Design, Efficiency and Recovered Energy of an Airto-Air Energy Recovery System for Building Applications in Hot-Humid Climate

Similar documents
Experimental investigation on the performance of an air-to-air energy recovery for building applications in hot-humid climate

CFD Modelling and Analysis of Different Plate Heat Exchangers

ENERGY AND ECONOMIC ANALYSIS OF AN AUDITORIUM S AIR CONDITIONING SYSTEM WITH HEAT RECOVERY IN VARIOUS CLIMATIC ZONES

Improving the Energy Performance of HVAC Systems in Operating Theatres by Using Heat Recovery Devices

Experimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in Buildings

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System

Fresh air pre-cooling and energy recovery by using indirect evaporative cooling in hot and humid region a case study in Hong Kong

This is a repository copy of A Review of Heat Recovery Technology for Passive Ventilation Applications.

Next Generation: High Efficiency Energy Recovery Ventilator (ERV) 11/14/11 Dais Analytic Corporation

A Solar Wall System Utilized in Rural Houses of Northeast China

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels

ENERGY CONSERVATION STRATEGIES FOR HVAC SYSTEMS

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

A Paradigm Shift in ERV Technology. Paul Ehrlich, PE President Building Intelligence Group PLLC

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

Building Energy Simulation of A. Run-Around Membrane Energy Exchanger (RAMEE) A Thesis Submitted to the College of. Graduate Studies and Research

ENERGY EFFICIENT TECHNIQUES AND SIMULATION OF ENERGY CONSUMPTION FOR THE SHANGHAI ECOLOGICAL BUILDING

INNOVATIONS IN VENTILATION TECHNOLOGY 21ST ANNUAL INTERNATIONAL AIVC CONFERENCE THE HAGUE, NETHERLANDS, SEPTEMBER 2000

IN THIS ISSUE INTRODUCTION BACKGROUND. March 2018 High Humidity in Winter: Analysis for Multi-Family Passive House Projects

ROOF TOP SPACE. SELF-CONTAINED REVERSIBLE AIR-AIR UNITS OF 23 TO 281 kw EVERY EFFICIENT SOLUTION FOR UNIVERSAL COMFORT NA C

Energy Recovery Process Cooling Example. Presentation - Overview. Air Change Australia Pty Ltd. Air Change Energy Recovery Range

APPLICATIONS Air-to-Air Energy Recovery

STUDIES ON THERMAL COMFORT AND ENERGY CONSUMPTION OF HVAC SYSTEM

Design, Fabrication and Experimental Study of a Novel Loopheat-pipe based Solar Thermal Facade Water Heating System

QATAR UNIVERSITY. Graduate Studies. College of Engineering INVESTIGATION OF A REGENERATIVE INDIRECT EVAPORATIVE COOLING SYSTEM.

Cooling coil optimisation in hot and humid climates for IAQ and energy considerations

Air Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil

Analysis of Heat Gain in Computer Laboratory and Excellent Centre by using CLTD/CLF/SCL Method

Managing. Delta T in Buildings

Performance Mapping for Variable Ductless Heat Pump Systems in Heating, Cooling and Defrost Operation

Outdoor air treatment units

Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies.

US1 IEA. Renovation of Wausau West High School, Wisconsin, United States of America

EXPERIMENTAL INVESTIGATION ON OPERATION PARAMETERS OF 3Å MOLECULAR SIEVE DESICCANT COATED TOTAL ENERGY RECOVERY WHEEL FOR MAXIMUM EFFECTIVENESS

Energy Recovery Ventilation Equipment

HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT

Feasibility Study of Multiple-Pass Total Energy Recovery Ventilator with Built-in Economizer Using TRNSYS: A Case Study for Toronto, Ontario

THE USE OF HEAT RECOVERY DEVICES FOR REDUCING ENERGY CONSUMPTION OF TREATING VENTILATION AIR IN A TROPICAL OPERATING THEATRE

ANALYSIS OF EXERGY OF MOIST AIR AND ENERGY SAVING POTENTIAL IN HVAC BY EVAPORATIVE COOLING OR ENERGY RECOVERY

Operating Engineers Seminar Bob Ford Jeff Volovsek

Level 1 Modules tdp-101 hvac industry overview tdp-103 concepts of air conditioning tdp-102 abcs of comfort

