FEASIBILITY STUDY FOR GREEN ARCHITECTURE IN TEMPERATE REGIONS (GAZA CASE) GRADUATE SCHOOL OF ENGINEERING HOKKAIDO UNIVERSITY- JAPAN

Similar documents
Thermal Comfort in Architecture

Bio-climatic Chart for Different Climatic Zones of Northeast India

Design Strategies and Guide lines for Tropical Coast of Pakistan, Using Climate Consultant

Thermal Delight in Architecture

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Thermal Delight in Architecture

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE

Bioclimatic chart analysis in three climate zones in Cyprus

Workshop: Architecture-Tradition and Modernization. Climate Responsive Urban Design

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand

Bioclimatic Design Approach Integration into Architectural Design: a Library Case Study

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Research on indoor thermal environment of stilted buildings in Chongqing, China

Case Study: Bio-Climatic Building Design for Tropical Climates

SUSTAINABLE BY PASSIVE ARCHITECTURE, USING COURTYARDS IN NON-DOMESTIC BUILDINGS IN SOUTHEAST QUEENSLAND

Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa

ARPAN JOHARI. Architect. 13/08/10 AW Design. Ahmedabad

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA

VELUX A/S, Daylight Energy and Indoor Climate, Ådalsvej 99, 2970 Hørsholm, Denmark *Corresponding author:

Bioclimatic approaches of modern residential architecture in Cyprus,

Passive Houses in South West Europe

Attached Solar Greenhouse Plans for a solar heated greenhouse attached to your home

Solar Passive Techniques: Earth Air Tunnel

Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis

Sapporo Net-Zero Energy Home Hokkaido, Japan. Description. Setting. Super E Canadian Member. Super E Japanese Member. Super E Case Study

Thermal comfort in a 21st century climate

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

Thermal Comfort Evaluation of HDB flats

Senior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis

The use of Simulation Software to Evaluate the Thermal Performance of Buildings in Brazil

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

3.1 Noise Overlay District

Introduction of Heat Insulation Solar Glass

Optimal orientation for housing with low energy profile in a semi arid climate.

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE

COMFORT-PRODUCTIVITY Building costs COMFORT-PERFORMANCE. Radiant Heating and Cooling Systems for Better Comfort and Energy Efficiency INDOOR - OUTDOOR

Adaptive Climate Responsive Vernacular Construction in High Altitude

The Centre for Sustainable Building (ZUB) * A Case Study

Solar Home Design and Thermal Mass

Passive Cooling Design Options to Improve Thermal Comfort in an Urban District of Rome, Under Hot Summer Conditions

Facade Design for Super High- Rise Building in Subtropic Region in China

LOW ENERGY ONE FAMIL Y MASONRY HOUSE. Tor-Ulf Weck l

Potential of ventilative cooling in German residential buildings

Experimental investigation of zero energy office under natural and forced ventilation

THERMAL MASS CHAPTER 6. Understanding thermal mass. Seasonal effects of thermal mass

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

Urban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK

Assignment 3 Integrated Energy Design

Environmental Impacts of Urban Heat Islands and their Countermeasures - Experiences of Japanese dense cities-

SIMULATION OF A TYPICAL HOUSE IN THE REGION OF ANTANANARIVO, MADAGASCAR DETERMINATION OF PASSIVE SOLUTIONS USING LOCAL MATERIALS

Student Modeling Competition

Analysis 2: Alternative Thermal Window Design

Thermal insulation of buildings and cooling demand

Evaluating Appropriate Residential Ventilation Strategies in Dense Urban Environments and the Challenges for Passive Design

Size: length ft., bay width ft., number of bays: Square feet of floor space: Sq. ft. of bench/floor space covered by crops:

PASSIVE COOLING STRATEGIES. Passive Cooling

THE INFLUENCE OF ENVELOPING ON ENERGETIC AND ECOLOGICAL EFFICIENCY OF PASSIVE HOUSES

Module 3: Simulation and Data Analysis

.. Cost.. Efficiency... Of... Thermal Insulation. August 2002

Available online at ScienceDirect. Energy Procedia 57 (2014 )

