Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S. Patel 1 Hardik M.Patel 2

Similar documents
Modelling of Indirect Evaporative Air Coolers

Theoretical and computational analysis of closed wet cooling towers and its applications in cooling of buildings

Study on the heat transfer characteristics of an evaporative cooling tower B

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

A NOVEL TECHNIQUE FOR EXTRACTION OF GEOTHERMAL ENERGY FROM ABANDONED OIL WELLS

COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS

Performance Analysis of Cooling Tower

Exergy analysis of a flat plate solar collector

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

INVESTIGATION ON THE OPTIMUM DESIGN OF HEAT EXCHANGERS IN A HYBRID CLOSED CIRCUIT COOLING TOWER

Application of a cooling tower model for optimizing energy use

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

Parameters of the Atmospheric Air in the Dimensioning of Industrial Cooling Tower

Design and Analysis of Hydraulic Oil Cooler by Application of Heat Pipe

ENERGY SAVING IN BUILDING USING PCM IN WINDOWS

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014)

INVESTIGATION OF THE THERMAL PERFORMANCE OF A CROSS-FLOW WATER COOLING TOWER WITH DIFFERENT PACKINGS

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System

Performance of a counterflow heat exchanger with heat loss through the wall at the cold end

Ceiling Radiant Cooling Panels

CFD ANALYSIS OF MINI CHANNEL HEAT EXCHANGER USING WATER AS A WORKING FLUID

Cooling Tower Operation

Numerical Simulation of Spray Cooling Gas with High Temperature and Velocity in Compressor Inter-Stage

Study of water falling film over horizontal drop shaped and inverted drop shaped tubes

THE SEAWATER GREENHOUSE AND THE WATERMAKER CONDENSER. Philip Davies* and Charlie Paton

COOLING EFFECT ENHANCEMENT IN MAGNETRON SPUTTERING SYSTEM

Energy Conversion and Management

2. TECHNICAL DESCRIPTION OF THE PROJECT

Heat transfer modelling of slot jet impinging on an inclined plate

Sub Wet-Bulb Evaporative Chiller

Flow and Heat Transfer Characteristics in High Porosity Metal Foams

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.

Copper Micro-channel Loop Thermosyphon. A thesis presented to. the faculty of. the Russ College of Engineering and Technology of Ohio University

Experimental investigations on impaction pin nozzles for inlet fogging system

Abstract. Nomenclature. A Porosity function for momentum equations L Latent heat of melting (J/Kg) c Specific heat (J/kg-K) s Liquid fraction

Performance Analysis of Shell and Tube Heat Exchanger Using Miscible System

INDUSTRIAL COOLING TOWER DESIGN AND OPERATION IN THE MODERATE-CONTINENTAL CLIMATE CONDITIONS

Heat Transfer Correlations for Low Approach Evaporative Cooling Systems in Buildings


OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT

Experimental investigation of single-phase and twophase closed thermosyphon solar water heater systems

Thermal Analysis and Modelling of Thermal Storage in Solar Water Heating Systems

A Solar Wall System Utilized in Rural Houses of Northeast China

Investigations of N 2 O Transcritical Refrigeration Cycle Using Dedicated Mechanical Subcooling. Sanjeev Kumar 1 and Dr. D.K.

Design and distribution of air nozzles in the biomass boiler assembly

ANALYSIS OF REFRIGERATION CYCLE PERFORMANCE WITH AN EJECTOR

A calculation model for Trombe walls and its use as a passive cooling technique

Multi-Variable Optimisation Of Wet Vapour Organic Rankine Cycles With Twin-Screw Expanders

Effect of Twisted Tape Inserts On Heat Transfer in A Concentric Tube Heat Exchanger

Administrative Building Cooling Tower. University of Tennessee Chattanooga

Heat Transfer Simulation of Impinging Jet with Finned Heat Sink

Refrigeration Kylteknik

Ejector Expansion Refrigeration Systems

A Design of the Organic Rankine Cycle for the Low Temperature Waste Heat

PS Modeling airflow in outdoor grain pile aeration systems. Introduction

Critical exergy analysis of counterflow reversibly used cooling towers

Seasonal effect on the performance of counter flow induced draft cooling tower of class800 for 2x250mw

