MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems

Similar documents
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

KNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly

PERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO)

AAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight

TEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

TEST REPORT. Rendered to: COLLINS LIMITED, LLC. For:

PERFORMANCE TEST REPORT. Rendered to: SIMTEK FENCE. TYPE: SimTek Privacy Fence System

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America LLC. SERIES/MODEL: FCM B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight

MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall

TEST REPORT. Report No.: C Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip

PERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC.

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight

TEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

Structural Performance Certification Authorization Report

TEST REPORT. Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip

TEST REPORT. Rendered to: ENDURIS EXTRUSIONS INC. For: 6' high by 8' wide Dog Ear Picket Shadow Box Privacy Fence Systems

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia

Structural Performance Certification Authorization Report

TEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS:

Structural Performance Certification Authorization Report

OSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight

TEST REPORT. Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California. PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall)

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: Solutions Aluminum Guardrail System with Glass Balustrades

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Rendered to: KEYLINK FENCING & RAILING, INC. For: PRODUCT: Lancaster Series. TYPE: Aluminum Level Guardrail System

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina

Architectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post

TEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio

TEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series

TEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia

PERFORMANCE EVALUATION TEST REPORT. Rendered to: CBT SUPPLY, INC. / D.B.A. SMARTDESKS

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

PERFORMANCE TEST REPORT. Rendered to: DOW CORNING CORPORATION. PRODUCTS: Dow Corning 790 Silicone

ASTM D 4541 ADHESION STRENGTH PERFORMANCE TEST REPORT. Rendered to: BAUTEX SYSTEMS. PRODUCT: AMB 20-WN Liquid Applied Membrane

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

TEST REPORT AAMA 501.5

INTERNATIONAL WINDOW TEST REPORT

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window

MILLENNIUM METALS, INC TEST REPORT

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

Structural Performance Certification Authorization Report

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: Fabri Trak System. TYPE: Upholstered Panel

TEST REPORT. Rendered to: AFCO INDUSTRIES, INC. For: PRODUCT: Redi-Rail. TYPE: Aluminum Level Guardrail System

TEST REPORT. Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois. AD Skylight without Guard

TEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1" FABRI TACK

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NOVAWALL SYSTEMS, INC. SERIES/MODEL: 3/4" Weltless. TYPE: Stretch Fabric Wall System

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star

Dennis Fassnacht Jr :59:35-04'00'

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB. TYPE: Acoustical Wall Panel

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles

PERFORMANCE TEST REPORT. Rendered to: HILTI CORPORATION. PRODUCT: Extreme Weather Window & Door Insulating Foam Sealant

CBUCK Engineering. Evaluation Report Fixed Blades Wall Louver MPF G

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4" Fabri Trak

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to FABRITRAK SYSTEMS, INC. SERIES/MODEL: Fabri Flex Fabric with 6#

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: PAC INTERNATIONAL, LLC

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to SENECA RADIANT TECHNOLOGIES

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY. Series/Model: Whisper Mat CS

TEST REPORT. Report No.: G Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1

Transcription:

This report contains in its entirety: Cover Page: 1 page Report Body: 15 pages Sketches: 7 pages Drawing: 1 page MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Rendered to: BRICK-IT SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems Report No.: Test Dates: 04/22/08 Through: 04/24/08 Report Date: 07/02/08 Expiration Date: 04/24/18 Miami-Dade County Notification No.: ATI 08028 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Rendered to: BRICK-IT 35 Carlough Road, Unit 3 Bohemia, New York 11716 Report No.: Test Dates: 04/22/08 Through: 04/24/08 Report Date: 07/02/08 Expiration Date: 04/24/18 Miami-Dade County Notification No.: ATI 08028 Project Summary: Architectural Testing, Inc. was contracted by Brick-It to perform testing per Florida Building Code, Test Protocols for High Velocity Hurricane Zone, Protocols TAS 201-94, TAS 202-94, and TAS 203-94 on three Series/Model Brick Veneer Wall Panel Systems (Densglas) and three Brick Veneer Wall Panel Systems (OSB). The samples tested met the performance requirements set forth in the protocols for a ±75.0 psf Design Pressure rating. Test specimen description and results are reported herein. The samples were provided by the client. Test Procedures: The test specimens were evaluated in accordance with the following: TAS 201-94, Impact Test Procedures. TAS 202-94, Criteria for Testing Impact and Non Impact Resistant Building Envelope Components Using Uniform Static Air Pressure Loading. TAS 203-94, Criteria for Testing Products Subject to Cyclic Wind Pressure Loading. Drawing Reference: The test specimen drawings have been reviewed and verified by Architectural Testing and are representative of the samples tested. 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