CHAPTER 1: OVERVIEW OF ENERGY EFFICIENT CONSTRUCTION

COMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program

Performance-Risk Methodology for the Design of High-Performance Affordable Homes

THERMAL CHARACTERISTICS AND ENERGY CONSERVATION MEASURES IN AN INDOOR SPEED-SKATING ARENA

5.0 Daylighting Analysis (Breathe Study)

EC The Effective Detective : Finding Energy Savings at Home

HEAT LOSS REDUCTION OF ENERGY-EFFICIENT HOME BY BUFFER AREAS. Alexander Dvoretsky, KseniaKlevets

Zero Energy Building Example in Estonia. Tõnu Mauring

Assessing The Microclimate of Green and Less-Green Tropical Landscape Environment

WHITE PAPER. Phantom Motorized Retractable Screens Extend Living Space While Adding Energy Efficiency. February

A Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers

Adaptive Thermal Comfort in Warm Dry Climate: Economical dwellings in Mexico

Case study the Vela Roof UNIPOL, Bologna Use of on-site climate and energy resources

H.A.M.M.A.M. Project and Climate Design of Islamic Bath Buildings

SOLAR XXI: A Portuguese Office Building towards Net Zero-Energy Building

Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation

Energy Efficient Buildings in Germany An Introduction

Green Building Guideline of Jordan

Passive cooling and energy conservation design strategies of school buildings in hot, arid region: Riyadh, Saudi Arabia

DESIGN CRITERIA FOR WARM HUMID CLIMATES. A CASE STUDY ABSTRACT KEYWORDS INTRODUCTION

Integration of Energy Efficiency Through Architectural Design. Presentation by TERI. 10 th June,2010

Energy Consumption Measurement of Energy-saving Buildings and Analysis of Simulation Example

COMPUTATIONAL ASSESSMENT OF COOLING WITH LOW-TEMPERATURE HEATING SYSTEMS

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

Passive House Project documentation

ARCH-MEDES (I) CONSULTANTS PVT. LTD. Green Park Delhi

2000 Antwerp, terraced house

A Year-Round Opening-Air Experiment System for Global Warming to Predict Future Paddy Field Ecosystem

Designing Air-Distribution Systems To Maximize Comfort

A calculation model for Trombe walls and its use as a passive cooling technique

Assessment of the natural air ventilation of buildings in urban area with the CFD tool UrbaWind. Dr Stéphane SANQUER Meteodyn

Whole Building Energy Analysis using BIM

Natural Ventilation Approached on Circular Courtyard Building in Hot Humid Climate

DESIGN STRATEGIES OF THE RESIDENTIAL BUILDING IN WARM and HUMID CLIMATIC ZONES - TURKEY

EVALUATION OF THE SOLAR INCOME FOR BRAŞOV URBAN AREA

Transcription:

FEASIBILITY STUDY FOR GREEN ARCHITECTURE IN TEMPERATE REGIONS (GAZA CASE) Emad S.Mushtaha 1, Masamichi Enai 2, Hayama Hirofumi, Taro Mori 4 GRADUATE SCHOOL OF ENGINEERING HOKKAIDO UNIVERSITY- JAPAN ABSTRACT The environmental impact of house design, construction and operation has low priority in studies as compared to the conventional involvements in cost, size, form, location and aesthetics. Gaza s climatic data indicates that; 4% of the year is cold while 4% is warm, which requires finding a flexible design tool that can satisfy human comfort into a current predominant green architecture concept, which provides efforts to improve the thermal environment and ventilation of buildings through identifying, developing, and testing innovative concepts that have potentialities for diminishing the rapid use of purchased energy in houses. The bioclimatic charts and Mahoney tables are conducted herein; moreover, basic principles of Successive Integration Method have been utilized on some materials and varying passive elements to achieve new buildings strategies and modules. An integrated design with floor cooling and heating, natural ventilation and some additional passive techniques show that both indoor temperature and lower energy consumption are properly maintained. KEYWORDS Thermal comfort, design tools, natural ventilation, Successive Integration Method. 1. INTRODUCTION These days, several housing problems are subject to discussion, one such problem occurs in the Middle East where the highest densely populated areas in the world are located in Gaza s camps with. persons/km 2. [1] Moreover, a study was obtained from 4 housing projects distributed in several locations in Gaza. The results confirm that most housing projects have no organizational form; in addition incomplete buildings are a common phenomenon dwelling place [2]. Achieving healthy housing designs within the least means in a sound environment is more important than the balanced population growth. Hence, Gaza has several severe climatic problems through the year such as heat and humidity in summer, cold in winter and short periods of autumn and spring. Moreover, the monthly mean maximum air temperature is (1.2) o C in a typical summer, and monthly mean minimum air temperature is (6) o C in the winter. The percentage of winter heating is (4) % while in summer cooling is 4%. Nevertheless, the existing environmental concerns for thermal comfort focus on the summer rather than the winter due to the lack of mean annual precipitation (4) mm. Accordingly, this paper aims to achieve passive mobile strategies, which consider the relation of the human, building and climate with low energy usage. 1 Hokkaido University, Japan, Master Degree. 2 Hokkaido University, Japan, Professor. Hokkaido University, Japan, Associate professor. 4 Hokkaido University, Japan, Assistant professor. E-7