Numerical study of the influence of injection/production well perforation location on CO 2 -EGS system

Study on Heat Exchange Characteristics for PHC Energy Piles

COLD ROOM: Medium Temperature (Chiller) For Meat Storage. LOCATION: Bangkok, THAILAND BY: EMERSON PARTNER+ PROJECT DESIGN GROUP

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

Design of a Solar-Driven Ejector Cooling System

CLOSED-LOOP HEAT EXCHANGER FOR GROUND COUPLED HEAT PUMPS

Estimation of Boil-off-Gas BOG from Refrigerated Vessels in Liquefied Natural Gas Plant

Study and Performance Improvement of Solar Air Heater using Turbo-Ventilator

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

Oil Conservation in Biscuit Industry

Feasibility study of a roof top Solar room heater

Model Based Building Chilled Water Loop Delta-T Fault Diagnosis

Liquid-Solid Phase Change Modeling Using Fluent. Anirudh and Joseph Lam 2002 Fluent Users Group Meeting

Heat Storage Performance of a Honeycomb Ceramic Monolith

Exergy analysis of transcritical carbon dioxide refrigeration cycle with an expander

Design, Fabrication and Experimental Study of a Novel Loopheat-pipe based Solar Thermal Facade Water Heating System

Modeling of a Hot Gas Bypass Test Block for Centrifugal Compressors

ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

Combined Mass and Energy Transients

EFFECT OF THE NOZZLE EXIT POSITION ON THE EFFICIENCY OF EJECTOR COOLING SYSTEM USING R134A

A BASIC IMMERSION FIRETUBE FLOWNEX MODEL

The formation of oscillation marks in continuous casting of steel

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers

Theory Comparison between Propane and Methane Combustion inside the Furnace

HT A COMPUTATIONAL MODEL OF A PHASE CHANGE MATERIAL HEAT EXCHANGER IN A VAPOR COMPRESSION SYSTEM WITH A LARGE PULSED HEAT LOAD

CFD Simulation Studies on Integrated Approach of Solar Chimney and Earth Air Tunnel Heat Exchanger for Building Space Conditioning

DISPLACEMENT VENTILATION

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract

Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System

Fundamental Investigation Of Whole-Life Power Plant Performance For Enhanced Geothermal Systems

THE ITER HEAT REJECTION CHALLENGE.

Sensitivity Studies of a Low Temperature Low Approach Direct Cooling Tower for Building Radiant Cooling Systems

Live Transportation Research and Improvement Initiatives

Energy Recovery Ventilation Equipment

40-Ton Articulated Truck Cooling System Modelling Using STAR-CCM+

Plant Utilities and Energy Efficiency CH505

A STUDY OF MEMBRANE PROPERTIES ON AIR CONDITIONING PERFORMANCE ELIZABETH J. BOYER. B.S., University of Nebraska-Lincoln, 2011 A THESIS

Design of a Small Scale CFB Boiler Combustion Chamber for Laboratory Purposes

THEORETICAL AND EXPERIMENTAL ANALYSIS OF THE EVAPORATIVE TOWERS COOLING SYSTEM OF A COAL-FIRED POWER PLANT

II. SYSTEM DESCRIPTION AND MATHEMATICAL MODELING

Transcription:

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 05, 2015 ISSN (online): 2321-0613 Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S. Patel 1 Hardik M.Patel 2 1 P. G. Student 2 Assistant Professor 1,2 Shri S ad Vidya Mandal Institute of Technology, Bharuch-392001, Gujarat, India Abstract This paper aims to improve the performance of direct evaporative coolers with the help of Maisotsenko cycle called M-cycle. A new indirect evaporative cooler with counter current heat/mass exchanger configuration in which the product air and working air are entirely separated was developed in this research by design and experimental investigation. A new heat/mass exchanger using counter current flow configuration was designed by modified Ɛ- NTU method in terms of geometrical sizes with operating conditions. The theoretical results indicates that the heat/mass exchanger achieve wet bulb and dew point effectiveness approximately 115.21% and 84.12% respectively. Based on theoretical results, a prototype of heat/mass exchanger was constructed and the result indicates that the wet bulb and dew point effectiveness of experimental prototype ranged from 49.04% to 107% and 33.92% to 75.37% respectively. It is also concluded that this system is suitable for regions with dry, mild and hot climate and water is use as cooling agent so the pollution is vomited compared to conventional mechanical vapour compression refrigeration in which refrigerant use as cooling agent. Key words: Dew point cooling, Effectiveness, Evaporative Cooling, Maisotsenko Cycle I. INTRODUCTION In hot and/or arid regions air conditioning has become part of the people s life need. During the hottest summer period when air conditioning is in full operation, many cities experienced difficult power over loads that often led to unwanted grid cut-off. So, there is growing pressure on energy saving and carbon emission in building sector, seeking for routes to reduce fossil fuel consumption and increase utilization of natural or renewable energy during air conditioning process. These factors led to the active development of evaporative air coolers. Air coolers based on evaporative cooling consume less energy compared to traditional compressor systems. They are also more ecological and environmental friendly systems. The conventional direct evaporative cooling system is used for the cooling purposes in the dry and hot regions. This type of system gives the sufficient cooling, but the increased humidity of the air gives the feeling of discomfort. The other way to overcome the problem of increased humidity is use of indirect evaporative cooling system, but the cooling obtained with this system is less. For overcome these limits the former soviet scientist Valery Maisotsenko improved evaporative cooling technology and called the resulting cycle as Maisotsenko cycle (M-cycle). II. EVAPORATIVE COOLING SYSTEM Fig. 1: Types of evaporative cooling system A. Direct evaporative cooling (DEC): Direct Evaporative Cooling (DEC) keeps the primary (product) air in direct contact with water, which causes evaporation of the water and so the reduction of temperature of the air. As a result, the vaporised water is added into the air, which creates wetter air condition and causes discomfort to the occupants. The working diagram of direct evaporative cooling and the thermal process representing on the psychrometric chart are shown in Fig. 2. Fig. 2: Working diagram of DEC system B. Indirect evaporative cooling (IEC): In an IEC, water is separated from the primary (product) air using the heat exchanging plate. During operation, evaporation of the water occurs in one side of the plate All rights reserved by www.ijsrd.com 138

where the secondary (working) air flows; while the primary (product) air flows across the other side. Here, evaporation of the water causes the temperature reduction of the plate, so heat transfer between the primary air and the plate. Meanwhile, the vaporised water is taken away by the secondary (working) air across the wet-side of plate. By doing so, the primary air is cooled but no moisture is added into it, which is ideal more attractive option for the purpose of building air conditioning. Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Fig. 6 Schematic of the M-cycle counter flow heat and mass exchanger [1] Fig. 3 Working diagram og IEC system III. M-CYCLE IEC SYSTEMS For increasing cooling performance of the IEC heat exchanger, the M-cycle was suggested by Professor Valeriy Maisotenko. This is the new approach of making and operating a heat exchanger like as shown schematically in Fig. 1.4 and 1.5. Fig. 4 Principle of the heat and mass exchanger based on M- cycle and its representation on psychrometric chart Fig. 5 Schematic of the M-cycle cross flow heat and mass exchanger IV. LITERATURE REVIEW A many research works have been carried out to study the heat and mass transfer process and performance of various types of flow patterns, evaluation of optimize geometries, preferable operating conditions, cooling capacity, energy efficiency, energy saving and emissions reduction related to the IEC systems with plate heat exchanger. The important technical parameters, results and conclusions of the studied research works is presented here. X. Cui, et al., [1] presented the performance of an improved dew-point evaporative design for cooling application. ANSYS FLUENT 14.0 was employed to predict the heat and mass transfer process in evaporative cooler based on counter flow closed loop configuration. Eulerian Lagrangian computational fluid dynamics (CFD) model was adopted. Simulation results showed that the wet bulb effectiveness ranged from 122% to 132% while dew-point effectiveness spanned 81% - 93%.Ala Hasan, [2] presented Going below the wet-bulb temperature by indirect evaporative cooling: Analysis using a modified Ɛ-NTU method. For achieving a sub wet bulb temperature by indirect evaporative cooling of air is by indirectly precooling the working air before it enters the wet passage. Changhong Zhan, et al., [3] presented Numerical study of a M-cycle cross-flow heat exchanger for indirect evaporative cooling. The numerical model was established for heat and mass transfer using the finite-element method. The model was developed using the EES (Engineering Equation Solver). It is found that lower channel air velocity, lower inlet air relative humidity, and higher working-to-product air ratio yielded higher cooling effectiveness. The recommended average air velocities in dry and wet channels should not be greater than 1.77 m/s and 0.7 m/s, respectively. The optimum flow ratio of working-to-product air for this cooler is 50%. The recommend channel height is 4 mm and the dimensionless channel length, i.e., ratio of the channel length to height, should be in the range 100 to 300. Riangvilaikul, et al., [4] presented Numerical study of a novel dew point evaporative cooling system. Here, performed numerical study for counter flow regenerative IEC. Here, the governing equations were solved by employing finite differential approach and newton iterative method. The heat exchanger was able to achieve dew point effectiveness from 58 to 84 % and wet bulb effectiveness from 92 to 114%. Joohyun Lee, et al., [5] presented Experimental study of a counter flow regenerative evaporative cooler with finned All rights reserved by www.ijsrd.com 139

