FLUID APPLIED WATERPROOFING

Similar documents
Pacific Polymers Elasto-Deck BT Guide Specification

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING

ITEM 458 WATERPROOFING FOR STRUCTURES

SECTION RESILIENT SHEET FLOORING

A Design Review of Waterproofing Codes

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

TILE TILE

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards

PLATON FOUNDATION WRAP

SECTION MANUFACTURED ROOF EXPANSION JOINTS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION EPOXY TERRAZZO

ARCHITECTURAL GUIDE SPECIFICATIONS - DESCRIPTIVE

TEX COTE 600 TEXTURED COATING MASONRY PROTECTIVE COATING

SECTION COMMON WORK RESULTS FOR CONCRETE SSPECIALTY COATINGS

***********************************************************************************

AVM System 500. Aussie Membrane 500

SIKALASTIC-152 EXTERIOR WATERPROOFING MEMBRANE. Product. Scope. Appraisal No. 811 [2013] Appraisal No. 811 (2013) Amended 28 August 2017

KOSTER AMERICAN CORPORATION

Union County Vocational - Technical Schools Scotch Plains, New Jersey

CONCRETE STEPS, HANDRAILS, AND SAFETY RAIL

1.3 Work shall include all reinforcement and accessories necessary to complete installation.

General Applications Before applying, mix the pre-measured catalyst* into Liquid Roof by following label directions.

Application Specification:

SECTION ALPHAGUARD RESTORATION 20 YEAR WARRANTY SYSTEM. f. Conditions and Division 01 Specification Sections, apply to this Section.

Suggested Specification for Tri-Patch Versatile Concrete Patching Compound

Acceptable Floor Substrates: Concrete, cured mortar bed, plywood, and backer board.

SECTION LATEX-MODIFIED MEDIUM BED MORTAR

TOPCOAT Restoration Specifications Structural Concrete

A. Section includes hydraulic-cement-based, polymer-modified, self-leveling underlayment for application below interior floor coverings.

Fiber Reinforced Tile and Stone Mortar

1.2 Reference Standard: NOFMA - National Oak Flooring Manufacturers Association Grading Standards.

Engine Bay Floors Floor Resurfacing 4000

.1 Provide submittals in accordance with Section Submittal Procedures.

1.1 This Section includes surface preparation and the application of base coats, intermediate and topcoats.

SECTION CLAY BARREL TILE ROOFING. A. American Society for Testing and Materials (ASTM):

SPECIFICATION GUIDELINE

A. Section includes surface preparation and the application of high-performance coating systems on the following substrates:

GUIDE SPECIFICATION

CSI SECTION

Editing notes to assist users are separated from specification text by rows of asterisks. Delete these notes prior to final printing.

SECTION EPOXY FLOORING SYSTEMS

SECTION HYDRAULIC CEMENT UNDERLAYMENT

1. Division 09 Section "Rough Carpentry."

Perimeter Relief and Control Joints in Fire-Rated Gypsum Board

Weatherproofing & Sealing Systems

GUIDE SPECIFICATION

B. Related Sections: 1. Division 07 Section "Joint Sealants" for sealing of expansion, contraction, control, and isolation joints in tile surfaces.

CTIOA Field Report

ELASTOFLEX ELASTOMERIC TEXTURED ACRYLIC WALL COATING SPECIFICATION

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

Kolorines Glass Mosaic Tiles Project Specification

When I started tiling, we didn t do our own shower pans that BATHS

GE SCM3500 High Solids Silicone Roof Coating

A. Product Data: Submit manufacturer s product data, with complete general and specific installation instructions, recommendations, and limitations.

8245 Remmet Ave Canoga Park, CA (888) Installation Instructions - AVM System 700 Under Tile Waterproofing and Anti-Fracture Membrane

Florock Seamless Flooring Systems

Product Data Sheet Waterproofing Membrane for Ponds and Water Features Description Uses Suitable Surfaces Additional Uses Specification

PRODUCT GUIDE SPECIFICATION

SECTION EXPANSION CONTROL

ARDEX X 32 MICROTEC Universal Rapid Setting and Drying Thin-to-Thick Bed Mortar

Instruction Guide APPLICATION OF CIM TO CONCRETE

SECTION MOISTURE RESISTANT/WATER-PROOF FLOORING ADHESIVE FOR CONCRETE SLABS

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No.

SECTION 806 MANHOLE REHABILITATION

ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART GENERAL 1.

