Distribution Transformer Failures In Port Harcourt

Similar documents
Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc.

Moisture Phenomena in Insulating Systems of Dry, Gas Insulated and Liquid Immersed Transformers & Reactors

MOISTURE MEASUREMENT IN ELECTRICAL EQUIPMENTS

Weidmann Electrical Technology. Presenter Thomas A. Prevost, Weidmann-ACTI

Prediction of the Characteristics of Transformer Oil under Different Operation Conditions

Moisture in Transformer Oil Behavior A deeper look into a complex phenomenon

MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy

Study, Design & Manufacturing of Mobile Transformer Oil Filter Plant, Degassing & Drying Unit

Resin impregnated paper bushings. Product information

ANSI/IEEE Standard C57.12"Standard Guide for Loading Mineral Oil Insulated Transformers"

Bonded Neo Magnetization Guide

Thermal Aging Study of Cellulosic Materials in Natural Ester Liquid for Hybrid Insulation Systems

WEIDMANN Electrical Technology. Presentation at. NETA Trade Show. March 15 th, 2016

CARBON-GRAPHITE PRODUCTS PERMA-FOIL Graphite Sheet

Earthing in electrical network purpose, methods and measurement

Frequently Asked Questions. 3M Liquid-Filled Transformer Insulation

TRANSFORMER S MOISTURE ASSESSMENT WITH ONLINE MONITORING

Moisture equilibrium charts

WHITE PAPER The Criticality of Proactive Maintenance on Isolated Phase Bus Duct Systems

Small and Lightweight Reactor for Boost Converter

MECHANICAL AND PHYSICAL PROPRIETIES

Performance Analysis of High Grade M19 Silicon Steel Core for Distribution Transformer

Transformer Risk Assessment Considerations. Victor Sokolov José Mak Armando Bassetto Dave Hanson

PART MATERIAL REMARK Metal Case with Pig-tail. Brass (Metal Case) Copper (Pig-tail) Star Contact Copper Silver Plated

Design and Manufacture of the Superconducting Bus-Bars for the LHC Main Magnets

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CHARACTERISTICS... 6 MANUFACTURING FACILITIES... 7

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Data Sheet 110kV TD123II dry type outdoor termination

CHAPTER 4 INVESTIGATIONS OF FURANIC DERIVATIVES AND PERFORMANCE EVALUATION OF TRANSFORMER OIL USING UV-VISIBLE SPECTROPHOTOMETER

New designed XLPE-insulated cables substituting paper-insulated pipe type cables

Oil Diagnostics - Test Information

PI Electrical Equipment - tourse PI 30.2 INSULATION. On completion of this module the student will be able to:

Power Transformers. Dissolved Gas Analysis Siemens Energy, Inc. All Rights Reserved

Transforming know-how into reliable energy. TUMETIC and TUNORMA Oil-Immersed Distribution Transformers. Answers for energy.

FOREWORD. Communication on these practices is most welcome. MECHELONIC. The birth of Mechelonic took place a decade ago in January 1972.

Components, Systems and Service for Transformers.

Chapter 2.5: Insulation & Refractories

PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS

FORECASTING THE NATURE OF POWER TRANSFORMER INSULATION OIL USING CHEMICAL PROPERTIES OF DISSOLVED GASES

RB 107 Specification DuraSeal Splices

CIGRÈ 23 BRUGGE Onsite, Online and Post Mortem Insulation Diagnostics at Power Transformers. Germany

COSMOFIN FG Welding Guidelines

Assessment Schedule - TS.5

Production of High Power and Large-Area Negative Ion Beams for ITER

Engineered Gasketing Products

Study with Magnetic Property Measurement of Amorphous HB1 Material and its Application in Distribution Transformer

FAQ about OIL SIGHT GLASSES.

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

Performance investigation of composite and RTV SIR coated insulators at a coastal test station

Data Sheet 110kV TP123-II Porcelain Insulator Outdoor Termination

PROPERTIES OF MATERIALS PART HARDNESS

Offshore Wind Turbines Power Electronics Design and Reliability Research

Section Pot Cores Low Level Applications

NOMEX TYPE 410 TECHNICAL DATA SHEET. Electrical properties. Please note: PERFORM WHEN THE HEAT S ON TYPICAL ELECTRICAL PROPERTIES

TOGA Electrical Insulating Fluid Analysis. Improving performance and protecting assets.

