ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS

Similar documents
Optimizing Central Chilled Water Systems

Project Information. Measure Description

SGM Engineering, Inc.

How to Save Money and Become More Sustainable Through Energy Efficiency

Application of Variable Frequency Drives for Energy Savings

Chilled Water Energy Savings Study

Energy-Efficient Waste Water Treatment

Ohio Energy. Workshop G. Best Practices in Energy Efficiency to Help You Reduce Your Energy Spend. Tuesday, February 21, :45 a.m.

Deep Dive Into Process Efficiency AEP November 14, 2017

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate

A Case Study of Control Problems and Resolutions in a High rise

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

THE GREAT CHILLED WATER DEBATE. Michael Dagher

Agenda. Understanding the three basic piping systems. Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations (VPF)

Final Report for National Grid USA Service Company. Evaluation of 2003 Custom HVAC Installations Part II. September 27, 2005.

Management Committee December 3, Johnson County Community College Retrocommissioning Report

Building Hydronic Systems Pressure Profile

ARMSTRONG DESIGN ENVELOPE FAQ

FlowSet. Balancing Procedure

Ohio Energy. Workshop G. Energy Efficiency Through Better Control: Maximizing the Energy Efficiency by Minimizing Waste

Doubling Down on Not Balancing Variable Flow Hydronic Systems BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE

Xavier Energy Initiative

This article does not examine economic payback; a detailed energy. analysis is the best method of comparing system options and their respective

Chiller plant optimization

Persistence Tracking in a Retro-commissioning Program

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC

In typical commercial buildings, water-cooled chilled water plants use a signifi cant amount of energy.

impacts of Chilled-Water System Design Decisions

05/14/2012 THE CRIME OF IMPROPER ENERGY MANAGEMENT AGENDA

Pump selection: a real example

Teague Research Center

AR No. # Efficient Irrigation

Retro-Commissioning in Hospitals

September 22, Roy Hubbard HVAC Systems Technology

Secondary loop chilled water in super high-rise

Retrocommissioning Investigation Report

Optimal Set-point Synthesis in HVAC Systems

Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary

Pressure Independent Valve Systems. ASHRAE Seminar College of the North Atlantic, Doha, Qatar 20 th April 2013

D DAVID PUBLISHING. Optimizing Thermal Energy Storage Systems in the Hospitality Industry. 1. Introduction

Modeling and Simulation of Air Compressor Energy Use

EnergyPro Building Energy Analysis. Single-story School Building

Underf loor For Schools

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013

Large University Central Chiller Plant Design Considerations


Section A: CUSTOMER INFORMATION. Customer Name Electric Account Number Rate Application Number. Facility Address City State Zip Code

FIRST LARGE-SCALE SOLAR SEASONAL BOREHOLE THERMAL ENERGY STORAGE IN CANADA

ASHRAE s LowDown Showdown

Does NZEB pose a conflict to Good Indoor Air Quality? REHVA summit November 2017

OPTIMIZATION OF ICE THERMAL STORAGE SYSTEM DESIGN FOR HVAC SYSTEMS

AHU Models Using Whole Building Cooling and Heating Energy Consumption Data

Strategies for Persistence: Measurement and Verification. Ryan Hughes PE, CEM, LEED AP Eaton Energy Solutions

2. The requirements of Sections 502, 503, 504 and 505. In addition, commercial buildings shall comply with either Section 506.2, or

Meeting the Variable Needs of Energy- Efficient Mechanical Ventilation When and Where You Need It

Secondary loop chilled water in super high-rise

University of Southern California Main Campus Plant Energy use reduction of 49% compared to previous plants and control strategies.

FUNDAMENTALS OF CHILLED BEAMS ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

ENERGY AS SERVICES COMPANY ESCO. Jamal E. Alostaz. Projects Engineer Al-Salem Johnson Controls

REDUCING AIRFLOW ENERGY USE IN MULTIPLE ZONE VAV SYSTEMS

INFLUENCE OF FAULT AND OPTIMIZATION OF PID PARAMETERS IN BUILDING AIR-CONDITIONING SYSTEM

Energy Management Workshop

CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM

Commercial Retro-Commissioning Program Manual for 2015 SECTION 1

Ground-Coupled Heat Pump And Energy Storage

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619

Figure 26.5 Potential fan energy savings using fan speed limiting 16.