channels. The fins and heat transfer plates were made of aluminum and brazed for good thermal connection. Thin porous layer coating was applied to the internal surface of the wet channel to improve surface wettability. The cooling performance is found greatly influenced by the evaporative water flow rate. To improve the cooling performance, the evaporative water flow rate needs to be minimized as far as the even distribution of the evaporative water is secured. M. Jradi, et al., [6] presented Experimental and numerical investigation of a dew point cooling system for thermal comfort in buildings. A detailed numerical model was developed for the energy core with the cross-flow exchanger using Matlab. The coupled heat and mass transfer equations were solved using 2 nd order fully implicit accurate finite difference scheme to predict air temperature and humidity distribution throughout the dry and wet channels with newton raphson method. With a working to intake air flow ratio of 0.33, the system attained a wet bulb effectiveness of 112% and a dew point effectiveness of 78% with 5 mm channel height and 500 mm channel length. B. Riangvilaikul, et al., [7] presented An experimental study of a novel dew point evaporative cooling system. Counter flow regenerative heat and mass exchanger employed in a novel dew point evaporative cooling system for sensible cooling of the ventilation air. The results showed that wet bulb effectiveness ranged between 92 and 114% and the dew point effectiveness between 58 and 84%. condition by spraying water in the wet channel. The working channel has a closed-loop configuration. Fig 7 Schematic of the novel dew point evaporative air cooler A one dimensional model is developed to design geometrical sizes with operating conditions. Assumptions: 1) The cooler is assumed to be well insulated to the surrounding; 2) Longitudinal thermal conduction in the wall in the x-direction is neglected; 3) Heat and mass transfer coefficients inside each passage are constants; 4) Reynolds analogy is valid and the Lewis number is unity ( = 1); 5) The liquid side of the air water interface offers a negligible resistance to heat transfers so that the interface temperature is saturated at the water film temperature (Tf). From Fig. 8 observed that implementation of the sensible heat exchanger equations is not applicable due to the existence of two gradients: There is a temperature gradient between the temperature of air in the dry passage (T) and the water film temperature (Tf), There is an enthalpy gradient in the working wet channel passage between the saturated air water film interface and the moist air. This enthalpy gradient is due to sensible heat transfer between the water film and the moist air (Tf - T) and latent heat transfer due to water vapor mass transfer between the saturated water film and the moist air [Xs(Tf) _ X]. Table 1: List of recent contribution and development of dew point IEC systems V. MATHEMATICAL MODEL A. Concept of a dew-point evaporative air cooler: Fig. 7 represent a schematic of M-cycle based heat/mass exchanger evaporative air cooler. The cooler consists of a product/primary channel and two adjacent working/secondary channels. The cooler comprises a number of these channel pairs that are stacked together. The inner surface of the wet channel is maintained under wet Fig 8: Thermal profiles in an indirect evaporative cooler All rights reserved by www.ijsrd.com 140

