Daker DK kva. Parallel installation quick start. Part. LE08927AA-09/15-01 GF

Similar documents
Galaxy 300. Operation 05/

Table of contents. 1. Introduction

Galaxy 300 and Galaxy 300i

OWNER'S OPERATING MANUAL

The power behind competitiveness. Delta UPS - Modulon Family. DPH Series, Three Phase kva. User Manual.

Installation instruction Maintenance Bypass option

Imperial Series. Model IMP-425/525/625/825/1000AP IMD-425/525/625/825/1000AP IMP-1025/1200/1500/2000AP IMD-1025/1200/1500/2000AP

XBDM-HW63. 63A Model. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.

MODELS MB1K-1, MB1K-2 MB2K-1, MB2K-2 MB3K-1, MB3K-2

The power behind competitiveness. Delta UPS - Modulon Family. DPH Series, Three Phase kw. User Manual.

CONTINUOUS POWER-TIE CONFIGURATION

The power behind competitiveness. Delta UPS - Amplon Family. RT Series, Single Phase 5/ 6/ 10 kva. User Manual.

Delta UPS - Ultron Family. HPH Series, Three Phase 60/80/100/120 kva. User Manual. The power behind competitiveness EPO

APC Step-Down Transformer. Models: AP9626, AP9627, and AP9628

DPS. Save This Manual

User Manual. Network Pro Series Tower and Rack-Mount Convertible UPS. Table of Contents 1000/1500/2200/3000

Delta UPS - Ultron Family. HPH Series, Three Phase 60/80/100/120 kva. User Manual. The power behind competitiveness EPO

Installation and Operation Manual

EPS 7000 and EPS 8000

MAN488 Issue 3 WBS/FBS MAINTENANCE BYPASSES AUTOMATIC VERSION

Proposals and Process 2017 National Electrical Code

EC Type-Approval Certificate

Pre-installation Manual CONCEPT 301 D/401 D/501 D

The power behind competitiveness. Delta PQC Series Fixed Type Static VAR Generator. User Manual.

PD662 LOOP-POWERED METER Instruction Manual

PD6770 VANTAGEVIEW LOOP-POWERED PROCESS METER

PD662 LOOP-POWERED METER

kva single and parallel UPS Systems User s and Installation Manual

Installation. Smart-UPS VT in Parallel kva 380/400/415 V 208/220 V 200/208 V

Solar controller for thermalsophin system SR609C operation manual Contents

Installation & Calibration

WP200e Wallbox to CD Changer Adapter

Pre-Installation Guide

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Cabinet. User Manual.

APC by Schneider Electric MGE GALAXY 5500 Uninterruptible Power Supply Guide Specifications 20 kva to 120 kva Parallel UPS, three-phase

MGE TM Galaxy TM 6000: Specification guide

Maintenance Bypass Breaker Cabinet Series Configuration 2. Installation and Operation Manual

Wallbox Adapter. For Rowe CD51 and CD100 jukeboxes

Maintenance Bypass Breaker Cabinet Series Configuration 5. Installation and Operation Manual

MGE Galaxy /50/60/80/100/130 kva. The recommended power protection for all critical applications

SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard

kva single and parallel UPS Systems User s and Installation Manual

! CAUTION: Read and follow these instructions.

Liebert NXL Power-Tie Controls

Statement of Work. Single Phase Power Up Service Single Phase Power-UP. Implementation Services. Table of Contents. 1.0 Executive Summary

EN REAL TIME RECEIVER AND RW INSTALLATION AND USE

15 15A 20 20A 30 30A 40 40A 60 60A VAC VAC VDC 24VAC VAC. 1 Single-phase. SRH VAC Zero cross turn-on

64C Amplification Block. Instruction Manual

Wallbox Translator. Connect any vintage wallbox to your jukebox...

H-100 Fuel Cell Stack User Manual

H-300 Fuel Cell Stack User Manual

AUTOMATIC CAPACITOR BANK FOR LOW VOLTAGE NETWORKS INSTRUCTION MANUAL. MIBATBT_05i

INSULATION GUARD MEG (Code ) INSTRUCTION MANUAL ( M / 99A ) (c) CIRCUTOR S.A.

