THOMAS JEFFERSON UNIVERSITY HOSPITAL STANDARD OPERATING PROCEDURE FOR THE BUILD OUT OF TELECOMMUNICATIONS ROOMS AND ASSOCIATED SPACES

Similar documents
The University of Texas at Austin September 30, 2011

Communications Page 1 of 9

1 data PIC location (with 2 ports) typically asf for multiple staff members

Telecommunication Spaces

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

TELECOMMUNICATIONS ROOMS. Table of Contents PART 1 GENERAL 2 A. LOCATION: 2 B. SIZE 2 C. STRUCTURAL 3 D. ENVIRONMENTAL 3 E. ELECTRICAL AND LIGHTING 3

UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING. NAME: Communications Equipment Room ORIGINAL DATE:

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 27 Communication 0528 Pathways. Page 1 of 6

Standards and Procedures Security Room Construction/Renovations At University of North Carolina Wilmington

COMMUNICATIONS EQUIPMENT ROOM FITTINGS

FORMAT Technical specifications content and numbering system shall be based on 2004 CSI MasterFormat.

TABLE OF CONTENTS Public Safety Building

The University of Texas at Austin September 30, 2011

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 26 March 2013 ( ENCLOSURE 1)

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

DIVISION STRUCTURED CABLE

SECTION GROUNDING

ADDENDUM 2 - JULY 14, 2015

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Galvanized System

Exhibit A Library Shell Construction

A/E Design Guide for Drawings and Spec Section Communications Infrastructure.

A/E Design Deliverable Checklist

Alamo Colleges. Telecommunications Infrastructure Standards. For. New Facility Construction or Renovations. Version

Exterior Door & PA System Replacement, Domestic Water Piping System and B/F Access Upgrades

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES...

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

LACCD INFORMATION TECHNOLOGY STANDARD

1. Voice and data telecommunications for campus are managed by the Office of Information Technology (OIT) located in Gordon Palmer Hall.

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

SECTION COMMUNICATIONS EQUIPMENT ROOM FITTINGS

UMass Amherst Information Technology. Design and Construction Guidelines

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

SECTION GYPSUM BOARD & SHEATHING SYSTEMS

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DESIGN & CONSTRUCTION GUIDELINES

SECTION GROUNDING AND BONDING

C. Preparation and submission of complete engineered shop drawings for approval. E. Coordination with other affected work, trades and inspections.

SECTION Manufactured Metal Casework FLEXIBLE LABORATORY FURNITURE SYSTEM (OPTIMA) USA VERSION

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM)

CONTENTS. B. System Design and Performance Requirements

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

Telecommunications Design Guidelines University of Alberta Cabling Standards (version 2.1)

ALL DIMENSIONS FROM FINISHED FACE OF PARTITION TO FINISHED FACE OF PARTITION UNLESS OTHERWISE NOTED.

DESIGN DEVELOPMENT REVIEW PACKAGE CHECKLIST

A/E Design Deliverable Checklist

Watercrest - Sand Hill - Columbia, SC TABLE OF CONTENTS PROCUREMENT AND CONTRACTING REQUIREMENTS

Building Permit Application

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

c. Army Reserve Design Process Submittal Requirements (DPSR) d. USARC G-2/6 IT Design Criteria Updates, 17 October 2013 ( ENCLOSURE 1)

UBC Technical Guidelines Section Edition Audio-Video Infrastructure Page 1 of 5

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

A. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.

Power Electronics, Inc. Packaged Equipment Center Standard Construction and Design Features

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

INDEX. Page SECTION 1.0: SCOPE Toronto Hydro Requirements Ontario Electrical Safety Code 1 SECTION 2.0: PURPOSE 1

Third Party Design, Construction and Operations on FIU Campuses

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6

SECTION OUTLET, PULL, AND JUNCTION BOXES

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SPARTANBURG COUNTY BUILDING CODES DEPARTMENT

City of Westerville Guide to Commercial Inspections

PCC Structured Cabling Standards

Village of Glen Ellyn Basement Remodeling Project Guidelines

Santa Monica Fire Department SOLAR PHOTOVOLTAIC INSTALLATION GUIDELINE 2008 TABLE OF CONTENTS

Beverly Hills Fire Department SOLAR PHOTOVOLTAIC INSTALLATION GUIDELINE 2008 TABLE OF CONTENTS

MARBLEHEAD FIRE DEPARTMENT Standard Operating Guideline Draft for Photovoltaic/Solar Installations

