Optimal Design for a Hybrid Ground-Source Heat Pump

Similar documents
Energy and Buildings

The correct citation for this paper is:

Research on Ground Source Heat Pump Design

SIMULATION AND OPTIMIZATION OF GROUND SOURCE HEAT PUMP SYSTEMS

Simulation of Hybrid Ground Source Heat Pump Systems and Experimental Validation

Limitations of Using Uniform Heat Flux Assumptions in Sizing Vertical Borehole Heat Exchanger Fields

Ground-Coupled Heat Pump And Energy Storage

This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (

Pitfalls of Rules of Thumb in Geothermal Heat Pump Design

TransPacific Energy Advantage: Case Studies

GEOTHERMAL HEAT PUMPS CONFIGURATIONS/INSTALLATION

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

Residential Swimming Pool Heating with Geothermal Heat Pump Systems

Comparative Heating Performances of Ground Source and Air Source Heat. Pump Systems for Residential Buildings in Shanghai

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE

THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE

The design and operational analysis of ground source heat pump in large-scale construction

APPLICATIONS OF A DYNAMIC THREE-DIMENSIONAL NUMERICAL MODEL FOR BOREHOLE HEAT EXCHANGERS. M. He, S.J. Rees, L. Shao

Design guidelines for direct ground cooling systems in different climates

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

CLOSED-LOOP HEAT EXCHANGER FOR GROUND COUPLED HEAT PUMPS

RESIDENTIAL SWIMMING POOL HEATING WITH GEOTHERMAL HEAT PUMP SYSTEMS

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

MODELING THE VIABILITY OF UNDERGROUND COAL FIRES AS A HEAT SOURCE FOR ELECTRICAL POWER GENERATION

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

A NOVEL TECHNIQUE FOR EXTRACTION OF GEOTHERMAL ENERGY FROM ABANDONED OIL WELLS

SorTech package solution description

Field investigation on indoor thermal environment of a high-rise condominium in hot-humid climate of Bangkok, Thailand

This paper was presented at 12th REHVA World Congress (Clima 2016).

NUMERICAL MODELLING OF MULTIPLE STANDING COLUMN WELLS FOR HEATING AND COOLING BUILDINGS

The optimization of the mechanical night cooling system in the office building

Implications of Measured Commercial Building Loads on Geothermal System Sizing

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (

A quasi-two-dimensional standing column well model for ground source heat pump systems

Ground Source Heat Pump System Performance: Measuring the COP

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

ANALYSIS OF VARIOUS DESIGNING PARAMETERS FOR EARTH AIR TUNNEL HEAT EXCHANGER SYSTEM

Hafiz M K U Haq 1, Birgitta J. Martinkauppi 1, and Erkki Hiltunen 1 1 Department of Energy Technology

Study on Heat Exchange Characteristics for PHC Energy Piles

MODELING, VERIFICATION AND OPTIMIZATION OF HYBRID GROUND SOURCE HEAT PUMP SYSTEMS IN ENERGYPLUS SANKARANARAYANAN. K. P. Bachelor of Engineering

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE

DISPLACEMENT VENTILATION

Chilled Water Plant Redesign

PREPROCESSOR FOR THE GENERATION OF G-FUNCTIONS USED IN THE SIMULATION OF GEOTHERMAL SYSTEMS

Local Conduction Heat Transfer in U-pipe Borehole Heat Exchangers

Steve Kavanaugh Professor Emeritus The University of Alabama

MODELLING THE ENERGY PERFORMANCE OF NIGHT-TIME VENTILATION USING THE QUASI-STEADY STATE CALCULATION METHOD

Parametric Study for Evaluation of Design Parameters of Standing Column Well

EVALUATION OF GROUND COUPLED HEAT PUMPS FOR THE STATE OF WISCONSIN

Geothermal Heat Pump Systems Metropolitan Washington Council of Governments Built Environment and Energy Advisory Committee May 19, 2016

Promoting Building Energy Efficiency through Performancebased Standards: Is it a Challenge? By Priyantha Bandara

RETScreen Software Online User Manual

OPTIMIZATION OF ICE THERMAL STORAGE SYSTEM DESIGN FOR HVAC SYSTEMS

Heat Pump. Using Propane Heating Systems

Modeling of Standing Column Wells in Ground Source Heat Pump Systems

The Art of Thermal Mass Modeling for Energy Conservation in Buildings, Part 2

AB 2339 WORKING GROUP DRAFT DOCUMENT. Draft Energy Commission Policy for Ground Source Heat Pumps April 19, 2013

The desire for fossil fuel alternatives and environmentally friendly energy has

Horizontal Borehole Study

7S9X0 - Week 5 Uncertainties in building performance simulation

CASE STUDY HOW COULD WE OPTIMIZE THE ENERGY-EFFICIENT DESIGN FOR AN EXTRA-LARGE RAILWAY STATION WITH A COMPREHENSIVE SIMULATION?

