Ductile Iron Piles Corrosion Resistance

Similar documents
Iron is found in an oxidized state and is mined from the ground as an iron ore.

Concrete Pipe in Acid Sulfate Soil Conditions

Corrosion Control and Cathodic Protection Data Sheet

[ W H I T E P A P E R. Corrosion of Helical Anchors In Soil. T h o m a s B r a g g Ph.D. Director, Special Projects Pacific Housing Systems.

Corrosion Investigation for Contra Costa Community College District - Brentwood Campus

SACRIFICIAL ANODE CATHODIC PROTECTION OF LOW CARBON STEEL IN SEA WATER

CORROSION AND CORROSION CONTROL An Introduction to Corrosion Science and Engineering

SAS Micropile Manual. Basic dimensioning and design recommendations. Table of Content:

Corrosion is defined in different ways, but the usual interpretation of the term is an attack on a metallic material by reaction with its

FIGURE 1. FHWA Abrasion Levels. Consideration of velocities should be based on a frequent storm event, such as a 2-year storm. Water-Side Durability

DUCTILE IRON PILES ARE HIGHLY EFFECTIVE, FAST AND VERSATILE MODULAR DRIVEN MICROPILE SYSTEMS

1. CORROSION OF REINFORCEMENT

Sika Galvashield CC Embedded Galvanic Anodes for Corrosion Control in Contaminated but Sound Concrete

Distribution Review. Corrosion Control. Corrosion Control Vocabulary. American Water College 1. Corrosion Control Training Objectives

Estimation of Corrosion Protection Condition on Buried Steel Pipeline under Cathodic Protection with IR-free Probe

RAPID MACROCELL TESTS OF 2205 AND XM-28 REINFORCING BARS

2. Wet Corrosion: Characteristics, Prevention and Corrosion Rate

Performance Guideline for Buried Steel Structures

Re-alkalisation technology applied to corrosion damaged concrete

INNOVATIVE DEEP FOUNDATION SUPPORT USING DUCTILE IRON PILES

Bridge Preservation Corrosion Mitigation Option in Concrete Repair Systems

Methods of Corrosion Control. Corrosion Control or Corrosion Management?

ABSTRACT EXECUTIVE SUMMARY

STANDARD SPECIFICATIONS SECTION JACKED CASING

Laboratory Experiments in Corrosion Engineering II

Corrosion Control using Cathodic Protection for Prefabricated Buried Steel Pump Stations1

Design Aspects of Cathodic Protection

Galvanic Anodes Period 3 Intermediate Corrosion Course 2017

CORROSION & ITS CONTROL -Content. Introduction Classification Galvanic series Factors affecting Protection methods Summary

RAPID MACROCELL TESTS OF ENDURAMET 2304 STAINLESS STEEL BARS

Application of Computational Modeling to Predict the Effectiveness of CP on a PCCP Transmission Pipeline

a: potential difference before direct current is applied b: potential difference after the application of current

INSTITUTE OF INTEGRATED ELECTRICAL ENGINEERS OF THE PHILIPPINES, INC. (IIEE-ERCSA) First IIEE Accredited Foreign Chapter (Charter

Effects of Soil Properties to Corrosion of Underground Pipelines: A Review

Chapter 16 Corrosion and Degradation of Materials

CORROSION CONTROL OF ABOVE GROUND STORAGE TANK BOTTOM STEEL PLATES USING ALUMINUM MESH ANODE WITH NEWLY DEVELOPED BACKFILL

SANITARY SEWERS. B. Construct or relocate building sanitary sewer services, stubs, and connections.

Field Performance Evaluation of Polymer Coated CSP Structures in

DRAFT EVALUATION OF CORROSION RESISTANCE OF MICROALLOYED REINFORCING STEEL

EFFECT OF CHLORIDE CONCENTRATION IN SOIL ON REINFORCEMENT CORROSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

ONLINE MONITORING OF UNDERCOATING CORROSIONS UTILIZING COUPLED MULTIELECTRODE SENSORS. Xiaodong Sun Corr Instruments, LLC San Antonio TX, USA ABSTRACT

Foundation Innovations Ensure Successful Bridge Replacement

REAL-TIME MONITORING OF CORROSION IN SOIL UTILIZING COUPLED MULTIELECTRODE ARRAY SENSORS. Xiaodong Sun Corr Instruments, LLC San Antonio TX, USA

Contents. iii Copyright 2014 American Water Works Association. All Rights Reserved. AWWA Manual M27

CORROSION TYPES CHAPTER 4 6) FILIFORM CORROSION LECTURER SAHEB M. MAHDI

ENGINEERING SPECIFICATIONS

White Paper. Galvanized Pipe Failures in Dry Pipe Sprinkler Systems (April 2016) By Lucas Kirn, PE