A modification to the Ɛ-NTU method is introduced by connect (T) in the dry passage and (h) in the wet passage by a unique gradient. For the element with contact area (da) shown in Fig. 8, Heat transfer in the dry passage from air at temperature (T) to the water film temperature at (T f ) is dq = U da (T T f ).(1) Where,, neglecting thermal conduction resistance because of small thickness of the wall The energy transfer in air water contact operation can be represented by an overall process based on enthalpy potential difference between the air water interface and bulk air. Therefore, the heat transfer to air in the wet passage is a function of the difference between the saturation air enthalpy at the water film temperature hs(tf) and the air enthalpy in the wet passage (h) dq = hm da [hs(tf) h] (2) where hm = mass transfer coefficient for water vapor from the water film to the air stream. Now, let us assume a linear relation between air saturation temperature and enthalpy hs(t) = at + b (3) where, a = slope of the saturation line. Substituting in Eq. (2) for h s (T f ) from Eq. (3) gives dq = hm da [a Tf + b h]..(4) To eliminate (T f ), substituting for (T f ) from Eq. (1) in Eq. (2) gives Rearranging Eq. (4) ( )..(5) (6) This can be found from the heat balance on the air in the product dry passage ( ) ( ) ( ) (9) Rearranging this equation ( ) ( ) ( ) Or. (10) Where, a = slope of the temperature-enthalpy saturation line. For calculating the overall heat transfer coefficient, the Reynolds number and Nusselt number are defined, based on the hydraulic diameter, Dh, as follows :....(11)....(12) Because of the negligible wall thermal resistance, the surface heat flux and the surface temperature are presumed uniform for each small control volume. The Nusselt number of parallel wall for fully developed laminar flow is given by [4] :.23....(13) This method can be used for various flow directions in indirect evaporative coolers (regenerative, counter flow and parallel flow) and for single and multistage types. In the counter and parallel flow cases, iteration is not needed since the Ɛ-NTU method can solve the problem when the inlet conditions of air to the two passages are known, while iterations are needed for the regenerative case because the inlet air temperature to the wet passage is equal to the outlet temperature from the dry passage, which is unknown. We can note that the term (at + b) appearing in Eq. (6) can be defined as h s (T) according to Eq. (3), where h s (T) is the air saturation enthalpy at the dry air temperature (T). Hence Eq. (6) becomes ( )..(7) is The new transfer coefficient in this equation, which includes the overall heat transfer coefficient (U), the mass transfer coefficient (h m ) and the slope of the saturation line (a). Fig. 9 shows the profile of the air enthalpy (h) and the modified enthalpy hs(t). A new mass flow rate in the dry passage related to this modified enthalpy has to be determined. Fig. 9: Modified thermal profiles in an indirect evaporative cooler. Table 2: Procedure of solution for indirect evaporative cooler using the Ɛ-NTU method. B. Performance evaluation standards of IEC: 1) Wet-bulb effectiveness: Wet bulb effectiveness is defined as the ratio of the temperature difference between the inlet and outlet product air to the difference between the inlet product air s dry bulb and inlet working air s wet bulb temperature. This reflects the extent of the approach of the outlet product air temperature of the IEC against the wet-bulb temperature of the inlet working air, and can be written as: All rights reserved by www.ijsrd.com 141