Secondary loop chilled water in super high-rise

Hotel Design and Energy Consumption

EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE

Energy Consumption Measurement of Energy-saving Buildings and Analysis of Simulation Example

White Paper. Geothermal Heating and Cooling

GEO-HEAT CENTER EXECUTIVE SUMMARY

Design Progress and Analysis for ITER Thermal Shield

SOLAR HEAT INJECTION INTO BOREHOLES. Case Postale 6079, succursale «centre-ville», Montréal, Québec, Canada

Optimisation and Cost Analysis of a Lithium Bromide Absorption Solar Cooling System

Ceiling Radiant Cooling Panels

ENERGY SAVING IN BUILDING USING PCM IN WINDOWS

A Comparative Study of the Thermal Comfort of Different Building Materials in Sana a

Available online at ScienceDirect. Procedia Engineering 145 (2016 ) 18 25

Geothermal Systems: Harnessing Earth s Energy

a.k.a. David N. Shaw, P. E.

Ductless Mini Pilot Study

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

DESIGN OF A GREEN DEMO BUILDING IN A HOT AND HUMID CITY IN CHINA. Ana Bacall Sebesta Blomberg & Associates Woburn, MA

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

Italcementi Center for Research and Innovation

CHAPTER THREE. Load Curves The curve showing the variation of load on the power station (power plant) with reference to time is known as load curve.

COMPUTATIONAL ASSESSMENT OF COOLING WITH LOW-TEMPERATURE HEATING SYSTEMS

DIRECTIONAL-BORE GROUND SOURCE HEAT PUMP FIELD REPORT

Geothermal Comfort Systems

NUMERICAL STUDY ON THERMAL DEPLETION OF THE GROUND AROUND A GEOTHERMAL HEAT PUMP S PROBE

Simulations of a New Double U-tube Borehole Configuration with Solar Heat Injection and Ground Freezing

Article Control of Thermally Activated Building System Considering Zone Load Characteristics

Building Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System)

Performance evaluation of a small-scale polygeneration plant including a desiccant cooling system and an innovative natural gas ICE

3/6/2017 Past president & currently on the board of directors for the Wisconsin Geothermal Association

Using Annual Building Energy Analysis for the Sizing of Cooling Tower for Optimal Chiller-Cooling Tower Energy Performance

INVESTIGATION ON THE OPTIMUM DESIGN OF HEAT EXCHANGERS IN A HYBRID CLOSED CIRCUIT COOLING TOWER

Using Radiant Cooled Floors to Condition Large Spaces and Maintain Comfort Conditions

Nanocomposite Materials Used for Ground Heat Exchanger Pipes

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Solar Thermal Radiant Heating at Pohakuloa Training Area

Soil Temperature Monitoring and Study of Geothermal Heat Pump Systems

Transcription:

Optimal Design for a Hybrid Ground-Source Heat Pump Zhongyi Yu, Xudong Yuan, Bin Wang School of Environmental Science and Engineering, Huazhong University of Science and Technology, Wuhan 430074, China, Email: yuzhongyi9551@163.com Abstract: Although the advantages of ground-source heat pumps over their conventional alternatives make these systems a very attractive choice for air conditioning, not only for residential buildings but increasingly also for institutional and commercial buildings, a significant barrier to wider application of this technology is a high first cost. When used in cooling-dominated buildings, ground-source heat pumps that utilize vertical, closed-loop ground heat exchangers can experience performance degradation as the entering fluid temperature to the heat pump increases over time due to heat buildup in the borefield. In these cases, it is possible to displace a large portion of the system cost by installing a supplemental heat rejecter to balance the annual heat extraction from the ground. The paper presented has shown that the heat rejection of the GLHEs and the system energy consumption are approached to discuss the ground heat balance with different design procedures and control strategies though the system simulation. Keywords: hybrid ground-source heat pump systems (HGSHPs); cooling tower; system simulation 1 INTRODUCTION Although ground-source heat pump (GSHP) systems are recognized to be outstanding heating, cooling, and water-heating, a significant drawback to wider acceptance of the technology is a high first cost. This is especially true in cooling-dominated commercial and institution applications where the vertical closed-loop configuration is commonly preferred. As a result, the required ground-loop heat changer (GLHE) is greatly reduced if the amount between heat extracted from the ground and heat rejected into the ground was balanced. In order to decrease the system first cost and to improve the system performance, one of the available options is a hybrid ground-source heat pump application. Hybrid systems incorporate supplemental heat rejecters, such as cooling towers, fluid coolers, cooling ponds, or pavement heating systems, the capacity of which is typically sized so that the annual heat rejection to the ground approximately balances the annual heat extraction from the ground. However, the design of the system components also depends on the strategy used to control the supplemental heat rejecter. Therefore, a integral consideration among the size of GLHE, the capacity of the supplemental heat rejector, and the control strategy should be done. The size of GLHE and the capacity of the cooling tower is optimally designed based on the design procedures and control strategies under the condition of the heat balance in the ground in this paper. 2 HYBRID GSHPS IN TECHNOLOGY LITERATURE The paper is proposed to analyze the impact of supplemental heat rejectors on GSHP loop length design and annual ground heat balance. A review of recent literature on hybrid GSHP systems yielded only modest number of references to research documents. The works are summarized below. ASHRAE (1995)[1] discusses the benefits of hybrid GSHP systems for commercial/institutional buildings considering the first cost and available surface area limitations. A design procedure is suggested for cooling-dominated buildings that estimates the capacity of the supplemental heat rejecter based on the difference between the monthly average cooling and heating loads for the building. The ground-loop heat exchanger is sized to satisfy the building s heating load and the cooling load requirement for the ground loop in excess of that of the heating load is met through supplemental heat

