Thermal Energy Storage in Office Buildings Foundations

Similar documents
Dipl.-Ing. Herdis Kipry. IGS Institute of Building Services and Energydesign, Technical University of Braunschweig, Germany

SUCCESSFUL RETROFIT OF NON- RESIDENTIAL BUILDINGS: HEATING AND COOLING CONCEPTS

Effects of the use of DIN on the energetic assessment of residential buildings reflection on the calculation

NORTH AMERICAN MONITORING OF A HOTEL WITH ROOM SIZE GSHPS

F. Kabus, G. Möllmann, F. Hoffmann and J. Bartels

Geothermal Energy for the Renewable Energy House

German American Chamber of Commerce PRESENTATION ON NOVEMBER 6th, 2008 Axel Popp

Modeling and analyzing solar cooling systems in Polysun

Energy Audit. Project: ENergy Efficiency and Renewables SUPporting Policies in Local level for EnergY (ENER-SUPPLY) Work Package 4

ENERGY SAVINGS, SIMULATIONS AND ECONOMIC ANALYSIS OF A GROUND SOURCE HEAT PUMP WITH VERTICAL BOREHOLE HEAT EXCHANGERS FOR A BELGIAN OFFICE BUILDING

Urban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK

Simulation and data based identification of parameters affecting seasonal ATES efficiency

Energy and Comfort Performance Analysis of Monitored Thermally Activated Building Systems Combined with Geothermal Heat Pumps

Monitoring and Optimization of Building Operations of a Low-Energy School Building

EXPERIENCES WITH LOWEX PCM CHILLED CEILINGS IN DEMONSTRATION BUILDINGS

Advanced Building Systems Dirk Müller, Azadeh Badakhshani, Alexander Hoh

Work Package 2: Performance of naturally ventilated buildings

Energy Audit. Project: ENergy Efficiency and Renewables SUPporting Policies in Local level for EnergY (ENER-SUPPLY) Work Package 4

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA

Simulation based façade control implemented as a responsive building element

Results and lessons learned from geothermal monitoring of eight non-residential buildings with heat and cold production in Germany

NUMERICAL STUDY ON THERMAL DEPLETION OF THE GROUND AROUND A GEOTHERMAL HEAT PUMP S PROBE

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE

Research on integrated solar and geothermal energy engineering design in hot summer and cold winter area

Zero Energy Building Example in Estonia. Tõnu Mauring

Economic Estimation of Heat Storage Type Geothermal Source Heat Pump System Applied in K-Ward Office Building

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

Figure 1: Uncovered and covered PVT collectors

Building Commissioning for Energy Efficiency and Comfort, Vol.VI-8-4

*Corresponding authors. Tel.: x415, address: (N. Zhu)

Solar Energy Technologies

Indo-Swiss Building Energy Efficiency Project. Case Study: Aranya Bhawan, Jaipur

Ground Coupled Heat Pump Systems a Key for a Sustainable Development of Heating and Cooling Buildings

Comparative Study On Simulation Tools Of Annual Heat Load For Energy Management Y. Takahashi 1 *, G. Yoon 1, M. Yoshinaga 2, and R. Chiba 3 1 Graduate

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

Energy Audit. Project: ENergy Efficiency and Renewables SUPporting Policies in Local level for EnergY (ENER-SUPPLY) Work Package 4

Future European Heat. Renewable heating comparisons

Efficient utilization of energy sources

Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa

Strategies for energy efficiency improvement in residential and office buildings: their role at building and country scale

Ground-Coupled Heat Pump And Energy Storage

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

F. Kabus, G. Möllmann, F. Hoffmann and J. Bartels GTN Geothermie Neubrandenburg GmbH, Seestrasse 7A, Neubrandenburg, Germany

ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID DYNAMICS

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

District heating topics

SOPHARMA AND LITEX TOWERS Hi-tech intelligent building where light, architecture and sustainability meet business

Make the best of the sun meeting thermal and electrical energy demands

Future tree planting on the two acre lot will offset remaining lifetime carbon emissions.

