GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

Similar documents
TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

General Requirements. Technical Specifications for Insulators of Transmission Lines

SEAL & SIGNATURE OF THE TENDERER

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES

TECHNICAL SPECIFICATION

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

TECHNICAL SPECIFICATION OF MS TOR BARS FOR TRANSMISSION LINES

TECHNICAL SPECIFICATION FOR MS BEAMS 116X100 11MTR LONG FOR SUB-STATIONS

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

TECHNICAL SPECIFICATION OF TOWER MATERIAL FOR132KV-PANTHER TRANSMISSION LINE

TECHNICAL SPECIFICATIONS

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv

CONTENTS. IEC Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60

INSULATORS NEW. See page J-4 for more information.

Polymer Station Post Insulators for 69 to 345 kv Applications

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

TECHNICAL SPECIFICATIONS OF SUB STATION STRUCTURES

TECHNICAL SPECIFICATION OF HIGH AMPACITY ALLOY CONDUCTOR ZEBRA/MOOSE CONDUCTOR FOR TRANSMISSION LINE

TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED)

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

P.V.C. INSULATED UNARMOURED COPPER CABLES

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS

Energy Division Insulators

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

NPS/002/001 Technical Specification for Earthing Materials

TECHNICAL SPECIFICATION FOR CONDUCTORS

Technical Specification for LV ABC Fuse Switch Disconnectors

BIDDING DOCUMENT. Tavua 33 kv Substation Extension. Supply of 36kV Single Break Disconnectors, Structures and Accessories TENDER NO: MR 170/2015

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

Polymer Post Insulators for 46 to 500kV Applications

Polymer Suspension Insulators 69kV to 765kV

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

TENDER NO. MGVCL/PP/J1/5005/AB SWITCH/ TENDER NO. MGVCL/PP/J1/5005/AB SWITCH/

SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134

TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE

Technical Specification for Live Line Tap Connectors

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

Shackles. Applications. Range. Design. CAD drawings. Finish

THE KENYA POWER AND LIGHTING CO. LTD

Project number 36B/61109/Ed2. Date of circulation Supersedes document 36/225/MCR. Safety EMC Environment Quality assurance

TECHNICAL SPECIFICATION A.B. CABLE

Pins Insulator. Composite/Polymers Insulators

DATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0

AMERICAN INSTITUTE OF TIMBER CONSTRUCTION AITC

SECTION MECHANICAL EQUIPMENT - GENERAL REQUIREMENTS

Engineered Parts Your Design Our Competence

INSULATED JOINTS. Monolithic Joints for Electrically Isolating Pipelines

High Quality Porcelain Insulators for Transmission Lines

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Division Office,Jamla, 220 kv Sub-Station Compound

STANDARD SPECIFICATION FOR CRIBLOCK CONCRETE CRIBWALL

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS

Electrical Metallic Tubing (EMT) Fittings

GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

European Technical Assessment ETA-10/0422 of 08/01/2016

SECTION PLATE CONNECTED WOOD TRUSSES

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

D D TYPE A1, A2 & B MICHIGAN DEPARTMENT OF TRANSPORTATION 5-40 CONNECTION. L4" x 4" x 3/8" Brace. C8 x 4.25 Strut. WT9 x 17.5.

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Technical information

EVALUATION REPORT. PFC-5551 Reissued April 1, Filing Category: DESIGN Steel (038)

Why do Transmission Asset Owners Need a Transmission Restoration System (ERS)? Transmission Line Emergencies Do Occur

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer

Section 906. STRUCTURAL STEEL

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

úê üßµö ÖãÆü ü ¾Ö³ÖÖÖ - III

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

Penn State Forestland Management Office Multi-Strand High-Tensile Wire Fence Specifications

SECTION PACKAGE BOOSTER PUMP STATIONS

Technical specification for Rubber Injection Moulding Machine

SECTION 1 - INTENT, SYSTEM REQUIREMENT, DESIGN CRITERIA AND SCOPE

Supporting CE-Marking Obligations of Our Customers: The Role of the Galvanizer

15 kv EPR Insulated, Jacketed, URD Cable

1. Cast-in-place concrete is specified in Section

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D

High power chip resistors < Wide terminal type > LTR series

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

STOCKHOLDING DOCUMENT MANAGEMENT SERVICES LIMITED FORMERLY KNOWN AS SHCIL PROJECTS LIMITED

ISO INTERNATIONAL STANDARD. Elastomeric seismic-protection isolators Part 2: Applications for bridges Specifications

TECHNICAL SPECIFICATION FOR PRESTRESSED CEMENT CONCRETE POLES ( F.O.S. 2.5) FOR 11 KV AND LT LINES ( REC SPECIFICATION NO.

