P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

Similar documents
P.V.C. INSULATED UNARMOURED COPPER CABLES

138-1: 2015 CEB SPECIFICATION. AERIAL BUNDLE CONDUCTORS - 33 kv (95mm 2 and 150mm 2 )

137-1: 2015 CEB SPECIFICATION. XLPE INSULATED SINGLE CORE UNDERGROUND CABLES OF 11 kv RATED VOLTAGE

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

Single Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

TECHNICAL SPECIFICATION OF UNARMOURED FLAT 1100 VOLTS L.T. PVC INSULATED TWIN CORE 4.0mm² CABLE WITH ROUND ALUMINIUM CONDUCTOR BLACK SHEATHED.

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS

Single Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY)

Four Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

MATERIAL STANDARD FOR CABLES AND WIRES

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 22 kv, SINGLE CORE, 95mm 2 COPPER

Specification No. CSC-70/DH/UH/P&D/

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDER NO.8/2013 FOR THE SUPPLY OF CONDUCTORS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's

11-SDMS-01 REV. 03 ( )

2. RATED VOLTAGE: The rated voltage of the AB cables shall be 1100 volts

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1

Technical Specification for Insulated Low Voltage Single Core Copper Cable

MGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

TABLE OF CONTENTS FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 4

Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

Technical Specification for Helical Fittings for Overhead Power Lines

SPECIFICATION FOR STAY INSULATORS (PORCELAIN)

a) Temperature Variation : 5ºC to 55ºC b) Relative humidity : Upto 95% c) Altitude : 0 to 1000 Mtrs. d) No.of tropical monsoon months : 3 (Three)

Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

5.2 The phase conductors shall be provided with one, two & three ridges for easy identification.

066 : 1998 CEB STANDARD GALVANIZED IRON PIPES FOR SERVICE CONNECTIONS CEYLON ELECTRICITY BOARD SRI LANKA

SPECIFICATION FOR FRLS POWER CABLES

NPS/002/023 Technical Specification for 132kV Power Cables.

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

Maharashtra State Electricity Distribution Co. Ltd.

TECHNICAL SPECIFICATIONS

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION The ELECTRICITY (PEDE) TENDER DOCUMENTS FOR

2.2 Copies of any records and other connected papers that may be required by the Bureau shall be made available at any time on request.

TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS

TECHNICAL SPECIFICATION FOR RATE CONTRACT OF INSULATING MATS

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

Specification for: All Aluminum Alloy (AAAC) Type AL3 Stranded conductor For distribution overhead lines

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

056 : 1997 CEB STANDARD

SPECIFICATION FOR DISC INSULATORS (Standard Type)

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS

BIS or used as Amendment to STANDARD comments is 15 Nov. 2008

NPS/002/013 Technical Specification for Telephone and Pilot Cable Joints

SPECIFICATION OF HT-LT STAY (GUY) INSULATORS:

ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME. Technical Specification (T.S)

33-SDMS-02 SPECIFICATIONS FOR

TENDER NOTICE. 6. Separate tender documents should be used for each tender.

TECHNICAL SPECIFICATION

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS

TABLE OF CONTENTS. Page FOREWORD INTRODUCTION SCOPE NORMATIVE REFERENCES

project 36 MW 1.0 INTRODUCTION AND PROJECT INFORMATION

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

TECHNICAL SPECIFICATIONS FOR CROSS LINKED POLYETHYLENE INSULATED 3 CORE llkv CABLES

SPECIFICATION FOR HT-LT STAY (GUY) INSULATORS:

56-SDMS-01 REV. 01 SPECIFICATIONS FOR

ENGINEERING SPECIFICATION EE SPEC

018-3 : 1996 CEB STANDARD TOOLS FOR ERECTION OF AERIAL BUNDLED CONDUCTORS ACCESSORIES CEYLON ELECTRICITY BOARD SRI LANKA

Test Report No.: Page 2 of 35

TABLE OF CONTENTS INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3

--> Buy True-PDF --> Auto-delivered in 0~10 minutes. TB/T Translated English of Chinese Standard: TB/T1484.