2. OBJECTIVES The study aims to achieve: (a) The most effective and required strategies for environmental design to maximize human comfort. (b) Convenient concept of green s design elements within low-energy building.. METHODS The study is particularly specified as follows: (a) Applying the bioclimatic charts and Mahoney tables to Gaza, which facilitate the analysis of outdoor climatic data with different charts, moreover to infer required design tools to restore human comfort in buildings. (b) Developing some of the earlier revealed strategies by adopting some calculative equations, in addition to Successive Integration Methods to evaluate the thermal environment of the structure..1 BUILDING BIOCLIMATIC CHARTS & TABLES Bioclimatic charts analyze climatic elements of a specified area in order to clarify the needed corrective measures to get healthful and livable houses with reference to the thermal comfort zone, which is defined as the range of climatic conditions within which the majority of persons would not feel thermally discomfort either heat or cold []..1.1 Olgyay s bioclimatic chart The chart was developed in 196 to associate the outdoor climate into building design guideline process. The use of the chart is directly applicable only to inhabitants of the temperate zone at elevation not in excess of () feet above sea level with customary indoor clothing, doing sedentary or light work 8 9 11 7 6 4 12 2 1 4 6 7 8 9 Relative humidity % [4].This chart clarifies the needed Figure (1) Olgyay s bioclimatic char [] corrective measures to achieve the comfortable zones for a human being. In this chart the relative humidity is the abscissa and dry bulb temperature is the ordinate. The comfort zone is fixed around (21-27.8) o C and has small seasonal adaptations in winter and summer. Application of Olgyay s bioclimatic chart to Gaza Outdoor conditions have been plotted to Olgyay s bioclimatic chart as shown in figure (1), which is identifies conditions for each month of the year. They represent the average daily maxima and minima data of both dry bulb temperature and relative humidity. This chart suggests that for summer s months (June-September) ventilation is an innovative tool to restore comfort. The chart also indicates that for winter s months E-8