rejection. Kavanaugh and Rafferty (1997) [2] discuss a few alternatives for hybrid GSHP systems ground-loop heat exchanger design. The high cost is one of the primary factors that may mandate the consideration of a hybrid system. Other considera -tions include limited land area, the cost of the land, or the high cost of high-efficiency heat pumps. The size of the supplemental heat rejecter is based on peak block load at the design condition. Similar to that of ASHRAE (1995), the nominal capacity is calculated based on the difference between the ground-loop heat exchanger lengths required for cooling and heating. Kavanaugh (1998)[3] revises and extends the design procedures recommended by ASHRAE (1995) and Kavanaugh and Rafferty (1997). The revisions to the practice of hybrid ground-source heat pump system design involve balancing the heat flow to the ground on an annual basis in order to limit heat buildup in the borehole field. The annual operating hours of the supplemental heat rejecter needed to balance the heat rejection and extraction in the ground are calculated based on a set point control of the ground loop temperature (a typical range of 80 [27] to 90 [32]). The procedure is demonstrated on a multi-story office building placed in three different climatic regions. The author s results indicate that warm climates are most appropriate for the hybrid application since the savings in required bore length are much more significant than for moderate and cold climates. Yavuzturk and Spitler (2000)[4] use a system simulation approach to compare the advantages and disadvantages of various control strategies for the operation of a hybrid GSHP using a cooling tower in a small office building. The control strategies investigated may be broadly categorized into three groups: 1) a set point control to operate the cooling tower when the heat pump entering or exiting fluid tempera ture exceeds a set value, 2) a differential control to operate the cooling tower when the difference between the heat pump entering or exiting temperature and the ambient wet-bulb temperature exceed a set value, and 3) a scheduled control to decrease heat buildup in the ground by operating the cooling tower for a given period of time during the night. In general, the system simulation results showed that the most beneficial control strategies were found to be those that operate the supplemental heat rejecter primarily when heat rejection conditions are most favorable. 3 METHODOLOGIES FOR SYSTEM SIMULATION AND ANALYSIS 3.1 Building Description and Loads Calculation An office building in Wuhan City was selected for simulation the performance of hybrid GSHP systems. The total area of five storeys building is about 3200m 2. The following table 1 assumptions have been done to determine the annual building loads. The office occupancy is taken as 0.2 person per m 2. The schedule for work and rest is from 7:00 am to 17:00 pm. The index value descends to original 30% on the weekend. The annual building loads are simulated using DeST-C (2000) simulation software with typical meteorological year (TMY) weather data. Considering the actual running and operation conditions, the calculated annual building loads on an hour by hour basis are shown Figure 1. The total annual building heat loads are 136158kWh while the cooling loads are 342207 kwh adopting the BIN method. Obviously, when satisfy indoor comfortable environment is satisfied, the building rejects more heat to the ground than it extract on an annual basis. The heat buildup may occur in limited heat storage capacity soil, which degrades the performance as the entering fluid temperature to the heat pump increases over time. 3.2 Operation and Control Strategies In this present study, we adapt two control strategies as fellows. (a) The cooling tower is operated when the difference between the heat pump entering or exiting temperature and the ambient wet-bulb temperature exceed a set value and the heat pump exiting fluid temperature exceeds a set value