THE KENYA POWER AND LIGHTING CO. LTD

MANUFACTURER'S QUALITY ASSURANCE PLAN (QAP - Instrumentation cables)

TECHNICAL SPECIFICATION FOR CONDUCTORS

COMPILED BY FUNCTIONAL RESP APPROVED BY AUTHORIZED BY TABLE OF CONTENTS FOREWORD... 3 INTRODUCTION SCOPE TYPES... 3

DATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0

ACSR CONDUCTOR. March 2015 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

COMPILED BY FUNCTIONAL RESP. APPROVED BY AUTHORIZED BY TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES...

TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE

SECTION 07. TECHNICAL SPECIFICATIONS OF 11 KV XLPE CU CABLE (1x500 mm 2 )

TECHNICAL SPECIFICATION FOR SUPPLY OF WEDGE CONNECTOR TO BE USED IN POWER DISTRIBUTION SYSTEM

*** Supercedes: BECO E and COM , , & ***

GEMSCAB INDUSTRIES LIMITED STANDARD PLAN FOR HT XLPE CABLES AS PER IS:7098(PART-II)

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara:

CONSULTATIONS TECHNICAL GUIDELINE. HVDC extruded cable

1. All Members of Power Cables Sectional Committee, ET 09; 2. All Members of Electrotechnical Division Council; and 3. All other Interested.

CERTIFICATE OF ACCREDITATION

AN ISO 9001 : 2008 COMPANY

Technical Specification for Plastic-Insulated Low Voltage Cables

12-SDMS-01 Rev.02 SPECIFICATIONS FOR

SPECIFICATION FOR STOCKBRIDGE TYPE VIBRATION DAMPERS FOR DISTRIBUTION AND TRANSMISSION OVERHEAD LINES

Test Report No.: Page 2 of 34

SPECIFICATION FOR RUBBER INSULATING GLOVES FOR MEDIUM VOLTAGE CLASS 2, 3

Transcription:

CEB SPECIFICATION 005-1: 2012 P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935

CONTENTS PAGE 1. Scope 03 2. System Parameters 03 3. Service Conditions 03 4. Applicable Standards 03 5. Basic Features 04 6. Technical Requirements 04 7. Quality Assurance 05 8. Raw Material 06 9. Additional Requirements 06 10. Information to be furnished with the offer 07 11. Sample 07 12. Inspection and Testing 08 13. Annex Annex-A Schedule of guaranteed technical particulars 09 Annex-B Non Compliance Schedule 11 Annex-C Price Variation 12 Annex-D DS&S/2012/005 PVC Insulated Aluminium Service Main Wire 14 2/14

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE- FINISHED PRODUCT 1.0 SCOPE This specification covers design, manufacture and testing of the following PVC Insulated Aluminium Service Main Wires; a) Twin Service Main Wire with phase core insulated neutral core bare and both sheathed together. b) Twin Service Main Wire with both cores insulated and sheathed. 2.0 SYSTEM PARAMETERS a) Nominal System Voltage 400V ph to ph /230V ph to Neutral b) System Highest Voltage 440 V ph to ph /250V ph to Neutral c) System Frequency 50 Hz d) Method of Earthing Solidly earthed neutral at substations e) System Fault Level 25 ka 3.0 SERVICE CONDITIONS a) Annual average ambient temperature 30 C b) Maximum ambient temperature 40 C c) Maximum relative humidity 90% d) Environmental Condition Humid tropical climate with polluted atmosphere e) Operational Altitude From M.S.L. to 1900 meters above M.S.L. 4.0 APPLICABLE STANDARDS The items and components supplied shall be in accordance with the latest edition of the standard specified below and amendments thereof. However CEB specification shall supersede these standards in the event there is a discrepancy. BS 2627: 1970 IEC 61089: 1991 BS 6004: 2000 BS 7655-3.1: 1997 BS 7655-4.2:2000 BS EN/IEC 608111.1: 1995 ASTM B233-97 (2003) Specification for Wrought Aluminium for Electrical Purposes Wire Round wire concentric lay overhead electrical stranded conductors Electric Cables PVC insulated non armoured cables for Voltages up to and including 450/750V, for electric power, lighting and Internal wiring Specification for insulating & sheathing materials for cables. PVC insulating compounds. Harmonized types Specification for insulating & sheathing materials for cables. PVC sheathing compounds. General Application Insulating and sheathing materials of electric cables. Common test methods. General application. Measurement of thickness and overall dimensions. Test for determining the mechanical properties. Standard Specification for Aluminium 1350 Drawers stock for Electrical Purpose. 3/14

