ADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities

Similar documents
Service Saddles/ Brass Alloy/ Stainless Steel Straps for Cast, Ductile & PVC Pipe

PART 5 WATER SYSTEMS

KENNEBUNK, KENNEBUNKPORT & WELLS WATER DISTRICT MATERIAL SPECIFICATIONS 10/11/2018

CITY of DALLAS. Standard Drawings. & Oregon Standard Drawing Amendments. Water Drawings

SECTION 2100 WATER MAIN

ONE PIPE LENGTH MAX (REFER TO 1/4"/FT SLOPE (MIN) 5'-0" (MIN) OR 4" LATERAL NOTE #1) INCREASER RIGHT-OF-WAY/ 4"x6" REFER TO TYPICAL EXCAVATION,

7. Allowable Fittings.

CITY OF WARRENVILLE STANDARD SPECIFICATIONS WATER MAIN, SANITARY SEWER AND STORM SEWER

San Antonio Water System Material Standard Specifications

City of Port Moody. Water Meter Specifications

City of Middletown WATER & SEWER DEPARTMENT 82 Berlin Street Middletown, CT TEL: (860) FAX: (860)

Copper-Type K soft Drawn 40, 50 HDPE 100 and larger

East Wenatchee Water District Supplemental Provisions to the 2012 WSDOT/APWA Standard Specifications

ISSUE DATE JANUARY 1st, 2008 SECTION 5G FIBERGLASS PACKAGE LIFT STATION

Water & Industrial Products Catalog

CALAVERAS COUNTY WATER DISTRICT Ebbetts Pass Water System Reach 3A Pipeline Replacement Project CCWD CIP No ADDENDUM 2

SECTION A-A NTS. Figure 4.1 Alternative Flow Dispersal Trench NOTES:

SECTION TAPPING SLEEVES AND VALVES

MATERIAL/MANUFACTURER SPECIFICATIONS FOR DISTRIBUTION WATER MAINS AND APPURTENANCES

B. Stipulated Price (Lump Sum). If Contract is Stipulated Price Contract, payment for work is in this Section is included in total Stipulated Price.

SECTION PLUMBING PIPING

General Design Standards

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

FS-DUO. Wastewater Flow Distributor Technical Data. Submittal Special Precautions Specifications Installation. (62.2 cm) (62.2 cm)

Effective Date: Revision #: 1. Section I: Castings and Aluminum Covers. Valve Boxes. Service Clean-out Box and Lid

Engineering Design Center. Standard Drawings. 1st Edition -January 2016

MAXIMUM TRENCH WIDTH AS REQUIRED SEE MEASUREMENT AND PAYMENT SECTION OF SPECIFICATIONS

Public Water Supply District #2 of St. Charles County, Missouri

STANDARD CONSTRUCTION DETAILS SANITARY SEWER REVISED MARCH 2018 DEPARTMENT OF ENGINEERING

Rockwood Water People s Utility District Cross Connection Implementation and Regulations

Section 7: Specifications

1. Will have water lines designed by a North Carolina Registered Professional Engineer.

HAMILTON TOWNSHIP MUNICIPAL UTILITIES AUTHORITY

EFFECTIVE FEBRUARY note: drainage permit required to call for a dampproof inspection

ROUTE 3 OLD WINTHROP ROAD PROJECT LOCATION I-95 PROJECT LOCATION WESTERN AVENUE NORTH BELFAST AVE.

D-1 FIRE PROTECTION PRODUCTS TAPPING VALVE. MUELLER Tapping Valves. MUELLER Tapping Sleeves and Crosses. MUELLER Stainless Steel Tapping Sleeves

CITY OF MIDDLETOWN ADDENDUM #1 TO BID # BID # LABORATORY TESTING SERVICES. Date Issued: September 1, 2016

SV24. Submittal Special Precautions Specifications Installation. 12½" (31.8 cm) 12½" (31.8 cm) 12" (30.5 cm) 12" (30.5 cm) 12" (30.