(Dec March) solar radiation is needed more than (April, May, Oct, Nov) about 8w/m 2 to mitigate the outdoor temperature to comfort zone.on the other hand; the chart for months (April, May, October, November) indicates that daytime lies in the comfort zone but at night a space heating is required..1.2 Givoni s bioclimatic chart A study was developed by Givoni 1976 to address the problems associated with Olgyay s charts discussed previously. Moreover, it is based on the expected indoor temperature of buildings instead of the outdoor temperature and it is graphically drawn on a conventional psychrometric chart. The chart suggests boundaries of climatic conditions within which various 4 11 12 1 2 building design strategies []. Proper Figure (2) Givoni s bioclimatic chart [] passive cooling and heating strategies were achieved by plotting the linear relation between average mean temperature and relative mean humidity. Application of Givoni s bioclimatic chart to Gaza Outdoor conditions have been plotted to Givoni s bioclimatic chart as shown in figure (2), which clarifies twelve different monthly lines of the year. It has noticed that a thermal gain and an effective measure are needed to restore comfort for the months of (December-March) and for (April and November) s nights. Moreover, natural ventilation coupled with mechanical ventilation to restore comfort for the months of (June -Sep). Furthermore, (October and May) fall in the comfort zone except a few short periods during the night, which fall outside the comfort zone, when passive heating is required. Therefore, this chart determined the required strategies for achieving the comfort zone..1. Mahoney tables HMV High mass with nighttime ventilation. HT High thermal mass. EC Evaporative cooling. NVM natural and mechanical ventilation. Mahoney tables are applied to fit building s characteristics to the existent climatic conditions. The Department of Development and Tropical Studies of the Architectural Association in London developed theses tables for achieving methodologies for a responsive design. The predicted elements of some constructions are being tabulated to consider the relation between building details and their contact with the surrounding climatic data. Generally, the monthly climatic data are tabulated such as mean temperature maxima and minima, mean relative humidity (maxima and minima), rain and wind. Utilizing these tables and following the processes of each table s diagnosis, new indicators were concluded in numbers, which in turn, estimated how the building s elements should be in a region. The processes and steps are as follows: 6 8 7 9 E-9

(a) Climatic data The climatic data (dry bulb temperature, relative humidity, precipitation and wind) are classified into some groups as follows: Dry bulb temperature The climatic data represented in monthly mean maximum and minimum air temperature are tabulated in the whole year s months as in table (1). Annual mean temperature (AMT) is calculated according (AMT= highest+lowest/2) while; Annual mean range (AMR) is calculated according (AMR= highest-lowest). High temperature is the highest value of monthly mean maximum temperature while; low temperature is the lowest value of monthly mean maximum temperature. Air Temperature ( o C) J F M A M J J A S O N D High AMT Monthly mean max 16.6 17.2 17.7 22.9 2.8 27. 1.2 28.6 2. 2 18.9 1.. Monthly mean min 9.8 11. 1.9 17.8 21.7 26 24. 22.8 19.1 1.9 12.6 9.8 21.4 Monthly mean range 6.8 7.2 6.2 7 6.8.2..8 6.4 7.1 6. Low AMR Table (1) Air temperature Hence AMT is a value equal more than,then from table () the choice is arranged for AMT> in table (2) with the classifications of the humidity groups from 1-4 supported by humidity s percentages. AMT> Average Day Night (RH) HG Lower-Upper Lower- Upper - 1 26-4 17-2 - 2 2-1 17-24 -7 2-29 17-2 7-4 22-27 17-21 Table (2) Climatic data Relative humidity In table () the data of relative humidity is classified into groups according to table (). Relative Humidity J F M A M J J A S O N D Monthly mean max (am) 8 78 8 74 87 86 8 81 87 81 8 79 Monthly mean min (pm) 1 4 6 62 6 62 8 7 2 4 Average 6. 64 66. 8. 7 74 74 71. 72. 69 66 66. Humidity group 4 4 4 4 4 Table () Classifications of the relative humidity Percipitation and wind Rainfalls and winds are investigated to get average of rainfalls, which are evaluated by (4) mm; while the winds directions are being significantly tabulated with their type as shown in table (4), which will be conducted to tables (7), (8). rainfall and wind J F M A M J J A S O N D Total Rainfall mm 11.2 67.1 7. 1..7.2 2. 6.89.8 4 Wind, prevailing SW SW SW SW NW NW NW NW NW W SW SW Wind,secondery SW SE SE SE W W W W NW NW SW SE Table (4) Rainfall and wind (b) Comfort limits Comfort limits are classified according to the average percentage of relative humidity (RH%) and to the annual mean temperature (AMT) as in table (). E-6