ROLINX Laminated Busbar. Design Rules Version 01 (12/2015)

Federal Power Transformers LLC

OUR VISION J & S POWER SOLUTIONS QUALITY OBJECTIVES... CORE VALUES : OUR TQM PRACTICES... VISION : Call for service 24 x 7 x

X-RAY Contents lists available at

ABSORPTION FILTERS FAP SERIES

Polyisobutylene (PIB) Primary Sealant

Design features - Polymer-housed arresters, PEXLIM

ELECTRICAL SAFETY INSPECTION REPORT

Induction Heating. Jean Callebaut, Laborelec. 1 Introduction Physical principles Induction Installations... 5

Magnetization Fixture Design and Evaluation

ELECTRICAL SAFETY INSPECTION REPORT

Chemical Vapour Deposition: CVD Reference: Jaeger Chapter 6 & Ruska: Chapter 8 CVD - Chemical Vapour Deposition React chemicals to create a thin film

Distribution Transformers Latest Technology in Manufacturing and Best Practices in Maintenance

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

Experiment 3: Determination of an Empirical Formula

Andrew Lamb Magefekt. Batteries

Smart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013

Accreditation No: LAB 041. Electrical Measurement & Test Laboratory (EMTL), PCSIR Labs. Complex, Lahore Pakistan.

SGC switchgears compatible with real service conditions : Solutions that address on-site conditions Pieter Himpens

PARYLENE ENGINEERING. For Longer Lasting Products

A Superconducting Magnet System for Whole-Body Metabolism Imaging

3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series

Recent Developments in Stay Cable Systems

Q & A on Moisture in Transformer Oil

Designing of Amorphous Core Distribution Transformer and Comparison with CRGO Core Distribution Transformer

Instruction guide Medium Voltage equipment on sites exposed to high humidity and/or heavy pollution. Recommendations for installation and use

PRY-MOULD. High Voltage Accessories for Extruded Cables

CRYOGENIC SUPPORTS INTRODUCTION

s d fo r a rs t ed ta g la t after the flood How to prevent future failures and outages after the immediate damage is fixed

NORDTEST METHOD NT BUILD NT BUILD

Pomona, CA May 24 25, 2016

Low Curie temperature material for induction heating self-temperature controlling system

DFE... The Evolution in Filter Element Multi-Pass Development Testing Hy-Pro s Competitive Advantage

Excellent Insulation and Cooling of Power Transformer Oil 25#&45# Brand Transformer Oil Specification

6. SHEATH MATERIALS, THERMOWELLS, FITTINGS, AND TERMINATIONS

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-P W

Improved Determination of Moisture in Oil-Paper-Insulations by Specialised Moisture Equilibrium Charts

CRYOGENIC SUPPORTS INTRODUCTION

Moisture Equilibrium and Moisture Migration Within Transformer Insulation System

PTFE semi-finished products and finished parts

DGA - Method in the Past and for the Future

Study on Thermal Ageing Characteristics of Silicone Rubber and Pressboard in Mineral Oil

Electrical containment penetrations 3 ROUTINE TESTING (PRODUCTION TESTING)

Isolation vs Insulation:

Featured Product. Transformer Monitoring and Diagnostic Systems

Transcription:

Global Advanced Research Journal of Engineering, Technology and Innovation (ISSN: 2315-5124) Vol. 3(7) pp. 202-206, November, 2014 Available online http://garj.org/garjeti/index.htm Copyright 2014 Global Advanced Research Journals Review Distribution Transformer Failures In Port Harcourt 1 John Tarilanyo Afa, and 2 Anireh Vincent Ike Emeka 1 Department of Electrical Engineering,Niger Delta University, Wilberforce Island, Bayelsa State, Nigeria E-mail:jhnafa@yahoo.co.uk Tel: +2348036908502 2 Department of Electrical/Computer Engineering, Rivers State University of Science and Technology, Port Harcourt, Rivers State, Nigeria. E-mail:viaemeka@gmail.com Tel: +2348033229172 Accepted 01 August 2014 Seventy-five percent of power consumed in Rivers State is within Port Harcourt city and about four thousand distribution transformers are spread within various distribution areas. These transformers range from 200KVA to 1.5MVA. Most of the transformers that have been installed about 25 years are usually taken out of service due to damage of various parts. Transformers have no moving parts and are designed to last for over 40 years. It is therefore necessary to look at the reasons of failures of the transformers. This will enable engineers to regulate and monitor the transformers for better performance. From the study it was clear that the problems were as a result of lack of care, unscheduled loading, and unbalance operation of the transformer and activity of the vandals (transformer oil). If good maintenance programmes is provided it will increase the life span of the transformer. Keywords: Insulating oil, magnetostriction, Pressboard, Dielectric strength, radial and axial stress. INTRODUCTION A transformer is a static piece of apparatus and used for transferring power from one circuit to another without change in frequency. The physical circuits linked by a common magnetic flux through a path of low reluctance. According to the Faraday law of electromagnetic induction = - - - (1) Where M = mutual inductance, e = induced emf. If the second circuit is closed, a current flows in it and electric energy is transferred (entirely magnetically) from the first coil to the other (Primary to Secondary). The instantaneous value of counter electromotive force (Lawson et al., 1977). = /2 To obtain the rms values of counter emf e 1, the maximum value is divided by 2. Therefore, the result is =. It could finally be expressed generally as = 4.44 - - - (2) (1 and 2 describe the primary and secondary). Apart from active materials like copper and cold rolled grain-oriented silicon steel, a number of ferrous and

Afa and Anireh, 203 nonferrous insulating materials are employed for building up of a transformer. Optimum utilization of all materials in consonance with their electrical, mechanical, physical, chemical and thermal characteristics is necessary for obtaining a compact size and efficient transformer operation (Sokolov and Vanin, 1974). These characteristics of transformer are given in table 1. These characteristics determine the life of the solid and liquid insulations. In fact the life of the transformer is actually the life of the internal insulation system. Another area of consideration is the electromagnetic forces in power transformer. The most sever mechanical stress occurs in a transformer when it is subject to a sudden short circuit. Since the current flowing through the windings at that time is enormous, the forces generated are also enormous (Oommen and Lindgren, 2001 ; IEEE, 2007 ; Cigre, 2009). Two main forces vectors are the radial force and the axial force. Radial forces are those that act in the radial direction and are generated by the interaction of the current and the axial component of the leakage flux density. They tend to sequeeze the inner winding and burst the outer winding. The simple formula for radial force could be derived from the basic formula. = The average radial force is = 1 " 2 #$%&'! ( )* --------- (3) The maximum force per turn will occur at the inner-turn of inner most layer of the outer winding and the outer turn of the inner winding and is =2+/ -- - - (4) Axial forces are those that act in the axial direction and are generated by the interaction of the current and the radial component of the leakage flux density. The electromagnetic forces arising due to a short circuit are oscillatory in nature and act on an electric system immersed in oil and consisting of winding conductors, insulation components and clamping structures. Attempts have been made to obtain empirical equations for the effective length of path of the radial leakage flux. The simplest of all these approaches is that of waters (Oommen and Lindgren, 2001). Considering that there is an unbalance of Ampere-turns (NI), the mean radial flux density (B r ) and is given by =, -... $% ( /00 ---------- (5) The axial force on the winding f a is 1 = 2 -...#3& 4 5 6789 ---------- (6) ( /00 A short circuit can result in severe radial and axial forces which can damage the insulation integrity. Axial forces are controlled by the proper preloading of the transformer coil during manufacture. The windings are preloaded to a pressure which is at least as high as the maximum calculated axial short circuit force. As long as the transformer clamping system maintains pre-load pressure the winding will remain tight during a short circuit event and should therefore not sustain any damage due to movement of the conductors (Kers, 2011), (Griffin, 1996). Any change in the thickness of the materials in the winding and associated end insulation will change the pressure on the winding. The thickness of the conductor material will not change except for the thermal expansion and contraction during load cycles. The cellulose insulation material, being organic will change in thickness and elasticity over time resulting from the effect of moisture, temperature and aging (Kers, 2011), (Jalah and Abdallah, 2011) It is known that materials which are purely elastic according to Hooke s Law bear a relationship between compression in materials and the pressure. This can be defined by the Modulus of Elasticity as = #: ;&/ ; ---------- (7) Where E = modulus of elasticity (N/mm 2 ) : = pressure (N/mm 2 ) L = thickness of the material mm ; = change in thickness of material mm Electrical and Environmental Factors It can be seen that insulation suffers mainly from processes caused by environmental factors such as thermal degradation, oxygen in oil, and moisture in the oil. Moisture consist of free water that exist in three states When the oil temperature changes several other parameters change as well. If temperature increases, there is an increasing number of water molecules that can dissolve in the oil before saturation occurs. Besides that, the viscosity decreases and the conductivity of transformer oil increases. The degradation of transformer paper has besides electrical stressing many other causes. Other degradation factors are temperature, oxygen, acids and contamination. Due to these factors, the state of the paper changes (Du et al., 2011). In transformer insulation, moisture exists in the capillaries of cellulose. The conductivity of paper changes as the moisture content increases. This change in conductivity subsequently increases its tan= (Du et al., 2011), (Doble, 1946) There is a balance between the moisture in the paper and the moisture in the oil. Moisture can dissolve better in hot oil than in cold oil. Combined with the hot conductors in a transformer, this will drain the moisture out of the paper into the oil. When the transformer cools down again moisture will go back from the oil into the paper. This is in fact a temperature