FLEXY EC HIGH EFFICIENCY ROOFTOP kw AIR COOLED COOLING ONLY/HEAT PUMP/ GAS/ DUAL FUEL

Year-round Energy Saving Potential for a Stratum Ventilated Subtropical Office. C.K. Lee Zhang Lin K.F. Fong

Rooftops High performance, proven reliability and easy installation

LAHU Heat Recovery System Optimal Operation and Control Schedules

CV of Prof. Dr. Li-Zhi ZHANG

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

SHIYUN CHEN ADVISOR: DR. BAHNFLETH. 1 Executive Summary Building Summary 3. 3 Existing Mechanical System. 4

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

IMPROVING THE DURABILITY OF FLAT ROOF CONSTRUCTIONS Durability of flat roof construction

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

CO₂emission of FC which is the most commercialized type of household fuel cell and gas fired boiler. Therefore, energy saving effect and carbon emissi

Economical Analysis of the Cold Air Distribution System: A Case Study

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

PERFORMANCE ANALYSIS OF FOOD PRESERVING OF POTATO COLD STORAGE

Technical Feasibility Study of Hybrid Ventilation for a High-rise Office Building in Shanghai

CAE 331/513 Building Science Fall 2017

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES

Performance evaluation of a small-scale polygeneration plant including a desiccant cooling system and an innovative natural gas ICE

Energy aspects of HVAC system configurations problem definition and test cases

on a Run-Around Membrane Energy Exchanger Saskatoon

Modelling of Indirect Evaporative Air Coolers

Ventilation performance measurement of a decentralized mechanical system with heat recovery using Tracer gas decay method

Mechanical Product Overview

Exergy Analysis as an Assessment Tool of Heat Recovery of Dwelling Ventilation Systems

Critical exergy analysis of counterflow reversibly used cooling towers

Available online at ScienceDirect. Energy Procedia 105 (2017 )

Development and Performance Evaluation of Indirect-Direct Evaporative Cooling System

Heat Pump Technology Applies on Air-conditioners Impact on Electric Power

International Journal Of Scientific Research And Education Volume 3 Issue 3 Pages March-2015 ISSN (e): Website:

Air distribution and temperature control in classrooms

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space

A, B, C, D VENTILATION SYSTEMS: COMPARISON

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

CEN/TC 89 - Thermal performance of buildings and building components

ashrae) VENTILATING PRINCIPLES AIR CONDITIONING OF HEATING AND 7th Edition A Textbook with Design Data Based on the 2013 ASHRAE Handbook Fundamentals

Heat Pump Hot Water Supply Systems

Study of the energy performance of a retrofitting office

THEORETICAL STUDY OF COOLING TECHNOLOGIES DRIVEN BY GEOTHERMAL ENERGY FOR USE IN TERTIARY BUILDINGS IN BELGIUM

Simulation And Optimization of a Solar Absorption Cooling System Using Evacuated Tube Collectors

Use of MathCad and Excel to Enhance the Study of Psychrometric Processes for Buildings in an Air Conditioning Course

Energy performance of a ventilation system for an apartment according to the Italian regulation

Achieving Near Net-Zero Energy Usage in Laboratory

Application of Advanced Energy Technologies

Experimental Study on PCM-Air Heat Exchanger Used For Building Ventilation System

BUILDING INTEGRATED VENTILATION SYSTEMS MODELLING AND DESIGN CHALLENGES

TDPs provide you with new technical training materials designed to help your contractors, engineers, and designers to effectively design, specify,

Optimal design for a dual-airflow window for different climate regions in China

Depth: Mechanical Redesign

Effect of Different Ventilation Conditions on Indoor CO2 Levels

Theoretical and computational analysis of closed wet cooling towers and its applications in cooling of buildings

A Primer on Recovery Efficiency Ratio

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM

Access from the University of Nottingham repository:

RESULTS OF LONG-TERM ENERGY EFFICIENCY MONITORING OF TEST BUILDINGS UNDER REAL CLIMATIC CONDITIONS

Experimental comparison of performance between single and dual core energy recovery ventilation systems

Mechanical Depth. Redesign and Analysis

Transcription:

Design, Efficiency and Recovered Energy of an Airto-Air Energy Recovery System for Building Applications in Hot-Humid Climate M. F. Zafirah 1, A. Mardiana 2 1, 2 Energy, Indoor and Environmental Quality Research Group, School of Industrial Technology, Universiti Sains Malaysia, 11800 USM, Pulau Pinang, Malaysia Abstract: Recently, concerns on energy consumption and air quality in buildings have significantly increased. Hence, a system namely air-to-air energy recovery has been introduced to overcome this problem. It functions to pre-heat and/or pre-cool the incoming air by using the outgoing air and simultaneously provides healthy fresh air to indoor spaces. The application of this system has widely been used in countries that experience cold climates. However, only a few studies present scientific works pertaining to hot-humid climate zone in open literature. To close this gap, thus this study presents a work on an air-to-air energy recovery system for building applications in hot-humid climate. The objective of this study was to evaluate the efficiency and recovered energy of the system. Experimental investigations were conducted under controlled conditions in Energy and IEQ Testing Unit located in School of Industrial Technology, Universiti Sains Malaysia. Tests were carried out under different airflow rates ranged from 1.0 to 3.0 m/s and intake air temperature of 31 C, 35 C and 40 C. The efficiency and recovered energy of the system were calculated and evaluated by adopting calculation method by ASHRAE Standard. The efficiency of this system ranged from 45 to 85 % and the highest recovered energy of 17.5 kw was achieved at 1.0 m/s and 31 C. From these results, it was found that the efficiency decreased and in contrast the recovered energy increased with increasing airflow rates. Keywords: Air-to-air energy recovery, Efficiency, Recovered energy 1. Introduction Total energy consumption of buildings accounts for significant percentages of national energy consumption worldwide. According to IEA [1] buildings represent about 40% of primary energy consumption in most countries. The major energy consumption in buildings are heating, cooling and air-conditioning (HVAC) systems. Liu et al. [2] stated that space heating is the most important building energy consumer in cold countries, whereas air-conditioning is a major contributor to peak electricity demand in hot-humid climate countries or during summer. These HVAC systems will continue to take a large proportion of total energy consumption in buildings as reported in [3]. Therefore, if targets for energy reduction in buildings are to be met, it is essential that technologies to reduce energy consumption are designed to have the maximum impact of energy saving. With the growing concern of buildings require a source of fresh air and energy reduction, air-to-air energy recovery system appears as one of the key solutions to generate energy saving [4]. The air-to-air energy recovery system, also known as energy recovery ventilator or heat recovery is a mechanical system that removes stale, polluted air from indoor spaces and replaces it with fresh outdoor air. Besides, the system involves a process of recovering energy (heat and/or mass) from a stream at a high temperature to a low temperature stream through a heat exchanger to maintain a comfortable temperature of indoor spaces [2]. In other words, in this system, the energy that would otherwise be lost is used to heat the air in cooler stream - helps to recover a part of energy loss. Routlet et al. [5] and Zhang et al. [6] reported that the system also can be operated as a ventilation system in summer or hot season and cost effective. Therefore, more and more air handling units are equipped with energy recovery technologies with the aim of decreasing the energy consumption in buildings in the current years [7] and [8]. In conserving energy, the system pass the warm air from one stream (warm) to the other stream (cool) through an internal component which is the heat exchanger where heat transfer occurs. Typically, the system has the capability to recover about 60-95% of heat in exhaust stream [4]. Min and Su [9] in their paper had explained about a basic physical model of air-to-air energy recovery system and its components, which makes it unique in its operation and behaviour. As a whole, the system varies according to its type, size and flow arrangement as discussed in [10], [11], [12], [13], [14] and [15]. To date, as reported in [10] many studies have been conducted on air-to-air energy recovery systems for building applications. Some of the findings are reported in [16], [17], [18], [19], [20] [21], [22], [23], [24]. Only a few studies provide scientific works on the air-to-air energy recovery systems in relation to climate zones. For instance, Zhong and Kang [25] analysed the role of the air-to-air energy recovery systems in reducing energy consumption in four different climate zones in China. On the other hand, Fehrm et al. [26] performed a research on the application of air-to-air energy recovery system in Europe, particularly for cold climate. Delfani et al. [7] and [27] studied about air-to-air energy recovery system for building applications in various climates of Iran. Despite the enormous number of research devoted to the system since 1980s [28], little attention has been paid on the performance in terms of efficiency and energy load for building applications in hot-humid climate zone, at least in open literature. To narrow this gap, this study proposed a design of an air-to-air energy recovery system for potential Paper ID: SEP14495 1803