KENT COUNTY WATER AUTHORITY. ERRATUM to Rules and Regulations of the Kent County Water Authority

PERMANENT PAVEMENT REPAIR NO SCALE

Request for Bids Water Department. City of Portsmouth, New Hampshire Water Inventory Bid #33-08

Underground Exhaust System

OLYMPIC VIEW WATER AND SEWER DISTRICT APPROVED MATERIALS LIST FOR USE ON NEW CONSTRUCTION OF WATER AND SEWER FACILITIES

DRINKING WATER LINE INSTALLATION STANDARDS

UL / FM D-1 FIRE PROTECTION PRODUCTS TAPPING VALVE. MUELLER Tapping Sleeves and Crosses. MUELLER Tapping Valves

Changes for the. TOHOPEKALIGA WATER AUTHORITY Standards, Specifications and Details

SECTION FIRE HYDRANTS

SERVICE LINES, METERS AND APPURTENANCES

t y p e V S A S E W A G E P U M P

SECTION PUBLIC WATER SERVICE CONNECTIONS

SPECIFICATIONS FOR THE INSTALLATION OF REDUCED PRESSURE BACKFLOW PREVENTERS AND CONCRETE VAULTS FOR METERS 4 AND LARGER

GGI-750. Gravity Grease Interceptor Technical Data. Submittal Special Precautions Specifications Installation

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

INSTALLATION GUIDE. Model #PP2 Pumpout Port Kit For Use with Grease Interceptors Models GB-50, GB-75 and GB-250. Contents

This specification describes the minimum requirements for piping systems for the following service: Plant air systems operating up to 125 PSIG.

SECTION MEASUREMENT AND PAYMENT

WATER SYSTEM REQUIREMENTS

OLYMPIC VIEW WATER AND SEWER DISTRICT APPROVED MATERIALS LIST FOR USE ON NEW CONSTRUCTION OF WATER AND SEWER FACILITIES

CITY OF WESTLAND, MICHIGAN MIDDLE BELT ROAD SANITARY PUMPING STATION MODIFICATIONS

120 WATER DISTRIBUTION SYSTEMS

Student Services & Classroom Addition. A. This Section includes the following sanitary drainage piping specialties:

Union County Vocational - Technical Schools Scotch Plains, New Jersey. A. This Section includes the following sanitary drainage piping specialties:

BUILDING SEWER AND GRINDER PUMP CONNECTION & CONSTRUCTION STANDARDS

SECTION GROUND WATER STORAGE TANKS

September 6, 2016 Page 1 of 5

CLEVELAND DIVISION OF WATER CONSTRUCTION STANDARDS. Details Index

ELEVATION (A - A) PLAN GATE W ELL JOB NO. SHEET NO. DATE MARCH 2015 OF. Gate Wel Dimensions - Inches

.1 ANSI/ASME B31.1, Power Piping, (SI Edition)..2 American Society for Testing and Materials (ASTM)

SECTION PIPING SPECIALTIES AND ACCESSORIES

Diffused Aeration Piping Equipment

City of Port Moody. Water Meter Specifications

FS-TRIO. Wastewater Flow Distributor Technical Data. Submittal Special Precautions Specifications Installation. (62.2 cm) (62.

DUKE UNIVERSITY CONSTRUCTION STANDARDS

MANHOLES, VAULTS AND CATCH BASINS SECTION A. Section Soil and Aggregate Materials. C. Section Storm Drainage Systems

A New Municipal Building for Limerick Township

Combination Air Valves - Stainless Steel/ Sanitary Sewer/ For 2 Thru 12 Mains

1. Required Minimum Flow:

TECHNICAL SPECIAL PROVISION FOR FINANCIAL PROJECT ID:

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION PRECAST CONCRETE MANHOLES

PIPE OUTSIDE DIAMETER GUIDE

CHAPTER 5 WATER SYSTEM DESIGN STANDARDS

SECTION III: Water Main Materials Specifications

WASHOE COUNTY DEPARTMENT OF WATER RESOURCES WATER DESIGN STANDARDS

SPECIFICATIONS FOR PIPE FITTINGS VALVES FIRE HYDRANTS CITY OF ALLIANCE, OHIO. Alan Andreani, Ed. D. Mayor of Alliance

SECTION MISCELLANEOUS METALS

Effective Date: Revision #: 1. Section H: Repair Sleeves, Couplings, Clamps & Non-Pressure Adapters. Pipe Adapters, Non-Pressure

Series Sump and Sewage Systems

SANITARY SEWERS. B. Construct or relocate building sanitary sewer services, stubs, and connections.