Getting Started with Your First Project: Considering Rules

Troubleshooting Piping Systems

Building Control Strategies That Work to Improve Your Energy Bottom Line

Summary Paper on Controls for HVAC

Xavier University of Louisiana

7 th NATIONAL CERTIFICATION EXAMINATION Nov FOR ENERGY MANAGERS & ENERGY AUDITORS

UCSF Mission Bay Campus Arthur and Toni Rembe Rock Hall th Street San Francisco, California

Calculate the Costs of Piping System Elements

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

Best Practice Pump Control

South Carolina Society for Hospital Engineers

Central Chiller Plants

CONTINUOUS COMMISSIONING OF SALT LAKE COMMUNITY COLLEGE SOUTH CITY CAMPUS

David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option. Proposal

Varying Views. Variable-primary flow chilled-water systems are of. on Variable-Primary Flow WHAT IS VARIABLE-PRIMARY FLOW? >>>

Georgetown University New Science Center

Canada Published online: 28 Feb 2011.

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE

ASHRAE 90.1 The evolution continues

EnergyPro Building Energy Analysis. Nine-story Office Building

CHILLED WATER SYSTEM OPTIMIZER

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

Improving the efficiency, occupant comfort, and financial well-being of campus buildings

Success with MEASUREMENT & VERIFICATION

Advancing Energy Efficiency in (Commercial) Buildings: The Advocates Role

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne

Army Exceeds Energy Goal Ahead of Mandate (Actual Energy Reduction of 38% vs 30% and Achieved in 2010 vs 2015)

Continuous Commissioning Leading Energy Project Process - An Industry Approach

DEVELOPMENT OF A SOLAR COLLECTOR/SOLAR WATER HEATING SYSTEM TEST CENTER IN IRAN

Evaluation of the Impact of Off-Design Operation on an Air-Cooled Binary Power Plant. G. L. Mines. September 22, 2002 September 25, 2002

Recommissioning Energy Savings Persistence

Transcription:

ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS University of Dayton, Dayton, Ohio Vijay Gopalakrishnan, Lead Engineer Alexandra Brogan, Lead Engineer Rohan Das, Research Assistant Kelly Kissock, Ph.D., P.E., Director Donald Chase, Ph.D., P.E., Chair ABSTRACT About one-fifth of all U.S. utilities incentivize variable frequency drives (VFDs) (NCSU 2014), and many of these drives control pumping systems. Field studies and research show that few variable-flow systems are optimally controlled and the fraction of actual-to-ideal savings is frequently as low as 40% (Kissock 2014a; Ma 2015; L. Song, Assistant Professor, Department of Mechanical Engineering, University of Oklahoma, pers. comm., July, 2013.). Utility incentive programs that rely on ideal energy saving calculations could overestimate savings by 30% (Maxwell 2005). Previous work has shown that excluding the effects of changing motor efficiency, VFD efficiency, pump efficiency, and static head requirements results in overestimating savings (Bernier and Bourret 1999; Maxwell 2005). This work considers the difference between actual and ideal savings caused by bypass, position and setpoint of control sensors, and control algorithms. This paper examines the influence of these factors on energy savings using simulations, experimental data, and field measurements. In general, energy savings are increased when bypass is minimized or eliminated, pressure sensors for control are located near the most remote end use, and the pressure control setpoint is minimized. INTRODUCTION According to some estimates, pumps account for between 10% and 20% of world electricity consumption (EERE 2001; Grundfos 2011). In industrial applications, pumps frequently account for 25% of plant energy use (EERE 2001). Unfortunately, about two thirds of all pumps use up to 60% too much energy (Grundfos 2011). A primary reason is that, although pumps are designed for peak flow, most pumping systems seldom require peak flow and the energy efficiency of flow control methods varies significantly. Before variable-frequency drives (VFD), bypass and throttling were common, but inefficient, methods of varying flow to a specific end use. Today, the most energy-efficient method of varying flow is by varying pump speed with a VFD. Previous work has shown that excluding the effects of changing motor efficiency, VFD efficiency, pump efficiency and static head requirements results in overestimating savings (Bernier and Bourret 1999; Maxwell 2005). The quantity of energy saved in variable-flow systems is highly dependent on other factors in addition to motor, pump, and VFD efficiencies. Field studies and research show that few variable-flow systems are optimally controlled and the fraction of actual-to-maximum savings can be as low as 40% in poorly-controlled flow systems (Song 2013; Kissock 2014a; Ma 2015). In fact, it is not uncommon to find instances where VFDs actually increase energy use

