MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall

Similar documents
PERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

TEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

TEST REPORT. Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California. PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC.

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

Structural Performance Certification Authorization Report

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

Architectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina

Structural Performance Certification Authorization Report

TEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series

Structural Performance Certification Authorization Report

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO)

PERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania

TEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS:

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window

TEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

MOCK-UP TEST REPORT. Report No: NCTL Test Dates:06/22, 07/23-27/10 Test Dates: 08/23-25/10 Report Date: 08/26/10

TEST REPORT. Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois. AD Skylight without Guard

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight

TEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut

ASTM D 4541 ADHESION STRENGTH PERFORMANCE TEST REPORT. Rendered to: BAUTEX SYSTEMS. PRODUCT: AMB 20-WN Liquid Applied Membrane

TEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas. Cycles 2,000,000. Summary of Results

MOCK-UP TEST REPORT NCTL ACURLITE STRUCTURAL SKYLIGHTS MOCKUP TEST UNIT TEST DATES 03/13/17, 03/21/17 03/23/17 REPORT DATE 04/03/17

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: TUBELITE, INC.

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

Structural Performance Certification Authorization Report

PERFORMANCE TEST REPORT. Rendered to: DOW CORNING CORPORATION. PRODUCTS: Dow Corning 790 Silicone

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: MGM INDUSTRIES. SERIES/MODEL: 4600 Picture Window

Dennis Fassnacht Jr :59:35-04'00'

TEST REPORT. Rendered to: COLLINS LIMITED, LLC. For:

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: TUBELITE, INC.

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: GAMCO CORPORATION

PERFORMANCE TEST REPORT. Rendered to: SIMTEK FENCE. TYPE: SimTek Privacy Fence System

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight

TEST REPORT. Rendered to: AFCO INDUSTRIES, INC. For: PRODUCT: Redi-Rail. TYPE: Aluminum Level Guardrail System

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: Solutions Aluminum Guardrail System with Glass Balustrades

TEST REPORT. Rendered to: ENDURIS EXTRUSIONS INC. For: 6' high by 8' wide Dog Ear Picket Shadow Box Privacy Fence Systems

Construction Consulting Laboratory, International

TEST REPORT. Rendered to: KEYLINK FENCING & RAILING, INC. For: PRODUCT: Lancaster Series. TYPE: Aluminum Level Guardrail System

PERFORMANCE TEST REPORT. Rendered to: HILTI CORPORATION. PRODUCT: Extreme Weather Window & Door Insulating Foam Sealant

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel

AAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania

SURFACE PROPERTY TEST REPORT. Rendered to: VANGUARD ADA SYSTEMS OF AMERICA. PRODUCT: Detectable Warning/ADA Non-Skid Coating

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post

Architectural Testing

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

STRUCTURAL PERFORMANCE TEST REPORT. Rendered to: DIGGER SPECIALITIES, INC. For: 8 ft by 42 in Westbury Style C10 Level Aluminum Guardrail Assembly

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless. TYPE: Stretch Fabric Wall System

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: MGM INDUSTRIES. SERIES/MODEL: 4600 Double Hung

PERFORMANCE EVALUATION TEST REPORT. Rendered to: CBT SUPPLY, INC. / D.B.A. SMARTDESKS

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America LLC. SERIES/MODEL: FCM B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight

TEST REPORT. Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1" FABRI TACK

INTERNATIONAL WINDOW TEST REPORT

TEST REPORT. Report No.: G Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A AAMA TEST REPORT SUMMARY

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB. TYPE: Acoustical Wall Panel

TEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

OSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

REPORT NUMBER: COQ-003 ORIGINAL ISSUE DATE: July 19, 2013

Transcription:

Architectural Testing MOCK-UP TEST REPORT Rendered to: TUBELITE INC PROJECT: 300 ES Interior Glazed Curtain Wall Report No: 94346.01-602-32 Test Completion Date: 09/10/09 Report Date: 09/14/09 Record Retention End Date: 09/10/13 5906 Saxon Avenue Schofield, WI 54476 phone: 715-241-8624 fax: 715-241-8425 www.archtest.com

Architectural Testing Project: 300 ES Interior Glazed Curtainwall MOCK-UP TEST REPORT Rendered to: TUBELITE 3056 Walker Ridge Drive NW Suite G Walker, Michigan 49544 Report No: 94346.01-602-32 Test Completion Date: 09/10/09 Report Date: 09/14/09 Record Retention End Date: 09/10/13 Project Summary: Architectural Testing, Inc. was contracted by Tubelite to conduct performance testing on a curtain wall mock-up. The mock-up met the specified performance requirements. This report includes complete written and photographic documentation of all testing performed and a copy of "As-Built" mock-up drawings. Drawing Reference: "As-Built" drawings; Sheet No.; 1 of 1, and dated 08/15/08, copy attached to this report. General Mock-up Description: Project Type: Interior Glazed Curtain Wall Mock-up Size: 6' 7" wide by 5' 9-3/8" high Test Methods: Air Infiltration: ASTM E 283-04, Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors. Testing was conducted at 6.24 psf positive static air pressure difference. Static Pressure Water Resistance: ASTM E 331-00, Standard Test Method for Metal Curtain Walls and Doors by Uniform Static Air Pressure Difference. Testing was conducted at 15.0 psf positive static air pressure difference for a 15 minute duration. Water was applied to the mock-up at a minimum rate of 5 gal/ft 2 /hr. 5906 Saxon Avenue Schofield, WI 54476 phone: 715-241-8624 fax: 715-241-8425 www.archtest.com