This section includes materials and installation of ductile-iron pipe and fittings for potable and recycled water systems.

A. Gravity-Flow, Nonpressure, Drainage-Piping Pressure Rating: 10-foot head of water (30 kpa).

SECTION DRAINS AND CLEANOUTS. 1. Division 7 - Thermal and Moisture Protection Piping (Plumbing).

CITY OF GAINESVILLE DEPARTMENT OF WATER RESOURCES

Facility Sanitary Sewers

FLOOR AND AREA DRAINS

SECTION CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION

TOWN OF HOLLY SPRINGS ENGINEERING DEPARTMENT

CITY OF FARGO SPECIFICATIONS SEWER AND WATER SERVICE CONNECTIONS

All definitions are defined according to ANSI/AWWA C

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following storm drainage piping specialties:

Transcription:

ADDENDUM NO. TO Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities Date of Addendum: December, 00 Hethcoat & Davis, Inc. 78 Franklin Road, Suite 00 Brentwood, Tennessee 3707 6-77-4300 Copyright 00

ADDENDUM NO. Page MVUD Technical Specifications & Design Criteria for Water Supply & Distribution Facilities This Addendum forms a part of and modifies the Document dated February 00. Changes to Technical Specifications. Section 3, Paragraph 3.7.A Tapping Sleeves. Change to read as follows: Tapping sleeves shall consist of an ASTM A-36 steel body, AWWA C07 Class D steel ring flange and designed to fit tapping valve lip per MSS SP-60. Outlet gasket shall be manufactured of NBR meeting ASTM D000. Bolts and nuts shall be high strength, low alloy steel meeting requirements of AWWA C. The sleeve shall contain a ¾-inch test plug. Coating shall be fusion bonded epoxy or corrosion resistant shop coat paint primer. Tapping sleeves shall be rated for a working pressure of 7 psi. The steel tapping sleeve shall be manufactured by Romac Industries, Style FTS40 or JCM Industries 4.. Section 3, Paragraph 3.4.D Water Meters. Delete reference to Sensus Omni Meters. 3. Section 3, Paragraph 3..B. Meter. Delete reference to Sensus Omni Meters. 4. Section 6, Paragraph 6.0.J Water Line-Sanitary Sewer/Storm Drainage Relationships. Revise second sentence to read as follows: A minimum of eighteen (8) inches of vertical separation is required. Changes to Standard Details. Revision dated December 00 for Standard Detail TSW-00 4, 6, 8 or 0 Fire Meter Assembly - Revision to manufacturer of meter.. Revision dated December 00 for Standard Detail TSW-00 3, 4, 6 or 8 Compound Meter - Revision to manufacturer of meter. 3. Revision dated December 00 for Standard Detail TSW-004 Packaged Meter Vault with 4 x 48 Hatch for Meter Revision to manufacturer of meter. 4. Revision dated December 00 for Standard Detail TSW-008 Fire Hydrant Setting Detail. Revision to Pumper Outlet Height.

