Senergy Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor GPS Plus Rigid Insulation Board

Similar documents
Acrocrete Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor rigid insulation board

Finestone Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor rigid insulation board

Acrocrete Platinum CI Stucco Ultra Typical details for a premium impact and puncture resistant rain screen design cement plaster stucco system

Finestone Stucco System

Finestone Stucco Ultra Wall System

Pebbletex Wall System Class PB Exterior Insulation and Finish System providing a primary moisture barrier. Typical Details

Sentry Stucco Ultra Wall System

Senturion TM I Wall System

Senturion TM III Wall System

Magnum Board Coatings

SC-01 Cross-Section. Cement Board Substrate Master Wall Mesh and Base Coat Superior Finish

3. Aesthetic Groove. 5. Window Head (Flush) 6. Window Head (Recessed) 7. Window Jamb Detail (Flush) 8. Window Jamb Detail (Recessed)

AcroWall-ES System. Class PB Exterior Insulation and Finish System providing a primary moisture barrier. Typical Details

Senershield -R / Senershield -VB

The better way to build TM. Installation Manual NAILBASE PANELS

OCS ONE COAT STUCCO A custom blend of Portland cement, sand, extenders, fiber reinforcement and modifiers.

BULLETIN FROM THE FIRST COAST CHAPTER ICC~BOAF

STRATUM GUARD I AND II An Exterior Insulation and Finish System with Drainage DSC106C. Stratum Guard I and II System Installation Details

WeatherSmart Air Barrier Installation Guide

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING

R E S I D E N T I A L B U I L D E R S R E F E R E N C E G U I D E

Detail Booklet StoTherm ci XPS

Pella 250 Series. Wood Frame Construction with Vinyl Siding... V250-ID-888 Wood Frame Construction with Brick Veneer...

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS DAVIS, CALIFORNIA

DuPont. Tyvek Sheathing Membrane Installation Guidelines. Version 2. Canadian Version

DuPont Tyvek Air Barrier Installation Guidelines. Canadian Version. Version 2

WHATEVER THE CHALLENGE, PHILLIPS HAS YOU COVERED.

2002 Advanced Building Products, Inc., P.O. Box 98, Springvale, Maine TEL: ; FAX: ; WEBSITE:

Application Instructions

Discussion of the Stucco Identification of All Panels

Ultra Wall System. CAD Detail Sets

Light-Metal Roof Edge, Raised

Perimeter Relief and Control Joints in Fire-Rated Gypsum Board

WEB BASED APPLICATION SPECIFIC INSTALLATION INSTRUCTIONS

KARRIER PANEL - BRICK

BUILDING SUCCESSFULLY WITH DRYVIT RESIDENTIAL SYSTEMS.

NCMA TEK TEK 19-5A FLASHING DETAILS FOR CONCRETE MASONRY WALLS

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

LP SmartSide Perfection Shingle

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

DuPont Tyvek Wall Underlay Install Guide

FirstEnergy Program Overview

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: DIRECT-APPLIED FINISH SYSTEMS REPORT HOLDER: BASF CORPORATION WALL SYSTEMS

WARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS

Insulation. First Revison October DC14 Drainage Mat INSTALLATION GUIDE FOR RESIDENTIAL & COMMERCIAL APPLICATIONS

ICC-ES Evaluation Report Reissued April 1, 2010 This report is subject to re-examination in two years.

DuPont Flashing Systems Commercial Installation Guidelines

GLOBAL PROPERTY INSPECTIONS TECHNICAL BULLETIN

1 Exam Prep Architectural Sheet Metal Manual Tabs and Highlights

Stone and Masonry Veneer

ESR-1794* Reissued September 1, 2012 This report is subject to renewal November 1, 2014.