when VFD efficiency losses are greater than pump power savings (Seryak, John. 2014. "Fan and Pump System Low-Cost/No-Cost Energy Efficiency Opportunity Identification. Triple Point Energy Saving Seminar, Chillicothe, OH, April 10, 2014.). This work considers the difference between actual and ideal savings caused by bypass, position and setpoint of control sensors, and control algorithms. The paper begins by defining ideal flow control as the most energy-efficient type of flow control, and compares pump power from reducing flow by throttling to the ideal case. Since some minimum flow is required in most pumping systems, the effect of bypass flow on pumping energy use is considered. The control variable for most variable flow pumping systems is pressure; hence, the effect of the location and setpoint value of pressure sensors on pump power is considered. Finally, a case study is presented which demonstrates how pumping energy can be reduced through application of these ideas. IDEAL FLOW CONTROL In order to consider the effect of bypass and control on pumping system energy use, it is useful to define the maximum savings that can be expected from reducing flow. Figure 1 shows two operating points of a pumping system. Point 1 represents the pump operating at full flow. Point 2V is the operating point if pump speed is slowed by an optimally-controlled VFD. Point 2V lies on a system curve in which dh (the pressure head) approaches zero as volume flow rate approaches zero and pump head varies with the square of volume flow rate. This ideal case represents the minimum pumping power that can be expected when flow is reduced from V 1 to V 2. The reduction in pump power is also defined by the pump affinity law shown in Equation 1, where W is fluid work and V is volume flow rate at respective operating points. W 2V = W 1 ( V 2 ) V 1 3 1 Figure 1. The ideal system curve approaches zero head at zero flow. Few actual pumping systems achieve the power reduction defined by the pump affinity law because of throttling, minimum flow constraints, static head requirements due to changes in

elevation, velocity and pressure between the inlet and outlet of the piping system, and control losses. In the following sections, these deviations from the ideal case are investigated. THROTTLED FLOW CONTOL One of the most common methods of varying flow is to throttle flow by partially closing a valve in the piping system. In this section, we compare pump power from reducing flow by throttling to reducing flow by slowing the pump with a VFD. The University of Dayton Hydraulics Lab (UDHL) is equipped with two pumps, a VFD, a parallel piping network with four branches, pressure sensors, and flow meters. In Figure 2, Point 1 is the operating point with the pump at full flow. Point 2T is the operating point when flow was throttled to volume flow rate, V 2. Point 2V is the operating point when pump speed was slowed by a VFD to volume flow rate, V 2. Pump power is proportional to the product of head and flow, which is represented by the rectangular area defined by each operating point. The data show that when flow was controlled by throttling at Point 2T, the pump ran at 1,800 rpm and consumed 8.5 kw. When flow was controlled by the VFD at Point 2V, the pump ran at 1,180 rpm and consumed 3.25 kw; pump power decreased by 62%. Clearly, reducing flow with a VFD is more energy-efficient than throttling flow. Figure 2. Measured energy penalty due to throttled flow. In pumping systems the power transmitted to the fluid, Wfluid, is given by Equation 2 where dh is the pressure head across the pump and V is the volume flow rate. W fluid [kw] = dh[ft H 2O ] V[gpm] 0.746 [kw 3,960 [gpm ft H 2 O/hp] hp ] 2 At Point 2V, the fluid work was: W fluid [kw] = 71.6 ft H 2O 81 gpm 0.746 kw = 1.09 kw 3,960 gpm ft H 2 O/hp hp However, the electrical power to the pump motor is always greater than fluid work because of efficiency losses in motor, pump, and VFD. Using the measured power draw and calculated fluid work, the combined efficiency, ηcombined, is given by Equation 3.