5.0 BASIC FEATURES 5.1 General The Service Main Wires shall be of 300/500 V grade and shall comply with BS6004: 2000 in regard to thickness of the Insulation and the Sheath. The formation of insulations and overall sheathing shall be as per drawing No. DS&S/2012/005. The core for the Service Main Wires stipulated under Clauses 5.2(a) and 5.2(b) shall be ¾ hard drawn aluminium (H6) wires as per BS 2627: 1970. The Insulation shall be of harmonized PVC type TI 1 complying with BS7655-3.1: 1997. The Sheath shall be PVC type 6 complying with BS7655-4.2: 2000.It shall fit closely to avoid ingress of moisture while in service but shall not adhere to the Insulation or to the bare conductor so that it shall be possible to remove the Sheath easily without damage to the Insulation. 5.2 Manufacture (a) Twin Service Main Wire phase core Insulated, neutral core bare and both Sheathed. The Service Main Wire shall be of twin type, phase core shall be insulated with Brown coloured PVC Insulation, the neutral core shall be bare, both lay parallel and cores are sheathed with Black PVC sheath material. The sheath shall separate the insulated conductors by a minimum thickness of 3.5 mm to provide additional Phase to Neutral Insulation. In addition to this a groove of width not less than 1mm shall be provided on the sheath between the phase and the neutral so that the both could be separated easily without bearing the Neutral as per drawing No DS&S/2012/005. Cross sectional area of the cores shall be (10mm 2 /16 mm 2 ) as indicated in the schedule of the prices. (b) Twin Service Main Wire both cores Insulated and Sheathed. The Service Main Wire shall be twin type, and the colours of the insulation shall be Black, and Gray and both lay in parallel and sheathed with Black colour PVC sheath material. Cross sectional area of the cores shall be (10mm 2 /16 mm 2 ) as indicated in the schedule of the prices. 6.0 TECHNICAL REQUIREMENTS (A) General a) Type of service main wire As per clause 5.0 b) Nominal cross sectional area 10 mm 2 or 16 mm 2 c) No. of wires & nominal diameter for (10 mm 2 ) wire 7/1.35mm 7/1.71mm for (16 mm 2 ) wire d) Number of cores Two cores e) Colour of Sheath Black 4/14

(B) Conductor a) Conductor material ¾ Hard drawn Aluminium (H6 as per BS 2627) b) Conductor Diameter for (10 mm 2 ) for (16 mm 2 ) 4.05mm 5.12mm c) Conductor D.C. Resistance for (10 mm 2 ) for (16 mm 2 ) 2.8264 ohm/km 1.7665 ohm/km d) Tensile Strength of Conductor material 125 N/mm 2 ~165 N/mm 2 e) Result of wrapping Test of wire (only for 10mm 2 ) No crack (C) Insulation a) Insulation Type Type TI 1 as per BS 7655-3.1: 1997 b) Thickness 1 mm c) Smallest thickness 0.8mm d) Tensile Strength 12.5 N/ mm 2 e) Tensile Strength after ageing 12.5 N/ mm 2 with max. Variation ±20% f) Elongation at break 125 % g) Elongation at break after ageing 125 % with max. Variation ±20% h) Resistance to cracking Temp:150±2 C Requirement: No crack (D) Sheath (E) Tests a) Sheath type Type 6 as per BS 7655-4.2 : 2000 b) Thickness for (10 mm 2 ) wire for (16 mm 2 ) wire 1.2mm 1.3mm c) Smallest Thickness for (10 mm 2 ) wire for (16 mm 2 ) wire 1mm 1mm d) Tensile Strength 12.5 N/ mm 2 f) Elongation at break 125 % h) Resistance to cracking Temp:150±2 C Requirement: No crack a) Spark test-a.c. (r.m.s.)-10 kv No breakdown b) Voltage test- A.C. (.r.m.s.)-2.0 kv No breakdown c) Flame propagation of single cable As per BS EN 50265-2-1. 7.0 QUALITY ASSURANCE The Manufacturer shall possess ISO 9001: 2008 Quality Assurance Certification valid throughout the delivery period of this tender, for the plant where the Service Main Wire is being manufactured. The Bidder shall furnish a certified copy of the ISO Certificate along with the offer. Quality Assurance System conforming to ISO 9001:2008 shall be followed in the manufacture of the Aluminium Re-draw Rods. The Bidders shall furnish documentary evidence that the Aluminium Redraw Rods manufacturers have obtained ISO 9001:2008 Certification. Offers of bidders who fail to furnish the proof of ISO 9001:2008 certificates will be rejected. 5/14