ETALLODOMI S.A. Head Office: 12, Kastorias str Athens GREECE. Main Warehouse: 49, Agiou Orous str. GREECE

4 1 /2 MARK 73-5 AMERICAN FLOW CONTROL. It s What We Know. AMERICAN-DARLING FIRE HYDRANT AMERICAN-DARLING 4 1 /2 MARK 73-5 FIRE HYDRANT

Lattice Beam User Guide USG001-

Surge arrester 3EB4. with polymeric composite housing for operating aboard traction units

Electric Service Standards

SECTION MECHANICAL SPECIFICATION GRIT COLLECTION EQUIPMENT

Introduction Introduction

2. TEST RECORDS: All records of tests and analysis shall be kept in suitable forms approved by the Bureau.

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

Anchor HSA Fastening. Technology Manual HSA. Stud anchor. Version /

Transcription:

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220, 132 & 66 COMPOSITE SOLIDCORE STATION POST INSULATORS GETCO/E/2,1,6 TS 1-Composite BPI/R0 May15 Page 1 of 10

SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before submitting your bid. 1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in AutoCAD format and manuals in PDF format, for offered item shall be submitted. Also the hard copies as per specification shall be submitted. 2. The bidder shall submit Quality Assurance Plan for manufacturing process and Field Quality Plan with the technical bid. 3. The bidder shall have to submit all the required type test reports for the offered item. In absence of this confirmation, the evaluation shall be carried out accordingly as non-submission of type test reports. 4. The bidder must fill up all the point of GTP for offered item/s. Instead of indicating refer drawing, or as per IS/IEC, the exact value/s must be filled in. 5. All the points other than GTP, which are asked to confirm in technical specifications must be submitted separately with the bid. 6. The bidder is required to impart training in view of manufacture, assembly, erection, operation and maintenance for offered item, at his works, to the person/s identified by GETCO, in the event of an order, free of cost. The cost of logistics will be bear by GETCO. 7. Please note that the evaluation will be carried out on the strength of content of bid only. No further correspondence will be made. 8. The bidder shall bring out all the technical deviation/s only at the specified annexure. 9. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE). Page 2 of 10

QUALIFYING REQUIREMENT DATA (For Supply) Bidder to satisfy all the following requirements. 1) The bidder shall be Original Equipment Manufacturer (OEM). The offered equipment have to be designed, manufactured and tested as per relevant IS/IEC with latest amendments. 2) The minimum requirement of manufacturing capacity of offered type, size and rating of equipment shall be 3 times ( for 220 kv,132 kv & 66 kv) tender / bid quantity. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE). 3) Equipment proposed shall be of similar or higher rating and in service for a minimum period of THREE (3) years and satisfactory performance certificate in respect of this is to be available and submitted. 4) The bidder should clearly indicate the quantity and Single Value Contract executed during last FIVE (5) years, for the offered equipment. Bidder should have executed one single contract during last five years for the quantity equivalent to tender / bid. The details are to be submitted in following format, Sr. No ITEMS SUPPLIED TO ORDER REFERENCE No. & DATE ITEMS QUANTITY ORDER FULLY EXECUTED. YES/NO STATUS, IF ORDER UNDER EXECUTION REMARK 5) Equipment offered shall have Type Test Certificates from accredited laboratory (accredited based on ISO/IEC Guide 25 / 17025 or EN 45001 by the National accredition body of the country where laboratory is located), as per IEC / IS / technical specification. The Type test reports shall not be older than SEVEN years and shall be valid upto the expiry of validity of offer. Page 3 of 10