Dipl.-Ing. Edmond D. Krecké, Luxembourg. 1. Starting position

Innovative Solar thermal systems for heating and cooling

D DAVID PUBLISHING. Efficiency of Combined Solar Thermal Heat Pump Systems. 1. Introduction. 2. Solar Thermal and Heat Pump Systems

Bioclimatic Design Approach Integration into Architectural Design: a Library Case Study

The BTES project in Crailsheim (Germany) Monitoring results

City of Altheim Geothermal Energy Supply

Next Generation District Heating

Energy-efficient buildings in Germany - learnings and outlook Oliver Rosebrock, Sep 18, Dublin

Energy Efficient Heat Pump System Applied Short Term and Seasonal Thermal Energy Storage Part 1 Design concept of the system

Verified net Zero Energy Building with air source heat pumps for SME

Yokohama, Japan b School of Environmental Sciences, University of East Anglia,

Building Retro-Commissioning

New developed solar thermal systems for heating and cooling Budapest, 16 th April 2009 Tsekouras Panagiotis Mech. Engineer NTUA Centre for Renewable

SolarCity Partnership. Toronto Fire Station # kwt Solar Water Heating Installation. Technology. Monitoring. Best Practices

Commissioning ground coupled heat pump office building Bayer Diegem. VCB Hernieuwbare energie voor gebouwen,

Climate neutral buildings and districts first projects in Germany

Operating Engineers Seminar Bob Ford Jeff Volovsek

dr.ir. Wout Parys prof.dr.ir.-arch. Dirk Saelens

Retro-commissioning and on-going commissioning 23 November 2016

THERMAL CHARACTERISTICS AND ENERGY CONSERVATION MEASURES IN AN INDOOR SPEED-SKATING ARENA

LOW-ENERGY HOUSING ESTATE SUNDAYS

Introduction to Geothermal Comfort Systems in INDIA

STUDY ON THE DESIGN PROCEDURE OF GEOTHERMAL HEAT PUMPS: GEOTHERMAL HEAT PUMP SYSTEM WITH

Active solar heating system with concrete plate heating analysed with dynamical thermal simulations

Parametric Louver Design System Based On Direct Solar Radiation Control Performance

An Adaptable Façade Concept for Sustainable Office Refurbishment

The optimization of the mechanical night cooling system in the office building

Energiewende in Germany

RETRO-COMMISSIONING OF A HEAT SOURCE SYSTEM IN A DISTRICT HEATING AND COOLING SYSTEM Eikichi Ono 1*, Harunori Yoshida 2, Fulin Wang 3 KEYWORDS

Australian Solar Cooling Interest Group (ausscig) Conference Financial analysis of solar cooling systems in Australia

Available online at ScienceDirect. Energy Procedia 78 (2015 )

The energy benefits of View Dynamic Glass

ENERGY EVALUATION BY SIMULATION FOR EFFECTIVE USE OF SEWAGE HEAT

Allstream Centre Energy Performance Report

Holistic Design Approach For Energy Efficiency ASHRAE TECHNOLOGY AWARD CASE STUDIES

ScienceDirect. Simulation based mixed mode building design

Optimal integration of a Geothermal Energy Control Center into a bivalent heating and cooling supply system H2 Office, Duisburg

ARPAN JOHARI. Architect. 13/08/10 AW Design. Ahmedabad

POTENTIAL OF APPLICATION OF PV SYSTEM FOR BWRO DESALINATION IN GAZA

Sustainable Building Façade and Advanced Fenestration Systems

Available online at ScienceDirect. Energy Procedia 91 (2016 )

Introduction to Geothermal Comfort Systems in INDIA

RAMBOLL THERMAL TECHNOLOGY WITH DISTRICT ENERGY SYSTEMS

Renewables. Vacuum Tube Solar Systems. Solar Energy to the Power of

Design guidelines for direct ground cooling systems in different climates

AUTARKIC COOLING VIA BUILDING SKINS - RESULTS FROM COOLSKIN-PROJECT COOSLKIN This project is funded by the Austrian Klima- und Energiefonds