POWER FACTOR REGULATOR. Computer-12e-xx INSTRUCTION MANUAL ( M / 02A ) (c) CIRCUTOR S.A.

APC by Schneider Electric MGE GALAXY 9000 Uninterruptible Power Supply Guide Specifications 800/900 kva to 4800/5400 kva Parallel UPS, three-phase

MGE Galaxy /30/40/60/80/100/120 kva. The recommended power protection for all critical applications

MPM 100 Monitor Product Description Guide

UPS Electrical Design and. Installation. critica POWER SUPPLIES

HotSwap MBP Maintenance Bypass

PDM16 & PDM32 User Manual

FAST POWER FACTOR REGULATOR. Computer-14df - xx - 144a INSTRUCTION MANUAL ( M / 00A ) (c) CIRCUTOR S.A.

INSULATION MONITORING RELAIS

Equipment Specifications Low Voltage. Active Harmonic Filter

PALLET SCALE CPS SERIES OWNER'S MANUAL

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 10/02/2017 TSEWG TP-19: STATIC UNINTERRUPTIBLE POWER SUPPLY (UPS)

Solar Eye User Manual

CRON HDI-920 Site Planning. Customer Responsibilities

XSTi Standby UPS. 400VA, 600VA, 800VA Models. User & Installation Manual

USER S MANUAL release 2.0

ENGLISH USER S MANUAL. compact omnidirectional bar code scanner

PD662 Loop-Powered Meter Instruction Manual

Critical POWER Supplies Projects Support

Power Supply Featuring OMRON s Unique, New Undervoltage Alarm Function with Compact Body Contributing to Machine Downsizing

ENel Sp. z o. o. - WROCŁAW DESIGN AND MANUFACTURE OF POWER ELECTRONIC DEVICES INVERTER WELDING MACHINE ENEL250A USER MANUAL DEALER:

Carbon Dioxide Controller

Installation & Calibration Manual

WS 10 Weighing indicator USER MANUAL

Power Supply Featuring OMRON s Unique, New Undervoltage Alarm Function with Compact Body Contributing to Machine Downsizing

Ceiling Camera Lift 2015

PLEASE READ THIS MANUAL CAREFULLY BEFORE OPERATION

XPI SERIES GRID SOLAR POWER SYSTEM

Powerware 9390 Integrated Accessory Cabinet IAC-D Configuration Installation and Operation Manual. For use with kva and kva UPS Models

Operations Manual. For Research Use Only. PH: EM: WEB:

General Safety Information

Model HH Signal-Conditioner / Indicator

Powerware 9120 UPS. Date: Issued By: Product Affected May 27, 2003 Gary Bankay PowerFlex 7000 MV Drive

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

electroplating DC power supply type SIFCO PROCESS POWER PACK 1028

Operating Manual. Wärtsilä JOVYTEC L 6kVA 10kVA. BAX 3297_en

Thank you for purchasing the SC-CONVERSION System 500/600 Conversion Kit. This Kit is available in two different versions:

SUPPLY NETWORK ANALYZER CVM-SP SERIES INSTRUCTION MANUAL ( M / 01A

LIEBERT Nfinity UPS. GUIDE SPECIFICATIONS for a 4 to 16 KVA (208/120V or 240/120V) Single - Phase Uninterruptible Power Supply System 1.

AM SYSTEM(AS002) Manual

DIGITAL PORTION SCALE PS-5 OWNER S Manual

Owner's manual SAX SAZ-1500D

EGT-AF08 USER GUIDE WHEEL WEIGHING SYSTEMS WITH VARIOUS PLATFORMS

SIO Series RS485 Modbus RTU Remote IO Modules User Manual

IP/V24 WALLBOARD 2 x 16 digits TECHNICAL MANUAL AUTHOR DATE REFERENCE. V. Bafour 23/01/2008 D

APC by Schneider Electric APC SYMMETRA MW 400 kw to 1600 kw Multi-Module Uninterruptible Power Supply