1 SCOPE TECHNICAL SPECIFICATION FOR 400/ 220/132/66 kv COMPOSITE SOLIDCORE STATION POST INSULATORS This specification provides for the supply of 220, 132, & 66 kv composite solid core station post insulators required for the 220 kv, 132 kv or 66 kv substations at various sites in State of Gujarat. 2 DESIGN The composite solid core station post insulators required for sub-station bus support purpose shall consist of a load bearing cylindrical insulating solid core made of resin impregnated fibers, a housing (outside the insulating solid core) shall be made of elastomeric material (e.g. silicon or ethylenepropylene) and end fittings attached to insulating core. Composite solid core station post insulators are intended to cater cantilever, torsion, tension and compression loads. The applicable standard shall be IEC 62231:2006 amended up to date. It shall be outdoor type, suitable for operation under tropical conditions, with high temperature, humidity and rainfall. The insulation level should be as under: Power frequency Impulse withstand Item withstand value strength 1 min (dry)/ (wet) (Peak) in (rms) 220 kv solid core post insulator 510/460 kv 1050 kvp 132 kv solid core post insulator 275 kv 650 kvp 66 kv solid core post insulator 165/140 kv 350 kvp The composite solid core station post insulators shall be suitable for outdoor operation and shall be suitable for mounting on lattice. The mounting bolts, nuts and washers shall be in the scope of supply. The successful bidder shall indicate all relevant dimensions and values necessary for identifying and testing the insulator in accordance with applicable standard. Each insulator shall be marked with the name or trademark of the manufacturer and the year of manufacture, Maximum Design Cantilever Load (MDCL). These markings shall be legible and indelible. The transport, storage and installation shall be in line with IEC 62217. 3 PROTECTION AGAINST CORROSION All malleable iron steel work, steel bolts and nuts and flanges shall be hot dip galvanized in accordance with IS: 2629/1966 with the latest amendment thereof. Page 4 of 10

4 ELECTRICAL AND MECHANICAL CHARACTERISTICS OF INSULATORS The design shall be defined by material of core, housing, end fittings with method of attachment, housing layer thickness over core, and diameter of core. Electrically the insulator type shall be defined by its arcing distance, creeepage and housing profile, while mechanically, by its length, core diameter, core material & design and method of attachment. Imported insulator meeting electrical and mechanical characteristics will be accepted if only they are offered against suppliers import license and the transit breakages if any, are also covered by the supplier for replacement of material from their stock. 5 TECHNICAL PARTICULARS Sr. No. Technical particulars of 220, 132 & 66 solid core post insulator (Guaranteed details to be furnished by the bidder in Schedule-A attached with the specification). Description Unit Solid core post insulator 220 kv 132 kv 66 kv 01 02 03 05 06 07 1 Highest system voltage kv 245 145 72.5 2 Height of unit mm 2300+3.5 1500+2.5 770 ± 1 3 Bending strength (approximate failing load): a) Upright 4 Tensile strength (Approximate) 5 Compression strength (Approximate) 6 Torsion strength (Approximate) 7 a) Power frequency flashover voltage (dry) b) -do- (wet) 8 a) Impulse flashover voltage (Positive) b) -do- (Negative) 9 a) One minute power frequency withstand voltage (dry) b) -do- (wet) 800 600 400 Kgf Kgf 8000 7000 3500 Kgf 20000 14000 7000 KgfM. 450 300 200 625 570 1210 1450 510 460 275 275 650 650 275 275 180 155 355 405 165 140 Page 5 of 10

10 Impulse positive/negative withstand voltage 11 Power frequency puncture voltage 12 RIV a) Test V to Ground (rms) b) at 1000 KHz with grading rings 13 (a) Visible discharge 1050 650 350 mv Puncture proof <500 mv 154 Puncture proof --- 105 Puncture proof --- 53 (b) Switching surge p -- -- -- withstand voltage 14 Creepage distance (Approximate) mm a) Total 6125 3625 1815 b) Protected 3065 1815 910 15 Top metal fitting PCD mm 4 holes of 4 holes of 127 ± 0.2 M16 M16 PCD = 127 PCD = 127 16 Bottom metal fitting PCD mm 8 holes of 4 holes of 127 ± 0.2 M18 and M18 and PCD = 254 PCD = 225 17 All ferrous part should be Yes Yes Yes hot dip galvanized to IS:2629/1966 18 Suitable for Hot line Yes Yes Yes washing 1KN = 101.972 Kgs. 6 TESTING The bidder shall clearly state in their tender whether they have in their factory adequate facilities for carrying out type tests and routine tests as specified in related ISS & IEC and its latest amendments. Offers of those firms who have necessary equipment in their factory for carrying out type tests will be preferred. Bidder shall submit all the reports of design tests and type tests in line with IEC 62231: 2006 amended up to date from the NABL laboratory. Those reports shall not be older than Seven years from the date of validity of offer. If the reports are not available from NABL laboratory, bidder shall submit confirmation for carrying out the same in the event of an order, free of cost to GETCO, before commencement of supply, without affecting delivery schedule. Page 6 of 10