RESEARCH AND TECHNOLOGY BUILDING RENOVATION MAY 18, 2009 SECTION COMMUNICATIONS

DIVISION 22 PLUMBING SECTION INTERIOR SANITARY WASTE AND VENT PIPING SYSTEM

SUMMARY 1234 Main St.Loudon TN Buyer Name 08/28/2018 9:00AM

SEISMIC PROTECTION SYSTEMS Bracing Products for Racks & Cabinets

SECTION PATIENT BED SERVICE WALLS

Element Z General Design Requirements Existing Facilities Information

UNIVERSITY OF CHICAGO

a) Line and load compartments must be separated by a stable barrier.

ELECTRON BEAM DUMP - ROOM DATA SHEET

Kaf-Tech Product Specification

SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System

1. Section , Gas and Vacuum systems for Laboratory and Healthcare Facilities

NC State University Design and Construction Guidelines Division 00 Planning & Design Space Planning

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

Project No. # PART 1 - GENERAL. Guide Specification. University Pullman. be all- MS Word Tracking. section. that the. requirements of the

Submittal Transmittal

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

September 23, 2016 ADDENDUM #2

C. Preparation and submission of complete engineered shop drawings for approval. E. Coordination with other affected work, trades and inspections.

CONSTRUCTION REQUIREMENTS

SECTION GYPSUM BOARD

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW

It is acceptable to place all required information in the main element (such as D5010) and delete the sub-elements provided in this template.

CSO / BSU NW2 NORTH RESIDENTIAL NEIGHBORHOOD PHASE #2 VOLUME 1 PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

KITCHEN REMODELS CITY OF MISSION VIEJO BUILDING SERVICES DIVISON 200 CIVIC CENTER, MISSION VIEJO, CA (949)

SECTION MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS

NYULMC AMBULATORY CARE CENTER FIT-OUT PHASE 1 Perkins & Will Architects PC 222 E 41st ST, NYC Project: Issued for GMP March 15, 2017

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

SECTION BASIC ELECTRICAL REQUIREMENTS

Transcription:

THOMAS JEFFERSON UNIVERSITY HOSPITAL STANDARD OPERATING PROCEDURE FOR THE BUILD OUT OF TELECOMMUNICATIONS ROOMS AND ASSOCIATED SPACES PREPARED BYBALA CONSULTING ENGINEERS, INC FOR THOMAS JEFFERSON UNIVERSITY HOSPITAL J~f!e~sO~m. I" r; )\0, ~ 1-i THOMASJEF'PEnS{JN UNrVHRSITY HOSPHALS

PUBLICA TION RECORD DOCUMENT VERSION PUBLICATION DATE PRIMARY AUTHOR REVIEWED BY 1 10/17/08 C. Lowe R. Squillace Review 2 6/22/09 C.Lowe R. Squillace ISSUE 3 DESCRIPTION October 17,2008 STANDARD OPERATING PROCEDURE Page 2

DOCUMENT INTENT... 5 A. GENERAL PLACEMENT AND SIZING CONSIDERATIONS... 5 1. TELECOMMUNICATIONS ROOMS (IDF AND MDF) PLACEMENT...... 5 2. IDF AND MDF ROOM DIMENSIONS... 5 B. FLOOR COVERINGS AND FINISH CONSIDERATIONS... 5 1. IDF AND MDF FLOOR COVERINGS... 5 2. IDF ANDMDF CEILINGS... 6 3. IDF AND MDF ROOM WALL FINISHES... 6 C. DOOR SIZING AND PLACEMENT... 6 1. IDF AND MDF DOOR SIZING..... 6 2. IDF AND MDF DOOR PLACEMENT......... 6 3. MISCELLANEOUS IDF AND MDF REQUIREMENTS......... 7 D. MDF AND IDF FIRE RATING CONSIDERATIONS... 7 1. FIRE RATING CONSiDERATIONS................. 7 MECHANICAL DESIGN COMPONENTS... 7 A. COOLING AND RELATIVE HUMIDITY... 7 1. IDF AND MDF COOLING REQUIREMENTS........ 7 2. IDF AND MDF RELATIVE HUMIDITY (RH) REQUIREMENTS... 8 3. IDF AND MDF GENERAL MECHANICAL DESIGN COMPONENTS... 8 4. SIZING OF UNITS... 8 ELECTRICAL DESIGN COMPONENTS...8 A. POWER REQUIREMENTS AND POWER DISTRIBUTION... 8 1. UNINTERRUPTABLE POWER SUPPLY (UPS)........... 8 2. CIRCUIT REQUIREMENTS AND PLUG CONFIGURATIONS........... 9 3. POWER DISTRIBUTION IN THE TR SPACE... 9 4. LIGHTING REQUIREMENTS IN TR SPACES......... 9 5. TELECOMMUNICATION CABLE PATHWAYS.......... 9 A. PLUMBING... 9 1. AVOID HAVING ANY PLUMBING PIPES ROUTE THROUGH TELECOMMUNICATIONS SPACES... 10 2. EXISTING PLUMBING PIPES SHOULD BE REMOVED AND REINSTALLED TO AVOID TELECOMMUNICATIONS SPACES........ 10 B. FIRE PROTECTION... 10 1. HOUSEKEEPING... 10 2. FIRE STOP SOLUTIONS......... 10 C. DETECTION... 10 1. SMOKE DETECTORS.............. 10 2. HEAT DETECTORS...... 10 D. SUPPRESSION... 10 BCE No. 40-08- THOMAS JEFFERSON UNIVERSITY Bluestone October 17,2008 STANDARD OPERATING PROCEDURE Page 3 for the build out oftelecommunications

