STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 863 REINFORCED SOIL SLOPES. October 19, 2012

Similar documents
Wall Modular Block Mechanically Stabilized Earth, Item S.

MODULAR CONCRETE RETAINING WALL

DETERMINATION OF THE LONG TERM PROPERTIES FOR MIRAFI PET-SERIES REINFORCEMENT GEOTEXTILES BY GRI-GT7 AND NCMA GUIDELINES

DETERMINATION OF THE LONG-TERM PROPERTIES FOR MIRAGRID XT GEOGRIDS

SECTION SPECIFICATION FOR STONEBRIDGE RETAINING WALL SYSTEM

SEGMENTAL BLOCK RETAINING WALLS. Comply with Division 1 - General Provisions and Covenants, as well as the following:

CONCRETE SEGMENTAL RETAINING WALL SYSTEM

02632 Segmental Concrete Retaining Wall System Page - 1

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 836 SEEDING AND EROSION CONTROL WITH TURF REINFORCING MAT January 18, 2013

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7)

GRI Standard Practice GG4(b) * "Determination of the Long-Term Design Strength of Flexible Geogrids"

TION GUIDE ALLA T INS

AEC Premier Straw Double Net Quick Mow EROSION CONTROL BLANKET SPECIFICATION

ICC-ES Evaluation Report Issued July 1, 2011 This report is subject to renewal in one year.

PRODUCT SPECIFICATION CSI FORMAT Slope and Channel Grid Systems April 2009

STANDARD SPECIFICATION FOR CRIBLOCK CONCRETE CRIBWALL

BENTOMAT CL GEOSYNTHETIC CLAY LINER SPECIFICATION GUIDELINES

Curlex High Velocity EROSION CONTROL BLANKET SPECIFICATION

This paper describes the salient features of a

LANDSCAPE RETAINING WALLS

Curlex II EROSION CONTROL BLANKET SPECIFICATION

Ohio Department of Transportation Division of Production Management Office of Geotechnical Engineering. Geotechnical Bulletin

ENGINEERING DIRECTIVE

QUALITY CONTROL PROGRAM OUTLINE

Design and Installation Guidelines for Retaining Walls. 1 P age. Geo Products, LLC 8615 Golden Spike Lane Houston, TX Phone:

This supplemental technical specification replaces Section 713 of the 2007 Standard Specifications for Highway Construction.

Stability of a Mechanically Stabilized Earth Wall

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

SKAPS Industries.

Section Soil Erosion Protection Tender No. [ ] Page 1

SECTION PERMEABLE INTERLOCKING CONCRETE UNIT PAVEMENT

Specification Guidelines: Allan Block Modular Retaining Wall Systems

EXPANDED POLYSTYRENE (EPS GEOFOAM) EMBANKMENT DIVISION 31 EARTHWORK

DIVISION: EXTERIOR IMPROVEMENTS SECTION: RETAINING WALLS SECTION: SEGMENTAL RETAINING WALLS REPORT HOLDER:

Geoguide 6 The New Guide to Reinforced Fill Structure and Slope Design in Hong Kong

DESIGN CONSIDERATIONS FOR NSWS NATURAL STONE RETAINING AND FREE-STANDING WALL SYSTEMS

Specifications for Concrete Embedment Liner

SECTION 806 WATER COURSE AND SLOPE EROSION PROTECTION

R-TANK SPECIFICATIONS

SPECIFICATION FOR PREFABRICATED VERTICAL DRAINS

A. Product Data: Submit manufacturer s product data, with complete general and specific installation instructions, recommendations, and limitations.

SECTION 20 INDEX PAVING FABRIC 1. SCOPE OF WORK MATERIAL REQUIREMENTS CONSTRUCTION AND INSTALLATION REQUIREMENTS...

2010 NTPEP Report Series

SECTION TRENCHING & BACKFILLING

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING

ODOT Design & Construction Requirements for MSE Walls

BENTOMAT ST GEOSYNTHETIC CLAY LINER GUIDE SPECIFICATION

ITEM 458 WATERPROOFING FOR STRUCTURES

1. Cast-in-place concrete is specified in Section

SLAB ON GRADE Insul-Joint or Expansion Joint Material as Required by A/E Specifications AquaCheck Liquid Coating 400 (Waterproofing Membrane) with Aqu

Trusted ICC ES. Conformity! Evaluation. ICC-ES Evaluation

SECTION RIPRAP, BOULDERS, AND BEDDING

Bureau of Materials Materials Approval Procedures

Redi Rock Specification and Installation Manual

@Copyright 2016 SKAPS Industries.