All the acceptance/routine tests shall be carried out as per IEC 62231: 2006 (latest amendments). Power Frequency (dry) withstand test shall be carried out on selected samples at the time of Acceptance Test. a) List of design tests: 1) Tests on interfaces and connections of end fittings (cl. 9.1) 2) Load tests on assembled core 3) Tests on shed and housing material 4) Tests on core material b) List of Type Tests: 1. Visual Examination & Verification of dimensions (cl. 9.1) 2. Dry lightning impulse voltage test (cl. 9.2.1) a) withstand voltage procedure with 15 impulses b) 50% flashover voltage procedure 3. Wet Power frequency voltage withstand test (cl. 9.2.2) 4. Wet Power frequency flashover voltage test (cl. 9.2.2.3) 5. Mechanical test a) Cantilever failing load test, b) Specified tensile Test, c) Compression and buckling withstand load test, c) List of Acceptance Tests: The rules for sampling will be in line with cl. 10.1 1) Verification of the dimensions 2) Galvanizing test 3) Verification of specified mechanical loads d) List of routine tests: 1) Visual inspection 2) Tensile load test 7 DEVIATION The offer shall conform in all respects to the above specifications. If not, the deviations shall specifically be brought out in specified annexure XII only, otherwise it will be presumed that the offer conform to above specifications in all respects. 8 SPECIAL CONDITIONS The following information shall invariably be furnished by the tenderer along with the tender, if the same is not furnished along with the tender, the offer may be ignored without making correspondence. a. Name and full address of the manufacturer of composite solid core station post insulators offered. b. Make and Electrical and Mechanical characteristics of post insulators. c. Testing facilities available with the factory for carrying out type tests and routine tests. d. Dimensional drawings with full particulars. Page 7 of 10

e. The list of orders executed for the offered items by the manufacturer of the composite solid core station post insulators giving full details such as voltage, type, quantity etc. f. The un-priced schedule of the offered item shall also be submitted in technical bid. 9 Bidder shall furnish, MQP and FQP along with technical bid. Also drawings shall be submitted for approval in the event of an order. 10 Bidder shall give all the required guaranteed technical parameters as per attached Schedule A. Page 8 of 10

SCHEDULE - A SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 245/145/72.5 kv composite solid core station POST INSULATORS (To be filled in and signed by the Tenderer) Sr. No. Description Unit Guaranteed. Value 1 Highest system voltage kv 2 Name or trade mark of insulator 3 Overall length of unit from flange face to face of end fitting 4 Applicable standard mm 5 Material of core of insulator Diameter of core 6 Material of housing Thickness of housing 7 Housing profile a) Shed overhang b) Shed thickness c) Shed spacing d) Shed inclination e) Shed repetition 8 Guaranteed maximum cantilever load kn 9 Bending strength (approx. failing load): i) Upright 10 Tensile strength (Approx.) kn 11 Compression strength (Approx.) kn 12 Torsional strength (Approx.) kn 13 Buckling load kn 14 a) Power frequency flashover voltage (Dry) b) Power frequency flashover voltage (Wet) 15 a) Impulse flashover voltage (Positive) b) Impulse flashover voltage (Negative) 16 a) 1 min. power frequency withstand voltage (Dry) b) 1 min. power frequency withstand voltage (Wet) kn kv kv kvp kvp kv (rms) 17 Lightning Impulse positive / negative withstand voltage. kvp 18 Power frequency punctures voltage. kv 19 Visible discharge voltage kv Page 9 of 10

20 Radio Interference Voltage Micro Volts 21 Creepage distance (Minimum) : a) Total b) Protected mm mm 22 Dry Arcing distance (Minimum) mm 23 Type of end fitting material of end fitting 24 Top end fitting PCD with hole size mm 25 Bottom end fitting PCD with hole size mm 26 All ferrous parts should be hot dip galvanized to IS:No.2629/1966. 27 Terminal connector details, if indicated in Schedule A of respective tender. -- YES Date: Page 10 of 10