application in hot-humid climate. Efficiency and recovered energy were investigated and evaluated using experimental approach. 2. Design and System Description The air-to-air energy recovery system in this study was designed to recover energy in hot-humid climate with the design parameters of: i) airflow ranged from 300 to 60,000m 3 /h; ii) intake temperatures ranged from 30 to 45 C; room temperatures ranged from 20 to 25 C. In this system, the air-to-air energy recovery core was formed based on hydrophilic polymeric membrane layers, impregnated with unique ingredients and addictive and structured with 23 pieces of waveform stand or sinusoidal plate-fin channels. The membrane layers were arranged in a cross-flow manner and have the capabilities to transfer both heat and moisture simultaneously. This configuration also allowed air to change direction in a manner that ensures sufficient air comes in contact with heat transfer surface prior leaving the core (airflow of 300 to 60,000 m 3 /h). The dimensions of the core were 0.2 m height, 0.2 m length and 0.1 m width with 0.002 m height of sinusoidal plate fin channels. A core shell was designed to house the core at the centre with two separate flexible air ducts (intake and exhaust) (Figure 1). The shell was made of 0.025 m thick polystyrene sandwich panels with thin aluminium sheet for insulation purpose. Each duct has a diameter of 0.015 m. The shell helped to station and separate two airstreams (intake and exhaust) of the core. Two DC centrifugal fans with maximum of 24 V were installed in the intake and exhaust ducts to assist airflow and distribute the air through the air-to-air energy recovery system. Figure 1: Design of air-to-air energy recovery system 3. Experimental Set Up and Procedure A series of experimental investigation was conducted under laboratory conditions in Energy and IEQ Testing Unit located in School of Industrial Technology, Universiti Sains Malaysia. Figure 2 illustrates the experimental set up of the system. The air-to-air energy recovery system was tested in a controlled experimental chamber that includes a room (R) with a dimension of 2.9 m x 4.6 m x 5 m, an insulated test room (TR) with a dimension of 2 m x 2 m x 2 m and air-toair energy recovery system Figure 2: Experimental set up of air-to-air energy recovery system in Energy & IEQ Testing Unit The test room was made of 0.045 m polyurethane foam sandwich panel to reduce the effect of surroundings. The test room was used as a controlled chamber to regulate hot temperatures between 30 and 45 C. An artificial heating system was used to generate heat in the test room. Meanwhile, an air-conditioning equipment was placed to simulate cold temperature in the room. Measurements were carried out under different airflow rates ranged from 1.0 to 3.0 m/s using established method by Fisk et al. [29] as stated in [30]. In order to test the efficiency of the system at different airflows, two speed controllers were connected to the DC centrifugal fans. temperature before entering core (T i ), intake air temperature after entering core (T s ), return air temperature (T r ) and exhaust air temperature after entering core (T e ) were recorded using type-k thermocouple (+/- 2.2⁰C or +/- 75%) and were placed at 16 different points across the experimental chamber. Four thermocouples were placed in the test room (TR) and five thermocouples were placed in the room (R). For airflow Paper ID: SEP14495 1804

