorption refrigeration type water-chilling package provides chilled water to a central piping system; and the piping system supplies cooled water, as required, to water-air heat exchangers (terminal units) serving the conditioned space of the building. The water chilling package, including its heat-rejecting element and the terminal unit are considered to be ACMV system components.

6 c. Multiple units systems In this type, a number of units of ACMV Equipment, each receiving a supply of electric energy, perform the functions of cooling air for distribution to a space or zone of the building. 2.1.1 Air- Conditioning Air conditioning is treating air for temperature, cleanliness and humidity, and directing its distribution to meet requirements of a conditioned space. Comfort air conditioning is when the primary function of the system is to provide comfort to occupants of the conditioned space. The term industrial air conditioning is used when the primary function is other than comfort. There are three basic types of air conditioners: a. Direct expansion coolers include window air conditioners, heat pumps and packaged or rooftop units. Air is cooled and dehumidified as it moves past a cold, refrigerant-filled coil. b. Chilled water systems use water cooled by a refrigeration machine instead of air. This cool water supplies a coil, which cools and dehumidifies the air. c. Evaporative (or swamp ) coolers are usually only appropriate in hot, dry climates and bring hot air in contact with a water spray or damp surface. The result is evaporation of moisture, which lowers the temperature of the air.

7 2.1.2 Mechanical Ventilation Ventilation is a process that either supplies or removes air from a space by natural or mechanical means. All air that is exhausted from a building must be replaced by outside air. Outside air must be brought to a certain temperature by makeup air units used throughout the building. Negative building pressure can be a problem during winter heating season and could lead to a number of other problems such as difficulty in opening doors and equipment operation. Air seeps through gaps around windows, doors and ducts. Equations are available to estimate makeup air heating costs in the Guide to Industrial Assessments for Pollution Prevention and Energy Efficiency, referenced at the end of this document Air is distributed through ducts. Units such as a window air conditioner, distribute air directly from the unit. Other units using baseboards or radiators may deliver heat through water, steam or electric resistance systems. Blowers and registers deliver air in forced air systems. 2.2 GREEN BUILDING A Green building focuses on increasing the efficiency of resource use energy, water, and materials while reducing building impact on human health and the environment during the building s lifecycle, through better sitting, design, construction, operation, maintenance, and removal. Green Buildings should be designed and operated to reduce the overall impact of the built environment on its surroundings. These are the important about green building: a. Green buildings are designed to save energy and resources, recycle materials and minimise the emission of toxic substances throughout its life cycle. b. Green buildings harmonise with the local climate, traditions, culture and the surrounding environment. c. Green buildings are able to sustain and improve the quality of human life whilst maintaining the capacity of the ecosystem at local and global levels.