SPECIFICATIONS FOR THE INSTALLATION OF REDUCED PRESSURE BACKFLOW PREVENTERS AND CONCRETE VAULTS FOR METERS 4 AND LARGER

Similar documents
SECTION CROSS CONNECTION CONTROL AND BACKFLOW PREVENTION

The exterior skin of the enclosure shall be manufactured from thick H32 aluminum which has been powder coated with polyester powder.

University of Central Florida Main Campus. Domestic Water. Service and Meter Installations Requirements. Issued January 26 th, 2017.

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section AUTOMATIC CONTROL VALVE INSULATED ENCLOSURE (HOT BOX)

Rockwood Water People s Utility District Cross Connection Implementation and Regulations

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

City of Port Moody. Water Meter Specifications

SECTION HYDRONIC PIPING

SECTION HYDRONIC PIPING

ASSE International Product (Seal) Listing Program. ASSE Outdoor Enclosures for Fluid Conveying Components

SECTION HYDRONIC PIPING

Design and Construction Standards SECTION HYDRONIC PIPING

Diffused Aeration Piping Equipment

RULES AND REGULATIONS FOR WATER AND WASTEWATER SERVICE APPENDIX G BACKFLOW PREVENTION AND CROSS CONNECTION CONTROL (BPCCC) PROGRAM

DUKE UNIVERSITY CONSTRUCTION & DESIGN STANDARDS

SECTION PLUMBING SPECIALTIES

SAFETY-GUARD BSS01/BSS02 SAMPLE STATION (SITE SPECIFIC BACTERIOLOGICAL SAMPLING POINT)

HOT, CHILLED, AND CONDENSING WATER PIPING SPECIALTIES (HVAC)

SECTION ALUMINUM GATES

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

September 6, 2016 Page 1 of 5

SECTION ENTRANCE FLOOR GRILLES STAINLESS STEEL GRATING

WATER METER SPECIFICATIONS

SERVICE LINES, METERS AND APPURTENANCES

ARRANGE FOR INSPECTION FORTY-EIGHT HOURS IN ADVANCE

ADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities

SECTION PUBLIC WATER SERVICE CONNECTIONS

CHINO VALLEY FIRE DISTRICT FIRE PROTECTION STANDARD

SECTION SLUICE GATES

SECTION ENTRANCE FLOOR GRILLES STAINLESS STEEL GRATING

SECTION BASIC FIRE SUPPRESSION MATERIALS AND METHODS. A. Section includes pipe, fittings, valves, and connections for sprinkler systems.

BACKFLOW PREVENTION ASSEMBLY INSTALLATION STANDARDS

SECTION ROOF ACCESSORIES

Combination Air Valves - Stainless Steel/ Sanitary Sewer/ For 2 Thru 12 Mains

SECTION FACILITY POTABLE WATER DISTIBUTION

KENT COUNTY WATER AUTHORITY. ERRATUM to Rules and Regulations of the Kent County Water Authority

Design and Construction Standards SECTION POTABLE WATER SYSTEMS

A. This Section includes the following sanitary drainage piping specialties:

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

A. Codes and Standards that are Standard at the University: 1. AGA Compliance: LC 1-91 Interior Fuel Gas Piping Systems

SECTION WASTEWATER FORCE MAINS

SECTION [ ] COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SPECIFICATIONS - DETAILED PROVISIONS Section Stainless Steel Sluice Gates C O N T E N T S

ARRANGE FOR INSPECTION FORTY-EIGHT HOURS IN ADVANCE

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers.