Tab. 1 The dominating heat index inside the building Influence factor Radiant heat gains (W/person) Wet gains (kg/h) Lighting loads (W/m 2 ) Equipment loads (W/m 2 ) Fresh air volume (m3/h) The index value per person 64 0.084 9 20 30 (b) This control strategy is put forward mostly based on the following reasons: in the initial stages of cooling, the cooling tower operation is solely done. At the stage the outdoor temperature is not high which benefits the effective operation of the cooling tower and reduce the running time of GLHEs to recover the ground temperature. In the medium stages, both of the cooling tower and GLHEs operate for cooling. In the last stages, similarly, the cooling tower operation is solely done. The operation conditions is described below. (c) Because the compute time in the BIN method is not continuous, the calculation is not analyzed on an hour by hour basis. It is necessary to revise the solely operation condition of GLHEs. 3.3 Ground-Loop Heat Changer and Cooling Tower Sizing In the optimal design process of ground-loop heat changer and cooling tower( the supplemental heat rejecter), it is discovered that the capacity of cooling towers is sized after the ground loop is determined to meet the building heating loads for above-mentioned design methods. It is neglected that when the outdoors air temperature is not very high and the building cooling loads exist, the entering fluid temperature to the heat pump could lower by adopting a cooling tower. Additionally, the proper adjustment between cooling tower and GLHEs should be done to lower the entering fluid temperature to the heat pump and benefit the heat pump performance because the exiting temperature of GLHEs increase over a long running time. It is necessary that the size of cooling towers is firstly determined to avoid the performance degradation of heat pump in the field where the balance amount between the heat rejection and the heat extraction. The design procedures brought forward by the author is following. 1) According to the empirical operation data of the heat pump, the average entering fluid temperature (T jp ) to heat pump in situ should be achieved. 2) The relation between the exiting fluid temperature (T cl )and outdoor wet bulb temperature (T s ) is described as: T cl =Ts+4(3~5). The cooling towers is more beneficial to the operation efficiency of heat pump than ground loop heat exchangers when T cl is less than T jp under the same flux. Hence, Ts which equals to (T jp - 4) is taken as the temperature balance point (T sˊ ) of the cooling tower size. 3) According to the annual outdoor wet and dry bulb temperature on a hourly basis, the average temperature (Tgˊ) corresponding to outdoor dry bulb temperature (T g ) is found out when Ts is equal to ' Ts. The building cooling loads ( Q c ) is calculated at the outdoor climatic condition. 4) According to the running parameters of the heat pump and the energy efficiency ratio (EER), the heat rejected to the ground is calculated as : 1 Q f = Qc + 1 EER 5) The cooling tower size is determined according. 6) The lengths required (Lc) of ground loop heat exchanger for cooling and The lengths required (Lh) of ground loop heat exchanger for heating is calculated using the design procedure commended by IGSHPA[5]. 7) The GLHE lengths with supplemental cooling towers for cooling as is calculated as: Qc-Qc Lc = L Q If Lc is not less than L h, the GLHE lengths equal to L. Otherwise the lengths equal to. c c The ground and the cooling tower sizing method c L h

Fig. 1 Annual building loads for climatic conditions typical of wuhan(cooling load are negative and heating loads are positive) is described below for each simulation case with different control strategies. Case 1 (base case ). For this case, the GLHEs was sized without any supplemental heat reject The average entering fluid temperature (T jp ) to the heat pump in wuhan city is taken as 28. The nominal capacity of the heat pump was 500kw for cooling and 350kw for heating. The borehole field for the base case consisted of 64 boreholes in a 8 8 configuration with a borehole depth of 73.4m and a borehole spacing of 4m.. A large loop was required because of the great cooling load The heat transfer for base case was water with a flow rate of 0.0291m 3 /s per borehole. Undisturbed ground temperature of 17.3 was chosen for the system simulation. Other configurations of the boreholes geometry included a constant average thermal conductivity of 2.8W/m k and thermal diffusivity of 1.56 10-6m 2 /s for the ground, a constant average thermal conductivity of 0.42 W/m k for the grount, borehole diameter of 0.11m, a constant average thermal conductivity of 1.0 W/m k and a constant fluid convective thermal conductivity of 2700 W/m 2 k and inner diameter of 0.026m and the outer diameter of 0.032m for the U-tube pipe. Case 2,3,4,5,6. For these cases, the borehole field was reduced from 49 (7 7 configuration) boreholes to 25 (5 5 configuration) boreholes.the other configurations of the boreholes geometry were similar to the base case. The GLHEs was sized based on the cooling tower with the nominal capacity of 244kw. Heat was rejected to the cooling tower using the differential control strategy as described above. Table 2 summarizes the length of GLHEs, the capacity of the cooling tower, and the different control strategy for each case. 4 RESULT AND DISCUSSION Table 3 summarizes the heat rejection and the total energy consumption for each case. The details are discussed below. As analysis of the data presented in Table shows that Case 1 is the highest energy consumption alternative. It is evident the system energy consumption is mainly dominated by nothing more than GLHEs. Even though the length of GLHEs for Case 2 is small than Case 3 and Case 4, the total energy consumption and total heat rejection are obviously the highest. This is basically due to the overfull running time of GLHEs resulting in bad heat emission effect. The better energy conservation can be achieved and the heat rejection of GLHEs become less after leaving out the sole operation of GLHEs for Case 3 and Case 4.