1. DRY-PIPE DOUBLE INTERLOCK... 10 BONDING, GROlTNDING AND EARTHING...10 A. BONDING AND GROUNDING...11 1. REQUIREMENTS......... 11 2. TELECOMMUNICATIONS MAIN GROUNDING BUSBAR... 11 3. TELECOMMUNICATIONS GROUNDING BUSBAR... 11 BCE No. 40-08- THOMAS JEFFERSON UNIVERSITY Bluestone October 17,2008 STANDARD OPERATING PROCEDURE Page 4 for the build out oftelecommunications

Document Intent This document is intended to provide Thomas Jefferson University Hospital Information Technology department with a standard document for which they can present to other TJU internal departments, engineers or architects to provide a basic understanding of their construction requirements. ARCHITECTURAL DESIGN COMPONENTS A. General Placement and Sizing Considerations 1. Telecommunications Rooms (IDF and MDF) Placement a. IDF and MDF should be placed as close to core of building as possible. b. IDF and MDF rooms should have minimum of two (2) of the architectural walls available for cable entry points from the IDF / MDF to the open office work stations. c. IDF and MDF rooms should be vertically aligned in multistory buildings. d. Place a minimum of one (1) IDF on each floor with designated voice and data work stations. There shall be (1) MDF per building. At times this may co inhabit within the IDF. e. IDF and MDF room space should not be co-mingled with any other critical systems spaces other than what is required to achieve the required Mechanical, Electrical Plumbing. Fire Protection and Security for the IDF or MDF space. f. IDF and MDF rooms should not be located in close proximity to water closets or wet areas. IDF and MDF rooms should be placed as far away from wet areas as possible. g. IDF and MDF rooms should not be placed above or below any space that could have possible water infiltration. Any direct exposure to moisture may adversely affection the operation of equipment, cabling, and systems within the TR space. 2. IDF and MDF Room Dimensions a. IDF Dimensions - Telecommunications rooms need to be sized in accordance with the intended room use, network gear and cabling requirements. b. MDF Dimensions - Telecommunications rooms need to be sized in accordance with the intended room use, network gear and cabling requirements. B. Floor Coverings and Finish Considerations 1. LDF and MDF Floor Coverings BCE No. 4(1-.08 THOMAS JEFFERSON UNIVERSITY Bluestone October 17, -:008 STANDARD OPERATING PROCEDURE Page 5