η combined = W fluid[kw] P[kW] At Point 2V, the combined efficiency was: 1.09 kw η combined = 100% = 34% 3.25 kw 3 The combined efficiencies at Points 2T and 2V were 32% and 34%, respectively. These results indicate that about 70% of pump power was lost due to inefficiencies in the motor, pump, and VFD. MINIMUM FLOW CONSTRAINTS Most pumping systems require some minimum flow due to constraints such as minimum VFD speed, minimum flow through the pump, or minimum flow through equipment such as a chiller evaporator. Hence, a bypass is needed to provide a path for minimum flow when end uses reduce flow below this minimum. In the ideal case, no bypass flow is permitted when the end uses require more than minimum flow. Flow in excess of the minimum required flow increases pumping power and wastes energy. Ideal Bypass Flow Control Primary-only pumping systems use a single pump (or set of pumps in parallel) to move fluid through a chiller and to end uses. In primary-only pumping systems, best practice to meet a minimum flow constraint is to add bypass piping with an actuated 2-way valve to the piping system (Avery 2009). The bypass valve is closed when the end uses require more than minimum flow. The valve opens to allow minimum flow based on a flow meter as shown in Figure 3 (Taylor 2012) or based on the pressure difference through the chiller as shown in Figure 4 (J. Fauber, Senior Mechanical Engineer, Heapy Engineering, E, pers. comm., May 2015). Figure 3. Primary-only system with 2-way bypass controlled by flow meter. Figure 4. Primary-only system with 2-way bypass controlled by differential pressure. Another way to guarantee minimum flow through chillers is by dedicating primary pumps to move water through the chiller(s) and secondary pumps to move water to end uses. In primary-secondary systems, constant-speed primary pumps provide minimum flow to the chiller(s) which eliminates the need for a bypass valve as shown in Figure 5.

VFD dp Secondary Pump Constant Speed Primary Pump Chiller Chilled Water to End Uses Excess Bypass Flow Figure 5. Primary-secondary system eliminates the need for a bypass valve The effect of excess bypass flow on energy savings in variable-flow pumping systems was experimentally measured in the UDHL. In this experiment, flow through the process end use was 81 gpm with the manually-controlled bypass valve closed. Next, flow through the process end use was maintained at 81 gpm with the bypass valve about 50% open. Figure 6 shows that with the bypass valve closed, the VFD ran at 1,180 rpm, total flow was 81 gpm, and the operating point is 2VC. With the bypass valve 50% open, the VFD ran at 1,212 rpm, total flow was 134 gpm, and the operating point shifted to 2VO. Since flow through the process end use was maintained at 81 gpm, 53 gpm traveled through the bypass loop. In this case, pump power increased from 3.25 kw to 4.12 kw or about 27%. When the manually-controlled bypass valve was fully open, pump power increased by 54%. This indicates that if the effect of excess bypass flow is neglected in savings calculations, those calculations will significantly overestimate savings. These results also suggest that savings can be significantly increased by minimizing excess bypass. Figure 6. Measured energy penalty associated with bypass 50% open Three common piping systems that result in excess bypass flow are shown below. The first is a 3-way valve at one or more end uses as shown Figure 7. The 3-way valve(s) always allows some bypass flow, thus wasting pumping energy.

Figure 7. 3-way bypass valve at one end use. Another piping system that allows excess bypass flow uses a manually-controlled bypass valve as shown in Figure 8. Manually-controlled valves are always at least partially open and hence allow bypass flow even when no bypass is required. The recommended commissioning practice in a system with a manually-controlled bypass valve is to close all end use loads and throttle to allow minimum required flow (J. Kelley, Energy Engineer, Plug Smart, LLC, E, pers. comm., February 2015.). However, when end use valves close, flow through the bypass valve increases due to rebalancing of flow, allowing more than minimum flow through bypass. Rebalancing of flow is shown experimentally by the difference in flows V 2TO and V 2VO in Figure 6. In industrial systems, manually-controlled bypass valves are often neglected after installation and allow unmonitored excess bypass flow. Figure 8. Manually-controlled bypass valve. A third common piping system that allows excess flow uses an automatic flow-limiter on the bypass pipe as shown in Figure 9. Automatic flow-limiters are better than manuallycontrolled valves since they prevent rebalancing of flow. However, they still allow a fixed amount of bypass flow when no bypass is required, resulting in wasted pumping energy. Figure 9. Automatic flow-limiter bypass valve.