Architectural Testing 94346.01-602-32 Page 2 of 5 Test Methods: (Continued) Dynamic Pressure Water Resistance: AAMA 501.1-05, Standard Test Method for Metal Curtain Walls for Water Penetration Using Dynamic Pressure. Testing was conducted with a dynamic pressure equivalent of 15.0 psf for 15 minute duration. Water was applied to the mock-up at a minimum rate of 5 gal/ft 2 /hr. Structural Performance: ASTM E 330-02, Structural Performance of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference. Testing was conducted at positive and negative loads of 45.0 psf design pressure as listed in the test results. Witnesses: The following representative witnessed all or part of the testing: Name Steve DeYoung Jeffrey Zibton David Kauffman Company Tubelite Inc. Architectural Testing, Inc. Architectural Testing, Inc.

Architectural Testing 94346.01-602-32 Page 3 of 5 FINAL TEST RESULTS 09/08/09 General Note: Unless otherwise stated, all comments relative to location are as viewed from the interior. Title of Test Measured Allowed Air Infiltration @ 6.24 psf <0.01 cfm/ft 2 max. 0.06 cfm/ft 2 max. Static Pressure Water Resistance PASSED No uncontrolled @ 12.00 psf leakage Dynamic Pressure Water Resistance PASSED No uncontrolled @ 12.00 psf leakage Static Pressure Water Resistance PASSED No uncontrolled @ 15.00 psf leakage Dynamic Pressure Water Resistance PASSED No uncontrolled @ 15.00 psf leakage FINAL TEST RESULTS 09/09/09 Uniform Load Deflection @ +22.5 psf (Preload) PASSED @ +45.0psf (Design Load) PASSED See Table #1 and Sketch #1 @ -22.5 psf (Preload) PASSED @ -45.0 psf (Design Load) PASSED See Table #1 and Sketch #1

Architectural Testing 94346.01-602-32 Page 4 of 5 FINAL TEST RESULTS 09/09/09 (Continued) Repeat Static Pressure Air Infiltration PASSED @ 6.24 psf <0.01 cfm/ft 2 0.06 cfm/ft 2 max. Repeat Static Pressure Water Resistance PASSED No uncontrolled @ 15.00 psf leakage Uniform Structural Overloads @ +33.75 psf (Preload) PASSED @ +67.50 psf (Overload) PASSED See Table #2 and Sketch #1 @ -33.75 psf (Preload) PASSED @ -67.50 psf (Overload) PASSED See Table #2 and Sketch #1 END OF TESTING "As-Built" Mock-up drawings, data sheets, a copy of this report, or other pertinent project documentation will be retained by Architectural Testing, Inc. for a period of four years from the original test date. At the end of this retention period, such materials shall be discarded without notice and the service life of this report by Architectural Testing, Inc. will expire. Results obtained are tested values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC.: Jeffrey Zibton Senior Technician Wanda Matis Director Regional Operations JMZ:hlc Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Alteration Addendum (1) Appendix-B: Table (1) Appendix-C: Sketch (1) Appendix-D: Drawings (1)

Architectural Testing 94346.01-602-32 Page 5 of 5 Revision Log Rev. # Date Page(s) Revision(s) 0 09/14/09 N/A Original report issue This report produced from controlled document template ATI 00301, revised 04/13/09.

94346.01-602-32 Appendix A Alteration Addendum Note: No alterations were required.

94346.01-602-32 Appendix B Table

94346.01-602-32 TABLE #1 Uniform Load Deflection (Deflection in inches) Indicator Positive Net Negative Net Location 45.00 psf Deflection 45.00 psf Deflection Allowed* 1 0.71 0.21 2 0.51 0.08 0.24 0.08 0.396 3 0.47 0.11 4 0.62 0.19 5 0.63 0.06 0.21 <0.01 0.206 6 0.52 0.22 *General Note: Allowable amounts are based on l/175 of their clear span for framing members. Refer to Sketch #1 for dial indicator locations. TABLE #2 Uniform Structural Overloads (Permanent Set in inches) Indicator Positive Net Perm. Negative Net Perm. Location 67.5 psf Set 67.5 psf Set Allowed* 1 0.05 0.02 2 0.04 <0.01 0.02 <0.1 0.139 3 0.03 0.04 4 0.02 0.01 5 0.03 <0.01 0.02 <0.01 0.072 6 0.04 0.03 *General Note: Allowable amounts are based on 0.2% of their clear span for framing members. Refer to Sketch #1 for dial indicator locations.

94346.01-602-32 Appendix C Sketch

94346.01-602-32 Appendix D Drawings