DISTRIBUTION MAIN TAPPING SLEEVE IRRIGATION REFER TO TSW-00 FOR LAYOUT 9 FOR 4"& S 0" FOR 8" S 44" FOR 0" S O.S. & Y 3 4 6 7 8 MIN SCISSOR CLAMP 7" FOR 4", & 0" 60" FOR 8" BOX TAPPING OR REFER TO TSW-00 FOR LAYOUT GROUND LINE DOMESTIC 30" COVER C SCISSOR CLAMP SUMP PIT & SUMP PUMP BOX R 900 RF RADIO READ " PLUG PLAN R 900 RF RADIO READ (LEAVE SLACK IN WIRE SO COVER CAN BE OPENED LADDER BARS BILCO OR HALLIDAY VAULT DOOR 4 x6 OFFSET TO THE LADDER SIDE OF THE VAULT " " 8 VARIES 3 4 6 SEAL ALL OPENINGS O.S. & Y O.S. & Y COMPACT STRAINER NEPTUNE HP FIRE SERVICE TURBINE DETECTOR CHECK LOCATION OF " PLUG & " BALL ON NEPTUNE FORD STYLE FLANGE COUPLING ADAPTOR w/ SET SCREWS B 7 SPOOL BY PLAIN END PIECE 0" T.S.&V. OR TEE A 4" MIN 8 O.S. & Y SUMP PIT & SUMP PUMP SUMP PUMP TO BE PROVIDED WITH AUTOMATIC CUT OFF FLOAT AND 0 VOLT POWER CONNECTION ALL CONCRETE TO BE 4000 PSI / " 0 SCH. 40 PVC SUMP PUMP DISCHARGE. STRAP PIPE TO VAULT WALL W/ 3 STRAPS. PROVIDE UNION AT PUMP DISCHARGE FOR REMOVAL OF PUMP CONC. BLOCK AS REQUIRED FOR PIPE / SUPPORT DIMENSIONS (INCHES) SIZE A B C 4" 33.00 0.7 3. 4.00.44 9.00 8" 3.00.7.00 0" 68.00 9.8 7.0 ELEVATION CONCRETE: 4000 PSI @ 8 DAYS REINFORCING: #4 BAR (GRADE 60) @" o/c EA. WAY @ CENTERLINE OF WALLS WITH CORNER BARS * DISCHARGE FOR SUMP PUMP, TO GO THROUGH TOP OF VAULT AND DISCHARGE AT GRADE. NOTE: ALL FIRE S TO BE FOLLOWED BY A REDUCED PRESSURE BACK PREVENTER PRESSURE REDUCING S ARE ALSO RECOMMENDED ON THE CUSTOMER SIDE OF THE. ADDED SENSUS BRAND AND PRV NOTE DELETED SENSUS BRAND 0/00 /00 4",, 8" OR 0" FIRE ASSEMBLY (SEPARATE DOMESTIC & IRRIGATION REQUIRED) TSW-00

REFER TO TSW-00 FOR LAYOUT DISTRIBUTION MAIN IRRIGATION 9 FOR 3", 4"& S 0" FOR 8" S 44" FOR 0" S O.S. & Y 3 4 6 7 MIN SCISSOR CLAMP 7" FOR 4", & 0" 60" FOR 8" TAPPING OR TAPPING SLEEVE SCISSOR CLAMP SUMP PIT & SUMP PUMP GROUND LINE BOX C 30" COVER R 900 RF RADIO READ R 900 RF RADIO READ (LEAVE SLACK IN WIRE SO COVER CAN BE OPENED) LADDER BARS A PLAN 3 4 BILCO OR HALLIDAY VAULT DOOR 4 x6 OFFSET TO THE LADDER SIDE OF THE VAULT B " " 8 VARIES 3 4 6 7 SEAL ALL OPENINGS O.S. & Y O.S. & Y COMPACT STRAINER NEPTUNE TRU- COMPOUND " TEST PORT ASSEMBLY (BRASS) w/" RISER, " BALL & " PLUG FORD STYLE FLANGE COUPLING ADAPTOR w/ SET SCREWS SPOOL BY PLAIN PIECE. 0" O.S. & Y 4" SUMP PIT & SUMP PUMP SUMP PUMP TO BE PROVIDED WITH AUTOMATIC CUT OFF FLOAT AND 0 VOLT POWER CONNECTION ALL CONCRETE TO BE 4000 PSI DIMENSIONS (INCHES) SIZE A B C ELEVATION / " 0 SCH. 40 PVC SUMP PUMP DISCHARGE. STRAP PIPE TO VAULT WALL W/ 3 STRAPS. PROVIDE UNION AT PUMP DISCHARGE FOR REMOVAL OF PUMP CONC. BLOCK AS REQUIRED FOR PIPE / SUPPORT 3" 7.00 0.0 8.7 4" 0.00.0 0.0 4.00.7.0 8".37.7.0 0" 6.00.0 8. CONCRETE: 4,000 PSI @ 8 DAYS REINFORCING: #4 BAR (GRADE 60) @ " o/c EA. WAY @ CENTERLINE OF WALL WITH CORNER BARS * DISCHARGE FOR SUMP PUMP, TO GO THROUGH THE TOP OF VAULT AND DISCHARGE AT GRADE. NOTE: ALL S TO BE FOLLOWED BY A REDUCED PRESSURE BACK PREVENTER. PRESSURE REDUCING S ARE ALSO RECOMMENDED ON THE CUSTOMER SIDE OF THE. ADDED SENSUS BRAND AND PRV NOTE DELETED SENSUS BRAND 0/00 /00 3", 4",, 8" OR 0" COMPOUND (SEPARATE IRRIGATION REQUIRED) TSW-00