204 Glo. Adv. Res. J. Eng. Technol. Innov. Table 1 Electrical Mechanical Physical Chemical Electric strength Tensile strength Substance g.m 2 Mineral Ash (Breakdown volt) Dissipation factor of unimpregnated paper Enlongation at break Moisture content at 105 0 C Conducting paths % Conductivity of 5% aqueous extract Internal resistance Heat stability tearing Water absorption Air permeability Oil absorption Density g/cm 3 ph value chloride content of aqueous extract conductivity of organic extract dependent equilibrium reaction. Absorption of moisture by the paper does not occur in an equal measure and as such the moisture will diffuse in the oil, thus lowering the concentration gradient. The water solubility for oil can be expressed in Arrhenius form as 8>+? = @ " A- - ---------- (8) Where, r s is the saturation solubility of water in oil in ppm a A is the temperature in Kelvin A and B are different coefficients Insulating oil undergo oxidative degradation in presence of oxygen to give a number of oxidation products. The final products of oxidation are acidic materials that can affect the characteristics of insulating fluid as well as damage the components of electrical unit. The high temperature in due course causes the fluid to oxidize and ultimately produce sludge and soluble acid in sufficient quantity to impart its heat transfer and dielectric efficiency (Waters, M.), (Roth, 1936). Sludge formation is the terminal stage of the determination process. Common Faults Of Transformers In Port Harcourt District These common faults are put in the following categories: Damage to winding (HT or LT or both) Failure of winding insulations Ingress of moisture or water Loss of phase Low voltage on a phase or all the phases Drying up of oil or leakage of oil These faults were identified as faults due to external or internal causes or both. More than fifty (50) percent of the existing transformers are as old as twenty-five years or more. Presently, several distribution transformers were installed to reduce the load on the existing ones and to take care of the incoming load. This is a welcome development but it was identified that the causes of failure was contributed by relatively lack of proper maintenance or neglect. The other factors were excess overloading and short circuits within and near the transformer. In overloading the temperature rises due to the resistive losses (I 2 R), stray, and eddy current losses. The increasing temperature greatly influences the properties of the insulation and the oil surrounding it. The heating up of the oil have consequences for multiple parameters: Moisture goes from the paper to the oil Increasing solubility Increasing conductivity Decreasing viscosity of oil Due to the heating, the decreasing moisture level of the paper and the increasing moisture level of the oil cause the following: (i) Increase tan= of oil (ii) Decrease breakdown strength of the oil (iii) Increasing breakdown strength of the paper. In short circuit condition whether external or internal, depending on the severity of the short circuit and the effectiveness of the protective devices may cause damage to the transformer winding. Also in certain cases, it may cause electrodynamic vibrations which may results to lose ends. The electromagnetic forces arising due to a short circuit are oscillatory in nature and act on winding conductors, insulation components and clamping structures. Such forces dynamically transmitted to various parts such as conductors, and supports, press plate and clamps. Failures due to these forces (axial and radial) could