PERMEABLE INTERLOCKING PAVERS

Construction of MSE Wall Using Tire Shred-sand Mixture as Backfill (SPR-3470)

10,000. Peak Connection Strength, lb/ft 8,000 6,000 4,000 2,000

BASE CONSTRUCTION MATERIALS A Aggregate

COMBINED CONCRETE SIDEWALK AND RETAINING WALL. Comply with Division 1 - General Provisions and Covenants, as well as the following:

C. Foundation stabilization for pipe and utility structures.

Master Specification SECTION 02621

TensarTech TW1 Wall System Earth Retaining Structures

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

A.2.a Random Riprap... Table

T-WALL & STONE STRONG

ASTM D % 8.02% NA 1223 NA for App. Usage NA for App. Usage. NA for App. Usage. NA for App. Usage. NA for App.

TENAX t-block retaining wall system for geogrid reinforced block walls

SPECIFICATION FOR PREFABRICATED VERTICAL DRAIN

SPECIFICATION FOR REINFORCED SOIL WALL

Designer Supplement: AS-2-15 Approach Slab Installation January 16, 2015

SECTION CAST-IN-PLACE CONCRETE

INSPECTION GUIDE FOR SEGMENTAL RETAINING WALLS TEK 18-11B

VERTI-BLOCK - DESIGN MANUAL

B. Subsurface data is available from the Owner. Contractor is urged to carefully analyze the site conditions.

SECTION FOUNDATION DRAINAGE

SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 5 REINFORCING STEEL. 5.1 General Certification Fabrication...

BIO-AQUIFER STORM SYSTEM

1. ASTM F : Standard Specification for Impact Attenuation of Surface Systems Under and Around Playground Equipment.

STANDARDIZATION IN GEOTECH SECTOR V.K.PATIL

ITEM D-701 PIPE FOR STORM DRAINS AND CULVERTS

PRODUCT DATA SHEET SikaProof Bentonite

File No Supplemental November Geotechnical and Environmental Consulting Engineers

PRODUCT SPECIFICATIONS

INDEX FOR SPECIFICATIONS FOR JACKING CULVERTS THROUGH EMBANKMENTS SCOPE... 2

MSE. Mechanically Stabilized Earth Systems. Permanent and Temporary MSE Walls Reinforced Soil Slopes Embankments

SECTION REINFORCING STEEL

2013 World of Coal Ash (WOCA) Conference - April 22-25, 2013 in Lexington, KY

MATERIAL ALLOWANCES AND UNIT PRICES

HYDROGRID SUBSURFACE IRRIGATED HARTRU TENNIS COURTS

SPECIFICATION for ISCO HDPE DUAL CONTAINMENT PIPE

May 8, 2017 ADDENDUM #1. IFB Resin Floor System For Highway Department Central District Building

MECHANICALLY STABILIZED EARTH (MSE) WALL SYSTEMS

SECTION STRUCTURAL PRECAST HOLLOW CORE SLABS

Solving Slope Protection Problems Geoweb Cellular Confinement System

PART 1 - GENERAL 1.01 General Provisions A. The Conditions of the Contract and all Sections of Division 1 are hereby made a part of this Section.

Click on image to enlarge.

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

ACOUSTICAL WALL TREATMENT SECTION 09840

Transcription:

STATE OF OHIO DEPARTMENT OF TRANSPORTATION 863.01 Description 863.02 Materials 863.03 Construction 863.04 Method of Measurement 863.05 Basis of Payment SUPPLEMENTAL SPECIFICATION 863 REINFORCED SOIL SLOPES October 19, 2012 863.01 Description. This work consists of constructing an embankment or slope that is reinforced with geogrid. 863.02 Materials A. Geogrid. Geogrid is a geosynthetic material formed by a regular network of integrally connected polymer elements (ribs) with apertures of sufficient size to allow interlocking with the surrounding soil. Furnish geogrid which is dimensionally stable and able to retain its geometry under construction stresses. Furnish geogrid that is resistant to ultraviolet degradation and to all forms of chemical and biological degradation encountered in the soil being reinforced. Furnish geogrid that is recommended by the manufacturer for use in reinforced soil slope construction. Furnish geogrid that conforms to the requirements presented in Table 863.02-1 for the type of geogrid shown on the plans. Furnish geogrid consisting of either high density polyethylene (HDPE), polypropylene (PP), or PVC coated polyester (PET). For geogrids manufactured from PET, ensure that the carboxyl end group content is less than 30 mmol/kg according to ASTM D7409, and the number average molecular weight of the polymer is greater than 25,000 as determined from either gel permeation chromatography or by correlating with the inherent viscosity value determined in accordance with ASTM D4603 and GRI:GG8 (GRI is the Geosynthetic Research Institute). Do not furnish PET geogrid if the ph of the reinforced embankment soil is greater than 9. Thirty days before reinforced slope construction begins, submit to the Engineer for review and acceptance certified test data according to C&MS 101.03 that verifies the geogrid meets all the requirements. Allow 14 days for review by the Department. Do not begin reinforced slope construction until the Department accepts the geogrid submittal. The Department will accept test data from the National Transportation Product Evaluation Program (NTPEP) as certified test data. 1