Aqua Coast Engineering

EIFS Rain Control EIFS. Face Sealed Perfect Barrier. Beware of EIFS: They must be done correctly They leak at joints Avoid moist sensitive substrate

Ultrakote Cementitious Finish System

WrapShield SA Brick Tie Penetration

application instructions

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150

SRP-AirOutshield UV Issued:

In addition to performing as an interior vapor retarder, MemBrain the Smart Vapor Retarder may be installed as a continuous, interior

SECTION FLEXIBLE FLASHING SYSTEM FOR MASONRY VENEER

Building Envelope Enclosures That Work, What Owners Want!

General. Moisture. Secondary Water-Resistive Barrier. Storage. Gaps & Sealants. Stud Spacing. Flashing, Windows, Doors & Openings

Accent is cracked with stains Accent is sloped away from the home Flat accent is not sealed to window

SECTION Fiber Reinforced Stucco 1

Galvanized Steel Bead Accessories for Stucco and Plaster Installations ALABAMA METAL INDUSTRIES CORPORATION. Contract Number:

RevealShield SA Penetrations

DuPont RainVent Batten Installation Guidelines

ELEVATION FOR DETAIL REFERENCE ONLY

Exterior Stucco and Siding Installation

Code Compliance Research Report CCRR-0231

2019 IAQA Annual Meeting

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

DuPont Tyvek Water- Resistive and Air Barriers Installation Guidelines

ELEVATION FOR DETAIL REFERENCE ONLY

SECTION PORTLAND CEMENT PLASTER (STUCCO) WITH ACRYLIC FINISH

Primary Concerns and Defects

Commercial Flashing Details

SPECIFICATION GUIDELINE

Architectural Roof and Wall Products Guide Specifications

SPECIALTY STRUCTURE CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION

Inspection Fundamentals: Stucco & EIFS

LOWER MACUNGIE TOWNSHIP COMMUNITY CENTER ADDITIONS AND RENOVATIONS

Insulated Concrete Forms (ICFs)

SINGLE FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS

BUILDING ENVELOPE DESIGN GUIDELINES APPENDIX 3

INSTALLATION MANUAL. ZIP System R12 Sheathing. Contents. 07 ZIP System R12 Sheathing Window Installation 08 ZIP System R12 Sheathing Siding Guidelines

DUPONT TYVEK MECHANICALLY FASTENED AIR AND WATER BARRIER INSTALLATION GUIDELINES FOR BUILDINGS GREATER THAN 4 STORIES AND HIGH PERFORMANCE

DIVISION 9 SECTION 09220

GAF EnergyGuard Polyiso Wall Sheathing

Architectural Wall Products Guide Specifications

Brick Masonry. Best Practices Guide

Ameriplate. Rain Screen Wall System

AquaFlash System Installation Guide DS196

Third Party Inspection Guidelines For Inspectors As Part of the dryvitcare EIFS Repair/Restoration

ELEVATION FOR DETAIL REFERENCE ONLY

Omniplate Barrier Wall System

DIVISION 04 MASONRY CAST STONE. A. Design Considerations. 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone.

GCP APPLIED TECHNOLOGIES PERM-A-BARRIER VPL 50

Nortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1

Section Metal Lath and Accessories

Transcription:

Senergy Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor GPS Plus Rigid Insulation Board

