SGM Engineering, Inc.

Similar documents
Agenda. Understanding the three basic piping systems. Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations (VPF)

Large University Central Chiller Plant Design Considerations

Chilled Water Distribution Systems. APPA Institute for Facilities Management New Orleans, LA January 19, 2016

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation

District Cooling Sustainable Design. Presented by George Berbari CEO of DC PRO Engineering

Condenser Water Heat Recovery"

WHITE PAPER. Chiller Plant Optimization - A Practitioner s Perspective. Abstract

AR No. # Efficient Irrigation

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne

Ground-Coupled Heat Pump And Energy Storage

Chilled Water Plant Redesign

Use of Building Automation Systems for (Retro)Commissioning

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants

Central Chiller Plants

5/7/2012. Agenda. What is High Performance? Ensuring a Successful Transition to Sustainable, High-Performance Operations

Campus-Wide Cooling Plant Load Analysis & Thermal Energy Storage (TES) System Concept Engineering Study

Field Accuracy of Temperature Measurements in TAB Work Andrew P. Nolfo, PE

Intelligent Process Cooling Technology Saves on Water and Energy, Improves Productivity

Varying Views. Variable-primary flow chilled-water systems are of. on Variable-Primary Flow WHAT IS VARIABLE-PRIMARY FLOW? >>>

Pump selection: a real example

Thermal Storage Vessel Sizing

ISPE CASA Energy Management Forum - Energy Management of Capital Projects at Novartis

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Permanent Load Shifting Program

This session is approved for 0.2 IACET or 1.5 PDH. Many states accept this for Professional Continuing Education.

REPORT DOCUMENTATION PAGE

B. System Design and Performance Requirements

Persistence Tracking in a Retro-commissioning Program

CHILLED WATER DISTRIBUTION SYSTEM

Chilled Beams. The new system of choice?

Secondary loop chilled water in super high-rise

Secondary loop chilled water in super high-rise

Eco-Flow - C VARIABLE FREQUENCY DRIVE PRODUCT BROCHURE. for Commercial Swimming Pools & Water Feature Pumps. H flow 2. Pool & Spa Products Division

Innotech is a registered Trademark of Mass Electronics Pty Ltd Copyright 2013 Mass Electronics Pty Ltd

Texas Hospital. Central Plant Redesign. Central Utility Plant SECOND PLACE HEALTH CARE FACILITIES, EXISTING 2013 ASHRAE TECHNOLOGY AWARD CASE STUDIES

Building Automation Systems

Thesis Proposal. Park. Findlay 12/10/2010. Connor Blood

BUILDING FOR THE FUTURE

Mission Critical Commissioning for Healthcare Facilities

Implications of Measured Commercial Building Loads on Geothermal System Sizing

Pacific Energy Center

Doubling Down on Not Balancing Variable Flow Hydronic Systems BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE

Planning for Biomed Facility Puts Energy Efficiency Under Microscope

By Mark M. MacCracken, P.E., Member ASHRAE

South Carolina Society for Hospital Engineers

LEED Commissioning and Actual Energy Use. John Kokko, P.Eng. LEED A.P. Vice President Enermodal Engineering

FlowSet. Balancing Procedure

Chilled Water System Optimization

Chiller Optimiser Technical Specification

Sustainable Maintenance Best Practice: Energy Efficiency in the Carbon Free World. Michel Abi Saab. Team Leader, Energy Efficiency LEED AP, CEM, CMVP

A chiller as unique as your needs. YORK YVAA AIR-COOLED SCREW CHILLERS

NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.40

Booster Pump Fundamentals. By: Bill Baglot

PRESENTATION BY: Sean P. Murray Energy/Facility Use Manager St. Lucie County Public Schools. Art Munns Senior Project Engineer OCI Associates, Inc.

Cogeneration. Thermal Chillers. and. .. ASHRAE National Capital Chapter. Arlington, VA 10/10/2012

Financial Validation Assessment Report

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training

Knowledge is Power. Belimo Energy Valve

Indiana University Glick Eye Institute. LEED Measurement & Verification Plan

ABSTRACT I. INTRODUCTION II. METHODS AND MATERIAL

Variable Frequency Drives Opportunities in Agriculture

Thermal Energy Storage (TES) Systems in Educational Facilities

Sub Wet-Bulb Evaporative Chiller

Thermal Energy Storage

Safer, More Efficient Combustion Control for Fired Heaters

Geothermal Comfort Systems

Residential Swimming Pool Heating with Geothermal Heat Pump Systems

Equipment Design. Detailed Plant Conceptual Design. Version 9.0

Ice-enhanced Air-cooled Chiller Plant. An EarthWise System from Trane

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m.