HOBO Plug Load Logger (UX ) Manual

Transcription:

Daker DK 4.5-10 kva Parallel installation quick start Part. LE08927AA-09/15-01 GF

Daker DK 4.5-10 kva UK ENGLISH 3 2

Daker DK 4.5-10 kva Index Introduction 2 1 Important Safety Instructions 2 2 Parallel system installation 3 3 Single Unit Check 5 4 Parallel Setting 7 4 Parallel Mode Start up 8 5 Trouble Shooting 9 3

Introduction This document is a reference guide to install the Daker DK UPS 4,5-10kVA in parallel for N+1 redundancy operation. The parallel installation and configuration procedure is divided in 4 phases : Parallel system installation To physically connect each unit. Single Unit check To verify and confirm that each unit works properly with the correct parameters and output voltage Parallel Setting To setup each units parameters to work in parallel mode. Parallel Mode Start up To verify that the parallel system works normally. 1 Important Safety Instructions Only qualified and trained electricians are allowed to install the UPSs in single unit or parallel systems. Please read the Installation guide carefully before installing these UPSs to avoid electrical hazards or damages to the UPS and the loads connected. To prevent potential leakage current hazard, ensure that the AC main supply is securely grounded. Please note that the Parallel function of the UPS can be enabled only in Normal Mode operation. Before to set a parallel installation, ensure that the output voltage tolerance for each UPS at zero-load condition is less than 0.5Vac.Please consult your authorized dealer if any of the UPS output voltage has the tolerance over 0.5Vac. Ensure that the communication cables plugged into the UPS RJ45 connectors are connected securely to avoid damage to both the UPS and the output devices. Ensure that two and only two UPS units of the parallel system have the terminal resistors on the rear set in On position. Only UPS with the same rating and type can be installed in parallel. Please ensure to add a 40Arms/250Vac and 30Arms/250Vac NFB(Non-fuse Breaker)at the input and output of each UPS respectively. 4

Daker DK 4.5-10 kva 2 Parallel system installation Accessories The following accessories (included in the parallel kit) are requested to install the UPS in parallel mode. C1 C2 F1 ACCESSORIES DESCRIPTION Standard cat5 cable with Rj45 connector (max length: 1050mm) Standard cat5 cable with Rj45 connector (max length: 1900) Bracket to secure C1 and C2 to the UPS box QUANTITIES 2 UPS 3 UPS 4 UPS x 1 x 2 x 3 x 1 x 2 x 3 x 4 The design of the air flow for the convertible UPS is to flow in from the front ventilation holes to the rear ventilation holes. It is recommended to leave at least 30 cm around the UPS and Battery bank to allow good ventilation conditions. Please refer to the UPS manual for the detailed installation guide. To reduce noise interference do not cross or mix input, output, and battery cables. Please install the communication wires for parallel and control signal functions (including cat5, serial, usb and EPO cables) keeping them away from input/output and battery cables. To prevent potential leakage current hazard, ensure that the AC main supply is securely grounded. Please refer to the single UPS input/output current specifications and recommended conductors listed below: AC input and output Battery Input MODEL MAXIMUM CURRENT CONDUCTOR SECTION 4,5-6KVA 33A AWG #9 10KVA 54,3A AWG #7 MODEL MAXIMUM CURRENT CONDUCTOR SECTION 4,5-6KVA 25A AWG #10 10KVA 41A AWG #10 5

Recommended Circuit Breakers to be installed at the UPS input/output MODEL INPUT (CBi) OUTPUT (CBo) 4,5-6KVA 40A 30A 10KVA 63A 63A The breaker type should be C or D with the following current ratings: Install and connect the UPS units according to the diagrams in figure 2, 3, 4, 5. CAUTION The MTBS is an optional for maintenance. 2 Parallel system installation Figure 1 CBi : installation input breakers CBo : installation output breakers CB1 : UPS utility input breaker Utility input UPS output 6