NOTES

Senergy Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor GPS Plus Rigid Insulation Board TABLE OF CONTENTS 1. Typical Fastening Pattern 2. Typical Framed / Sheathed Construction 3. Typical Masonry / Concrete Construction 4. Typical Termination at Foundation - Flush with Casing / Stop Bead 5. Typical Termination at Foundation with Casing / Stop Bead 6. Typical Termination at Foundation with Amico C-I Weep Trac 7. Typical Change in Substrate 8. Typical Trim Junction 9. Typical Surface Control Joint 10. Typical Inside Corner Control Joint - Framed / Sheathed Construction 11. Typical EPS Shape Application 12. Typical Corner Bead 13. Typical Decorative Shape 14. Typical Window Head (Flush) 16. Typical Flanged Window Head 17. Typical Window Jamb (Flush) 18. Typical Window Jamb (Recessed) 19. Typical Flanged Window Jamb 20. Typical Window Sill (Flush) 21. Typical Window Sill (Recessed) 22. Typical Flanged Window Sill 23. Typical Pipe Penetration 24. Typical Dryer Vent 25. Typical Downspout 26. Typical Light Fixture 27. Typical Termination at Metal Coping / Roof Edge Flashing - Option 01 28. Typical Termination at Metal Coping / Roof Edge Flashing - Option 02 29. Typical Flashing / Termination at Roof 30. Typical Kick-Out Flashing 15. Typical Window Head (Recessed) Install BASF materials in accordance with current installation instructions. Water-resistive barriers other than Senershield-R/Senershield-VB, Tyvek StuccoWrap and DrainWrap require grooved Neopor GPS Plus Rigid Insulation Board. Grooves are 25 mm x 6 mm (1 x 1/4 ) deep at 305 mm (12 ) o.c., parrallel to the 610 mm (2 ) dimension. Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products. The details within represent BASF Corporation - Wall Systems (hereinafter referred to as BASF Wall Systems) latest recommendations. They are presented in good faith by BASF Wall Systems. The details are subject to change without notice. BASF Wall Systems accepts no liability for the end use of the details. For conditions not shown, consult BASF Wall Systems for review of specific detail.

Senergy Platinum CI Stucco Details TYPICAL FASTENING PATTERN Sheathing: Fasten per sheathing manufacturer s recommendations or project design requirements. Water-Resistive Barrier: Install per barrier manufacturer s instructions. Rigid Insulation Board: Secure with 2-3 fasteners per board to hold in place until lath attachment. Lath: : use appropriate fasteners spaced not more than 152 mm (6 ) o.c. vertically, 406 mm (16 ) o.c. horizontally; metal or wire lath: use appropriate fasteners spaced not more than 178 mm (7 ) o.c. vertically, 406 mm (16 ) or 610 mm (24 ) o.c. horizontally, per requirements of ASTM C1063. PCIS-01 1215

Continuously Insulated (CI) Cement Plaster Stucco System featuring Neopor GPS Plus Rigid Insulation Board Basic requirements for water resistive barrier and insulation: - One layer No 15 felt ASTM D226 Type I or equivalent and grooved Rigid Insulation Board. - SENERSHIELD-R/SENERSHIELD-VB or one layer Tyvek StuccoWrap and flat NEOPOR GPS PLUS Rigid Insulation Board. - Water-resistive barrier shall comply with applicable building code. Basic requirements for Plaster Base: - 3/8 to ½ thickness: Min. 1 20 ga. wire, min. 2.5 lb/sq.yd. metal lath or acceptable alternative. - equal to or greater than ½ thickness: or min. 1½ 17 ga. wire, min. 2.5 lb/sq.yd. metal lath or acceptable alternative. TYPICAL FRAMED/SHEATHED CONSTRUCTION PCIS- 02 0616 Water-resistive barrier over concrete or masonry substrate is optional Basic requirements for Plaster Base: - 3/8 to ½ thickness: Min. 1 20 ga. wire, min. 2.5 lb/sq.yd. metal lath or acceptable alternative - equal to or greater than ½ thickness: or min. 1½ 17 ga. wire, min. 2.5 lb/sq.yd. metal lath or acceptable alternative TYPICAL MASONRY/CONCRETE CONSTRUCTION MASONRY/CONCRETE* PCIS- 03 0616

Senergy Platinum CI Stucco Details TYPICAL TERMINATION AT FOUNDATION - FLUSH WITH CASING / STOP BEAD Terminate the PLATINUM CI STUCCO system a minimum of 152 mm (6 ) above raw earth and 50 mm (2 ) above paved surface. Ensure water-resistive barrier laps over the casing/stop bead flange. Ensure casing/stop bead includes weep holes to facilitate drainage. FLASHING* CASING / STOP BEAD WITH WEEP HOLES SEALANT* FOUNDATION* PCIS- 04 0616 TYPICAL TERMINATION AT FOUNDATION WITH CASING / STOP BEAD Terminate the PLATINUM CI STUCCO system a minimum of 152 mm (6 ) above raw earth and 50 mm (2 ) above paved surface. Provide minimum 25 mm (1 ) overlap at framing/foundation transition. Ensure water-resistive barrier laps over the casing/stop bead flange. Ensure casing/stop bead includes weep holes to facilitate drainage. CASING / STOP BEAD W/ WEEP HOLES SEALANT* FOUNDATION* PCIS- 05 0616