measurements, a hot-wire anemometer (±3% of reading, ±0.05m/s) was used to measure airflow rates of intake and exhaust airstreams at the same points of temperature measurement. Log-Tchebycheff method was applied in order to obtain accurate airflow rate values [31]. For each test, the experimental chamber was allowed to come to steady state condition which was achieved after 45 minutes. The measurements were carried out after the experimental chamber reached steady state conditions using data acquisition system comprising DT800 with DeLogger TM 5 Pro Software. Data were collected over a period of 2 h for each test. Results were analysed to evaluate the efficiency and recovered energy of the system. The tests were carried out at mean room temperature of 24 C and mean intake temperature (T i ) of 31 ⁰C, 35 ⁰C and 40 ⁰C. Efficiency (Ԑ ER ) and recovered energy (Q ER ) of the system were then calculated and tabulated at different airflow rates by adopting calculation method as suggested by ASHRAE Standard [14], [30] and [32]. 4. Results and Discussion 4.1 Airflow rate and temperature data Table 1: Measured and calculated data at 31 ⁰C Table 1, 2 and 3 show the measured and calculated data of the air-to-air energy recovery system at mean intake temperature (T i ) 31 ⁰C, 35 ⁰C and 40 ⁰C, respectively for airflow rate ranged from 1.0 to 3.0 m/s (0.018 0.054 m 3 /s). From this data it was calculated that the temperature difference ( T) at intake temperature 31 ⁰C was 3.53 C, at 35 ⁰C was 8.91 C and at 40 ⁰C was 14.02 C for airflow rate of 1.0 m/s (0.018 m³/s). On the other hand, at airflow rate 3.0 m/s (0.054 m 3 /s), T was found to be in a range of 4.15 to 9.71 C. 1.0 0.018 0.021 31.08 27.55 25.36 30.14 1.5 0.027 0.031 31.07 27.48 24.68 31.48 2.0 0.036 0.042 31.20 27.77 25.18 31.12 2.5 0.045 0.052 31.09 26.54 22.88 32.02 3.0 0.054 0.063 30.90 26.75 23.89 30.00 Table 2: Measured and calculated data at 35 ⁰C 1.0 0.018 0.021 34.97 26.06 23.58 33.84 1.5 0.027 0.031 35.08 28.88 25.15 35.17 2.0 0.036 0.041 35.07 28.94 25.27 34.73 2.5 0.045 0.052 35.14 28.43 23.17 36.95 3.0 0.054 0.062 35.08 29.83 25.98 34.53 Table 3: Measured and calculated data at 40 ⁰C 1.0 0.018 0.020 40.07 26.05 23.66 36.80 1.5 0.027 0.030 39.94 29.83 25.39 39.38 2.0 0.036 0.041 40.14 30.42 26.48 39.23 2.5 0.045 0.051 40.15 30.16 23.19 42.99 3.0 0.054 0.061 40.04 30.33 26.06 39.18 4.2 Efficiency of the system y = -9.3x + 93.9 Equation 3 Figure 3 illustrates the efficiencies of the system based on the measured for airflow rates (V i ) ranged from 1.0 to 3.0 m/s (Q i = 0.018 to 0.054 m 3 /s) and tested intake temperatures (T i ) of 31 ⁰C, 35 ⁰C and 40 ⁰C. From the figure, it can be seen efficiency increased with increasing airflow rates for every tested temperature. The relationship between efficiency and airflow rates at 31 ⁰C, 35 ⁰C and 40 ⁰C can be expressed by Equation 1, 2 and 3, respectively. y = -2.7x + 65.9 Equation 1 y = -4.9x + 78.5 Equation 2 This trend can be explained by a theory of residence time within the air-to-air energy recovery core, which is the average amount of time that a substance (air) spends in the core. The higher the residence time, the higher is the effectiveness [31]. In contrast, efficiency decreased with increasing intake temperature. The efficiency ranged from 45 to 85%. The highest efficiency (85%) was achieved at (0.018 m 3 /s) and 40 ⁰C. Meanwhile, the lower temperature was achieved at (0.054 m 3 /s) and 40 ⁰C. Thus, intake air conditions give significant effects to the performance in terms of efficiency of energy recovery system as suggested in [33]. Paper ID: SEP14495 1805