TABLE 863.02-1 REQUIRED GEOGRID PROPERTIES Geogrid Type Test Primary Secondary Property Method P1 P2 P3 P4 P5 S1 S2 Ultimate Tensile Strength Long-Term Design Tensile Strength Ultraviolet Stability ASTM D 6637 (see below) ASTM D 4355 lb/ft (kn/m) lb/ft (kn/m) 1300 (19) 2000 (29) 2500 (36) 3300 (48) 4200 (61) 70% at 500 hours 1400 (20) 2100 (31) Note: Determine tensile strength according to ASTM D 6637, Method B. Determine long-term design tensile strength according to the procedure described below. All values, except ultraviolet stability, are minimum average roll values, MARV (average value minus two standard deviations.) The strength requirement is for the direction perpendicular to the face of the slope. This is typically in the machine or roll direction for the primary geogrid and in the cross machine direction for the secondary geogrid. 1. Long-Term Design Tensile Strength. Calculate the long-term design tensile strength (T A ) using the equation below. The calculated value must be greater than or equal to the corresponding value in Table 863.02-1 for the specified geogrid type. Where: T A = T ULT RF CR RF ID RF D RF JNT T A = Long-term design tensile strength T ULT = Ultimate tensile strength according to ASTM D 6637 RF CR = Reduction factor for creep RF ID = Reduction factor for installation damage RF D = Reduction factor for durability RF JNT = Reduction factor for joints With the certified test data, submit calculations that demonstrate the proposed geogrid meets the required long-term design tensile strength based on the specific reduction factors for the geogrid. 2. Reduction Factor for Creep, RF CR. This value is the ratio of T ULT to the creep limited strength determined according to ASTM D5262 and extrapolated for a 75-year design life according to Appendix B of FHWA Publication No. FHWA-NHI-00-043. Do not extrapolate by more than one order of magnitude at a designated temperature. Elevated temperature testing, as well as in-situ temperature testing, for a minimum of 10,000 hours are required in order to extrapolate the creep test data to a 75-year design life. Perform creep testing on representative samples of the product and not on a single component of geogrid. Submit certified test data 2

demonstrating the appropriate value of RF CR for the geogrid. There is no default value for RF CR ; the contractor must submit certified test data. 3. Reduction Factor for Installation Damage, RF ID. Determine RF ID from installation damage tests consistent with ASTM D5818 and Section 5.1 of FHWA Publication No. FHWA- NHI-09-087, Corrosion/Degradation of Soil Reinforcements for Mechanically Stabilized Earth Walls and Reinforced Soil Slopes. Do not use a value less than 1.10, or if granular embankment or granular materials are specified or used for the reinforced embankement, do not use a value less than 1.20. If certified test data is not available to determine RF ID, use a default value of 1.80 for granular embankment or granular materials and a default value of 1.40 for natural soill. 4. Reduction Factor for Durability, RF D. Use the values listed in Table 863.02-2 based on the geogrid material and the retained strength after ultraviolet exposure. Test data is not required. TABLE 863.02-2 REDUCTION FACTOR FOR DURABILITY Geogrid material HDPE PP Coated PET Retained Strength at 500 hours RF D ASTM D4355 retained strength > 90% 1.10 retained strength between 70 and 90% 1.40 retained strength > 90% 1.10 retained strength between 70 and 90% 1.40 ph of Reinforced Embankment ASTM G51 from 5 to 8 1.15 less than 5 or greater than 8 1.30 5. Reduction Factor for Joints, RF JNT. If the Contractor will join two strips of primary geogrid together to meet the length requirements shown on the plans, then determine RF JNT by dividing the unjointed geogrid strength by the jointed geogrid strength. Determine both the jointed and the unjointed geogrid strength according to ASTM D5262 with sustained tension tests lasting at least 1,000 hours. For the testing, use the same method and procedure for connecting or joining the geogrid as will be used during construction. Use a value of 1.00 if there is no reduction in strength of the joined samples or if no joints are used. If certified test data is not available to determine RF JNT and joints are required, use a default value of 2.0. B. Reinforced Embankment. Furnish embankment soil to be used in conjunction with the geogrid reinforcement that is either natural soil as defined in 703.16.A or granular embankment material as defined in 703.16.B. Furnish embankment material that also meets the requirements in the table below. For landslide repair projects, reuse excavated material when the material conforms to these requirements. Submit test results for each source before beginning work and again whenever the source changes. 3