POTENTIAL FOR THE ENERGY EFFICIENCY ADVANCEMENT IN DISTRICT HEATING AND COOLING PLANT BY RENOVATION

Heat Pump Field Trials and Implications for Design

VELUX A/S, Daylight Energy and Indoor Climate, Ådalsvej 99, 2970 Hørsholm, Denmark *Corresponding author:

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate

Transcription:

Thermal Energy Storage in Office Buildings Foundations H. Schnürer, C. Sasse, M. N. Fisch Technical University of Braunschweig Institute for Building Services and Energy Design D-38106 Braunschweig, Germany Tel: 0049-531-391-3555 sasse@igs.bau.tu-bs.de 1. BACKGROUND The R&D-project Thermal Energy Storage in Office Buildings Foundations analyses foundation absorbers, energy piles and borehole heat exchangers (max. depth 150 m) for seasonal heat and cold supply of office buildings. The R&D-project has a duration of three years and ends in June 2007. It is supported by the Federal Ministry of Economics and Technology (BMWi) and coordinated by the Project Management Organisation Jülich (PTJ). Since the late nineties office buildings in Germany are being constructed using the surrounding ground of their foundations for heat exchange and seasonal thermal energy storage. Via a heat pump those seasonal UTES-systems extract heat from the surrounding ground during the cold period. The backflow of the heat pump cools down the foundation and surrounding ground. The volume cooled down beneath the building can be used afterwards as a heat sink during summer time. The planning of those UTES-systems implies a closer look on the surrounding geological conditions, physics, heat and cold demand of the building. During planning process complex planning software like TRNSYS or FEM software is often applied. Simple planning tools are not available. To develop those easy to use tools a systematic evaluation of those systems is being elaborated by our R&D-project. The evaluation includes nine low energy office buildings and one library constructed between 2002 and 2004. Those office buildings have a gross floor area varying from 3 500 m² to 73 500m². All buildings are using the UTES in connection with low temperature heating systems (22 to 27 C with ground coupled heat pump) and high temperature cooling systems in a direct cooling mode (17 C to 22 C). These ranges are ideal for an efficient ground coupled energy supply. Most of those buildings are equipped with concrete core activation (CCA). Here the concrete core of the ceiling is fitted out with closed circuits of water filled hoses. Depending on temperature gradient, water flow as well as position and distance of the tubes in the activated ceiling, the cooling or heating power achieves a value between 25 and 40 W/m²). The specific heating energy demand of the evaluated buildings differs from 55 kwh/(m² a) to 200 kwh/(m² a). The UTESs cover only a certain part of their heating/cooling demand. Only a few buildings additionally use the UTES for air conditioning. The buildings show a great difference of planning and design effort put into the evaluated UTES. Our monitoring also reveals that fitting out and constructing those systems is not a today problem. The performance of those UTESs depend in a great mater on a sophisticated controlling ability of the facility management in charge. An overview of the participating buildings and their implemented systems is given in table #1. Table # 1: Building data of some of the examined buildings VW University Library of the Technical University of Berlin Usage / Floor area Library building / 34.000 m² (completion 2004) 8.000 m² horizontal foundation heat exchanger supplying a concrete core activation system for cooling and heating Heating capacity 80 kw by HP (basic heat load supply) Cooling capacity 100 kw free cooling (basic cooling load supply)