AMT> AMT 1- AMT<1 RH Day Night Day Night Day Night Average HG Lower-Upper Lower- Upper Lower-Upper Lower- Upper Lower-Upper Lower- Upper - 1 26-4 17-2 2-2 14-2 21-12-21-2 2-1 17-24 22-14-22-27 12- -7 2-29 17-2 21-28 14-21 19-26 12-19 7-4 22-27 17-21 -2 14-18-24 12-18 Table () Comfort limit Moreover, tables () supports table () and (6) to find out the classifications of relative humidity and thermal stresses during the year. (c) Diagnosis Diagnoses the earlier data to get classified thermal stresses data during each month s day and night; therefore required times and strategies could have been achieved to undertake building during the year as established in table (6). ( o C) J F M A M J J A S O N D AMT Monthly mean max 16.6 17.2 17.7 22.9 2.8 27. 1.2 28.6 2. 2 18.9. Day comfort, upper 29 29 29 29 27 27 27 27 27 29 29 29 Day comfort, lower 2 2 2 2 22 22 22 22 22 2 2 2 Thermal stress, day C C C C O H H H H O O C Monthly mean min 9.8 11. 1.9 17.8 21.7 26 24. 22.8 19.1 1.9 12.6 Night comfort, upper 2 2 2 2 21 21 21 21 21 2 2 2 Night comfort, lower 17 17 17 17 17 17 17 17 17 17 17 17 Thermal stress, Night C C C C O H H H H O C C Table (6) Diagnosis Table (7) shows the classification of the humid and the arid indicators that combine with the previous tables for achieving table (8). Type Indicator Thermal stress Rainfall H.G Monthl MeanRange Day-Night mm o C Air movement essential H1 H 4 H 2- < Air movement desirable H2 O 4 Rain protection Necessary H >/month Thermal capacity necessary A1 1- > Outdoor sleeping desirable A2 H 1-2 H O 1-2 > Outdoor sleeping desirable A C Table (7) The humid and arid indicators An initial response is represented in indicators form and is shown in table (8), which is related to the previous tables. The whole procedure is carried out to insert the results into table (9) to get design recommendations for proposed buildings. J F M A M J J A S O N D Total H1 1 1 1 1 4 H2 1 1 H A1 A A 1 1 1 1 1 Table (8) Indicators (d) Design recommendations Mahoney s table (9) consists of 8 fields to find out the way of developing housing designs from the sketching stage until the construction. E-61

H1 H2 H A1 A2 A 4 1 Humid Arid 1.Layout - X 1.1 Orientation north and south (long axis East west) 11or12-12 -4 1.2 Compact courtyard planning. 2.Spacing 11 or 12 2.1 Open spacing for breeze penetration 2- X 2.2 As above, but protection from hot and cold wind or 1 2. Compact layout of estates.air movement -12 X.1 Rooms single banked, permanent Provision for air movement -.2 Rooms double banked, temporary Provision for 1 or2 6-12 air movement 2-12. No air movement requirement or 1 4.Opening or 1 4.1 Large openings, 4 8% 11or12 or 1 4.2Very small openings, % Any other conditions X 4.Medium openings, 4%.Walls -2 X.1Light walls, short time lag -12.2Heavy external and internal walls 6.Roofs - X 6.1Light, insulated roofs 6-12 6.2Heavy roofs, over 8h time lag 7.Out door sleeping 2-12 7.1 Space for outdoor sleeping required 8.Rain protection -12 8.1 Protection from heavy rain necessary Table (9) Mahoney s table In table () assembling the previous mentioned recommendations as one unit in total. element Recommendations 1.Layout Orientation of buildings north and south on (long axis east-west). 2.Spacing Open spacing for breeze penetration but protection from hot and cold wind is required..air Room single banked, permanent provision for air movement. movement 4.Opening Medium openings, 4%..Walls Light walls, short time lag 6.Roof Light, insulated roofs Table () Recommendations for Gaza s building design 4. ANALYSIS Different approaches have been adopted to determine the needed tools to achieve thermal comfort through the analysis of charts and tables. Accordingly, the percentage of the twelve lines in the Givoni and Olgyay charts is approximated according to its location to the comfort zone and it was noticed that the solar radiation utilized about % of the year in Olgyay s chart and regarded as the most effective tool for heating to restore thermal comfort in a building whereas 47% as a passive heating is achieved from Givoni s chart and 4% from Mahoney table. In the Givoni chart, natural ventilation represents 2% of the year whereas Olgyay s chart represents about % of the year and E-62