Daker DK 4.5-10 kva Connect the parallel CAT5E cables as a Ring Network (Figure 3) using the parallel kit plate to fix them to the UPS rear panel (Figure 4) 2 units parallel 3 units parallel 4 units parallel Figure 2 Figure 3 CAUTION The maximum length of the communication connecting wires shall be less than 7M. All the Input/ output power cable should have the same length (max 25m) Figure 4 1050mm RJ-45 communication connecting wire 1900mm RJ-45 communication connecting wire Max. 25M; all Input Power cables shall be with the same lenght 1900mm RJ-45 communication connecting wire 7

3 Single Unit Check Parameters Check CAUTION The following operations have to be done on each UPS separately and independently. Ensure that all the circuit breakers at the input (Cbi) and output (Cbo) are set to off position. Ensure that all the utility input breakers (CB1) for each UPS is set to off position Turn on the AC input of the UPS to be checked : Turn on only the input breaker CBi connected to the UPS to be checked, and the utility breakers CB1 on the rear panel of the UPS itself. DO NOT TURN ON THE INVERTER! Figure 5 Enter in setting mode by pressing <On> & < > keys simultaneously for 3 seconds (Figure 6). Verify that all the UPS s parameters match with the default values (Table 1) 8

Daker DK 4.5-10 kva Item Press < > to change Display List Default Press < > to change Buzzer on/off Self-Test Bypass Voltage Range (Available in Line-Mode Only) Inverter Synchronize Frequency range Inverter Output Voltage * Operation Mode Output Voltage Adjustment Parallel ID Number ** Parallel Function On/Off *** SAVE Press < > to Save After Saved UPS Locked Shut off AC input power to reset the UPS Table 1 ** Single unit ID number must be 01, or UPS will have an Er17 error occurred. *** Single unit Parallel function must be OFF (P 01), or UPS will have an Er21 error occurred. 9

3 Single Unit Check CAUTION Bypass Voltage Range, Inverter Synchronize Frequency Range, Inverter Output Voltage and Output Voltage Adjustment are adjustable parameters but for parallel function every unit must have the same settings Change item by pressing < > until the display shows the text Save. Press < Enter > to save the setting. Turn off the UPS utility input breaker (CB1) while the LCD shows LINE OFF to reset the UPS. Basic Function Check Turn on the AC input (UPS utility input breaker) and then turn on the UPS inverter (press <ON>) Test the UPS switching from normal mode to stored energy mode and viceversa Verify that the LCD panel works normally and doesn t display errors. Output Error Voltages Check Verify the output voltage for each UPS unit (at 0 load), and make sure the voltage difference between each unit is under 0.5Vac. If the voltage difference is between 0.5~1.0Vac, the parallel error current will be higher. If the voltage difference is over 1.0Vac, a calibration should be performed on the unit(s) which has over-limit error voltage otherwise the parallel could fail (If this condition occurs please contact your local dealer for technical support) Turn off the inverter (press <off>) and then the AC input (Turn off CBi and the UPS utility input breaker) and restart the process for the next unit. 10

Daker DK 4.5-10 kva 4 Parallel Setting Terminal resistor setting Each UPS unit is equipped with a terminal resistor S1 placed on the rear panel (Figure 7) besides the RJ45 connectors. Set the terminal resistor according to the configuration shown in the Table 2 PARALLEL UNITS Table 2 TERMINAL RESISTOR STATUSOUTPUT (CBo) UPS1 UPS2 UPS3 UPS4 2 UNITS ON ON -- -- 3 UNITS ON OFF ON -- 4 UNITS ON OFF OFF ON CAUTION Only 2 UPS units must have the terminal resistor in ON position. A wrong Terminal Resistor setting will cause unpredictable failure or UPS burned out. Eventual error can t be detected automatically by the UPS. Parallel Function Enable and ID Numbers setting Ensure that all the circuit breakers at the input and output are set to off position. Turn on the AC input of the UPS to be configured Turn on only the input breakers CBi connected to the UPS to be checked, and the utility breakers CB1 on the rear panel of the UPS itself. DO NOT TURN ON THE INVERTER! Enter the UPS in Setup Mode (See single unit check) Set the UPS ID. Each UPS must have a different ID number. CAUTION One of the UPS must have the Id01. This UPS will be the default master unit of the parallel system. 11