PUMP SPEED CONTROL Fixed Pressure Setpoint Control Automatically-controlled VFDs modulate pump speed based on data from a control variable; the most common control variable is pressure. The setpoint pressure determines the y- intercept of the system curve; hence, a high pressure setpoint increases pump power at all flows. This concept is demonstrated in Figure 10. The rectangle defined by Point 2V80 represents pump power when the pressure setpoint value is 80 ft. H2O. The rectangle defined by Point 2V40 represents pump power when the pressure setpoint value is 40 ft. H2O. The difference in the size of the rectangles represents the additional energy associated with setting the dp at 80 ft. H2O compared to setting it at 40 ft. H2O. Figure 10. Additional energy associated with a higher dp setpoint is represented by the difference in the rectangles. The setpoint pressure must be large enough to push fluid through the end uses and depends on the location of the sensor in relation to the pump and end uses. The influence of sensor location on pressure setpoint is demonstrated by considering four common pumping systems. Figure 11 shows a closed-loop chilled water system with a sensor located at the pump outlet measuring differential pressure between the supply and return headers. At this location, the pressure setpoint has to be high enough to push fluid from point 2 through the supply header, through the most remote end use, and back to point 3 through the return header. If the differential pressure sensor were located near the most remote end use, the pressure setpoint would only have to be high enough to push fluid through the most remote end use. Thus, controlling the VFD based on the differential pressure near the most remote end use results in a lower setpoint pressure and reduced energy use. Locating a differential pressure sensor at the most remote location is recommended by ASHRAE Standard 90.1-2010 (ANSI/ASHRAE Standard 90.1-2010). Another way to consider pumping energy use is to characterize energy savings in terms of flow reductions and head reductions. In Figure 11, from reference points 1-to-2 and 3-to-1, energy savings would be realized from flow and head reductions. From reference points 2-to-3, energy savings would only be realized from flow reduction in end uses. Thus, the total pressure drop across the pump would decrease only slightly due to reduced flow through the chiller.

Figure 11. Closed-loop chilled water system with differential pressure sensor at the discharge of the pump. Figure 12 shows a closed-loop chilled water system with a sensor measuring pressure at the discharge of the pump. At this location, the pressure setpoint has to be high enough to push fluid from point 2, through the end uses, through the chiller, and back to the pump at point 2. Thus, controlling the VFD based on pump discharge pressure results in an even higher setpoint than in Figure 11, and increased energy use. As before, pumping energy use through Figure 12 can also be described in terms of flow reductions and head reductions. From reference points 1-to-2, energy savings would be realized from flow and head reductions. From reference points 2-to-1, energy savings would only be realized from flow reduction in end uses. Thus, the total pressure drop across the pump would remain nearly constant even as flow is reduced, and energy savings from pressure reduction are minimal. Figure 12. Closed-loop chilled water system with single pressure sensor at the discharge of the pump. Figure 13 shows an open-loop cooled-water system with a sensor measuring pressure at the discharge of the pump. At this location, the pressure setpoint has to be high enough to push fluid from point 2 through the end uses and into the open tank. Moreover, additional pressure head is required to lift the fluid from 3-to-2. Thus, controlling the VFD based on pump discharge pressure results in a high pressure setpoint. As before, from reference points 1-to-2 and 3-to-1, energy savings would be realized from flow and head reductions. From reference points 2-to-3 and to lift the fluid through the elevation gain, energy savings would only be realized from flow reduction.

Figure 13. Open-loop cooled-water system with single pressure at the discharge of the pump. Figure 14 shows an open-loop cooled-water system with a sensor measuring pressure at the discharge of the pump. At this location, the pressure setpoint has to be high enough to push fluid from point 2 through the entire supply header and through the most remote end use. If the pressure sensor were located near the most remote end use, the pressure setpoint would only have to be high enough to push fluid through the most remote end use. Thus, controlling the VFD based on the pressure near the most remote end use results in a lower setpoint pressure and reduced energy use. As before, from reference points 1-to-2 and 4-to-1, energy savings would be realized from flow and head reductions. From reference points 2-to-3 and to lift the fluid through the elevation gain, energy savings would only be realized from flow reduction. Figure 14. Open-loop system with single pressure sensor at the discharge of the pump. Resetting Pressure Setpoint Based on Valve Position As demonstrated above, a high pressure setpoint reduces energy savings when reducing flow. In fixed pressure setpoint control, the pressure setpoint must be high enough to maintain flow at peak conditions. However, many pumping systems seldom require peak flow. In these cases, the pressure setpoint can be dynamically reduced to save pumping energy. In valve position control, the pressure setpoint, and hence VFD speed, decreases until at least one valve is almost fully open. Thus, valve position control supplies the required flow, at minimum pressure, without starving any end uses. The effect is to approach zero head at zero flow and approach the ideal pumping system shown in Figure 1. Valve position control is especially effective in parallel-flow piping systems where pressure based control may starve some end uses. For example, if the parallel-flow piping system shown in Figure 15 used fixed setpoint pressure control, locating the differential pressure sensor