a passive cooling strategy of Mahoney s method represents about 4 % of the year as illustrated in figure (). Moreover, Gaza, located in a temperate zone, was noticed through the analysis of charts and tables, to have changeable climatic times that are happening during the year which in turn guides the thinking to applying a flexible tool tackling the cool climate about 4% of the year by a passive heating tool, and tackling the warm climate about 4% of the year by adopting a passive cooling tool. Percentage 8 7 6 4 Solar radiation Ventilation Comfort Passive heating Figure () Application of (Olgyay-Givoni- Mahoney) methods to Gaza NVM Comfort Passive heating Passive cooling Olgyay Givoni Mahoney Comfort. SIMULATION S MODEL The preceding results clarified the needed percentages of cooling and heating during the year. Therefore, an integrated design with natural ventilation, southern solar panels and floor radiant cooling and heating system, in which pipes of cold and hot water are embedded inside the concrete floor slabs has been implemented to lessen pollution within low energy concepts. Moreover, analyzing the indoor environmental conditions of many parametric study s cases will achieve the optimal case of Pent floor Gaza s human comfort model. Proposed building for simulation consists of two floors and penthouse with entirely approximated gross area of 14m 2. Moreover, ventilation processes are conducted throughout the stairwell. For evaluating the performances of the proposed building, it has been divided into seven zones as shown in figure (4), (). The hottest and coldest day of the year were used for the numerical simulations. Moreover, the list of the conducted simulation conditions is shown in tables (11), (12). Seasonal winds 7 Chimney 6 Bed Room Bed Room Kitc -hen Second floor Dining Room Figure (4) Model s Plans 1 1 First floor Bed Room Bed Room 4 Living Room 2 Hg Hc Hg Hf Hv Insulation (shutters) Panel s Body H H Hc Hf H H Hg Hc Hv H H 1 Figure () longitudinal section of summer s case in the nighttime and winter s case in the daytime E-6

Type Shading devices Ventilation Insulation Solar Panel Case.1 Case.2 X Case.b1 X Case.b2 X X Case.4 X X Case. X X X Case.6 X X X X Wall.A, M.O Wall.A,M.O Wall.A, M.O Wall.A, M.O Wall.B, S.O Wall.B, S.O Wall.B, S.O Table (11) Simulation cases Note: M.O medium openings about 28% of wall area of the model s elevations; while S.O small openings about 18%..1 Results and discussion Case (1) The original case has been typically represented by case (1) as shown in table (11), (12). Moreover, openings are being actualized for the current dimensions M.O. It is noticed that, indoor air temperature has an increased average about (+.1) o C, to reach (.6) o C, while the average outdoor air temperature was (.2) o C as shown in figure (6). Moreover, it is being laid outside the thermal comfort zones. A difference of average air temperature between the basement and outdoor shows (+1.4) o C; while about (+8) o C between the penthouse and the outdoor. Therefore, it is noticed that, the temperature has accumulated gradually from the lower degree of the basement floor to the higher degree at upper floors, which in turn compel one to examine some design tools to evaluate the temperature. In winter 4 Minimum outdoor air temperature was 4 about (4.1) o C in the coldest day of the year and the average air temperature was about (6.9) o C. A difference of air temperature between higher floors and 2 outdoor shows an increase of (+1.) o C that reaches the average temperature to 1 (8.4) o C. The indoor air temperature has an increased average about (+.) o C, to reach average of (7.) o C, while; the basement has an average difference of (-.) o C with average of (6.4) o C as shown in figure (6) i.e. higher floors Type Wall-A Hollow block Wall-B Hollow block Insulation Hollow block Insulated roof Reinf. Concrete Rock wool Foam concrete Floor in case-6 Reinf. Concrete Water layer 1 2 4 6 7 8 9 11 12 1 14 1 16 17 18 19 21 22 2 24 2 Thickness (cm) 2 8 2 1.2 6 Table (12) Construction types Figure (6) Case.1 in summer and winter E-64