Motor Systems Optimization Case Studies in the Peoples Republic of China

MAXE YST Steam-Turbine Drive Chillers

e-hmseries STAINLESS STEEL HORIZONTAL MULTI-STAGE PUMPS BROeHM R2

University of Central Florida Main Campus. Chilled Water. Service and Meter Installations Requirements. Issued January 26 th, 2017.

TruTech Technical Training

Advantages of Financing Continuous Commissioning As An Energy Conservation Retrofit Measure

CHILLED WATER PRODUCTION SUB-ELEMENT

UC Irvine Energy Efficiency Energy Storage Energy Optimization. Matt Gudorf CEM, LEED AP Assistant Director Energy, Engineering, and Inspection

Model Based Building Chilled Water Loop Delta-T Fault Diagnosis

Pressure Independent Valve Systems. ASHRAE Seminar College of the North Atlantic, Doha, Qatar 20 th April 2013

Modeling for LEED. Refer to Additional LEED credits on page 6 90 for a list of credits TRACE 700 may help to achieve.

Robert E. McMains Date Robert E. McMains Date

Fiberglass Cooling Towers

Marketing Guide FOR. Titus Vertical Stack Fan Coil Risers

A Discussion of Natural Gas Pipeline System Efficiency. Gas/Electric Partnership Houston, Texas February 11, 2010

Saving Water With Cooling Towers

Empire State Building PY 2 M&V Report. Empire State Building. Performance Year 2 M&V Report March 1, 2013 Rev.1 (August 15, 2013)

Thermal Mass Flow Meters Help Reduce Energy Costs and Enhance Emissions Monitoring Systems

Life Cycle Costing for HVAC Systems

The purpose of this paper is to bring some additional understanding to the dynamics of variable flow chilled

A Technical Perspective on Controlling Legionella in Building Water Systems

Energy Conservation at the University of Pittsburgh - FY2014 and Beyond

M&V Plan for DG/CHP System

University of Virginia

METHODOLOGY FOR ENERGY AUDITS IN POWER PLANTS REGARDING ANALYSIS OF ELECTRICAL ENERGY CONSUMPTION

AALSO Summary of Formulas needed for Levels I, II and III.

Recommissioning Energy Savings Persistence

TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series

Energy Savings. Performance contracting installs energy. costs, paid for out of guaranteed energy savings from your existing operating budget.

Transcription:

SGM Engineering, Inc.

1. What is a typical Central Energy Plant consists of? BAS controls, chillers, pumps, cooling towers, electrical distribution, piping, chemicals, heating systems, and generators. 2. How to scope and define a CEP project? What is CEP and why do we need CEP? Create utility master plan Short term and long term needs Budget Warranty and service contracts (in-house or outsource)

3. What is the benefit of BAS for large operation? BAS could be a BACnet, Lonworks and Modbus. Monitors total consumption in $, BTUH, KW per hour, per day, per month and per year. This is good tool for DMS. Would have a chart as a comparison between current and previous years. Would display hours of operation for each chiller, pumps, and cooling towers. LEAD /LAG must be implemented. BAS should not allow the chillers to cycle more than twice per hour. Low flow cut-off must be on primary alarm system.

4. How REVIT lod400-500 can integrate with BAS? Construction and Building Operation. The final level of development represents the project as it has been constructed including as-built conditions. The model is configured to be the central data storage for integration into building maintenance and operations systems. LOD models will include completed parameters and attributes specified in the owners BIM deliverable specification.

A proper chiller plant operation requires: A written SOP(standard operating procedure). However: do not rely on operators to program or analyze the system. It doesn t work like that. Always specify maintenance friendly system. Primary-secondary pumping systems are easier to understand and use, yet variable primary systems can save a lot of pumping energy. Even though larger plants can be intimidating, they should be considered single stages of cooling and allow for integral controls to handle each plant. Best way to control pumping still is with differential pressure sensor, but location of the sensor is of utmost importance. Chillers are always controlled with temperature. Here is when chiller optimization come into the picture because these temperature and pressures have to be tested for efficiency. An over pressurized or under pressurized system can cost the owner and reduce life of the system. In order for larger plants to work properly and back each other up, system must have a true loop. The flow velocity in the loop should NOT TO EXCEED 7 FEET PER SECOND. Building s chilled water tertiary pumps would operate efficiently if they are VSD. If thermal storage is owner s preference, full ice storage is easier understood by the maintenance staff than partial ice.