in circuit A may starve end uses in the circuit B if circuit B requires more flow and pressure than circuit A. Valve position control is less effective on systems with multiple end uses of different sizes. Moreover, valve position control does not set the lower limit on VFD speed; this is done elsewhere in the control algorithm. CASE STUDY Figure 15. Parallel-flow pumping system. The following case study demonstrates energy saving potential from minimizing bypass flow and pressure control losses. The variable-flow HVAC chilled water system shown in Figure 16 employs best practice by locating a differential pressure sensor near the most remote end use. In addition, the pressure sensors across the chiller evaporators can be used to measure flow through the evaporators to ensure minimum flow. The use of reverse return balances unregulated flow through the air handlers (Taylor 2002). The use of a three-way bypass valve at AHU 1 is not a recommended practice because some flow is always being pumped through the bypass. Figure 16. Chilled water pumping system in case study. Despite the existence of VFDs and well-located pressure sensors, data from the control system indicate non-optimal control. Figure 17 shows measured five-minute VFD speed versus building differential pressure (dp) data from April 2014 to November 2014 when only Pump 1

was operating. Figure 18 shows measured five-minute VFD speed versus chiller evaporator dp data from April 2014 to November 2014 when only Pump 1 was operating. In a properly controlled system, the VFD should vary speed to maintain a constant building dp. However, the data show that the building dp varies between 1 psi and 8 psi. In addition, in a properly controlled system, the VFD speed and building dp should be highly correlated. However, statistical analysis shows an R2 value of 0.02 between VFD speed and building dp. In fact, Pump 1 operates at 70% for 55% of the time. According to the chiller specification sheets, the chiller evaporator dp must be between 1.4 psi and 6.4 psi. However, it maintains an average chiller evaporator dp of 6 psi and often exceeds the limit of 6.4 psi. All this indicates very poor control. 100 100 90 80 80 70 70 VFD Speed (%) VSD Speed (%) Upper limit of chiller evaporator dp, 6.4 psi 90 Building differential pressure varies from 1 psi to 7.5 psi. 60 60 50 50 40 40 30 30 20 20 10 10 0 0 2 4 6 8 Building dp (psi) 10 0 0 1 2 3 4 5 6 7 Evaporator dp (psi) Figure 17. Building dp vs. VFD Speed. Figure 18. Chiller Evaporator dp vs. VFD Speed. Time series data offers more insight into the control problems. As seen in Figure 19, the VFD operated at an average speed of 70% on Saturday, May 10, when the average outdoor air temperature was 65.5 F, the average relative humidity was 70% and occupancy and internal loads were small. In Figure 20, the VFD operated at an average speed of 64% on Thursday, July 10, when the average outdoor air temperature was 70.7 F1 and the average relative humidity was 66%2 and occupancy and internal loads were high. If properly controlled, the VFD speed would be higher on a hotter, wetter day with higher occupancy and internal loads. However, the opposite is true. The VFD speed is stuck at 70% on May 10 and drops to 30% on July 10. This indicates inefficient control. Figure 19. Trend data on Saturday, May 10, 2014. Figure 20. Trend data on Thursday, July 10, 2014. Average daily temperatures were taken from Kissock s Average Daily Temperature Archive: http://academic.udayton.edu/kissock/http/weather/ 2 Relative humidity taken from Weather Underground: http://www.wunderground.com 1 8