have higher temperatures than lower floors, due to the differences of solar gains and thermal performances. Nevertheless, the calculated temperatures lay out the bioclimatic thermal comfort zone. This practice ensures that the existing buildings deal summer rather than winter. Case (2) To achieve healthy buildings, ventilation is needed through summer and winter. This case conducted the ventilation and compared to the non-ventilated case. It is noticed that the accumulated heat inside the living spaces is being decreased during morning times and nighttimes to have a difference of up (-2.7) o C, (-1.6) o C in the basement and (-.2) o C in the penthouse as shown in figure (7). Therefore, ventilation has obviously affected and activated the air to lessen a gradient of temperature. In winter Being compared to the original case, it has been noticed that ventilation reduced the average temperature inside spaces of (-.4) o C. Therefore airtight buildings as shown in figure (7) are desirable. Therefore, sizing orifices are a significant study and should be studied for achieving more distinctive thermal comfort. Case (b1) Shading devices with wall type-a with the absence of ventilation are being practiced in this case to emphasize the effect of shading devices by reducing the transmitted solar radiation especially during hot and sunny days. This practice has been compared to the original one to examine shading devices. Therefore, a significant 4 2 1 4 2 1 4 2 1 1 2 4 6 7 8 9 11 12 1 14 1 16 17 18 19 21 22 2 24 2 Figure (7) Case.2 in summer and winter 1 2 4 6 7 8 9 11 12 1 14 1 16 17 18 19 21 22 2 24 2 Figure (8) Case.b1 in summer and winter 1 2 4 6 7 8 9 11 12 1 14 1 16 17 18 19 21 22 2 24 2 Figure (9) Case.b2 in summer and winter E-6

difference of temperature of up (-2.6) o C shows an improvement in the penthouse and (-.6) o C in living spaces as shown in figure (8), while in winter there is almost no difference due to the altitude angle, which causes a capability for penetrating the spaces. Case (b2) For mitigating the thermal environment of indoor spaces, it has combined the ventilation with walls type-a and the shading devices, which reduce the solar radiation in the building during the summer season. This practice is compared to case (1) and it is noticed that the temperature is being reduced to (-2.9) o C in living spaces, (-1.8) o C in the basement and (-4.7) o C in the penthouse as shown in figure (9). Moreover, shading devices prevent the solar radiation from penetrating while ventilation improves the thermal environment. Therefore, temperature is reduced inside spaces to (-.2) o C. In winter The shading devices have almost no effect during winter, while ventilation should be controlled during the winter case, It has been noticed that temperature in living spaces has been 4 2 1 4 2 1 1 2 4 6 7 8 9 11 12 1 14 1 16 17 18 19 21 22 2 24 2 Figure () Case.4 in summer and winter reduced to (-.4) o C and (-.6) o C in the penthouse as shown in figure (9), while at the base case it showed an improvement unlike this case due to the ventilation performances. Case (4) For improving the thermal environment of indoor spaces, insulation within walls-b and roofs, shading devices and small openings are being conducted. Moreover, this case is carried out with the absence of ventilation in both cases. Comparing this practice to the original case, a gradient temperature is improved of up (-1.8) o C on living spaces and (- 4.) o C on penthouse s space, due to the efficiency of shading devices and to the insulation, which is reducing the heat transfer. Therefore, temperature is improved inside spaces as shown in figure (). In winter It shows an improvement of about (+.7) o C in living spaces and (+1.) o C in the upper spaces as shown in figure (). Therefore, it indicates that there may be room for modest modification of Mahoney data. For example utilizing insulated roofs and walls 1 2 4 6 7 8 9 11 12 1 14 1 16 17 18 19 21 22 2 24 2 Figure (11) Case. in summer and winter E-66