Afa and Anireh, 205 cause loss of a phase(s). Ingress of moisture or water to the transformer is a regular occurrence in most transformers in the district. This is due to weather condition and the Algae growth on insulating rubbers gasket, bushing and the external contacts. The ingress of moisture, combined with high temperature in the paper insulation reduces the dielectric strength of both the cellulose materials and transformer oil. Excessive moisture in the insulation causes partial discharges within the moisture-soaked cellulose paper reducing its effective life. Drying of oil is a clear indication of lack of care or it may be as a result of theft but such act is possible to cause a transformer life to be shortened. Several experiments have be done regarding mixing of oils. The results indicate that the oil of two different sources though conforming to the same standards should not be mixed as the sludging properties of the oil are considerably affected by mixing. Another pit fall is the opening of the winding to air as it absorbs moisture from the air. This is possible even with oil opened to the air. The dielectric strength of oil is appreciably diminished by even minor quantities of solid impurities and dirt present in the oil. Therefore proper storage facility as well as care is needed in handling the transformer, oil and other accessories. CONCLUSION Due to the climatic conditions of the Niger Delta the life of a transformer could be reduced if proper maintenance programme is not adopted. Normally, the causes of damage transformers could be any one of the following surge voltage, heavy leakage of oil loose connection, ingress of moisture by loose gasket or non replacement of silica gel, poor earthing, overloading, LT. line faults, inadequate protections against overload, short circuit and lightning. Failure of transformer can also take place if proper care has not been taken during its erection. While receiving the transformer unloading, storing and assembling, the instructions of the manufacturer should be followed strictly. If the transformer is received with oil inside, all care as if the transformer is in service, is required with nitrogen gas. A strict watch is required on maintenance of pressure and purity of gas, all the time the transformer is stored. The auxiliary equipment such as radiators, conservator, piping explosion vent are to be stored with proper care. If the erection and commissioning is done properly, maintenance is required on the transformer to judge the performance in service. It consists of regular inspection, testing and reconditioning whenever necessary. RECOMMENDATIONS Oil level should be checked at frequent intervals and if necessary conservator should be topped up. Dielectric strength does not give a true indication of the correct condition of the oil, it is therefore necessary to carry out the required chemical test. The inside of the conservator should be cleaned periodically. A detachable end plate is provided to facilitate cleaning on all power transformers. Oil indicator glass should be kept clean and its holes at top and bottom be kept cleaned so that oil level is clearly and correctly visible. Breather should be inspected frequently especially in this environment that temperature and humidity changes considerably, as transformer is subjected to fluctuating load. The oil level in the oil seal must be maintained at the level marked in the cap. The diaphragms fitted at the exposed end and inner end of the explosion vent should be inspected frequently and replace if damaged. Failure to replace the outer diaphragm quickly will allow ingress of moisture to the oil. Porcelain insulators and connectors should be cleaned at convenient intervals and minutely examined for any cracks or other defects. There should be regular yearly maintenance. REFERENCES Lawson WG, Simmons MA, Gale PS (1977). Thermal Ageing of Cellulose paper Insulation IEEE Transaction on Electrical Insulation Vol.EL1-12 1977. Sokolov V, Vanin B (1974). Inservice Assessment of water content in Power Transformer Proceedings of the 62 Annual International Conference of Doble Clients 1974. Oommen TV, Lindgren SR (2001). Bubble evolution from Transformer overload IEEE 2001 IEEE (2007). Guide for Loading Mineral Oil Immersed Transformer, 579119 95 ed, New York United States of America 2007. Cigre (2009). Ageing of Cellulose in mineral oil Insulated Transformers 2009. Kers JWB (2011). The Effect of Temperature Cycling and Transients on the Dielectric properties of Transformer impregnated Insulation. MSc Thesis, High Voltage Technology and asset Management. Delft University of Technology, 2011. Griffin PJ (1996).: Water in Transformer-so what! National Grid Monitoring Conference, 1996. Jalah M, Abdallah (2011). Investigating the Transformer Operation Conditions for Evaluating the Dielectric Response: World Academy of Science, Engineering and Technology, 51, pp. 1234 1244, 2011. Du Y, Mamishev AV, Lesieutre BC, Zahn M, Kang SH (2001). Moisture Solubility for Differently conditioned Transformer Oils IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 5, No. 5 2001. Doble F (1946). The Doble Water Extraction Method, Minutes of the 13 th Annual conference of Doble Clients, 1946, Sec. 10 401. Waters M (Provide year). The Measurement and Calculation of Axial Electromangetic Forces in Concentric Transformer Windings, Journal IEE, Vol. Part II.

206 Glo. Adv. Res. J. Eng. Technol. Innov. Roth E (1936).. Magnetic Leakage Inductance in Transformers with Cylindrical Windings and Forces Acting on the Winding, RGE, Vol. 40, August 1936.