2) Dew-point effectiveness: Dew point effectiveness is defined as the ratio of the temperature difference between the inlet and outlet product air to the difference between the inlet product air s dry bulb and inlet working air s dew point temperature. This reflects the extent of the approach of the outlet product air temperature against the dew point temperature of the inlet working air related to the IEC, shown as follows: 3) Cooling capacity: The cooling capacity defined as enthalpy change of the product air when flowing across the dry channels of the IEC heat exchanger, and is expressed as follows: ( ) 3. Since the air is cooled at the constant moisture content during the dry channels of the IEC exchanger, the enthalpy change of the air could be expressed by the temperature reduction of the air during its dry channel flow path. So, the above equation could be rewritten as: ( ) 3. 4) Power consumption: IEC system consumes less electrical power than conventional mechanical vapour compression refrigeration based air conditioning systems. The conventional systems use electrical power to drive compressor and fan/pump while IEC system uses electricity to drive fan and pump only. 5) Energy efficiency: Energy efficiency also known as coefficient of performance (COP), is the ratio of the cooling capacity of the IEC to the power consumption of the system. This term can be mathematically expressed as: Energy efficiency = If this figure is multiplied by a unit conversion factor of 3.413, the COP is converted into the energy efficiency ratio (EER). 6) Water evaporation rate: The water evaporation of IEC systems depends on the air flow, the contaminant cooling load, the cooling effectiveness and parameters of the intake air. Theoretically speaking, the water evaporation rate is given by the volume of the moisture increase in the working air during its indirect cooling operation and could be expressed as: 1 ( ) Table 3: Cooling system operating conditions C. Performance evaluation of heat and mass exchanger: A few simulations were carried out to investigate the effect of channel length, channel spacing/height and air velocity on the wet bulb and dew point effectiveness of heat/mass exchanger. From these studies, it is conclude that performance of cooler is dependent on a channel length, channel spacing/ height and air velocity. 1) Effect of channel length: Fig. 10 shows the effect of channel length on the wet bulb effectiveness of the cooler. Here, results were obtained by varying the channel length between 100 and 1500 mm while keeping air velocity 1 m/s and channel spacing/ height 3mm, 5mm, 6mm, 10mm. A result illustrates that wet bulb effectiveness increase with increasing channel length. This may be due to fact that longer channel length leads to an increase in contact time and area. It was decided that the length of heat/mass exchanger should be 1000 mm due to practical limits (the height of 1000 mm is not including upper water tank and lower water collector and spacing between tank/ collector and heat/mass exchanger). Fig 10 Effect of channel length and spacing on cooling effectiveness 2) Effect of channel spacing/ height: Fig. 10 shows the effect of channel spacing/ height on the wet bulb effectiveness of the cooler. Here, result were obtained by the varying the channel spacing/ height between 3 mm to 10 mm while keeping air velocity 1 m/s and channel length varies from 100 mm to 1500 mm. A result illustrates that wet bulb effectiveness decrease with increasing the channel spacing/ height. It is shown that for longer channel spacing/height, heat and mass transfer in dry and wet channel is very poor, which resulting in to higher air supply temperature and lower wet bulb and dew point effectiveness. When the channel spacing/ height is more than 6 mm, the wet bulb effectiveness is smaller than 100 %. So, in order to achieve the high cooling effectiveness, it is suggested that channel spacing/ height should be below 6 mm. 3) Effect of channel spacing/ height: Reynolds number and nusselt number are largely affected by air velocity. Therefore, air velocity plays All rights reserved by www.ijsrd.com 142

a significant role in influencing the heat and mass transfer process. Fig. 11 shows the effect of air velocity on the wet bulb effectiveness of the cooler. Here, the results were obtained by varying the air velocity between 0.5 m/s and 4 m/s while keeping channel spacing/ height 5 mm and channel length varies from 100 to 1500 mm. A result illustrates that wet bulb effectiveness decrease with increase in velocity for particular length. This may be due to the reduced contact time between working air and wet surfaces. When the air velocity is more than 1.5 m/s, the wet bulb effectiveness smaller than 100%. So, in order to achieve the high cooling effectiveness, it is suggested that air velocity should be below 1.5 m/s. Table 4: Cooling system geometrical specifications Table 5: Measured parameters from theoretical analysis VI. EXPERIMENTAL WORK Fig. 13 shows the line diagram of cooling test system and the locations of measuring instruments. The evaporative cooler prototype was placed in workshop. The supply and exhaust air ducts of the test unit were separately connected to a sealed chamber where a variable speed fan was mounted. Fig 11 Effect of air velocity on cooling effectiveness. 4) Effect of channel width: Fig. 12 shows the effect of channel width on the wet bulb effectiveness of the cooler. Here, result were obtained by the varying the channel width between 50 mm to 1000 mm while keeping air velocity 1 m/s and channel length 1000 mm. Results illustrates that the change in wet bulb effectiveness is minor compared to change in width. So, taken as constant for all the value of width. Fig 13 Test system and measurement locations Table 6: The measured parameters and the corresponding instruments Table 7: Details of measured variables Fig 12 Effect of channel width on cooling effectiveness. 5) Evaluation from theoretical analysis The channel spacing/height should be set below 6 mm. The channel length should be set above 500 mm. The channel air velocity should be set below 1.5 m/sec. Table 8: Measured parameters from experiment All rights reserved by www.ijsrd.com 143