TABLE 863.02-3 ADDITIONAL REQUIREMENTS FOR REINFORCED EMBANKMENT Property Test Method Required Value Organic content AASHTO T 267 4.0% Plasticity index AASHTO T 90 20 Before using PET geogrid, test the ph of the embankment material according to ASTM G51. If the ph is greater than 9, do not use PET geogrid. 863.03 Construction A. Storage and Handling. Follow ASTM D 4873 for geogrid labeling, shipment, and storage. Furnish product labels that clearly show the manufacturer s or supplier s name, product type, lot number, roll number, manufactured date, and roll dimension. Furnish a notation for each shipping document certifying that the material is in accordance with the manufacturer s certificate. During shipment and storage, protect the geogrid from direct sunlight, ultraviolet rays, temperatures greater than 160 F (71 C), flames including welding sparks, mud, dirt, dust, and debris. Keep the geogrid dry during storage and do not store directly on the ground. The geogrid will be rejected if it has defects, tears, punctures, flaws, deterioration, or damage incurred during manufacturing, transportation, or storage. If approved by the Engineer, torn or punctured sections may be repaired by placing a patch over the damaged area and mechanically connecting the edges to the geogrid beneath. B. Site Excavation. Prepare a level surface for placement of the first layer of geogrid, including removing any deleterious materials, sharp objects, and loose or otherwise unsuitable soils. Prepare the embankment foundation according to C&MS 203.05. The Department will inspect the base of the excavation to verify that the subsurface conditions are the same as those anticipated during the design. Do not place the first layer of geogrid until after the Department inspects the base of the excavation and accepts it. C. Geogrid Placement. Cut the geogrid to the required length shown on the plans. Measure the length from intact transverse rib to intact transverse rib. Do not include fingers (ribs only connected on one end) when measuring the length of the geogrid. Place the geogrid horizontally at the elevations and orientations shown on the plans. Maintain the vertical position of each layer within 2 inches (50 mm) of the design elevation. Verify the correct orientation (roll direction) of the geogrid (see Figure 863.03-1). Primary geogrid (Types P1, P2, P3, P4, and P5) will typically have its roll direction perpendicular to the slope face. Secondary geogrid (Types S1 and S2) will have its roll direction parallel to the slope face. However, the Contractor may place primary geogrid with the roll direction parallel to the face of the slope if the roll width is equal to or greater than the required length and the geogrid meets the specified strength requirements in the cross machine direction. 4

Required length Roll direction Required length Face of slope Face of slope Roll direction Directions Parallel to face of slope Perpendicular to face of slope Primary geogrid Secondary geogrid Figure 863.03-1 Typical roll orientation No overlap is required between adjacent rolls. However, when the geogrid will be exposed as part of a wrap-around facing system, overlap adjacent rolls of geogrid by at least 6 inches (150 mm). Secure each piece of geogrid in place at all four corners to prevent movement during fill operations. Secure the geogrid with staples or pins. Remove any slack in the geogrid before placing fill on top of it. D. Mechanical Connections. Place the geogrid in continuous strips for the required length. The Department will allow the Contractor to mechanically join two strips of primary geogrid together to meet the length requirement shown on the plans, provided that the calculation of the long-term design tensile strength of the primary geogrid includes a reduction factor for joints, RF JNT, according to 863.02.A.5. Join the two strips of geogrid using the same method and procedure that was used in the testing for RF JNT. The method must consist of a mechanical connection between the two strips of geogrid. The Department will not allow simply overlapping the geogrid without a mechanical connection. Use no more than one joint per length of geogrid. Locate joints at least 15 feet (4.5 m) behind the finished slope surface. Stagger joints at least 10 feet (3.0 m) between adjacent strips and between consecutive layers. E. Fill Placement. Place and compact embankment material according to C&MS 203, except as modified below. Compact embankment material to at least 98 percent of the maximum dry density determined according to Supplement 1015. Place, spread and compact the embankment in a manner that prevents the development of wrinkles or movement of the geogrid. Do not operate construction equipment directly on the geogrid. Place at least 6 inches (152 mm) of embankment material above the geogrid before operating construction vehicles on it. Do not turn equipment or brake suddenly on the first lift of fill above a layer of geogrid. Replace damaged geogrids at no cost to the Department. 5