MS-2A LINER SPECIFICATIONS: for STRUCTURAL REPAIR and SEALING of MANHOLES

E.PROTECT+ COMPOSITE DECK WATERPROOFING SPECIFICATION

REPORT HOLDER: COREV AMERICA BRITTMOORE PARK DRIVE HOUSTON, TEXAS EVALUATION SUBJECT:

B. All work of the section shall comply with the conditions of the contract, the drawings and any special conditions forming a part of the contract.

Liquid applied polyurea hybrid membrane

UFGS (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

LIQUID RUBBER INDUSTRIES ENGINEERING SPECIFICATIONS FOR ENGINEERS AND ARCHITECTS. Diagram 1: Standard Membrane Continuation 150 mm Overlap

Tensile ASTM D1970 MD = 939 psi / CD = 1252 psi Self Sealability / water penetration resistance around nails. ASTM D1970 Section 7.

SECTION CERAMIC TILE. B. Ceramic tile wall finishes including standard and custom designs.

SECTION SELF-ADHERING SHEET WATERPROOFING

Vulkem EWS with PUMA Technology (Heavy Duty) APPLICATION INSTRUCTIONS

QUALITY COATING & REPAIR PRODUCTS

The Original. The Innovator.

Atlas Chempruf TM. Coating and Lining Systems

POLYGUARD RD-6 A FAIL SAFE PIPELINE COATING SYSTEM FOR REHABILITATION OR GIRTH WELDS ON CATHODICALLY PROTECTED PIPELINES

TOPCOAT Restoration Specifications Fiberglass & MB Granulated Cap Sheets

A. ASTM C 150 Standard Specification for Portland Cement. B. ASTM C 595 Standard Specification for Blended Hydraulic Cements.

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

MasterSeal HLM Liquid cold-applied elastomeric waterproofing membrane system

Exterior Stucco and Siding Installation

A. Coordinate concrete unit masonry (also termed CMU and block ) work with work before and after, especially:

prospec.com Concrete Repair & Restoration

CEMENTITIOUS CRYSTALLIZING WATERPROOFING PART 1 GENERAL

BTM BT2K 600. Areas of Use

SECTION UNIT MASONRY SYSTEM

DESIGN GUIDELINE FLUID-APPLIED WATERPROOFING

METHOD STATEMENT 001 CONCRETE BALCONY WATERPROOFING FOR DIRECT FIXED TILES

TOPCOAT System Specifications Corrugated Transite Panels

Section Polished Concrete Finishing. Vexcon

Repair Maintenance Hangar Phase II August 2010

WATERPROOFING TAMKOWATERPROOFING.COM

SECTION CONCRETE PAVING SLABS SET IN MORTAR

Transcription:

SECTION 07120 FLUID APPLIED WATERPROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03300 - Cast-In-Place Concrete. 2. 09200 - Metal Studs, Metal Lath, Suspension Ceilings, Plaster, and Stucco. 3. 09310 - Ceramic Tile. 1.02 SUBMITTALS A. Submit properly identified manufacturer's literature and technical data before starting work. 1. Submit an affidavit from manufacturer approving applicator before installation. a. Applicator shall provide evidence of 5 years satisfactory application experience of the system specified. 2. Submit material product data, material specifications, and application manual from manufacturer describing completely the preparation of surfaces and application of specified materials. 1.03 QUALITY ASSURANCE A. Waterproofing Applicator: 1. Manufacturer trained and manufacturer approved for waterproofing system proposed. 2. Minimum of 5 years experience in the application of fluid applied waterproofing. B. Waterproofing Manufacturer's Factory Trained Representative: 1. Inspect and approve surfaces to receive waterproofing before start of the work. 2. Be present and observe start of application of waterproofing. 3. Periodically inspect the work and inspect completed waterproofing work. Project No. SPECIFICATION GUIDELINES 07120-1