Common causes of low ΔT syndrome include: Improper Coil and Control Valve Selection: Oversized or undersized coils. Dirty Coils (Air and Water Side): Reduces the overall heat transfer capacity of the coil, which results in the control system opening two-way control valves. This leads to increased flow and decreased return water temperature. Mismatched Design Conditions: System components designed for different chilled water ΔT can result in lower than plant design return water to the plant. Use of Three-Way Control Valves: Allows bypass of chilled water around coil at part load resulting in lower return water temperatures for all conditions except design. Low Supply Air Temperature Set Point: Arbitrarily lowering the supply air temperature set point below design can lead to uncontrollable operation and result in lower return water temperature.

Common causes of low ΔT syndrome include: System Differential Pressure Above Shut-Off Valve: Forces control valves open, leading to unwanted flow through coils, increasing system flow and resulting in lower return water temperature. Coil Piping Configuration: Coils must be piped such that water is counter-flow to air. If they are piped in reverse, the heat transfer efficiency of the coil will decrease resulting in lower chilled water return temperatures. Plant Chilled Water Mixing: Flow from chilled water supply to chilled water return through the plant neutral bridge or de-coupler occurs at part load conditions when the primary loop is pumping more than the secondary loop (primary-secondary). Building De-Coupler Mixing: Flow from chilled water supply to chilled water return through the building neutral bridge or de-coupler occurs in similar manner as with the plant neutral bridge.

The following is a list of the advantages to implementing a primary-secondary system: 1. Constant Flow Through Evaporator: The primary-secondary system maintains a constant flow through the evaporator of the chiller. This eliminates the concern for chiller performance and inadvertent shutdowns. Chiller capacity controls have traditionally lagged behind sudden changes in load. If the load suddenly drops, the chilled water supply temperature drops until the controls catch up. This sudden drop in supply temperature causes nuisance trips, due to low evaporator temperature. This is less of a concern today than it was in the past because of microprocessor-based controls. 2. Simplified Controls: Controls within a primary-secondary system are relatively simple and well established. Typical chiller controls packages do not have difficulty with the staging sequence for the chillers and responding to varying loads.

Advantages to implementing a primary-secondary system continued: 3. Past Experience: The primary-secondary system is a well established operational philosophy and plant personnel are familiar with its operation. In addition, this pumping scheme has been proven reliable if operated properly. 4. Divided Hydraulic Head: By dividing the total dynamic head between two hydraulically independent loops, the required motor size for each pump type (primary and secondary) will be smaller when compared to a direct-primary system. This also reduces the risk that the system discharge pressure will exceed the design of equipment, piping, and valves in the buildings.

Disadvantages to implementing a primary-secondary system : 1. Does not Resolve Low ΔT Syndrome: The primary-secondary system does not allow an increase in flow through the evaporator above design and; therefore, does not adjust to chilled water return temperatures that are lower than design. As the cooling load decreases, the secondary pump VFDs will ramp down to a lower speed, thus allowing these pumps to produce less flow. The constant volume circulation pumps will then over pump the primary loop causing supply water to flow through the neutral bridge and mix with return water. This mixing lowers the return water temperature and deteriorates the system ΔT as described previously

Disadvantages to implementing a primary-secondary system continued: 2. Capital Investment: More piping for secondary/primary system versus primary system. 3. Higher Operating and Energy Costs: The primary-secondary system uses both constant speed and variable speed pumps to circulate chilled water through the plant as well as the distribution system. Because the primary loop will always have a constant flow, energy is wasted within this loop at off-peak loads. In addition, this pumping scheme does not allow adjustable flow through the chillers and is subject to the part load operational inefficiency described above. These features and the need for two sets of pumps will generally yield higher energy and operating costs per annum when compared to the direct-primary system.

Disadvantages to implementing a primary-secondary system continued: 4. Requires More Plant Space: Two sets of pumps are needed to circulate chilled water through the chiller evaporator and the chilled water distribution system. This requires more floor space, more spare parts, and results in higher capital costs and pump maintenance costs when compared to the directprimary system.

4-Pipe system VS 2-pipe system 2-pipe system-chws/chwr/hws/&hwr The operation is based on outside /outdoor temperature. It uses chilled water or hot water in the same pipe. Its less construction cost than 4 pipe system. It requires more control valves for change-over for hot or chilled water. Extensive Sequence of operation and control setting to avoid damages. It requires more PM work especially on control valves. 4-pipe system- 2 pipe for CHWS/CHWR and 2 pipe for HWS/HWR Higher construction cost than 2 pipe system 2 separate coils (CHW & HW).