A. Effect of air channel velocity: From Fig. 14, it is found that the outlet dry bulb temperature was decreased gradually with increasing the intake channel air velocity. This may be due to the reduced contact time between working air and wet surfaces which results in a decreased evaporative rate. From Fig 15, it is found that the wet-bulb/dew-point effectiveness was decreased gradually with increasing the intake channel air velocity. For velocities below 1.5 m/s, the wet bulb effectiveness is higher than 90% and dew point effectiveness is higher than 60%. From Fig 16, it is found that the cooling capacity of the cooler was increased with increasing the channel air velocity from 0.5 to 4 m/s. and ranged from 23.4 to 26.4 C which is very close to the ambient wet bulb temperature. From Fig. 18, it is found that effectiveness values did not very much. The wet bulb effectiveness varied from 99.16 to 103.06 % and dew point effectiveness ranged from 69.43 to 75.37 %. Fig 17 Air temperature variations versus time Fig 14 Outlet air DB temperature versus channel air velocity Fig 18 Effectiveness variations versus time VII. VALIDATION Fig 15 Effectiveness versus channel air velocity A. Comparison between Theoretical and Experimental Results The experimental results of the evaporative air cooler prototype were compared against the theoretical results derived from the ε- NTU model. The comparison was made on the basis of the identical same structural and geometrical sizes of heat/mass exchanger. In Fig. 19 and Fig. 20, the rates of decreases in wet bulb and dew point effectiveness with increasing air velocity were similar between the theoretical analysis and experiment. Fig 16 Cooling capacity versus channel air velocity B. Air temperature versus time: Here, the performance of evaporative cooler observed under real ambient conditions. Furthermore, experiment was conducted between 10 am to 5 pm to observe the performance of cooler. From Fig. 17, it is found that outlet air temperature did not vary much Fig 19 Difference between theoretical and experimental wet bulb effectiveness as a function of air velocity All rights reserved by www.ijsrd.com 144

Fig 20 Difference between theoretical and experimental dew point effectiveness as a function of air velocity Fig 23 Difference between previous study and experimental dew point effectiveness as a function of air velocity In Fig. 24 and Fig. 25, the variation in wet bulb and dew point effectiveness with real ambient conditions were similar between the previous experimental study and recent experiment Fig 21 Difference between theoretical and experimental cooling capacity as a function of air velocity B. Comparision between previous study and experimental results The experimental results of the evaporative air cooler prototype were compared against the previous experimental study (Riangvilaikul and Kumar 2010). The comparison was made on the basis of the different operating conditions, structural and geometrical sizes of heat/ mass exchanger. In Fig. 21 and Fig. 22, the rates of decreases in wet bulb and dew point effectiveness with increasing air velocity were similar between the previous experimental study and recent experiment. In previous experimentally study inlet dry bulb temperature and humidity ratio maintained as a 34 C and 19 g/kg respectively. Fig 5.11 Difference between previous study and experimental wet bulb effectiveness as a function of time/temperature Fig 22 Difference between previous study and experimental wet bulb effectiveness as a function of air velocity Fig 5.12 Difference between previous study and experimental dew point effectiveness as a function of time/temperature The reasons for the gap were given by details observations and below are some important findings that could explain this gap. First of all, the wet surfaces of heat/mass exchanger were not well distributed with water film as expected. It was caused by the undesirable water distribution structure and deteriorated wetting conditions of sheets. Secondly, across the entrance of the heat exchanger, the intake air channel velocity was not distributed uniformly as assumed in the theoretical analysis. The All rights reserved by www.ijsrd.com 145