The Leader in Underwater Piling Repair Technology

CO forms CO 2. forms. (a) The coke reacts with the oxygen in the air to form carbon dioxide. C + O 2

HURST CORPORATION STAINLESS STEEL

Metropolitan Water Reclamation District of Greater Chicago 10/19/ Mark Joyce Senior Mechanical Engineer Engineering Department

RAPID MACROCELL TESTS OF ASTM A775, A615, and A1035 REINFORCING BARS

DURABILITY of CONCRETE STRUCTURES

Mr. Ron Zak NJDEP-Bureau of Nuclear Engineering 33 Arctic Parkway PO Box 415 Trenton, New Jersey 08625

Corrosion. Cause of Corrosion: Electrochemical Mechanism of Corrosion (Rusting of Iron)

OFFSHORE CATHODIC PROTECTION 101: WHAT IS IT AND HOW DOES IT WORK? Dick Baxter & Jim Britton

6.4.1 Concrete mix design. The four concrete mixes were designed using the absolute volume method as shown below:

Prevention Strategies Design and Coatings

CTB3365x Introduction to Water Treatment

AREMA COMMITTEE 8. Letter Ballot Number

WHAT IS THE ACTUAL COST OF YOUR COMMERCIAL WATER HEATER? LOOKING BEYOND EFFICIENCY INCREASING ROI THROUGH WATER HEATER MATERIAL SELECTION

Reinforcing Wire in Solutions with Chloride and Cement

Review of Cathodic Protection Systems for Concrete Structures in Australia Lessons Learnt and Future Directions

MMO Titanium Anode. Anode Shapes MMO anodes are available in different shapes like Rod, Tubular, Plate, Disc and Mesh anodes.

st. johns river OWER ARK A Joint Venture of Prepared by: John E. Reid, JEA Presented by: Kent Zammit, EPRI

Corrosion Resistance of Alternative Reinforcing Bars: An Accelerated Test

FOR REVIEW & COMMENT ONLY; NOT FOR DISTRIBUTION. Cathodic Protection of Aboveground Petroleum Storage Tanks

Cathodic Protection of Aboveground Petroleum Storage Tanks API RECOMMENDED PRACTICE 651 FOURTH EDITION, SEPTEMBER 2014

Corrosion Mitigation Systems for Concrete Structures

Introduction to Cathodic Protection

Prediction of Chloride Permeability of High Performance Concrete

EXECUTIVE SUMMARY POST-TENSIONING TENDON PROTECTION STRATEGIES FOR PRECAST ELEMENTS

Corrosion Mechanisms, Monitoring, and Service Life Enhancement of Reinforced Concrete Structures

Properties of Concrete. Properties of Concrete 1

Cathodic protection of harbour installations

The Effect of Calcium Nitrite on the Electrochemical Characterization of 3003 Aluminum Alloys in Sea Water. H.Mogawer and R.Brown

Galvanic corrosion evaluation of 6061 aluminum coupled to CVD coated stainless steel Elizabeth Sikora and Barbara Shaw 6/9/2016

Pipe Coating Failures. Gregory C Hardig, CPR Corrosion Protection Resources LLC

Corrosion: Occurrence and Implications

Corrosion Resistance of Aluminum

1. Introduction. Figure 1: Open Recirculation Cooling Water Tower (image courtesy of Solenis) Page 3

IPC TECHNICAL PAPER SERIES NUMBER 74 LOCALIZED CORROSION OF STAINLESS STEELS IN PAPER MACHINE WHITE WATER DAVID F. BOWERS FEBRUARY, 1979

Zn Ni alloy A probable replacement to Cadmium coating R Mani Sravani, Meenu Srivastava Surface Engineering Division, CSIR NAL, Bangalore

Protect Your Pipe: Invest in the Next 100 Years. Jeff Blakely Sr. Sales Engineer May 3, 2017

This new anode concept patented and developed by John Turner and Thomas Meyer provides a rolled anode without a welded joint or soldered slotted

Corrosion and Protection of Metal in the Seawater Desalination

CONSTRUCTION SPECIFICATION FOR CEMENT MORTAR LINING OF WATERMAINS

RAPID MACROCELL TESTS OF LDX 2101 STAINLESS STEEL BARS

CORROSION/DEGRADATION OF SOIL REINFORCEMENTS FOR MECHANICALLY STABILIZED EARTH WALLS AND REINFORCED SOIL SLOPES

Investigation of Fecraly Coating on Corrosion Behaviour of Mild Steel

Galvanic Corrosion Prevention Guide for Water Cooling Systems

TITLE: Surface Decontamination of Iron Compounds (Iron (II) Chloride (FeCl 2 )) by DeconGel TM

Termarust Technologies HRCSA Corrosion Mitigation System.