ARRANGE FOR INSPECTION FORTY-EIGHT HOURS IN ADVANCE

CITY OF FARGO SPECIFICATIONS SIGNING

PIPING SPECIALTIES (PLUMBING) A. American Society for Testing and Materials (ASTM):

SECTION PLUMBING PIPING

Cast Iron Sluice Gates Rugged Dependability in Demanding Applications

(Contaminant) Backsiphonage or Backpressure Backsiphonage or Backpressure

ASTM C857 A -16 AASHTO H -20 (for vaults beneath roadways) ASTM C857 A-8 (for vaults beneath incidental light truck traffic)

Student Services & Classroom Addition. A. This Section includes the following domestic water piping specialties:

130 CROSS CONNECTION CONTROL

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION DOMESTIC WATER PIPING SYSTEM

F-SERIES: F SPECIFICATIONS Four-Fold Door Systems

SECTION COOLING TOWER

Effective Date: Revision #: 1. Section I: Castings and Aluminum Covers. Valve Boxes. Service Clean-out Box and Lid

SECTIONAL OVERHEAD DOORS SECTION SECTIONAL OVERHEAD DOORS PART 1 GENERAL

OVERSHOT GATE TECHNICAL DATA SHEET

C. Samples: For each door face material, at least 3 by 5 inches (75 by 125 mm) in size, in specified finish.

NC State University Design and Construction Guidelines Division 33 Utilities

A. Section includes busway and fittings including plug-in units.

PHYSICAL BARRIERS MACHINE GUARDS ROBOTIC WORK CELLS PERIMETER OR AREAS GUARDS PHYSICAL BARRIERS

F-SERIES: FF XT SPECIFICATIONS Exterior Swinging Four-Fold Door Systems

SECTION SECTIONAL OVERHEAD DOORS

DIVISION 22 PLUMBING SECTION INTERIOR SANITARY WASTE AND VENT PIPING SYSTEM

University of Delaware

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION CHAIN LINK FENCING

10.1 APPLICATION 1 A. HOT PIPING 1 B. ANTI SWEAT PIPING 1 C. COLD PIPING FINISHES 2

SECTION CROSS CONNECTION CONTROL TABLE OF CONTENTS

MARLIN WINDOWS, INC 3500 HC SERIES 3 3 8" SLIDING WINDOW PAGE 1

Bid Opportunity PLUMBING SYSTEMS Section Installation of Boiler Heating Systems Page 1 of 7 Centennial Pool, 90 Sinclair

SECTION The specification section is organized by placing information in three standard parts:

CITY OF FARGO SPECIFICATIONS SIGNING

SECTION PLUMBING FIXTURES

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

SECTION SANITARY WASTE INTERCEPTORS

SECTION SECTIONAL OVERHEAD DOORS 522 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS. Display hidden notes to specifier. (Don't know how?

SECTION ACCORDION FOLDING PARTITIONS

SECTION SECTIONAL OVERHEAD DOORS

SECTION VALVES. This section includes materials, testing, and installation of manually operated valves.

SECTION PLUMBING SPECIALTIES

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION 8 SEPARATION OF LINES

SECTION NATURAL GAS DISTRIBUTION

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

A. ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials

SECTION METAL ATHLETIC LOCKERS

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION PAGE 1 SECTION SUPPORTING DEVICES

SECTION WALL AND DOOR PROTECTION

MODEL 16ASX T/S - SPECIFICATION

PRODUCT EVALUATION Effective Date: June 1, 2013 GDR-40

BASIC MATERIALS & METHODS

SECTION RESIDENTIAL OVERHEAD DOORS SIGNATURE COLLECTION WOOD GARAGE DOORS

D-10 OUTLINE SPECIFICATION FOR PRE FAB Undergrd Piping System

INSTALLATION GUIDE. Model #PP2 Pumpout Port Kit For Use with Grease Interceptors Models GB-50, GB-75 and GB-250. Contents

SECTION MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

Transcription:

SPECIFICATIONS FOR THE INSTALLATION OF REDUCED PRESSURE BACKFLOW PREVENTERS AND CONCRETE VAULTS FOR METERS 4 AND LARGER Updated January 2018