The original control algorithm executes the following steps: 1. Chiller 1 and Pump 1 turn on when the outdoor air temperature is above 65 F. For outdoor air temperatures between 55 F and 65 F, economizers on the air handling units (AHU) are able to meet the cooling load. 2. Differential pressure is read across the building and Chiller 1 evaporator: The chiller evaporator dp must be maintained between 1.5 psi and 6.4 psi. If it is higher or lower, the VFD ramps up or down to maintain the upper and lower bounds. The building dp setpoint is 10 psi. The VFD simultaneously ramps up or down to maintain 10 psi across the building. 3. If the building dp drops below 2.3 psi for 30 minutes, pump 2 turns on to increase building pressure. 4. If the chilled water supply temperature is greater than 48 F, Chiller 2 comes on to provide more cooling capacity to the building. Because of the 6.4 psi upper bound on the chiller evaporator dp, the VFD is always hunting for, but never reaches, the building dp setpoint of 10 psi. To improve energy-efficiency, the building dp setpoint should be reset to 2.3 psi. According to maintenance personnel this is sufficient to supply all air handlers with adequate flow. In addition, it guarantees a minimum of 1.4 psi pressure drop, and minimum flow, through the evaporator. This change will stop the VFD from hunting for a set-point it can never attain. Instead, the VFD speed will vary with the thermal building load; resulting in better controlled and more energy-efficient pumping. Using the pump affinity law with an exponent of 2.5, the estimated annual savings from implementing the reduced building dp setpoint are 47% of chilled water pumping energy use. After this change is successfully implemented, we will recommend replacing the 3-way bypass valve with an actuated 2-way bypass valve controlled to provide a minimum pressure drop, and hence flow, across the chiller evaporator. Next, we will recommend resetting the building dp setpoint based on valve position. We will begin implementing these changes after sufficient baseline data is collected so energy savings can be measured. CONCLUSIONS This paper describes several best practices for controlling variable-flow pumping systems. As variable-flow pumping systems become more common, adhering to these best practices are important in order to maximize energy savings. In our experience, many variableflow pumping systems are not optimally controlled, so the potential for savings is great. To maximize energy savings in variable-flow pumping systems, bypass flow should be minimized or eliminated. Best practice to eliminate excess bypass flow is to employ an actuated two-way bypass valve or primary-secondary pumping. If the effect of excess bypass is neglected, savings calculations will significantly overestimate savings. Best practice in controlling VFD speed is locating a differential pressure sensor near the most remote end use in the system. To increase energy savings, the dp setpoint should be as low as possible. Further, valve position can be used to reset the pressure setpoint downward to allow static head to approach zero and maximize energy savings.

ACKNOWLEDGMENTS We are grateful for support for this work from the U.S. Department of Energy through the Industrial Assessment Center program and through an Excellence in Applied Energy Engineering Research grant. We are very grateful to Steve Kendig and John Brammer for providing access to and information about the chilled water pumping system and for helping us develop an improved algorithm. We are also grateful to Bernard Glascoe for assisting us in the UDHL. We are also very grateful to Jeremy Fauber for technical support and feedback. Finally, we are grateful to the IAC students and staff upon whose work this effort is built. REFERENCES ANSI/ASHRAE Standard 90.1-2010, Energy Standard for Buildings Except Low-Rise Residential Buildings Avery, Gil and Rishel, James B. 2009. "Case Against Balancing Valves." ASHRAE Journal 26-29. ASHRAE, July. Bernier and Bourret, 1999, Pumping Energy and Variable Frequency Drives, ASHRAE Journal, December. EERE (Energy Efficiency and Renewable Energy). 2001. Pump Life Cycle Costs: A Guide to LCC Analysis for Pumping Systems. U.S. Department of Energy https://www1.eere.energy.gov/manufacturing/tech_assistance/pdfs/pumplcc_1001.pdf Grundfos Management. 2011. All You Need to Know About Pumps and Energy http://energy.grundfos.com/en/facts-on-pumps-energy/energy-and-pump-facts Kissock, J. 2014a. Energy Efficient Buildings: Duct System Design, CAV/VAV. http://academic.udayton.edu/kissock/http/eeb/energy%20efficient%20buildings_1.htm Ma, Y., Turker, A., Kissock, J. 2015. Energy Efficient Static Pressure Reset in VAV Systems. 2015 ASHRAE Winter Conference, Chicago: ASHRAE. Maxwell, Jonathan. 2005. How to Avoid Overestimating Variable Speed Drive Savings. NCSU (North Carolina State University). 2014. DSIRE (Database of State Incentives for Renewables & Energy Efficiency). www.dsireusa.org Taylor, S., Stein, J. 2002. Balancing Variable Flow Hydronic Systems. ASHRAE Journal, October. Taylor, S. 2012. Optimizing Design & Control of Chilled Water Plants, Part 5: Optimized Control Sequences. ASHRAE Journal, June.