Figure 3: Efficiency of the system versus airflow rate 4.3 Recovered energy of the system The variations of recovered energy with airflow rates are shown in Figure 4 for airflow rates (V i ) ranged from 1.0 to 3.0 m/s and tested intake temperature (T i ) of 31 ⁰C, 35 ⁰C and 40 ⁰C. From the study it was found that the recovered energy of air-to-air energy recovery system increased with increasing airflow rates. The highest recovered energy of 17.50 kw was achieved at 3.0 m/s and the lowest was achieved at 1.0 m/s for intake air temperature of 31 ⁰C. Whilst, for intake air temperature of 40 ⁰C, the lowest recovered energy of 5.77 kw was obtained at 1.0 m/s and the highest was obtained at 3.0 m/s. Figure 4: Recovered energy of the system 5. Conclusion An air-to-air energy recovery system was completely designed and tested to evaluate the efficiency and recovered energy of the system for building applications in hot-humid climate. In order to achieve its objectives, a series of experimental investigations were carried out at room temperature of 24 C and intake temperature (T i ) of 31 ⁰C, 35 ⁰C and 40 ⁰C in School of Industrial Technology, Universiti Sains Malaysia. It was found that the efficiency of the system decreased with increasing airflow rates. Meanwhile, when the airflow rate increased, the recovered energy increased. The efficiency of the system ranged from 45 to 85 % with the highest recovered energy of 17.50 kw. Thus, as a conclusion, the efficiency and recovered energy of the system were affected by the intake air conditions. A thorough study on thermal performance of the system should be further investigated in relation to sensible and latent loads as well as effects of various operating parameters. 6. Future Scope There are several directions where the current research work can be extended. A thorough study on thermal performance of the system should be further investigated in relation to sensible and latent loads as well as effects of various operating parameters. In addition, field testing and practical application of the system on real existing buildings should also be carried out in the future. Acknowledgments The authors wish to express their acknowledgements to MOE PRGS Grant (203/PTEKIND/6730116) and USM RUI Grant (1001/PTEKIND/811229) for the financial support associated with this study. References [1] IEA, 2014. http://www.iea.org [Accessed 30 August 2014]. [2] Liu, D., Zhao, F.Y. and Tang, G.F. Active low-grade energy recovery potential for building energy conservation. Renewable and Sustainable Energy Reviews, 14: 2736 2747. 2010. [3] Gong, G., Zeng, W., Wang, L. and Wu, C. A new heat recovery technique for airconditioning/ heat-pump system. Applied Thermal Engineering, 28: 2360 2370. 2008. [4] Shao, L., Riffat, S.B. Flow loss caused by heat pipes in natural ventilation stacks. Applied Thermal Engineering, 17: 393 399. 1997. [5] Roulet, C.A., Heidt, F.D., Foradini, F., Pibiri, M.C. Real heat recovery with air handling units. Energy and Buildings, 33: 495 502. 2001. [6] Zhang, L.Z., Zhu, D.S., Deng, X.H. and Hua, B. Thermodynamic modelling of a novel air dehumidification system. Energy and Buildings, 37: 279 286. 2005. [7] Delfani, S., Pasdarshahri, H., Karami, M. Experimental investigation of heat recovery system for building air conditioning in hot and humid areas Energy and Buildings, Volume 49, 62-68. 2012. [8] Mardiana-Idayu, A., Riffat, S.B. Review on heat recovery technologies for building applications. Renewable and Sustainable Energy Reviews, 16(2), 1241-1255. 2012. [9] Min, J., Su, M. Performance analysis of a membranebased energy recovery ventilator: effects of membrane spacing and thickness on the ventilator performance, Applied Thermal Engineering (30) 991-997. 2010. [10] Mardiana, A., Riffat, S.B., Worall, M. Integrated heat recovery system with wind-catcher for building applications: towards energy-efficient technologies in Materials and processes for energy: communicating current research and technological developments (A. Méndez-Vilas, Ed.).720-727. Formatex Research Centre, Spain. 2013. Paper ID: SEP14495 1806