4. Report unsatisfactory surfaces to receive waterproofing and unsatisfactory materials and construction to Contractor and A/E. 5. Roofing at covered walkways and shelters shall have a minimum 2 part coating and fabric. 1.04 PROJECT CONDITIONS A. Environment Requirements: 1. Surface Temperature: Between 40 and 110 degrees F. during application. 2. Weather: Clear with no rain during application or anticipated within 12 hours. 1.05 WARRANTY A. Furnish warranty covering watertight integrity or waterproofing for 5 years from date of Substantial Completion. 1. Warranty shall provide for prompt repair of leaks, ruptures, blisters, and other imperfections at no cost to the Board. 2. Warranty shall be signed by contractor and waterproofing applicator. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Fluid Applied Waterproofing: 1. Applied Polymers of America, Inc.: Ureloid One Part Membrane Adhesive, Self-Leveling Grade and Non-Sag Grade. 2. Anti-Hydro Waterproofing Co.: A-H Seamless Membrane, 2H and 2V. 3. Gates Engineering Co.: Gacoflex UWM-28. 4. 3M Company: Scotch-Clad Deck Coating System M. 5. Sonneborn Building Products Division Contech, Inc.: Hydrocide Liquid Membrane No.5000 in roller grade and trowel grade. 6. Toch/Carboline Co.: Thio-Deck Membrane. 7. Tremco Manufacturing Co.: Tremproof No.60. B. Protection Board: 1. Celotex Corp.: Elastiboard. Project No. SPECIFICATION GUIDELINES 07120-2

2. J&P Petroleum Products, Inc.: Tex-Mastic Backerboard. 3. W.R. Meadows: PC-2 Protection Course. 4. Tremco Mfg. Co.: Tremboard. 2.02 MATERIALS A. Fluid Applied Waterproofing: One-component moisture-curing or two-component urethane type waterproofing suitable for covered non-traffic below grade locations. B. Primer: As recommended by waterproofing manufacturer for each type of surface encountered. C. Protection Board: 1/8" thick asphalt composition board. D. Joint Filler: Closed-cell, round expanded polyethylene foam. E. Sealant: As recommended by waterproofing manufacturer for compatibility with waterproofing system. F. Materials: Provide 1/16" thick neoprene sheet material, adhesives or trowel grade urethane waterproofing, woven uncoated fiberglass mesh flashing reinforcement or nonwoven polyester fabric, thinners and application equipment necessary to complete work of this section as recommended by the waterproofing manufacturer. PART 3 EXECUTION 3.01 EXAMINATION A. Condition of Concrete Surfaces: 1. Horizontal: Trowel finished without sharp ridges, projections, voids, and concrete or mortar droppings. 2. Vertical: Smooth, formed without sharp ridges, projections, voids, and concrete or mortar droppings. B. Condition of Concrete Surfaces to Receive Waterproofing: 1. Water cured or cured with silicate type chemical curing compound compatible with waterproofing. a. Resin type curing compounds are not allowed. 2. Surfaces shall be dry and acceptable to waterproofing applicator. 3. Application of waterproofing will be considered as Project No. SPECIFICATION GUIDELINES 07120-3

3.02 PREPARATION acceptance of surfaces to receive waterproofing. A. Surface Preparation: 1. After concrete substrate has cured 14 days with a maximum of 8 percent moisture content, and with projections, voids, concrete, and mortar droppings corrected, thoroughly clean surfaces immediately before installation of waterproofing using compressed air, vacuum, or other methods. 2. Remove oil, grease, form oils, and resin type curing compounds with sandblasting or a commercial grade alkaline cleaner or solvent. Thoroughly rinse and dry. 3. Concrete surface shall be dry and pass a 4-hour rubber mat test with no condensation before application of waterproofing system. 3.03 INSTALLATION a. Test will not be required on vertical walls open on both sides. A. Joints, Cracks, and Depressions: 1. Clean expansion, control, and construction joints by cutting back a minimum of 1 inch. a. Install polyethylene foam joint backing rod compressed 50 percent providing a channel below level of slab of depth equal to 1/2 width and with 1/2" depth maximum. b. Fill joint to surface level with sealant, apply bond breaker, and cover with nonflowing type waterproofing, preformed neoprene, or urethane sheet to a width of 3 inches on each side of joint as specified. 2. Rout or saw cut cracks exceeding 1/16" in width and fill with sealant. a. Treat cracks by cleaning thoroughly and applying 60 mils of waterproofing extending 3 inches from each side of crack. 3. Prepare concrete substrates by filling voids, holes, and depressions with epoxy grout or bonding agent and cement-sand grout as recommended by waterproofing manufacturer. Project No. SPECIFICATION GUIDELINES 07120-4