a. Anti Static VCT floor covering should be installed in all MDF and IDF floors where raised floor or access floors are not available. 2. IDF and MDF Ceilings a. Drop ceilings should be utilized in the MDF and IDF rooms. b. Ceiling should be installed at ten (10) to twelve (12) feet above the finished floor. 3. IDF and MDF Room Wall Finishes a. W' AC grade plywood on three of the longest continuous walls. This will need to have further coordinated with potential existing services and architectural features. /1#lu,Ii,( b. Plywood shall be painted twice with two (2) coats of Bt-A-@*:- fire retardant paint on all sides and leading edges. (NOTE: Caution must be exercised when using any paint. Ensure that VOC emission compliance is adhered to. Plywood should not contain urea-formaldehyde). c. Plywood shall be installed Four (4) feet wide by eight (8) feet high for the entire length of all walls that are to have plywood coverings. d. Wall, floor, and ceiling finishes should be light in color. The color black is not recommended. e. When wall fields are anticipated to be supporting a large amount of cables, it is recommended that the plywood be attached to studs affixed to the architectural wall. Constructing the wall in this manner will create a pathway that can be utilized between studs and behind the plywood. C. Door Sizing and Placement 1. IDF and MDF Door Sizing a. IDF door sizes should be minimum 3'-0" wide and 6'-6" high for standard IDF and MDF rooms. When possible over sized 42" wide doors should be utilized. b. For the larger MDF rooms, or IDFs that house free standing cabinets doorways should be minimum of 6'-0" wide and 7'-6" high. 2. IDF and MDF Door Placement a. Doors should be oriented to afford the door to swing at least 180 degrees from closed position to the open position. If possible and permitted by code, doors should be installed to swing out of the space. This placement will allow more usable wall and floor space in the room. October 17,2008 ST ANDARD OPERATING PROCEDURE Page 6

b. Doors should be placed facing towards the most accessible common corridor. Placing doors into adjacent spaces that are not considered public spaces is not recommended. 3. Miscellaneous IDF and MDF Requirements a. Each door should be equipped for access control magnetic locking hardware or preferred access controlled entry device. It is recommended that a proximity or access control device be placed at each IDF and MDF door to manage and monitor entry into and out of the IDF and MDF space. b. Environmental Monitoring - All MDF Rooms must be equipped with a Netbotz unit to provide monitoring ofair temperature, humidity, water, and camera security. c. Door sills are not recommended. d. With larger IDF and MDF rooms that require double doors (6'-0") removable center posts are permitted. e. Access to the IDF and MDF should be limited to only the personnel responsible for the maintenance and operation of the cabling and network equipment and equipment within the space. The IDF and MDF rooms should not provide access into or out of any secondary rooms. D. MDF and IDF Fire Rating Considerations 1. Fire rating considerations a. IDF and MDF walls should be built and installed with all architectural and architectural support elements routed from solid floor to solid deck, with a minimum of 1 hour fire rating. b. IDF and MDF walls should be made of appropriate GWB finished wall coverings, for aesthetics, and to maintain designated min. 1 hour fire ratings. c. MDF spaces that house layer 3 active core electronic infrastructure, walls should provide a 2 hour fire rating. MECHANICAL DESIGN COMPONENTS A. Cooling and Relative Humidity 1. IDF and MDF Cooling Requirements a. For rooms that house active networking components, the temperature range should be maintained at a range of 64 and 75 degrees F. October 17, 2008 STANDARD OPERATING PROCEDURE Page 7

b. For rooms that do not house active networking components but do house low voltage Telecommunications infrastructure, the temperature range should be between 50 and 95 degrees F. 2. IDF and MDF Relative Humidity (RH) Requirements a. For rooms that house active networking components, the RH should be between the ranges of 30-55% RH b. For rooms that do not house active networking components the RH should be between the ranges of 30-55% RH 3. IDF and MDF General Mechanical Design Components a. Air handling and air distribution units must not be placed above the ceiling of IDF and MDF spaces. These units should be placed in adjacent non critical spaces, or planning must be made to place units in a suitable location that will not impact the IDF and MDF space for service requirements, maintenance, and accidental discharge or failure of units. b. IDF and MDF spaces should maintain positive air pressure. c. IDF and MDF spaces should be designed for a minimum of one air change per hour. d. IDF and MDF mechanical air handling and distribution units should be placed on back up power generation, or have the means to operate over an Uninterruptible Power Supply system if the IDF or MDF space is deemed mission critical. e. Air flow distribution with in the IDF and MDF should be accomplished via the use or supply and return ducts. Grill locations should be coordinated with the telecommunications design team. f. Air flow in the TR spaced should be static and have positive pressure to enable the IDF or MDF space to maintain healthy mechanical environments. 4. Sizing of Units a. IDF and MDF rooms can have various equipment requirements and HVAC unit sizing should be based upon the telecommunications department day one and anticipated heat loads. ELECTRICAL DESIGN COMPONENTS A. Power Requirements and Power Distribution 1. Uninterruptable Power Supply (UPS) October 17,2008 STANDARD OPERATING PROCEDURE Page 8 for the build out oftelecommunications