4 Parallel Setting Set the Parallel function to Enable (P 02) UPS# UPS#1 UPS#2 UPS#3 UPS#4 ID NUMBER PARALLEL FUNCTION Table 3 Turn off the inverter and then the AC input (Turn off CBi and CB1 of the UPS) and restart the process for the next unit. Er21 Check (Communication Failure or Can not find ID1 unit) Ensure that the AC input and the inverter is off for all the UPS connected. Turn on the AC input only for UPS#2, UPS#3, UPS#4 The UPS#2, UPS#3, UPS#4 LCD will show Er21. Turn on UPS#1 AC input. The UPS#2, UPS#3, UPS#4 stop showing Er21 4 Parallel Mode Start up UPS# UPS#1 UPS#2 UPS#3 UPS#4 TEST AC OFF TEST OK Table 4 If the error Er21 still appear on the display of one UPS please verify and eventually repeat the setting and wiring process described above to solve eventual communication problem. CAUTION do not start the UPSs inverters before the Er21 test is passed to avoid unpredictable failures or damages. 12

Daker DK 4.5-10 kva 4 Parallel Mode Start up Start up procedure Ensure that the input and output circuit breakers are set to off position for all the UPS. Turn on the input breaker (CBi and CB1) of all the UPS connected ( all the units are now in bypass mode) Turn on the inverter of the first unit (ID01). The other units will turn off the bypass line. When the bypass line of the other UPSs is off, turn on them progressively. Turn on all the output breakers connected to the UPSs (CBo and CBoutput) Redundancy Function Check If the parallel system is working properly ( N+1 redundancy operation) the N+1 redundancy LED is on. CAUTION If the N+1 led is off the loads exceed the redundancy level. The load has to be reduced until the N+1 redundancy LED turn ON. To verify that the redundancy function indicator works properly repeat the start up procedure turning on only part of the UPS connected in parallel, and apply a load above the values shown in the below table, the N+1 LED will turn off. PARALLEL UNITS REDUNDANCY LEVEL ( LOAD %) 2 UNITS 50% 3 UNITS 66% 4 UNITS 75% If the redundancy check is positive repeat again the start up procedure turning on all the UPS connected The Installation procedure is finished! 13

5 Trouble Shooting ERROR DESCRIPTION CAUSE POSSIBLE SOLUTION Er16 Output Parameters Setting Error If an Er16 appear during the parallel installation test, then there are one or more parameters setting conflict between the UPS units. Possible solution: repeat the process described in the paragraph parameters check 2and make sure that the common setting are the same for each units Process test 1.1 and check each parameters are the same setting between each unit. Er17 ID Numbers in conflict in or ID number Error in single unit 1. Two or more units have the same ID number. (Parallel system) 2. Parallel function is not enabled, but ID number is not 01. (Single unit) 1. Change ID number setting. 2. Change ID number as 01. Er27 The UPS Must Be Operated in Normal-Mode in Parallel System The UPS is not working in Normal Mode. ECO Mode and Frequency-Converter Mode are not supported for parallel system. Change UPS setting as Normal mode. Er08 DC BUS High Level Abnormal 1. If the output voltage difference between each unit is higher than 1.0Vac, an Er08 could Appear on the display panel during the parallel system start up. 2. Improper installation or parallel system communication failure. 1. Check the inverter output voltage independently for each unit and apply the calibration procedures to the units with abnormal output voltage. 2. Check the parallel setting and repeat the Er-21 checks described in the Test start up paragraph. Er34 Balance Function Conflict New UPS version unit(s) paralleled with older version unit(s). Use UPS Setting Tool software to enable special function flag #8 to make the new version compatible with the old one 14

World Headquarters and International Department 87045 LIMOGES CEDEX FRANCE : 33 5 55 06 87 87 Fax : 33 5 55 06 74 55 www.legrandelectric.com Legrand se réserve le droit de modifier à tout moment le contenu de cet imprimé et de communiquer, sous n importe quelle forme et modalité, les changements apportés.