8.0 RAW MATERIAL Aluminium Re-draw Rods Raw material shall not be supplied by the purchaser. Aluminium Re-draw Rods used in the manufacturing of Aluminium wire for the fabrication of Twin Service Main Wires shall conform to ANSI / ASTM 233-97. The Quality of Aluminium Re-draw rods used for the manufacture of Twin Service Main Wires shall be as stipulated below. (a) The purity of the Aluminium re-draw rods shall not be less than 99.5%. The percentage composition of other elements shall not be more than the values stipulated in the below. Element Allowed % Max. i. Silicon 0.10 ii. Iron 0.40 iii. Copper 0.05 iv. Manganese 0.01 v. Chromium 0.01 vi. Zinc 0.05 vii. Boron 0.05 viii. Gallium 0.03 ix. Vanadium plus titanium, total 0.02 x. Other elements, each 0.03 xi. Other elements, total 0.10 Total % of impurities shall not be more than 0.5 (b) (c) Temper of the Aluminium Re-draw Rods shall be H14 classification. The tensile strength of Rods shall be between 103MPa to 138MPa (10.3 N/mm 2 to 13.8N/mm 2 ). (d) The Maximum Electrical resistivity of the Aluminium Re-draw Rods shall be 0.028080Ω.mm 2 /m 9.0 ADDITIONAL REQUIREMENTS 9.1 Marking The outer sheath, of the Service Main Wire shall be embossed with letters "CEB" followed by the manufacturer's identification, rated voltage & conductor size according to clause 5.3 of BS 6004 at every 550mm or less along the length. 6/14

9.2 Packing The Service main Wire shall be delivered in 100 Metre or 250 Metre Coils (as stipulated in the schedule of prices) and wrapped in polythene. Each coil shall bear a tag under the polythene wrappings showing the following particulars. (a) Manufacturer's Name or Trade Mark, (b) Type of cable (c) Core size (d) Length of cable (e) Colour of Insulation /sheath. (f) Net weight/gross weight. 10.0 INFORMATION TO BE FURNISHED WITH THE OFFER 10.1 The following shall be furnished with the offer in English Language (a) Catalogues describing cables offered. (b) Completed schedule of guaranteed technical particulars (Annex A). (c) The manufacturer shall have at least 10 years of experience in the manufacturer of PVC cables and he shall furnish sufficient documentary evidence in the bid to prove his manufacturing experience. (d) ISO 9001:2008 quality assurance certificates as per clause 7.0 10.2 Type Test Certificates The certified copies of the Type Tests Certificates for the following tests as per BS 6004 IEC 61089 and ASTM B233-97 shall be furnished with the offer; (a) Insulation resistance ( as per BS 6004:2000, clause 7.6 ) (b) Compatibility test (as per BS 6004:2000, clause 8.4) (c) Voltage test on cores (as per BS 6004:2000 Clause 7.4) (d) Flame propagation of a single cable (as per BS 6004:2000, clause 8.5) (e) Joints in Aluminium wires (as per IEC 61089, clause 6.5.4) (f) Stress strain curves (as per IEC 61089, clause 6.5.1 and clause 6.5.2) (g) (Breaking strength of conductor (as per IEC 61089, clause 6.5.3) Aluminium Re-draw Rods (a) Tensile test. ( as per ASTM B233-97, clause 7) (b) Determination of chemical composition and purity. ( as per ASTM B233-97, clause 5) (c) Electrical resistivity test. (As per ASTM B233-97, clause 9) The type test certificates pertaining to recent manufacture of Aluminium Service Main Wire specified herein shall be from an independent testing authority acceptable to the purchaser. 11.0 SAMPLE The sample pieces of Aluminium Service Main Wire of length two.0 metre (2m) each for the conductor sizes indicated in the price schedule which are manufactured according to this specification shall be accompanying the offer. Bidder's identity shall be indelibly marked on the samples. 7/14