Hybrid Electrochemical Treatment Applied to Corrosion Damaged Concrete Structures

Impressed Current Cathodic Protection- An up to date review. Paul Chess, CPI FORCE Technology, Denmark FEREB

INITIAL EVALUATION OF CORROSION PERFORMANCE AND ALKALI REACTIVITY OF CERAMIC-COATED REINFORCING BARS

ONLINE MONITORING OF CORROSION UNDER CATHODIC PROTECTION CONDITIONS UTILIZING COUPLED MULTIELECTRODE SENSORS

Significance and influence of the ambient temperature as a rate factor of steel reinforcement corrosion

Transcription:

Ductile Iron Piles Corrosion Resistance Ductile Iron Piles are often a preferred, cost-effective foundation support solution for a variety of projects particularly in urban settings. Similar to other types of deep foundation systems (i.e. steel, concrete, timber piles, etc.) that are driven or drilled into the ground, the electro-chemical reaction between the soil and the foundation system needs to be considered in the design for long-term performance. These complicated reactions which can lead to corrosion of metals or degradation of concrete are often more pronounced in urban settings with impacted fill soils or in organic soils. This technical brief provides information pertaining to research on the corrosion potential of Ductile Iron Piles, comparisons with steel piles and design approaches to address corrosion of the piles. Soil Corrosion Potential Corrosion potential of soil is highly-variable and depends on many different conditions. According to the FHWA (2005), the following is a list of variables which indicate a high corrosion potential and form the basis of the ground aggressivity: Low resistivity of ground; High concentration of chlorides or sulfides in ground or groundwater; Too low or too high hydrogen potential (ph) of ground or groundwater; High saturation conditions; and Stray currents. Corrosion potential can be evaluated by performing a number of standardized tests as shown in Table 1. The criteria to classify the corrosion potential of the soil is also included. Table 1: Criteria for Assessing Ground Corrosion Potential (FHWA, 2005) Test Units Strong Corrosion Potential / Aggressive AASHTO Test Method ph - < 5, > 10 T 289 Resistivity Ohm-cm < 3,000 T 288 Sulfates ppm > 200 T 290 Chlorides Ppm > 100 T 291 Ground conditions are considered to have a strong corrosion potential if any of these limits are exceeded.

Testing A simulated corrosive environment was created in the lab at Vienna University of Technology to perform a comparison of corrosion resistance between Ductile Iron Piles and steel piles (Linhardt and Ball, 2014). Similar dimensioned samples of Ductile Iron Pile, and European S235 steel (ASTM A284 equivalent) and European S355 (ASTM A633, A656 equivalent) were selected (Figure 1). The samples were placed into a controlled environment consisting of compact sand in the lower portion and gravel in the upper portion as shown in Figures 2 and 3. The container was filled with an electrolyte (deionized water and dissolved salts). The electrolyte was routinely flushed with aerated water, but only in the upper portion to increase oxygen exposure. The compact sand environment models a stagnant, low oxygen environment while the gravel (upper) environment models a high-oxygen condition with routine flushes of the electrolyte. As a result of the test setup, the aerated (upper) section models an oxygen reduction reaction while the non-aerated (lower) section models anodic metal dissolution. Figure 1: Picture of Samples prior to Testing The test setup included instrumentation including shunt resistors, a reference electrode and a data acquisition system to record the corrosion current between the sections and the corrosion potential. Tests were performed continually over the course of 441 days to evaluate the effects on the samples. Figure 4 shows a picture of the prepared samples prior to introduction to the test device: Ductile Iron Pile, S235 steel, S355 steel (left to right). Figure 5 shows a picture of the samples following removal from the test environment. The testing found that the high-temperature casting annealing skin created as a part of the Ductile Iron Pile manufacturing process covers and adheres to the pile surface and provides superior protection to the metal beneath. The results show that this casting skin is dense and well-adhering to the piling. The integrity of the skin as well as its protective nature is evidenced by the lack of pebbles adhering to the pile surface in Figure 5. In the upper oxygen-rich portion of the test setup, the number of locations forming corrosion products in crevices between Figure 2: Schematic of Test Setup Figure 3: Picture of Lab Test Setup