Page 2 of 15 Test Specimen Description: Test Specimen #1 - #3: Series/Model: Brick Veneer Panel System (Densglas) Test Wall Description: The unit was installed onto an 8' 0-1/4" wide by 2' 9" tall Spruce-Pine-Fir wood wall, with 2x4 studs located 16" on center. Densglas sheathing was installed over the studs and secured with 1-5/8" drywall screws, located 2" from all corners and spaced 10" on center at each stud and around the perimeter. Test Specimen #4 - #6: Series/Model: Brick Veneer Panel System (OSB) Test Wall Description: The unit was installed onto an 8' 0-1/4" wide by 2' 9" tall Spruce-Pine-Fir wood wall, with 2x4 studs located 16" on center. OSB sheathing was installed over the studs and secured with 1-1/2" brad nails, located 2" from all corners and spaced 10" on center at each stud and around the perimeter. Product Type: Wall Panel System The following details apply to all test specimens. Overall Size: 8' 0-1/4" wide by 2' 8-3/4" high Individual Panel Size (4): 8' 0-1/4" wide by 8-3/16" high Finish: All veneer bricks were red. Test Specimen Description: A vapor barrier wrap was installed over the wall and secured with 3/8" crowned staples. Four 18 gauge (0.050") roll-formed steel interlocking panels were installed with 1" crowned staples located on each course around the perimeter and spaced 16" on center at each stud. Each panel was three brick courses high, resulting in 12 brick courses for the entire test specimen. The 7-1/2" wide by 2-1/4" high by 1/2" thick bricks were glued to the steel panels. All brick joints were then filled with mortar. A silicone sealant was used to seal the perimeter of the panel.

Page 3 of 15 Test Results: The following results have been recorded: Protocol TAS 202-94, Static Air Pressure Tests Test Unit #1 Design Pressure: ±75.0 psf Title of Test Results Air Infiltration 1.57 psf (25 mph) <0.01 cfm/ft 2 6.24 psf (50 mph) 0.22 cfm/ft 2 Indicator Readings (inch) Structural Loads #1 #2 #3 50% of Test Pressure (+56.43 psf) Maximum Deflection <0.01 0.02 <0.01 Permanent Set <0.01 <0.01 <0.01 Design Pressure (+75.24 psf) Maximum Deflection 0.01 0.04 0.01 Permanent Set <0.01 <0.01 <0.01 50% of Test Pressure (-56.43 psf) Maximum Deflection 0.01 0.06 0.01 Permanent Set <0.01 0.01 <0.01 Design Pressure (-75.24 psf) Maximum Deflection 0.01 0.09 0.01 Permanent Set <0.01 0.02 <0.01 Water Infiltration 15% Positive Design Pressure (+11.29 psf) No Penetration Test Pressure (+112.85 psf) Maximum Deflection 0.01 0.05 0.01 Permanent Set 0.01 0.01 <0.01 Test Pressure (-112.85 psf) Maximum Deflection 0.01 0.12 0.01 Permanent Set 0.01 0.03 0.01 Note: See Architectural Testing Sketch #4 for indicator locations.

Page 4 of 15 Test Results: (Continued) Protocol TAS 201-94, Impact Test Procedures Missile Weight: 9.25 lbs Muzzle Distance from Test Specimen: 17 ft. Test Unit #1 Impact #1: Missile Velocity: 49.9 fps Impact Area: Lower left corner dented steel interlock and damaged the densglas, no penetration. Impact #2: Missile Velocity: 50.0fps Impact Area: Five brick courses down at steel interlock, and in-between the wood studs at the third cavity from the left side. dented the steel interlock and damaged the densglas, no penetration. Impact #3: Missile Velocity: 49.9 fps Impact Area: Five courses up from the bottom, in-between the steel interlocks, and in-between the wood studs at the third cavity from the left side. dented the steel interlock, and damaged the densglas, no penetration. Note: Refer to Architectural Testing Sketch #1 for impact locations.