" WITH BOX HINGE SIDE PLAN " 4" 34" " INLET " OUTLET A " T-80 BRASS BALL 64" B FORD CF3-77 LIK-PAK COUPLING AND C " NEPTUNE TRU- COMPOUND " WITH BOX 4"x48" ALUMINUM HATCH R900 RF RADIO READ LEAVE SLACK IN WIRE SO COVER CAN BE OPENED D E F "x" TEE S" T-80 BRASS BALL " BRASS PLUG " BRASS CHECK " T-80 BRASS BALL G " BRASS NIPPLE (ALL ASSEMBLIES TO BE BRASS) A B C D E F 3" SEAL ALL OPENINGS (TYP.) G " " G ELEVATION " DRAIN w/ COVER SCREEN NOTES:. BASE AND WALLS SHALL BE AN INTEGRAL CAST UNIT NO SEPARATE BASE WILL BE PERMITTED.. ALL COMPOUND S ARE TO BE FOLLOWED BY A REDUCED PRESSURE BACK PREVENTER. PRESSURE REDUCING S ARE ALSO RECOMMENDED ON CUSTOMER SIDE OF. ADDED SENSUS BRAND AND PRV NOTE DELETED SENSUS BRAND ADDED NEPTUNE BRAND 0/00 /00 PACKAGED VAULT WITH 4"x48" HATCH FOR " TSW-004

HYDRANT SHALL BE SET ON CONCRETE BOX FOOTING BLOCK. CONCRETE BLOCK OR POURED CONCRETE (CLASS A) SHALL BE WEDGED FIRMLY BEHIND AND EXTENDING AROUND HYDRANT TO UNDISTURBED EARTH. CARE SHALL BE USED TO SET HYDRANT PLUMB. THE FIRE HYDRANT SHALL BE LOCATED NOT LESS THAN INCHES OR MORE THAN 8 INCHES FROM FACE OF CURB TO FRONT OF HYDRANT PROTECTION CASE. A MINIMUM OF CU. FT. OF CRUSHED STONE SHALL BE PLACED AROUND LEAD ADJOINING BLOCKING FOR DRAINAGE FROM WASTE OPENING. 8" 4" MAX. PUMPER OUTLET TO FACE STREET STANDARD CAST IRON BOX FRAME AND COVER UNDISTURBED EARTH 3 STANDARD CONCRETE BOX USE CARE TO INSURE THAT DRAIN PLUG IS NOT PLUGGED PRECAST CONC. BLOCK OR ROCK - "x"x (3/4" C.F. MIN) M.J. TEE OR M.J. ANCHOR TEE * HYDRANT BURY SHALL BE AT LEAST 48" + O.D. IF WATER LINE LOCATED IN ROADWAY AND 3 + O.D. IF LOCATED OUTSIDE ROADWAY. NOTE: ALL M.J. FITTINGS TO INCLUDE MEGA-LUG DEVICES FIRE HYDRANT SHALL NOT SIT CLOSER THAN FROM EDGE OF ANY POWER AND/OR LIGHT POLE. OUTLET HEIGHT /00 FIRE HYDRANT SETTING DETAIL TSW-008