12.0 INSPECTION & TESTING 12.1 Acceptance/Sample Test The Manufacturer shall make necessary arrangements for inspection by an Engineer appointed by the CEB during Manufacture and before dispatch and also to carry out in his presence the sample tests and routine tests (as per Clause 12.2 below) stated in BS 6004, EN 60811-1-1:1995 and IEC 61089. Following tests shall be witnessed by the Engineer on selected samples and the copies of the test certificates shall be supplied with the cable. (a) Cross section area of the conductor (as per IEC 61089 clause 6.6.1 ) (b) Conductor diameter (as per IEC 61089 clause 6.6.2 ) (c) Linear density-mass per unit length (as per IEC 61089 clause 6.6.3 ) (d) Breaking strength of wires (as per IEC 61089 clause 6.6.4 ) (e) Surface condition (as per IEC 61089 clause 6.6.5 ) (f) Lay ratio and direction of lay (as per IEC 61089 clause 6.6.6 ) (g) Measurement of insulation thickness and overall dimensions (as per EN 60811-1-1:1995, clause 8.1) (h) Conductor resistance (as per BS 6004, clause 7.2 ) (i) Insulation resistance as per BS 6004:2000, clause 7.6 ) (h) Voltage test on completed cable (as per BS 6004:2000 Clause 7.3) 12.2 Routine Test The following Routine test report of Service Main Wire shall be made available for the observation of the CEB inspector. (a) Visual inspection of cable markings (b) Absence of faults in the insulation (as per BS 6004:2000 Clause 7.5) 8/14

SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS (To be filled by the bidder Use separate sheet for each type of wire) (A) General a) Name of Manufacturer b) Type of service main wire c) Nominal cross sectional area of the conductor (mm 2 ) d) Number of strands & nominal diameter (mm) e) Number of cores f) Colour of insulation g) Colour of Sheath Annex-A (B) Conductor a) Conductor material b) Conductor overall Diameter c) Conductor D.C. Resistance for (10 mm 2 ) for (16 mm 2 ) d) Tensile Strength of Conductor at 20 0 C e) Result of wrapping Test (Crack / No crack) (C) Insulation a) Insulation Thickness (mm) b) Smallest measure of Thickness (mm) c) Tensile Strength (N/mm 2 ) d) Tensile Strength after ageing (N/mm 2 ) e) Elongation at break (%) f) Elongation at break after ageing (%) g) Resistance to cracking Temp: Requirement: No crack/crack (D) Sheath a) Thickness b) Smallest measure of Thickness c) Tensile Strength (N/mm 2 ) e) Elongation at break (%) g) Resistance to cracking Temp: Requirement: No crack/crack (E) Test on completed Cable a) Spark test-a.c. (r.m.s.)-10 kv (No breakdown/ breakdown) b) Voltage test- A.C. (.r.m.s.)-2.0 kv (No breakdown/ breakdown) c) Flame propagation of single cable (Pass/Fail) 9/14