Continuously Insulated (CI) Cement Plaster Stucco System featuring Neopor GPS Plus Rigid Insulation Board Terminate the PLATINUM CI STUCCO system a minimum of 152 mm (6 ) above raw earth and 50 mm (2 ) above paved surface. Provide minimum 25 mm (1 ) overlap at framing/foundation transition. Ensure water-resistive barrier laps over the Amico C-I Weep Trac flange. TYPICAL TERMINATION AT FOUNDATION WITH AMICO C-I WEEP TRAC TM AMICO C-I WEEP TRAC TM FOUNDATION* PCIS- 06 0616 Ensure water-resistive barrier application is continuous behind the PLATINUM CI STUCCO system at change in substrate. Do not apply finish into joint to receive sealant. TYPICAL CHANGE IN SUBSTRATE CONCRETE/MASONRY* BACKER ROD AND SEALANT* PCIS- 07 0616

Senergy Platinum CI Stucco Details TYPICAL TRIM JUNCTION At trim intersection it is recommended that the vertical trim be continuous. 3 MM (1/8 ) GAP OR AS RECOMMENDED BY TRIM MANUFACTURER ACCEPTABLE SEALANT NYLON ANCHOR OR WIRE TIE TO OR METAL PLASTER BASE MITER TRIM AS SHOWN VERTICAL TRIM TO BE CONTINUOUS ACCEPTABLE SEALANT NYLON ANCHOR OR WIRE TIE TO OR METAL PLASTER BASE 3 MM (1/8 ) GAP OR AS RECOMMENDED BY TRIM MANUFACTURER PCIS- 08 0616 TYPICAL SURFACE CONTROL JOINT Provide control joints every 13m² (144 ft²) and placement as determined by the Design Professional. Maximum recommended uncontrolled length or width is 5.5 m (18 ft) and a maximum uncontrolled length to width ratio of 2 ½ to 1. Lath must be broken at the control joint accessory. NYLON ANCHOR OR WIRE TIE SURFACE CONTROL JOINT PCIS- 09 0616

Continuously Insulated (CI) Cement Plaster Stucco System featuring Neopor GPS Plus Rigid Insulation Board Ensure water-resistive barrier application is continuous behind the PLATINUM CI STUCCO system. TYPICAL INSIDE CORNER CONTROL JOINT- FRAMED / SHEATHED CONSTRUCTION CORNER CONTROL JOINT PCIS- 10 0616 Extend BASF DIAMONDSHIELD or Senergy Reinforcing Mesh and Base Coat from band or shape onto a minimum of 76 mm (3 ). Provide a 6:12 slope on horizontal applications greater than 1. Adhere EPS or Neopor GPS Plus Rigid Insulation band/shape with Senergy base coat to surface. TYPICAL EPS OR RIGID BOARD SHAPE APPLICATION BASF DIAMONDSHIELD SENERGY REINFORCING MESH EMBEDDED IN SENERGY BASE COAT EPS OR INSULATION SHAPE PCIS- 11 0616

Senergy Platinum CI Stucco Details TYPICAL Attach corner bead with wire ties, anchors or fasteners to resist movement during application of. Fill corner bead solid with. NYLON ANCHOR OR WIRE TIE PCIS- 12 0616 TYPICAL DECORATIVE SHAPE WATER-RESISITVE BARRIER SENERGY ADHESIVE / BASE COAT FOR DECORATIVE SHAPE BASF DIAMONDSHIELD SENERGY REINFORCING MESH EMBEDDED IN SENERGY BASE COAT EPS OR Extend BASF DIAMONDSHIELD or Senergy Reinforcing Mesh and Base Coat from band or shape onto a minimum of 76 mm (3 ). Adhere EPS or Neopor GPS Plus Rigid Insulation band/shape with Senergy base coat to surface. PCIS- 13 0616