Page 5 of 15 Test Results: (Continued) Protocol TAS 201-94, Impact Test Procedures Missile Weight: 9.25 lbs Muzzle Distance from Test Specimen: 17 ft. Test Unit #2 Impact #1: Missile Velocity: 50.3 fps Impact Area: Upper right corner dented steel interlock and damaged the densglas, no penetration. Impact #2: Missile Velocity: 50.1 fps Impact Area: Five courses up from the bottom, in-between the steel interlocks, and in-between the wood studs at the third cavity from the left side. dented the steel interlock and damaged the densglas, no penetration. Impact #3: Missile Velocity: 50.4 fps Impact Area: Five brick courses down at steel interlock, in-between the wood studs at the third cavity from the left side. dented the steel interlock, and damaged the densglas, no penetration. Note: Refer to Architectural Testing Sketch #2 for impact locations.

Page 6 of 15 Test Results: (Continued) Protocol TAS 201-94, Impact Test Procedures Missile Weight: 9.25 lbs Muzzle Distance from Test Specimen: 17 ft. Test Unit #3 Impact #1: Missile Velocity: 50.3 fps Impact Area: Upper left corner dented and separated steel interlock approximately 4", densglas was damaged and separated from corner, no penetration. Impact #2: Missile Velocity: 49.8 fps Impact Area: Five courses up from the bottom, in-between the steel interlocks, and in-between the wood studs at the third cavity from the left side. dented the steel interlock and damaged the densglas, no penetration. Impact #3: Missile Velocity: 50.1 fps Impact Area: Five brick courses down at steel interlock, in-between the wood studs at the third cavity from the left side. dented the steel interlock, and damaged the densglas, no penetration. Note: Refer to Architectural Testing Sketch #3 for impact locations.

Page 7 of 15 Test Results: The following results have been recorded: Protocol TAS 201-94, Impact Test Procedures Missile Weight: 9.14 lbs Muzzle Distance from Test Specimen: 17 ft. Test Unit #4 Impact #1: Missile Velocity: 50.4 fps Impact Area: Lower left corner, three courses up from bottom at the interlock dented steel panel, no penetration. Impact #2: Missile Velocity: 50.8 fps Impact Area: Five courses up from the bottom, between the wood studs, and between the steel interlocks three cavities from the left side. dented steel panel, no penetration. Impact #3: Missile Velocity: 50.6 fps Impact Area: Five courses from top, between the wood studs, at the steel interlock, three cavities from the left side. dented steel panel, no penetration. Note: Refer to Architectural Testing Sketch #5 for impact locations.

Page 8 of 15 Test Results: (Continued) Protocol TAS 201-94, Impact Test Procedures Missile Weight: 9.14 lbs Muzzle Distance from Test Specimen: 17 ft. Test Unit #5 Impact #1: Missile Velocity: 50.9 fps Impact Area: Upper right corner, three courses from the top at the interlock dented steel panel, no penetration. Impact #2: Missile Velocity: 50.8 fps Impact Area: Five courses up from the bottom, between the wood studs, and between the steel interlocks, three cavities from the left side. dented steel panel, no penetration. Impact #3: Missile Velocity: 50.5 fps Impact Area: Five courses from top, between the wood studs, at the steel interlock, three cavities from the left side. dented steel panel, no penetration. Note: Refer to Architectural Testing Sketch #6 for impact locations.

Page 9 of 15 Test Results: (Continued) Protocol TAS 201-94, Impact Test Procedures Missile Weight: 9.14 lbs Muzzle Distance from Test Specimen: 17 ft. Test Unit #6 Impact #1: Missile Velocity: 50.5 fps Impact Area: Upper left corner, three courses from the top at the interlock dented steel panel, no penetration. Impact #2: Missile Velocity: 50.8 fps Impact Area: Five courses from top, between the wood studs, at the steel interlock, three cavities from the left side. dented steel panel, no penetration. Impact #3: Missile Velocity: 50.5 fps Impact Area: Five courses up from the bottom, between the wood studs, and between the steel interlocks, three cavities from the left side. dented steel panel, no penetration. Note: Refer to Architectural Testing Sketch #7 for impact locations.

Page 10 of 15 Test Results: (Continued) Protocol TAS 203-94, Cyclic Wind Pressure Loading Test Unit #1 Design Pressure: ±75.0 psf POSITIVE PRESSURE Pressure Average Number of Maximum Deflection at Indicator (inch) Range Cycle Time Cycles (psf) (sec.) #1 #2 #3 0.0 to 37.5 600 2.50 0.01 0.06 0.02 0.0 to 45.0 70 2.59 0.01 0.07 0.02 0.0 to 97.5 1 N/A 0.01 0.11 0.02 Permanent Set (inch) <0.01 0.04 <0.01 NEGATIVE PRESSURE Pressure Average Number of Maximum Deflection at Indicator (inch) Range Cycle Time Cycles (psf) (sec.) #1 #2 #3 0.0 to 37.5 600 2.29 0.01 0.05 0.03 0.0 to 45.0 70 2.24 0.01 0.05 0.03 0.0 to 97.5 1 N/A 0.02 0.12 0.04 Permanent Set (inch) <0.01 0.02 0.03 Result: Pass Note: Refer to Architectural Testing Sketch #4 for indicator locations.