Control drainage to prevent erosion. Reshape slopes that have been damaged by erosion during construction. If seeding and mulching is specified for the slope face, perform the seeding and mulching within 7 days. 863.04 Method of Measurement. The Department will measure the quantity of Geogrid by the number of square yards (square meters) completed and accepted in place. The Department will measure the length of the Geogrid by the distance from intact transverse rib to intact transverse rib. The Department will not include the length of ribs which are only connected at one end. The Department will not measure lengths greater than the required length or overlaps in the measurement for payment. The Department will measure Reinforced Embankment by the number of cubic yards (cubic meters) according to C&MS 203.09. 863.05 Basis of Payment. The Department will pay for embankment work according to C&MS 203.10. The Department will pay for accepted quantities at the contract prices as follows: Item Unit Description 863 Square Yard Geogrid, Type (Square Meter) 863 Cubic Yard Reinforced Embankment (Cubic Meter) 6

Designer Note: Design reinforced soil slopes (RSS) and reinforced embankments using the methods shown in the FHWA manual, Mechanically Stabilized Earth Walls and Reinforced Soil Slopes - Design and Construction Guidelines (Elias, et al., 2001). Design for a minimum overall (global) factor of safety equal to 1.5 for slopes and embankments that support structures and equal to 1.3 for all other slopes and embankments. Select the type of primary geogrid reinforcement from Table 863.02-1 (P1, P2, P3, P4, or P5) that will provide the long-term design tensile strength (T A ) required to produce an adequate factor of safety (FS) for the reinforced embankment. However, you may need to adjust the longterm design tensile strength depending on the slope stability program you use for the analysis. If you use a slope stability program that assumes the reinforcement force contributes to the resisting moment, such as ReSSA, RSS, and many others, then no adjustment is necessary. These programs apply the overall factor of safety to both the soil and reinforcement as part of the analysis, so the factor of safety is already applied within the slope stability analysis. However, if you use a slope stability program that assumes the reinforcement force is a negative driving component, then you need to adjust the long-term design tensile strength. With this assumption, the overall factor of safety is not applied to the tensile force from the reinforcement. In this case, multiply the tensile force from the slope stability program by the required factor of safety to determine the required long-term design tensile strength. See pages 198 and 199 in Elias, et al. (2001) for more information. Assume a pullout resistance factor, F*, equal to 0.67 tan and scale effect correction factor,, equal to 0.8 for geogrids. If you use a program that calculates the long-term design tensile strength based on reduction factors (such as ReSSA), use the long-term design tensile strength values given in Table 863.02-1 and a value of 1.0 for all reduction factors. When the contractor selects a geogrid manufacturer, that manufacturer will furnish certified test data that determines the reduction factors appropriate for its geogrid. The contractor will then calculate the long-term design tensile strength based on those specific reduction factors and furnish a geogrid that meets the required long-term design tensile strength. Whenever possible use existing on-site soil for the reinforced embankment, as this will generally be more cost effective. However, when granular embankment is required, use a plan note to specify the type of granular material required (Granular Embankment or Granular Material, Type ) and provide a pay item for Reinforced Embankment, As Per Plan. Use Geotechnical Bulletin 6 to estimate shear strength values for the proposed reinforced embankment. Ensure the plans show the following items, as appropriate: Face construction details, such as wrap-around facing with geogrid Item 659 Seeding and Mulching, Class 3B or 3C Item 670 Slope Erosion Protection Reference Elias, V., Christopher, B.R., and Berg, R. (2001) Mechanically Stabilized Earth Walls and Reinforced Soil Slopes Design and Construction Guidelines, FHWA-NHI-00-043, Federal Highway Administration, Washington, D.C. 7