ALUMINIUM RE-DRAW RODS (used for the manufacture Twin Service Main Wire) a) The tensile strength N/mm2 b) Temper Classification H c) Electrical Resistivity Ω.mm2/m d) Purity % e) Whether quality Assurance Certification As per ISO 9001:2008 Yes/No Furnished f) Chemical composition as indicated in the below Element % Max. i. Silicon % Max. ii. Iron % Max. iii. Copper % Max. iv. Manganese % Max. v. Chromium % Max. vi. Zinc % Max. vii. Boron % Max. viii. Gallium % Max. ix. Vanadium plus titanium, total % Max. x. Other elements, each % Max. xi. Other elements, total % Max. xii. Total % of impurities shall not be more than % Max. I/We do hereby certify that the above particulars are true and correct. ------------------------------------------------------------ -------------- Seal and the Signature of the manufacturer Date 10/14

Annex B NON COMPLIANCE SCHEDULE On this schedule the bidder shall provide a list of non-compliances with this specification, documenting the effects that such noncompliance is likely to have on the equipment s life and operating characteristic. Each non-compliance shall be referred to the relevant specification clause. Clause No. Non compliance ------------------------------------------------------------ ------------------- Seal and the Signature of the manufacturer Date 11/14

Annex C PRICE VARIATION The Bidders shall forward their offers on the basis of the Price Variation stipulated below. 1. BASIS OF THE OFFER (a) (b) Suppliers are required to make their offers on the basis of a Base Price plus a Fixed Price Margin. The Base Price shall be the Cash Seller s Official Average Price of High Grade Aluminium 99.7%, at London Metal Exchange (LME) in US Dollars on the day of the closing of Bids or the previous working day if the day of closing of Bid is a non working day at the LME. Accordingly for the evaluation, FOB Price for Foreign Bidders / Ex-factory price for Local Tenderers shall be computed as, [(Bo x WAl x US) + (FP x CC)] x TL Where Bo FP WAl TL CC US - Base Price which is the Cash seller s midday official average price of Aluminium High Grade 99.7% in USD per Metric Ton at the LME on the fixed date [as per Clause (1b)]. - Fixed Price Margin per kilometer of wire, in Currency of Choice. - quantity of High Grade Aluminium 99.7% in Metric Tons required to Manufacturer one kilometer of the wire. (MT/km) - Total Length of wire in km. - Conversion rate from the currency of choice to Sri Lanka Rs. Prevailing on the Date of Bid opening. - Conversion rate from the US Dollars to Sri Lanka Rs. prevailing on the Date of Bid opening. 2. AWARD PRICE a) The FOB Award Price for Foreign Bidders and the Ex-factory Award Price of Local Bidders shall be computed as; [B1 x WAl + FP] x TL Where B1 FP WAl TL - Base Price which is the Cash seller s midday official average price of Aluminium High Grade 99.7% in USD per Metric Ton at the LME on the first working day immediately after the day of award (please see clause 3 of Annex-c). - Fixed Price Margin per kilometer of wire, in Currency of Choice. - Quantity of High Grade Aluminium 99.7% in Metric Tons required to Manufacturer one kilometer of the wire. (MT/km) - Total Length of wire in km. (b) Intimation of the award will be faxed / telexed to the successful Bidder and or his agent in Sri Lanka. 12/14

3. CONVERSION OF CURRENCY a) For the purpose of the evaluation the Price Bo in US Dollars and the Fixed Price Margin (FP) in the currency of choice of the Bidder will be converted to Sri Lanka Rupees at the official Middle Exchange Rate of the Central Bank of Sri Lanka prevailing on the day of opening of Bids. b) The payment for the suppliers will be made in the currency quoted for the Fixed Price Margin (FP). The base price B1 in US Dollars will be converted to the currency of the FP at the exchange rates indicated in the bulletin of the LME applicable on the first working day immediately after the date of the award of the offer; where such exchange rate is not available for the currency of the FP in the Bulletin the official middle exchange rate at the Central Bank of Sri Lanka shall be applicable. 4) VARIATION FIGURES The Bidders shall furnish Fixed Price Margin and the weight of Aluminium required to manufacture one kilometer of the wire in the column provided for in the Schedule of Prices. Failure to furnish these particulars will result in the offer being rejected. 13/14

14/14 CEB Specification 005-1:2012