the pile surface and the pebble were few. The behavior in the lower anerobic portion of the setup was dictated by anodic reaction created by the electrical contact with the cathodic upper portion. This anodic reaction caused metal dissolution at localized areas thereby reducing the effectiveness of the corrosion passivation. However, this behavior resulted in only shallow, localized pitting of the skin. In contrast, the steel samples behave as an actively corroding metal. The rolling skin from the manufacturing process offered far less protection than the Ductile Iron casting skin, resulting in a more wide-spread pattern of corrosion evidenced by the nearly complete coverage of pebbles to corrosion locations (Figure 5). The development of this corrosion layer does have a benefit by acting to reduce the access to oxygen and reduce continued corrosion with time only after substantial corrosion has occurred. The presence of the electrical current created by coupling with the upper section intensified the corrosion and the dissolution of the rolling skin in the lower portion. Figure 4: Picture of Samples after Testing (pre-cleaning) Figure 5: Picture of Samples after Testing (post-cleaning) In summary, the Ductile Iron Pile exhibits superior corrosion protection. The ductile pile material performed better than steel in the simulated corrosive environment with only localized areas of corrosion product and shallow pitting a vast difference compared to the overall performance of the steel sections. Design Approaches The selection of the corrosion potential for foundation systems depend on many variables including aggressiveness of ground conditions, design service life, structure type, loading conditions, and consequences of failure. These factors are considered in the design of the Ductile Iron Piles. Corrosion implications for Ductile Iron Piles are handled through a few different approaches involving oversizing to capture a sacrificial (corroded) layer and / or encapsulation.

Firstly, the interior of Ductile Iron Piles is filled with grout to minimize exposure of the pile interior to any corrosive environment. Further steps depend on whether the pile develops capacity using either end-bearing or friction. All friction Ductile Iron Piles are installed by pumping sand-cement grout to fill through the interior of the pile. The grout is then pumped out the pile bottom to fill an exterior annular space between the pile and soil created by driving the patented oversized conical grout cap. The combination of the interior and exterior grout filling the annular space completely encapsulates the pile material with multiple inches of concrete. This encapsulation process protects the piling material from exposure to corrosive conditions. End-bearing piles only use interior grout, leaving the exterior pile face exposed to soil and groundwater. The construction industry employs a variety of tools to protect exposed materials from corrosion. These include epoxy-coating, corrosion-inhibiting compounds, sheathing and other approaches. Another common approach is to incorporate a sacrificial layer or reduction of material thickness due to corrosion losses. Despite the improved protection to corrosion offered by the Ductile Iron Piles, this common approach models the pile as a steel element. Corrosion loss rates are published in various standards and literature from different sources. FHWA references values for corrosion loss of 0.02 mm per year (1 mm for 50 year service life) for steel piles buried in a sea bed condition (FHWA, 1996). European ÖNORM standards for Ductile Iron Piles reference corrosion losses ranging from 0.6 mm up to 1.75 mm per side for a 50 year service life depending on the corrosion potential of the soil (Austrian Standards Institute, 2012). Ductile Iron Pile design loss rates of 1.5 mm per side ( 1 / 32 -inch) are often incorporated for a mild corrosion rate. A value of 3 mm per side ( 1 / 16 -inch) applies to a moderate rate. Highly-aggressive environments are often addressed using a grout encapsulation approach. Summary Ductile Iron Piles have been used in European foundation construction for more than two decades and are increasingly used in the United States and Canada as a cost-effective foundation system with rapid installation rates. Independent research shows that the Ductile Iron Piles provide superior protection against corrosion and performs better in side-by-side comparisons with various steel products. The favorable corrosion characteristics are largely attributed to the casting skin that develops from the manufacturing process compared with the rolling skin in steel. Despite the high resistance to corrosion, Ductile Iron Pile design considers the effects of corrosion by including a percentage of sacrificial material (material loss) in the design capacity and / or by grouting (encapsulating) a portion or all of the pile in grout.

References Austrian Standards Institute. (2012). ÖNORM B 2567 - Piles of Ductile Iron Dimensions, installation and quality assurance. Edition 2012-12-15. Wien, Austria. Federal Highway Administration (FHWA) (1996). NHI Courses No. 13221 and 13222: Design and Construction of Driven Pile Foundations Workshop Manual Volume 1. Publication No. FHWA-HI-97-013. Washington, D.C. p. Federal Highway Administration (FHWA) (2005). NHI Course No. 132078: Micropile Design and Construction - Reference Manual. Publication No. FHWA-NHI-05-039. Washington, D.C. p. 5-45 thru 5-51. Linhardt P. and Ball G. (2014). Report: Corrosion Testing of Piles Made of Steel and Ductile Cast Iron. Vienna University of Technology Institute for Chemical Technologies and Analytics. Vienna, Austria. January 30, 2014 (English translation).