NORD-LB, Hanover Usage / Floor area Office Building / 1.400 workplaces / 73.334 m² 122 energy-piles supplying a concrete core activation system for cooling and heating Heating capacity 155 kw by HP(basic heat load supply) Cooling capacity 128 kw free cooling (peak cooling load supply) VGH Inc., Lüneburg Usage / Floor area Office building / 3.500 m² (completion 2002) 98 energy piles for cooling and heating of a concrete core activation system and ventilation Heating capacity 90 kw by HP Cooling capacity 60 kw free cooling (basic cooling load supply) Rickmers, Hamburg Usage / Floor area 260 workplaces / 9920 m² (completion 2002) 17 BHE (depth: 100 m) for cooling and heating of concrete core act. and ventilation Heating capacity 90 kw by HP (basic heat load supply) Cooling capacity 60 kw free cooling (for basic cooling load supply) EnergyForum Berlin, Berlin Usage / Floor area Office Building / 21.200 m² (completion 2003) 198 energy piles 8.50 m deep for a concrete core activation system for cooling and heating Heating capacity 107 kw by HP (partial basic heat load supply) Cooling capacity 60 kw free cooling (partial basic cooling load supply) Gelsenwasser Inc., Gelsenkirchen Usage / Floor area Office building / 20.000 m² (completion 2003) 48 BHE (depth: 150 m) for supplying cooling/heating panels and ventilation Heating capacity 320 kw by 2 HP (basic heating load supply) Cooling capacity 260 kw free cooling (basic cooling load supply) 3. METHODOLOGY OF THE RESEARCH AND DEVELOPMENT PROJECT The R&D Project is structured in two parts. On one hand all ten buildings are being analyzed regarding to geological conditions, system configuration, energy performance as well as investment and operating costs. An important component of this analysis is the comparison of estimated and predicted values with the real values in operation. This comparison should help to detect inaccuracy and failures of the design and simulation tools. Furthermore monitoring five of the buildings is main part of the project. In those five buildings measuring equipment has been installed to analyze operation, energy performance and ground temperatures. Cold/heat meters are installed to log the energy output of the UTESs as well as its quota of total heating and cooling energy consumption. Furthermore the electric energy consumption of heat pumps and UTES-system-pumps is monitored to enable a complete evaluation. In order to optimize their efficiency and control algorithms the building will be simulated with dynamic thermal building and system simulation tools (TRNSYS). In order to gain sophisticated simulation data resource about 250 values are simultaneously logged every 15 minutes in each building. The data is then collected from our institute via internet and automatically visualized. This can be done at reasonable cost by using existing building control system infrastructures.

4. RESULTS AND EXPERIENCES AT VOLKSWAGEN LIBRARY OF THE TECHNICAL UNIVERSITY AND UNIVERSITY OF ARTS OF BERLIN The VW-Library of the Technical University and University of Arts of Berlin has been in service since fall 2004. Constructor has been the Federal State of Berlin itself, represented by the Senate Department of Urban Development. (see Fig # 1) Building Concept Fig. # 1: The VW-Library of the Technical University and University of Arts of Berlin (source: Prof. Walter A Nobel) Main part of the realized energy design is an 8 000 m² horizontal absorber placed below the base of the library. The absorber containing 126 parallel circuits with a tube diameter of 0.025 m and a tube distance of about 0.45 m is placed 1 m below groundwater table. The complete length of the implemented tubes is about 21 300 m. The UTES is used for seasonal heat and cold supply of concrete core activation implemented in 7 700 m² of ceiling area of offices and reading space. Just like in most buildings the cold is used for direct cooling. For heating in winter the system is coupled with an 80 kw heat pump. In addition to the concrete core activation covering the basic heat and cold supply, the offices and reading space are equipped with radiators using long-distance heating. In the reading space HVAC-systems (DCS-systems) are also implemented and the offices are realized with natural ventilation. (see Fig. # 2) Fig. # 2: Energy concept VW-Library of the Technical University and University of Arts

Energy performance During system design an equalized energy balance was estimated for horizontal absorber with a maximum charging and discharging energy amount of 142 MWh/a (see Fig. # 3). Contrary to those planning preferences the heating and cooling energy earnings by the foundation absorber were about 50 MWh/a and 178 MWh/a from March 2005 until March 2006. Fig. # 3: Predicted energy-output of the foundation absorber beneath the VW-Library This uneven energy balance is due to higher internal heat loads than estimated caused by more technical equipment fitted into the library. A second reason is the faster reacting space heating compared to the slower reacting concrete core activation during the heating period. In general the thermostatic valves of the space heating are operated by the office occupants themselves. Keeping them running on a high level, the room temperature increases above the intended temperature. Because of this the CCA reaches its activation point less often and the heat pump is running rarely and not at full load mode. In other words the slower concrete core activation is not able to supply the rooms with heat because the space heating preliminarily heats up the office section. (see Fig. # 4) Even though the heat demand is low, the SPF of the heat pump is about 3. Fig. # 4: Heat quantity of concrete core activation in comparison to heat quantity of space heating at the VW-Library, October 2005 till April 2006