4-Pipe system VS 2-pipe system Alternative solutions: Regarding chilled water/hot water 2-pipe system: It depends on geographical location. 2-pipe system are cost effective for geographical location with 100 Heating Degree Days or higher per year. Less changeover from heating to cooling or vice-versa. To calculate HDD, take the average of a day's high and low temperatures and subtract from 65. For example, if the day's average temperature is 50 o F, its HDD is 15. 4-pipe system are more cost effective for Hospitals, Labs similar places for high heating demand. Use of electric duct heaters for space heating and 2-pipe system for chilled water purposes.

4-Pipe system VS 2-pipe system Conduct a life cycle cost analysis to determine: 1. $Installation and operation(o&m) cost of 4-pipe system using chillers, and boiler per fiscal year. 2. $Installation and operation (O&M) cost of 2-pipe system using chillers, and boiler per fiscal year. 3. $Installation and operation (O&M) cost of 2-pipe system using chillers, and electric duct heaters per fiscal year.

Heating Degrees in Central Florida Base Year (2012) Comparison Year (2017) Comparison Percentages Month HDD CDD TDD HDD CDD TDD HDD CDD TDD January 12 359 371 5 477 482 32% 29% February 7 493 500 0 513 513 4% 2% March 0 677 677 0 607 607-10% -10% April 0 705 705 0 766 766 8% 8% May 0 869 869 0 946 946 8% 8% June 0 859 859 0 957 957 11% 11% July 0 1001 1001 0 1037 1037 3% 3% August 0 1003 1003 0 1070 1070 6% 6% September 0 945 945 0 965 965 2% 2% October 0 814 814 0 820 820 0% 0% November 0 470 470 0 642 642 36% 36% December 2 470 472 1 509 510 8% 8% Annual Total 21 8665 8686 6 9309 9315-71% 7% 7%

How to execute a successful CEP project? A clear scope of work, Includes: 1. Schedule 2. Budget 3. Short-term and long-term plan for the CEP. 4. A thorough selection process. Suggest mandatory attendance. Select firms who has track records for similar projects 5. Have the design team to have weekly if not daily presence on the job site during construction. 6. Monitor the energy consumption on regular basis. 7. Commission the CEP under separate contract to act as your eyes and ears 8. Extend the warranties on major components 9. Ask Local power companies for energy rebates.

Useful formulas Pump Hp = (GPM x Total Head in ft. water ) / (Pump Eff. x 3960) Chiller Design: Recommend minimum of 12 F Delta-T. kw/ton = 12/EER 1 Ton = 12,000 BTU/HR Tons = (GPM x Delta T x specific heat* x specific gravity*) / 24. where* for fluids other than water. Tower System Design Formulas Cooling Tower = 3 GPM per ton for 10F Delta T. 1 Tower Ton = 15,000 BTU/ hr. Tower Ton = GPM x ΔT/30 Chiller Tower = 2.4 GPM / ton 1 Chiller Ton = 12,000 BTU / hr. Chiller Ton = GPM x ΔT / 24 Rule of Thumb: There are 1.8 gallons per hour of evaporation per ton of cooling. Evaporation of 1 pound of water takes about 1,000 BTU of heat. Evaporating 1.8 Gallons of water requires 15,000 BTU of heat. Role of Project Manager

8 F delta-t, requires 2,250 GPM coil flow and all 3 chillers. Resetting temperature by 3 F to 41 F results in 10 F delta-t, coil flow of 1,800 GPM, and the need to operate only 2 chillers.

This system ensures that every load will be satisfied and guarantees that the design Delta T is maintained at all times.

Major Causes Solutions / Reduce Effects Dirty Coils Controls Calibration Leaky 2 Way Valves 3 Way Valves at end of Index Circuit Address the Cause Clean Coils Calibrate Controls Occasionally Sealed Proper 2 way valves and maintain them. No 3 way valves in design Find and correct piping installation errors Increase delta T across chillers With CHW re-set (down) Use Variable Speed Chillers & sequence to operate from 30% to 70% load Use VPF Systems (mitigates energy waste in plant)-vector performance factor Header pumps or cross connect piping.more pumps than chillers If dedicated pumping, over-size (design at 80% speed)

Conclusions Critical Factors for Successful Project Managers 1. Must have Management Support. 2. Agree on the goals and objectives. 3. Effective Communications. 4. Manage the work effectively. Lead by example 5. Sustainable design and lowest O&M cost