4. At horizontal, vertical, and corner expansion joints, provide joint filler and sealant application compatible with waterproofing system. a. Bridge joints using preformed neoprene or urethane membrane or with 60 mil coating of fiberglass mesh reinforced waterproofing or strip of neoprene sheet as standard with manufacturer, applied over bond breaker on expansion joint. b. Extend waterproofing a minimum of 6 inches from each side of joint, adhered to deck and vertical surfaces. B. Vertical Protrusions and Drains: 1. Clean exposed metal surfaces such as pipes, sleeves, drains, bases, and ducts by removing paint, rust, scale, or any foreign matter. a. Metal Preparation and Priming: According to manufacturer's recommendations and, if required, prime coat metal surfaces a maximum of 8 hours before membrane application with waterproofing manufacturer's metal primer. 2. Apply a 60-mil waterproofing coating to entire surface, extending waterproofing up to bottom of sealant in top surfaces of deck areas and extend membrane out on or up vertical surfaces 4 inches on projections. 3. Extend waterproofing over flanges of drains without sealing weep holes. C. Waterproofing: 1. Two Component Type Waterproofing: Mix materials according to manufacturer's published instructions without incorporating air bubbles. a. Do not thin or dilute mixture. b. Conform to recommended "Pot-Life" requirements. 2. For single component type waterproofing, use as furnished without dilution. 3. Apply waterproofing uniformly on surfaces to produce 60 mils (dry film) thickness using a trowel, calibrated notched squeegee or roller equipment approved by the manufacturer. a. 60-mil thickness is exclusive of previously applied waterproofing materials at cracks and joints. Project No. SPECIFICATION GUIDELINES 07120-5

4. Apply nonflowing type waterproofing material wherever a vertical surface exists, forming a continuous flashing and a 1/2" x 1/2" triangular cant, or other size recommended by waterproofing manufacturer. a. Extend waterproofing vertically up to bottom of sealant in deck top surfaces unless otherwise indicated. 5. Apply waterproofing under exterior quarry tile, paver tile, or concrete toppings above first floor. 6. At waterproofed basement floors, apply waterproofing on top of exterior wall foundations, interior column and wall foundations, mat type foundations, and working slabs. 7. Apply waterproofing to walls on earth side of room walls remaining earth fill. a. Extend waterproofing from foundation up to underside of floor resting on earth fill. 8. Apply waterproofing on exterior of elevator pit walls retaining earth fill from top of foundation up to finished floor on fill and from top of foundation up to within 4 inches of finished grade on exterior of building. 9. Apply waterproofing on exterior of below grade basement walls from top of foundation up to within 4 inches of finish exterior finish grade. 10. In planting bins within basement, apply waterproofing on interior bottoms and on interior sides from bottom to underside of ground floor slab. 11. Extend waterproofing material 6 inches minimum out on top of foundations. 12. At below grade rock anchors, pipe and conduit penetrations, extend membrane out on anchors, pipes and conduits 6 inches minimum to seal penetrations watertight. 13. Apply waterproofing to mechanical equipment room structural floor slabs below "floating slabs". a. Extend waterproofing on walls, curbs, pipes, and conduits up to top of the floating slab. 14. Tie-in to existing roofs require special detailing such as an area divider to properly seal both roof systems and maintain warranties. D. Protection Board: Project No. SPECIFICATION GUIDELINES 07120-6

1. Do not apply protection board to deck waterproofing until successful testing has been completed. 2. Apply protection board to horizontal surfaces and vertical surfaces of waterproofing. Adhere with spots of waterproofing. 3. On vertical surfaces where mechanical attachment is necessary to prevent protection board from sliding down, apply additional heavy trowel coat of fluid applied waterproofing where fasteners penetrate waterproofing. a. Use galvanized masonry nails for attachment of protection board. 4. Where protection board is to be applied to curved inside surfaces of planting bins, preform protection board using heat over a curved form. E. Alternate Protection for Vertical Surfaces of Fluid Applied Waterproofing (Contractor's Option): 1. In place of protection board, apply splatter coat of 1:3 mixture of cement and sand mortar, by hopper gun to final coat of waterproofing before coating cures. 2. After waterproofing and mortar splatter coat have set, apply 3/8" thick coat of Portland cement plaster by gun or by trowel. 3.04 TESTING a. Finish surface smoothly without damage to waterproofing. b. Refer to Section 09220, Metal Studs, Metal Lath, Suspension Ceilings, Plaster, and Stucco. A. Do not flood test waterproofing sooner than 36-hours following completion of application. 1. Flood test each horizontal or deck area for 48 hours minimum using a minimum of 2 inches of standing water. 2. Plug drains and place barriers to contain water. 3. Notify the manufacturer's representative before testing. B. Patching: Repair leaks that develop and retest. 1. Patch voids, bubbles, depressions, imperfections, or tears according to manufacturers published recommendations. Project No. SPECIFICATION GUIDELINES 07120-7

END OF SECTION Project No. SPECIFICATION GUIDELINES 07120-8