a. All network gear housed within the MDF and IDFs shall be supported by UPS units. Typically these units are housed within cabinets or two post racks. The size of the UPS is dependent upon the equipment it is intended to support. Space for these units, as well as the power and cooling required to support them needs to be considered prior to final mechanical and electrical engineering. n;ijl 2. Circuit Requirements and plug configurations ~'e:'/p,o.5 a. Plug configurations and outlet amperage will need to be defined on a case by case..5/el basis. b. Branch circuits from the local panel should be routed in EMT conduit from the panel to the receptacle location. c. Locate receptacles dedicated for rack mounted layer 2 or 3 networking gear as close as possible to the device being connected making certain to avoid any tripping hazards. This can be accommodated by placing the receptacles within cabinets, on an adjoining wall or onto an overhead cable tray raceway system. If a raised floor is present, this space can be used to convey the branch circuits to the required location. d. Convenience receptacles should be placed along perimeter walls. 3. Power Distribution in the TR space a. Provide a dedicated electrical panel for the networking equipment located in the IDF or MDF. This panel is not intended for non-networking equipment (lights, fans, HVAC, convenience outlets). 4. Lighting Requirements in TR Spaces a. Lighting should be placed minimum 8'-0" AFF b. Lighting fixtures should be arranged so that light paths are directed to the front and rear of the racks and cabinets. c. Lighting should be arranged so that light paths are directed towards major wall fields and wall mounted active networking equipment d. Lighting should be allocated for 50 LUX (500 Foot candles) measured at 3'-0" AFF. 5. Telecommunication Cable Pathways a. 4" conduit sleeves shall be required for MDF and IDF rooms. Quantity is to be determined by the cabling requirements. PLUMBING AND FIRE PROTECTION DESIGN COMPONENTS A. Plumbing October 17,2008 STANDARD OPERATING PROCEDURE Page 9

1. Avoid having any plumbing pipes route through telecommunications spaces. 2. Existing plumbing pipes should be removed and reinstalled to avoid telecommunications spaces. B. Fire Protection 1. Housekeeping a. Materials, solvents and trash should not be stored within IDF and MDF rooms. b. Fire retardant paint should be used on all plywood surfaces and cut edges. 2. Fire Stop Solutions C. Detection a. All solutions shall return the original fire rated integrity to the penetrated architectural structure or assembly. b. All fire stop solutions must be tested and classified with ASTM E814 (UL 1479). c. Mechanical firestop systems that are 100% protected whether empty or full should be utilized. d. Mechanical firestop systems should be re-enterable. e. Detailed documentation of all fires top solutions used should be documented and turned over to the Client as part of close out procedures. 1. Smoke DeteCtors 2. Heat Detectors D. Suppression 1. Dry-pipe Double Interlock a. Whenever possible avoid routing piping through any telecommunication space. If piping must be routed within the space, drip pans and leak detection systems should be used. Check valves should not be located within the IDF and MDF b. spaces. Sprinkler heads should be oriented logically to effectively extinguish potential fire hazards. c. Sprinkler heads should be installed with cages to protect the fuse pin trigger device against discharge by accidental contact. BONDING, GROUNDING AND EARTHING October 17,2008 STANDARD OPERATING PROCEDURE Page 10

A. Bonding and Grounding 1. Requirements a. All racks, cabinets and cable trays shall be bonded to an approved ground. b. Cold water pipes are not an acceptable ground. 2. Telecommunications Main Grounding Busbar a. The TMGB is a copper bar that is intended to provide a grounding "backbone" used for bonding the telecommunication equipment through out the building. b. A TMGB should be present in each building where low voltage telecommunications cable plant and associated active networking equipment is being utilized. Furnished and installed by the telecommunications contractor. c. The TMGB shall be bonded to the electrical service at the electrical service entrance facility, to building steel, to a local electrical panel and all TGBs by the electrical contractor. d. Size all bonding conductors in accordance with the National Electrical Code. 3. Telecommunications Grounding Busbar a. The TGB is a copper bar that is located in the immediate vicinity of telecommunications equipment that is intended to provide a ground from the TMGB. Furnished and installed by the telecommunications contractor. b. The TGB should be bonded to the TMGB, to a local electrical panel ground, and to building steel by the electrical contractor. c. Each IDF and MDF will have at least one Telecommunications Grounding Busbar (TGB). d. All racks, cabinets, metallic cable trays should be bonded to the TGB by the telecommunications contractor. e. Size all bonding conductors in accordance with the National Electrical Code. October 17, 2:108 STANDARD OPERATING PROCEDURE Page 11