In addition an undesired injection of heating energy into the UTES during winter months is caused by the rarely working system. Due to this the fluid in the heat pump circuit stands still and warms up in the pipes and has to be cooled down again while being pumped through the ground. Another reason for the uneven energy balance was a fault in the controlling strategy. In the past the system was controlled by the present outdoor temperature. So during transit time the system was permanently changing between heating and cooling. At night the building was heated and had to be cooled down at daytime because of internal gains. In order to optimize the foundation absorbers performance the energy charging has to be reduced and the discharging has to be increased. Therefore an additional compression chiller will be implemented to the cooling circuit to cover the higher than accepted heat load and realize a recovery of the overcharged UTES. To increase the heat supply quota the concrete core activation the space heating has to be turned down to a temperature below the intended room temperature. Faults and potentials are being detected step by step. Our scientific monitoring in cooperation with the facility management will lead to an improvement of the performance of the foundation absorber and the thermal comfort of the library. 5. RESULTS AND EXPERIENCES AT THE EXAMPLE OF THE ENERGYFORUM BERLIN Another monitored building is an office building standing on 198 energy-piles in the centre of Berlin, called EnergyForum. The approximately 21 000 m² large building was finished in 2003 and cost 55 million Euros. (see Fig. # 5) The EnergyForum reached its energetic goal of a primary energy consumption of 91 kwh/(m²a) for HVAC and lighting. Using ordinary Double-U Borehole piping material, the 8.50 m long energy-piles form a 6 732 m long heat exchanger below the building. The energy-piles are used for a seasonal base load supply of heat and cold for 4 100 m² of concrete core activation in the office ceilings. The 100 kw heat pump is covering about 17 % of the annual heating energy demand. About 83 % of the heating energy comes from a high efficient distance heating power plant. Fig. # 5: EnergyForum office building in the centre of Berlin The total investment cost of the UTES was 171 718. This is about 25 per energy-pile. Since the operation started in June 2003 the UTES yearly saved about 11 517 /a of heating and cooling energy cost (see Fig. # 11). During operation the heat pump performed an average SPF of 5.6 which is a very good result for a heat pump which has not been running in full load mode often.

Fig. # 6 (left): Coverage of the total heating energy consumption in 2004 of the EnergyForum. Fig. # 7 (right): Coverage of the total heating energy consumption in 2005 of the EnergyForum. 300 Measured heating power of convector heating and EP-HP 250 Power [KW] 200 150 100 50 0 1.9.2003 1.11.2003 Convector heating power 1.1.2004 1.3.2004 1.5.2004 1.7.2004 1.9.2004 1.11.2004 Time 1.1.2005 1.3.2005 1.5.2005 1.7.2005 1.9.2005 1.11.2005 1.1.2006 1.3.2006 Energy pile heat pump heating power Fig. # 8 (left): Weekly averaged measured Seasonal Performance Factor (SPF) of the 100 kw ground source heat pump at the EnergyForum Berlin. Fig. # 9 (right): Measured heating power of the installed convectors and the energy-pile heat pump from Sept. 2003 till April 2006. Those kind of UTESs are planed as even balanced systems in which only the same amount of energy should be extracted as is brought into the storage. This way the UTESs remain a stable system over decades. Another aspect in Berlin is that the UTES of the EnergyForum would be shut down by the authorities in case the UTES warms up the groundwater in an undesired level. Here takes the protection of drinking water resources priority over UTES-usage. As shown in Fig. # 10 below, the charging and discharging of the UTES of the EnergyForum was very imbalanced during the first six months of operation. This was a result of malfunctions in the building control system. In August 2004 the building reached a regular operation status. This regular operation status still leaves enough aspects for optimization. Especially the control of the CCA is in constant modification in order to reach better heat pump operation times and to lower consumption of long-distance heating energy.