Page 11 of 15 Test Results: (Continued) Protocol TAS 203-94, Cyclic Wind Pressure Loading Test Unit #2 Design Pressure: ±75.0 psf POSITIVE PRESSURE Pressure Average Number of Maximum Deflection at Indicator (inch) Range Cycle Time Cycles (psf) (sec.) #1 #2 #3 0.0 to 37.5 600 2.01 <0.01 0.03 <0.01 0.0 to 45.0 70 2.19 <0.01 0.04 <0.01 0.0 to 97.5 1 N/A <0.01 0.08 <0.01 Permanent Set (inch) <0.01 <0.01 <0.01 NEGATIVE PRESSURE Pressure Average Number of Maximum Deflection at Indicator (inch) Range Cycle Time Cycles (psf) (sec.) #1 #2 #3 0.0 to 37.5 600 2.16 0.01 0.08 0.01 0.0 to 45.0 70 2.40 0.01 0.08 0.01 0.0 to 97.5 1 N/A 0.06 0.23 0.03 Permanent Set (inch) 0.01 0.06 0.02 Result: Pass Note: Refer to Architectural Testing Sketch #4 for indicator locations.

Page 12 of 15 Test Results: (Continued) Protocol TAS 203-94, Cyclic Wind Pressure Loading Test Unit #3 Design Pressure: ±75.0 psf POSITIVE PRESSURE Pressure Average Number of Maximum Deflection at Indicator (inch) Range Cycle Time Cycles (psf) (sec.) #1 #2 #3 0.0 to 37.5 600 2.01 <0.01 0.03 <0.01 0.0 to 45.0 70 2.19 <0.01 0.04 <0.01 0.0 to 97.5 1 N/A <0.01 0.08 <0.01 Permanent Set (inch) <0.01 <0.01 <0.01 NEGATIVE PRESSURE Pressure Average Number of Maximum Deflection at Indicator (inch) Range Cycle Time Cycles (psf) (sec.) #1 #2 #3 0.0 to 37.5 600 2.16 0.01 0.08 0.01 0.0 to 45.0 70 2.40 0.01 0.08 0.01 0.0 to 97.5 1 N/A 0.06 0.23 0.03 Permanent Set (inch) 0.01 0.06 0.02 Result: Pass Note: Refer to Architectural Testing Sketch #4 for indicator locations.

Page 13 of 15 Test Equipment: Cannon: Steel pipe barrel utilizing compressed air to propel the missile Missile: 2x4 Southern Pine Timing Device: Electronic Beam Type Cycling Mechanism: Computer controlled centrifugal blower with electronic pressure measuring device Deflection Measuring Device: Linear transducers Laboratory Compliance Statements: The following are provided as required by the protocols for the testing reported herein. Upon completion of testing, specimens tested for TAS 201-94 met the requirements of Section 1626 of the Florida Building Code, Building (2004). Upon completion of testing, specimens tested for TAS 202-94 met the requirements of Section 1620 of the Florida Building Code, Building (2004). Upon completion of testing, specimens tested for TAS 203-94 met the requirements of Section 1625 of the Florida Building Code, Building (2004). Tape and film were used to seal against air leakage during structural testing. In our opinion, the tape and film did not influence the results of the test. Testing was conducted at the Architectural Testing, Inc. laboratory located in York, Pennsylvania. List of Official Observers: Name Michael D. Stremmel, P.E. Eric M. Brennan Company Architectural Testing, Inc. Architectural Testing, Inc.

Page 14 of 15 Detailed drawings, data sheets, representative samples of test specimens, a copy of this report, or other pertinent project documentation will be retained by Architectural Testing, Inc. for a period of ten years from the original test date. At the end of this retention period, such materials shall be discarded without notice and the service life of this report will expire. Results obtained are tested values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC. Eric M. Brennan Technician Michael D. Stremmel, P.E. Senior Project Engineer EMB:vlm Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Sketches (7) Appendix-B: Drawing (1)

Page 15 of 15 Revision Log Rev. # Date Page(s) Revision(s) 0 07/02/08 N/A Original report issue This report produced from controlled document ATI 00173, revised 12/01/07.

Appendix A Sketches

Appendix B Drawings