Tab. 2 Summary of design parameters for each simulation case Case The Capacity of Heat pump (kw) The length of GLHEs (m) The flux of GLHEs (l/s) The size of the cooling tower (kw) The Flow Rate of The cooling Tower (l/s) Control strategy 1 250 2 9400 29.1 0 0 2 200+300 3800 11.7 360 17.4 a 3 200+300 5400 17.2 250 11.9 b 4 200+300 5400 17.2 250 11.9 c 5 200+300 4800 11.7 360 17.4 a 6 200+300 6800 17.2 250 11.9 c The length of GLHEs for Case 5 and Case 6 is augmented based on Case 2 and Case 4 respectively. The energy consumption and the heat rejection amount for Case 4 is lower than that for Case 4 while the energy consumption and the heat rejection amount for Case 5 is higher than that for Case 2. This is mainly because that even if the exiting fluid temperature of 24 from GLHEs and the outdoor wet bulb temperature of 21 arrive, the cooling tower is not in operation according to the control strategy that the cooling tower does not operate until the difference between the exiting fluid temperature from GLHEs and the outdoor wet bulb temperature is over 4. However, if the building heat load is rejected by GLHEs together with the cooling tower, the heat rejection of GLHEs and the exiting fluid temperature decrease as well as the outcome of the combined operation is better than before. That is just the reason that the energy consumption amount and the heat rejection for Case 4 are higher than one for Case 2 as the length of GLHEs increases. The difference percentage between the heat rejected to the ground and the heat extracted from the ground is heat through different design procedures and control strategies. 2) The balance of ground heat does not depend 135.4%,71.4%,215.3% and 67.8% respectively for Case 2,4,5,6. It can be seen from the above analyses that difference between the heat rejected and the heat extracted for Case 6 is the least and the heat balance is well to benefit the ground heat recovery around the boreholes. 5. CONCLUSION A design procedure to determine the size of a hybrid GSHP system that utilizes a cooling tower as a supplemental heat rejecter has been presented. As the design is strongly influenced by the strategy used to control the cooling tower, the most efficient control strategy from the work of Yavuzturk and Spltler is adopted for this paper. The paper presented has shown that though the system simulation the heat rejection of the GLHEs and the system energy consumption are approached to discuss the ground heat balance with different design procedures and control strategies. Some specific conclusions of this study are as follows. 1) Case 6 is most beneficial to balance the ground on the high energy consumption and first cost using the effective control strategy.

Tab. 3 Summary of the system performance for all cases Case 1 2 3 4 5 6 Total energy consumption (kwh) 87414.5 84693.4 79864.1 79031.4 86895.4 75313 The heat rejected (kwh) 429611 240392 185597 175050 321982 171332 3) The study presented mainly discusses the design procedures and control strategies based on the ground heat balance. A life-cycle cost analysis is not performed to evaluate the economics of the various cases that were simulated. In the future study, the optimal size GLHEs and cooling towers with corresponding control strategy can be approached until a minimum cost has been found. REFERENCES [1] ASHRAE. Commercial/institutional ground source heat pump engineering manual[m]. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. 1995. [2] Kavanaugh, S.P., and K. Rafferty. Ground-source heat pumps: Design of geothermal systems for commercial and institutional buildings[m]. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.1997. [3] Kavanaugh,S.P. A design method for hybrid groundsource heat pumps[c]. ASHRAE Transac -tions,1998,104 (2): 691-698. [4] Yavuzturk, C., and J.D. Spitler. Comparative study of operating and control strategies for hybrid groundsource heat pump systems using a short time step simulation model. ASHRAE Transactions, 2000.,106(2): 192-209. [5] Bose J E. Geothermal Heat Pumps Introductory Guide. Oklahoma State University Ground Source Heat Pump Publications,1997.