RP-2 Installation Specifications 1. In W.H.U.D s service area the Reduced Pressure Backflow Preventer is the only Approved Device for new installations. (All Reduced Pressure Principal devices approved by the State of Tennessee s Division of Water Supply are acceptable. However no vertical installation is permitted.) 2. Assemblies shall be horizontally installed with 18-inch minimum clearance between relief valve discharge opening and concrete pad. Maximum height above the floor surface shall not exceed 60 inches. 3. The device shall be installed just down stream of the meter before any branch connections. 4. All devices shall be installed in accordance with manufactures instructions and shall possess appropriate water tight test adapters and caps for testing the device. 5. Y-strainers to be installed on all devices that do not have an approved strainer installed at the meter. Y-strainers shall be plugged with no valves allowed for flushing 6. Three-quarter-inch thru Two-inch devices shall be of bronze construction and installed with bronze, full port, ¼ turn, resilient seat ball valves immediately upstream and downstream. 7. Two and a half-inch thru ten-inch devices are to be installed with epoxy coated, resilient seat, wedge type, OS&Y valves. 8. Two and a half-inch thru ten-inch, devices shall be epoxy coated except those made of stainless steel. 9. The entire device shall be easily accessible for testing and repair. 10. Devices shall be located in an area free from submergence or flood potential. 11. Duplicate units, installed in parallel, shall be provided in cases where the water supply cannot be interrupted for routine testing and maintenance. 12. A WHUD approved protective barrier must be installed to prevent damage from traffic or equipment if deemed necessary by WHUD. 13. The concrete pad shall be constructed above final grade to help prevent eroded soil from obstructing the enclosure drain. 14. Installations shall be provided with a pre-fabricated Heated Enclosure with the following specifications: The enclosure shall be manufactured by Safe-T-Cover or an approved equal. The enclosure shall be constructed of 5052-H32 marine grade aluminum (.050/18 gauge), mill finish, ASTM B209 with polyisocyanurate insulation in the walls having a minimum thermal resistance of (10.0 R value).the enclosure shall be certified by ASSE to Class I of ASSE Standard #1060.The complete equipment assembly, including valve stems and hand wheels, shall be inside the enclosure. Access panels shall be completely removable and shall be provided with built-in locks keyed alike with two keys furnished to WHUD. The drain panel(s) shall have a stainless steel hinge and a stainless steel spring as a positive means of closure to prevent activation by wind. The drain panel shall be fabricated of the same materials as the enclosure and integrated into the access panel(s). All mounting hardware and threaded fasteners shall be furnished and shall be 300 series

RP-3 stainless steel or T6 aluminum. All masonry fasteners shall be metal wedge anchors. The enclosure shall be assembled and mounted to concrete pad in such a way that it will remain locked and secured to pad even if outside screws are removed. Enclosure shall be mounted on a concrete pad a minimum of 14 longer and wider than the inside dimensions of the enclosure. Heating Equipment (ASSE 1060 Class I-Required.) A. Heating equipment shall be furnished and sized by the manufacturer of the enclosure to maintain an interior temperature of +40 0 F with a worst case outside temperature of -30 0 F. B. The heater shall have two electrical resistance elements completely enclosed within a solid aluminum cast platen base. C. The platen heater shall be designed for attachment to the concrete base pad with mounting hardware provided. D. The platen heater shall be suitable for installation underneath a reduced pressure zone backflow prevention assembly and designed to sustain occasional water discharge without damage to or impeding the performance of the heater. E. The platen heater shall be provided with a thermostat adjustable from +40 F to +100 F. The thermostat, all conduits and wiring fittings provided shall be suitable for wet environment installation. F. On devices 2 inches or smaller heat tape may be used as an approved heat source if it is installed to the manufacturer s instructions for wet environments. Irrigation Systems Notes All previously mentioned specifications apply 1. If supplied by a domestic water tap, the connection for an irrigation system must be as close to the existing meter as possible with the protective device installed as close to the point of connection as possible. 2. A heated enclosure is not required on irrigation devices as long as the following requirements are met: (a) The irrigation system has its own separate water tap and can be winterized or: (b) The device is installed with unions to allow for winter removal.

H 2 O White House Utility District WATER & WASTEWATER