[11] Shao, L., Riffat, S.B., Gan, G. Heat recovery with low pressure loss for natural ventilation, Energy and Buildings (28) 179 184. 1998. [12] Lazzarin, R.M., Gasparella, A. Technical and economical analysis of heat recovery in building ventilation systems, Applied Thermal Engineering. (18) 47 67. 1998. [13] Lamb, B.R. Plate heat exchangers-a low cost route to heat recovery. Journal of Heat Recovery Systems (2):247-255. 1982. [14] Riffat, S.B, Gan, G. Determination of effectiveness of heat-pipe heat recovery for naturally-ventilated buildings. Applied Thermal Engineering (18):121-130. 1998. [15] Ahmadi, M.S., Blake, E., Simonson, C.J., Besant, R.W. Transient behaviour of run-around heat and moisture exchanger system. part І: model formulation and verification. International Journal of Heat and Mass Transfer (52):6000-6011. 2009. [16] Söylemez, M.S. On the optimum heat exchanger sizing for heat recovery. Energy Conversion and Management (41):1419-1427. 2000. [17] Navarro, H.A, Gómez, L.C. A new approach for thermal performance calculation of cross-flow heat exchangers. International Journal of Heat and Mass Transfer (48):3880-3888. 2005. [18] Hassam, N.C., Hughes, B.R., Abdul-Ghani, S. A review of heat pipe systems for heat recovery and renewable energy applications. Renewable and Sustainable Energy Reviews (16): 2249-2259. 2012. [19] Nobrega, C.E.L., Brum, N.C.L. Modeling and simulation of heat and enthalpy recovery wheels. Energy (34):2063-2068. 2009. [20] Zhang. Heat and mass transfer in a plate-fin sinusoidal passage with vapour-permeable wall materials. International Journal of Heat Transfer (51) 24-32. 2008. [21] Yau, Y.H. Experimental thermal performance study of an inclined heat pipe heat exchanger operating in high humid tropical HVAC systems. International Journal of Refrigeration (30):1143-1152. 2007. [22] Srimuang, W., Amatachaya, P. A review of the applications of heat pipe heat exchangers for heat recovery. Renewable and Sustainable Energy Reviews (16) 4303-4315. 2012. [23] Vali, A., Simonson, C.J., Besant, R.W, Mahmood, G. Numerical model and effectiveness correlations for a run-around heat recovery system with combined counter and cross flow exchangers. International Journal of Heat and Mass Transfer (52):5827-5840. 2009, [24] Simonson, C.J, Besant, R,W. Energy wheel effectiveness: part I-development of dimensionless groups. International Journal of Heat and Mass Transfer (42):2161-2170. 1999. [25] Zhong, K. and Kang, Y. Applicability of air-to-air heat recovery ventilators in China. Applied Thermal Engineering, 29(5): 830 840. 2009. [26] Fehrm, M., Reiners, W., Ungemach, M. Exhaust air heat recovery in buildings. International Journal of Refrigeration 25: 439 449. 2002. [27] Delfani, S., Pasdarshahri, H., Karami, M. Experimental investigation of dehumidification process in cooling coil by utilizing air-to-air heat exchanger in humid climate of Iran. Energy and Buildings, (42) 822-827. 2010. [28] Pescod, D. A heat exchanger for energy saving in an air conditioning plant. ASHRAE Transaction (85). 238-251.1979. [29] Fisk, W.J.,Turiel, I. Residential air-to-air heat exchangers: Performance energy savings, and economics. Energy and Buildings 5(3), 197-211. (1983). [30] Mardiana-Idayu, A., Riffat, S.B. An experimental study on the performance of enthalpy recovery system for building applications. Energy and Buildings 43(9), 2533-2538. 2011. [31] Zhou, C. Estimation of volumetric flow rate in a square duct: Equal area versus log-tchebycheff methods. Electronic Theses and Dissertations. 2005. [32] Mardiana-Idayu, A., Riffat, S.B. Review on physical and performance parameters on heat recovery technologies for building applications. Renewable and Sustainable Energy Reviews, 28(2), 174-190. 2013. [33] Min, J.C., Su, M. Performance analysis of a membranebased energy recovery ventilator: Effects of outdoor air state. Applied Thermal Engineering. 31(17), 4036-4043. 2011. Author Profile M.F. Zafirah received her BTech degree in. Environmental Technology from Universiti Sains Malaysia in 2013. Currently, she is pursuing her MSc in Environmental Technology in Universiti Sains Malaysia. She is also an academic fellow of Universiti Malaysia Pahang. A. Mardiana obtained her BTech degree in Environmental Technology from Universiti Sains Malaysia in 2003, Masters in Environmental Management from Universiti Kebangsaan Malaysia in 2006 and PhD in Engineering Science (Sustainable Energy Technologies) from University of Nottingham, United Kingdom in 2011. She had experience of working in industry after her graduation in 2003 until 2005. She joined USM as an academic staff in 2011 and then promoted to Senior Lecturer in Energy and Environmental Technology under School of Industrial Technology. She is a member of Institution of Engineering & Technology (IET) UK and a member of World Society of Sustainable Energy Technologies (WSSET). Paper ID: SEP14495 1807