30.0 20.0 Heat quantity [MWh] 10.0 0.0-10.0-20.0-30.0 Jun 03 Jul 03 Aug 03 Sep 03 Okt 03 Nov 03 Dez 03 Jan 04 Energy Piles Cooling Mode Feb 04 Mrz 04 Apr 04 Mai 04 Jun 04 Jul 04 Aug 04 Sep 04 Okt 04 Nov 04 Dez 04 Time Jan 05 Feb 05 Mrz 05 Apr 05 Mai 05 Jun 05 Energy Piles Heating Mode Fig. # 10: Measured energy-output of the 198 energy-piles beneath the EnergyForum from June 2003 till April 2006 Jul 05 Aug 05 Sep 05 Okt 05 Nov 05 Dez 05 Jan 06 Feb 06 Mrz 06 Apr 06 2500 2000 Savings [Euro] 1500 1000 500 0 Jun 03 Aug 03 Okt 03 Dez 03 Feb 04 Apr 04 Jun 04 Aug 04 Okt 04 Dez 04 Time Feb 05 Apr 05 Jun 05 Aug 05 Okt 05 Dez 05 Feb 06 Apr 06 Monthly Energy Cost Savings (Cold (0.10 /kwh) + Heat (0.06 /kwh)) Fig. # 11: Calculated monthly energy cost savings gained by the energy-pile system (UTES) from start of operation in June 2003 till April 2006 at the EnergyForum in Berlin. 6. CONCLUSION Our R&D-project shows that it is possible to fit UTES-systems into today s office buildings energy concepts. They are ideal to be combined with low temperature heating or high temperature cooling systems like concrete core activation or heating/cooling ceilings. In this combination UTES coupled heat pumps reach high SPF s. In order to implement a cost-effective seasonal UTES-system, it must be taken in consideration throughout the entire design of a building, that high temperature cooling systems (fluid temp. = 17 to 22 C) need modern façade-systems which keep the external load out of the offices.

The investment cost per meter energy-pile lies around 17 and 28 /m. A borehole heat exchanger (BHE) costs about 45 to 75 /m in Germany. One of the biggest parts of investment costs of the UTES are the heat pumps. About 30 to 40 % of the investment costs have to be spent here. In day to day practice it shows that a relatively low experience level of the facility management might lead to long lasting underperformance of a seasonal UTES-system. Therefore the control strategies have to be double checked during commissioning phase. In case of starting operation of a seasonal UTES-system during cooling period it must be kept in mind that an overheating can easily occur due to a non pre cooled underground. The high storage capability of the ground prevents high temperatures from being lowered during just one heating period. Those circumstances might lead to an underperformance of cooling over years. During spring and autumn malfunctioning controls often cool down an office building during daytime and heat it up at nighttime. As a result lots of energy is being wasted by running heat pump and circulation pumps. This demonstrates that a seasonal UTES performs the best if it is strictly operated during cooling and heating periods only. Under hydro geological aspects we recognized a clear difference between the ground temperatures forecasted by planning simulation and the real ground temperatures at begin of operation. Here all influencing side effects have not yet been worked out. In the next months we will combine our monitoring results with dynamic building and system simulations to elaborate optimizing strategies. In order to reach a more detailed simulation of groundwater flow induced temperature drift a coupled simulation with TRNSYS and ANSYS is in development. The first results of the project show that operation of energy-piles, foundation absorbers and borehole heat exchangers used as seasonal UTESs are still in need of optimization as well as research work in order to reach full user acceptance and better cost-effectiveness. 7. REFERENCES VDI guideline 4640. (December 2000). Thermische Nutzung des Untergrundes / Thermal use of the underground. Fundamentals, approvals, environmental aspects. Beuth-Verlag. Düsseldorf. R.Himmler, M. N. Fisch. (October 2004) Ganzheitliches Energiedesing von Bürogebäuden am Beispiel des EnergieForums Berlin / Integral energy design of office buildings on the example of the EnergyForum Berlin. TAB Technik am Bau.Fachzeitschrift für Technische Gebäudeausrüstung. Bauverlag AG. Gütersloh. M. N. Fisch, M. Bodmann, L. Kühl, C. Sasse, H. Schnürer. (2005). Wärmespeicher / Heat Storage. BINE Informationsdienst. TÜV-Verlag GmbH. München.