with small windows is more convenient, i.e. insulation proved to be the way for maintaining the indoor thermal environment and reducing heat transfer. Case () Properly, the pervious case (4) is being conducted with ventilation but without high technology evaluations such as exploiting the solar energy by solar panels. It has been compared to the current situation during the years and has been noticed. Obviously, an improvement of temperature about (-.87) o C is being shown in living spaces, (-1.92) o C in the basement, while about (-6) o C in the penthouse. The temperature in living spaces reached average of (1.8) o C, (29.8) o C in the basement spaces and (2.16) o C in the penthouse as shown in figure (11). Generally, the average indoor temperature considered about (1.) o C. Temperature is decreased due to the smaller openings dimensions with the shading devices, thermal massive walls and natural ventilation, which in turn reduced the indoor temperature. Therefore, the natural tools could mitigate the climatic severe problems of Gaza. Moreover, this practice has been interpreted and joined strongly with Mahoney s recommendations. In winter The ventilation negatively affected the interior spaces, while opposite occurs where insulation is used. Thus, a small improvement of temperature about (+.) o C is being shown in the living spaces and kept the internal temperature stable as much as possible as shown in figure (11) due to the same earlier interpretations, and this case still tackled only warm temperatures. Case (6) The previous case () integrated solar panels (6 m 2 ), floor pipes on the first and the second floor, an automatic pump and shutters. Water flows into floors through embedded pipes. This system is supported by an automatic pump, which works during the summer s nighttimes. Moreover, a sensor is used for controlling movement of shutters, which are shutting the panels during the daytime and opening them during the nighttime. Comparing this case to the original one, it has been noticed that an improvement in temperature of (-4.4) o C in living spaces to reach maximum average of (.8) o C and about (-7) o C in upper spaces to reach maximum average of (1.) o C as shown in figure (12a). Moreover, water temperature of panels was cooler than indoor spaces by (-2.) o C, thus it has enhanced the natural cooling system inside spaces. Therefore, it is reasonable to exploit and utilize the solar panels to reduce the gradient 4 8 6 4 2 28 26 24 22 1 2 4 6 7 8 9 11 12 1 14 1 16 17 18 19 21 22 2 24 2 outside Temp basement Stack Stair First floor second Floor pent H Figure (12a) Case.6 in summer 2 1 1 2 4 6 7 8 9 11 12 1 14 1 16 17 18 19 21 22 2 24 2 Figure (12b) Case.6 in winter E-67

temperature. In winter Shutters shut the panels during the nighttime and will open them during the daytime with running water in the pipes during the daytime. Comparing this case to the original one, it is noticed that a considerable improvement of temperature of (+1.) o C inside the building. Therefore, this practice successfully tackled the heating system of living spaces during the cold weather, as shown in figure (12b). 6. SUMMARY AND RECOMMENDATIONS For achieving the thermal comfort zone of the original case, it was noticed that the needed temperature of [(6.) o C cooling, (1.) o C heating] in living spaces, where in the case (), consists of (shading devices, insulation, ventilation and small openings with double glass panes), required [(2.2) o C cooling, (1.4) o C heating], but in the case (6) it was noticed that [(1.8) o C cooling, () o C heating]. Accordingly, results of Gaza are satisfied; hence the required energy to cover a difference of temperature was low. Therefore, the most effective parameters have been gradually assembled to develop the thermal environment of indoor spaces in summer were Ventilation, insulation, solar shading and shading devices ; while in winter were the solar panel and thermal insulation. Therefore, assembling the most effective and natural parameters, which developed the thermal environment of indoor spaces is desired to lessen the environmental pollution with low energy consumption. Accordingly cases () and (6) have achieved high thermal environment with its positive impact in terms of sustainability. Therefore, it is recommended to adopt them through the design processes. Moreover, design s characteristics of cases (), (6) are economic affordability, applicability and reliability, i.e. the most effective strategies of green s design have been maintained for Gaza city. 7. REFERENCES [1] Palestinian National Authority, Regional Plan for Gaza Governorates, Ministry of Planning and International Cooperation, Vol.1, (1998), pp 22-. [2] Adnan Enshassi, Site Organization and Supervision in Housing Projects in The Gaza Strip, International Journal of Project Management (U.K), Vol.1, No.2, 1997, pp 9-99. [] Ali Sayigh, A.Hamid marafia Thermal Comfort and the Development of Bioclimatic Concept in Building Design, Renewable and Sustainable Energy Reviews, Vol.2, 1998, pp -24 [4] Olgyay V. Design with Climate Bioclimatic approach and architectural regionalism. Princeton (NJ), Princeton University Press, New Jersey, U.S.A, 196,pp 17-7. [] Givoni B. Climate Considerations In Building And Urban Design, Van Nostrand Reinhold, U.S.A, 1998,pp 2-4. E-68