uneven air velocity distribution results in the decreased performance of heat/mass exchanger. Thirdly, it is found that small quantities of water droplets were spilled over from the wet channels to the dry channels during the operation of cooler. This may be due to the perforations on the aluminum sheets of exchanger were not perfectly drilled in workshop. It is believed that machinery work will remove this inaccuracy if the cooler is mass produced in factory. VIII. CONCLUSION The performance of the heat/mass exchanger has been investigated using an optimal design, and experiments. Some key findings are summarised in the following statements: The wet bulb/dew point effectiveness of the developed evaporative cooler depends mainly on the air velocity, the geometrical sizes of channels but less depends on the feed water temperature. Decreasing the channel spacing/height of heat/mass exchanger in developed evaporative cooler will result in an increase of effectiveness. To achieve an acceptable effectiveness, the channel height could be controlled below 6 mm, and the channel length would be designed to above 0.5 m. It has been found that the wet-bulb/dew point effectiveness decrease with increasing the air velocity. A low velocity improves the performance of evaporative cooler, but also may increase cost due to the demand for an increasing exchanger size. In an air conditioning application, the intake air velocity of channel should be controlled to the value below 1.5m/s. For the experiment prototype, its wet bulb effectiveness varied from 49.04% to 107%, with a dew point effectiveness ranging from 33.92% to 75.37% under all test conditions. Although the wetbulb effectiveness derived from experiment was less than that predicted by theoretical analysis which was as high as 115.21 %. The supply temperatures achieved by the experiment prototype ranged from 22.5 C to 31.6 C under all test conditions. The cooling output of the dew point system varies according to the air channel velocity and under real ambient conditions. For the experiment prototype, its cooling capacity varied from 91.43W to 335.26W under all test conditions. NOMENCLATURE a -Slope of saturation line, J/kg k A -Surface area of plate sheet, m 2 C c, C h -Heat capacity rate for cold and hot fluid respectively, kg/s C -Specific heat at constant pressure, J/kg k DEC -Direct evaporative cooling D h -Hydraulic diameter, m EER -Energy efficiency ratio, which is the COP multiplied by 3.413 H -Heat transfer co-efficient, W/m 2 k h -Specific enthalpy, kj/kg h m -mass transfer coefficient, kg/m 2 s HMX -Heat and mass exchanger IEC -Indirect evaporative cooling L e -Lewis number m -Mass flow rate, kg/s NTU -Number of transfer units Nu -Nusselt number P -Perimeter, m Q cooling -Cooling capacity, W R -Heat capacity ratio Re -Reynolds number T -Flow temperature, C u -Air velocity, m/s U -Overall heat transfer co-efficient, kg/m 2 s W -Measured total power consumption, W x -Humidity ratio or Moisture content, kg/kg of dry air Greek symbols Ɛ -effectiveness ρ -Density, kg/m3 Subscripts a -Air db -Dry bulb dp -Dew point f -Water film i -Inlet o -outlet s -Saturation wb Wet bulb 1 -Primary / product channel 2 -Working / secondary channel REFERENCES [1] X. Cui, K.J. Chua, W.M. Yang, K.C. Ng, K. Thu, V.T. Nguyen (2014) Studying the performance of an improved dew-point evaporative design for cooling application, Applied Thermal Engineering,Vol.63, pp.624-633 [2] Ala Hasan (2012) Going below the wet-bulb temperature by indirect evaporative cooling: Analysis using a modified e-ntu method, Applied Energy, vol. 89, pp. 237 245 [3] Changhong Zhan, Xudong Zhao, Stefan Smith, S.B. Riffat (2011) Numerical study of a M-cycle cross-flow heat exchanger for indirect evaporative cooling, Building and Environment, vol. 46, pp. 657 668 [4] B. Riangvilaikul, S. Kumar (2010) Numerical study of a novel dew point evaporative cooling system, Energy and Buildings, vol. 42, pp. 2241 2250 [5] M. Jradi, S. Riffat (2014) Experimental and numerical investigation of a dew-point cooling system for thermal comfort in buildings, Applied Energy, vol. 132, pp. 524 535 [6] Joohyun Lee, Dae-Young Lee (2013) Experimental study of a counter flow regenerative evaporative cooler with finned channels, International Journal of Heat and Mass Transfer, vol. 65, pp. 173 179 [7] B. Riangvilaikul, S. Kumar (2010) An experimental study of a novel dew point evaporative cooling system, Energy and Buildings, vol. 42, pp. 637 644 All rights reserved by www.ijsrd.com 146