Continuously Insulated (CI) Cement Plaster Stucco System featuring Neopor GPS Plus Rigid Insulation Board Ensure water-resistive barrier laps over the Amico C-I Weep Trac flange. Provide end-dams at flashing terminations. Seal flashing drip edge to window frame. TYPICAL WINDOW HEAD (FLUSH) WINDOW HEAD FLASHING* BACKER ROD AND SEALANT* AMICO C-I WEEP TRAC TM WINDOW* PCIS- 14 0616 Ensure water-resistive barrier laps over the Amico C-I Weep Trac flange. TYPICAL WINDOW HEAD (RECESSED) AMICO C-I WEEP TRAC TM BACKER ROD AND SEALANT* WINDOW* PCIS- 15 0616

Senergy Platinum CI Stucco Details TYPICAL FLANGED WINDOW HEAD WINDOW HEAD FLASHING* BACKER ROD AND SEALANT* AMICO C-I WEEP TRAC TM WINDOW* As recommended by window manufacturer, apply sealant to back of window flange at head prior to installation of window. Ensure water-resistive barrier laps over the Amico C-I Weep Trac flange. Provide end-dams at flashing terminations. Seal flashing drip edge to window frame. PCIS- 16 0616 TYPICAL WINDOW JAMB (FLUSH) AMICO C-I WEEP TRAC TM BACKER ROD AND SEALANT* WINDOW* Ensure water-resistive barrier is properly applied into rough opening in accordance with water-resistive barrier manufacturer application guidelines. Do not apply finish into joint to receive sealant. Use non-hole punched version of Amico C-I Weep Trac on jambs. PCIS- 17 0616

Continuously Insulated (CI) Cement Plaster Stucco System featuring Neopor GPS Plus Rigid Insulation Board Ensure water-resistive barrier is properly applied into rough opening in accordance with water-resistive barrier manufacturer application guidelines. Use non-hole punched version of Amico C-I Weep Trac on jambs. TYPICAL WINDOW JAMB (RECESSED) BACKER ROD AND SEALANT* AMICO C-I WEEP TRAC TM WINDOW* PCIS- 18 0616 Ensure water-resistive barrier is properly applied into rough opening in accordance with water-resistive barrier manufacturer application guidelines. As recommended by window manufacturer, apply sealant to back of window flange at jamb prior to installation of window. Use non-hole punched version of Amico C-I Weep Trac on jambs. TYPICAL FLANGED WINDOW JAMB AMICO C-I WEEP TRAC TM BACKER ROD AND SEALANT* WINDOW* PCIS- 19 0616

Senergy Platinum CI Stucco Details TYPICAL WINDOW SILL (FLUSH) WINDOW* Ensure water-resistive barrier is properly applied into rough opening in accordance with water-resistive barrier manufacturer application guidelines. Do not apply finish into joint to receive sealant. Use non-hole punched version of Amico C-I Weep Trac on sill. AMICO C-I WEEP TRAC TM BACKER ROD AND SEALANT* PCIS- 20 0616 TYPICAL WINDOW SILL (RECESSED) WINDOW* Ensure water-resistive barrier is properly applied into rough opening in accordance with water-resistive barrier manufacturer application guidelines. Use non-hole punched version of Amico C-I Weep Trac on sill. WINDOW SILL FLASHING* AMICO C-I WEEP TRAC TM SEALANT* PCIS- 21 0616

Continuously Insulated (CI) Cement Plaster Stucco System featuring Neopor GPS Plus Rigid Insulation Board Ensure water-resistive barrier is properly applied into rough opening in accordance with water-resistive barrier manufacturer application guidelines. Do not seal window sill flange unless recommended by window manufacturer. Use non-hole punched version of Amico C-I Weep Trac on sill. TYPICAL FLANGED WINDOW SILL WINDOW* PCIS- 22 0616 Ensure all penetrations through the PLATINUM CI STUCCO system are properly sealed. TYPICAL PIPE PENETRATION SECONDARY SEAL* SEALANT* PIPE* PCIS- 23 0616

Senergy Platinum CI Stucco Details TYPICAL DRYER VENT VENT SLEEVE* DRYER VENT FLANGE SET IN SEALANT* Ensure all fastener penetrations through the PLATINUM CI STUCCO system are properly sealed. SEALANT AT PERIMETER OF SHEATHING PENETRATION* DRYER VENT* FASTENERS THROUGH SLEEVE* FASTENERS SET IN SEALANT* PCIS- 24 0616 TYPICAL DOWNSPOUT Ensure all fastener penetrations through the PLATINUM CI STUCCO system are properly sealed. DOWNSPOUT* FASTENER W/ SLEEVE SET IN SEALANT* DOWNSPOUT STRAP SET IN SEALANT* PCIS- 25 0616

Continuously Insulated (CI) Cement Plaster Stucco System featuring Neopor GPS Plus Rigid Insulation Board Ensure all fastener penetrations through the PLATINUM CI STUCCO system are properly sealed. TYPICAL LIGHT FIXTURE LIGHT FIXTURE FLANGE SET IN SEALANT* MOUNTING BOX WITH BLOCKING, AS NEEDED* LIGHT FIXTURE* PCIS- 26 0616 It is recommended to lap coping or roof edge flashing over the PLATINUM CI STUCCO system a minimum of 50 mm (2 ) with drip edge sealed. TYPICAL TERMINATION AT METAL COPING / ROOF EDGE FLASHING - OPTION 01 METAL COPING / ROOF EDGE FLASHING* ROOFING MEMBRANE* BLOCKING* CLEAT* CASING / STOP BEAD* SEALANT* PCIS- 27 0616

Senergy Platinum CI Stucco Details TYPICAL TERMINATION AT METAL COPING / ROOF EDGE FLASHING - OPTION 02 METAL COPING / ROOF EDGE FLASHING* ROOFING MEMBRANE* BLOCKING* CLEAT* FRAMING * SEALANT* AMICO C-I WEEP TRAC TM It is recommended to lap coping or roof edge flashing over the PLATINUM CI STUCCO system a minimum of 50 mm (2 ) with drip edge sealed. PCIS- 28 0616 TYPICAL FLASHING / TERMINATION AT ROOF AMICO C-I WEEP TRAC TM AND CORNER BEAD OR CASING / STOP BEAD WITH WEEP HOLES FLASHING* ROOF SYSTEM* Ensure water-resistive barrier laps over the Amico C-I Weep Trac flange. Terminate PLATINUM CI STUCCO system a minimum of 50 mm (2 ) above sloped roof. PCIS- 29 0616

Continuously Insulated (CI) Cement Plaster Stucco System featuring Neopor GPS Plus Rigid Insulation Board Ensure water-resistive barrier laps over the Amico C-I Weep Trac flange. Terminate PLATINUM CI STUCCO system a minimum of 50 mm (2 ) above sloped roof. Extend step flashing 50 mm (2 ) behind PLATINUM CI STUCCO system. Kickout flashing: sealed or soldered seams, recommended minimum 100 mm (4 ) in height, extend 50 mm (2 ) from wall and angled to direct water into gutter/away from wall surface. TYPICAL KICK-OUT FLASHING AMICO C-I WEEP TRAC TM AND CORNER BEAD OR CASING / STOP BEAD WITH WEEP HOLES STEP FLASHING* SHINGLES* SEALANT* KICK-OUT FLASHING* GUTTER* PCIS- 30 0616

Senergy Platinum CI Stucco Details For the most current version of this literature, please visit our website at www.senergy.basf.com. BASF Corporation - Wall Systems 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255 F: 904.996.6300 www.senergy.basf.com 2016 BASF Corporation rev 160218