Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO )

Similar documents
LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO )

LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO )

Impact Sound Testing of Floor Covering on a Heavyweight Standard Floor

B Page 1 of 21-

KINETICS NOISE CONTROL TEST REPORT #AT001067

Laboratory Measurement of Impact Sound Insulation of Floor Coverings on a Heavyweight Concrete Slab Floor

Determination of the sound reduction and sound absorption of a railroad noise barrier

KINETICS NOISE CONTROL TEST REPORT #AT001035

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS EXPOSED NU SHADEX PERFORATED PLASTER CEILING TILES (600MM

KINETICS NOISE CONTROL TEST REPORT #AT001110

KINETICS NOISE CONTROL TEST REPORT #AT001049

KINETICS NOISE CONTROL TEST REPORT #AT001052

ACOUSTIC PERFORMANCE AND STC RATING OF A PARTITION WALL WITH DOUBLE SOCKETS AND POLYSEAM PUTTY PADS

INTRODUCTION SPECIMEN DESCRIPTION

Volume II FWPRDC PN Maximising impact sound resistance of timber framed floor/ceiling systems. Page 183

KINETICS NOISE CONTROL TEST REPORT # AT001084

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

KINETICS NOISE CONTROL TEST REPORT #AT001032

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CASINO 600MM

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CELL AIR 1200MM

SPEEDPANEL. Fire & Acoustic Rated Wall Systems. Speedpanel. Intertenancy systems SPEEDPANEL

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT

Evidence of Performance Joint sound reduction of filling material

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT

KINETICS NOISE CONTROL TEST REPORT #AT001021B

ACOUSTICAL PERFORMANCE TEST REPORT

Evidence of Performance Airborne sound insulation of building components

Sound Insulation for Glass and Panel

TECHNICAL DOCUMENT - SOUND INSULATION R9 SYSTEM. Dated: 30 August 2013

Maximising impact sound resistance of timber framed floor/ ceiling systems Volume 3

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E90 AND ASTM E492 TESTING ON ATTAIN LVT OVER 2 MM ECOSILENCE UNDERLAYMENT

Measurement of Airborne & Impact Sound Insulation. University of Durham, Pavilion H, Howlands Farm, Durham.

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

CONSIDERATIONS REGARDING IMPACT SOUND INSULATION PERFORMANCES OF DIFFERENT FLOOR MATERIALS

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

Intertek Testing Services

Laboratory Airborne and Impact Sound Insulation of a Robust Details Appendix F Floor with PhotonStar LED Ltd. Downlights

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA

Testing Procedure: AS ISO

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

The specimen B W was identified by the client as a Skyfold Classic operable partition, with panels, seals, and clearances in configuration 4E.

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to PROFLEX PRODUCTS, INC.

FIELD IMPACT INSULATION TESTS 133 SCARBOROUGH STREET, SOUTHPORT TEST REPORT

Testing Procedure: AS ISO

Laboratory Airborne Sound Insulation of Stud Walls with Warmcel 500 Insulation. Prepared for:

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to REGUPOL AMERICA

G R1 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to PROTECTO WRAP COMPANY

Report Number BTC 16234A

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT

D R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY. Series/Model: Whisper Mat CS

Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Vinyl

Comparative Impact Performances of Lightweight Gym Floors

Testing Procedure: AS ISO

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9100AB REVRB. TYPE: Acoustic Baffles

LABORATORY MEASUREMENTS OF THE SOUND REDUCTION INDEX ROCKWOOL ABLATIVE COATED BATTS

Measurement of Sound Absorption Coefficient for Perfopan slotted Wall Panels Code No. SLT 7x7-PR 12%, DS 270, on 45 mm mineral wool

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF 2MM ECHOPANEL WALL TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM.

Classification report Airbourne sound insulation of building elements

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to VENEKLASEN ASSOCIATES

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to VENEKLASEN ASSOCIATES

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to URBAN SURFACES

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to FABRITRAK SYSTEMS, INC. SERIES/MODEL: Fabri Flex Fabric with 6#

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 492 AND ASTM E Rendered to REGUPOL AMERICA

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM C423. Rendered to NEW ENGLAND SOUNDPROOFING SERIES/MODEL: REVRB TRADITIONAL SERIES

Report Number BTC 14020A

Ceramic Tile, LATICRETE 253 Gold Mortar and LATICRETE 170 Sound & Crack Isolation Mat on 6 Inch Concrete Slabs. Page 1 of 5. CONDUCTED: 1 May 2008

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to URBAN SURFACES. Series/Model: Urban Surfaces Soundtec

C R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10

palmer acoustics TEST REPORT

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to REGUPOL AMERICA

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

Test report No B0082 IN CM 26-M56-I

Test report No B0082 IN CM 26-M55-I

Report Number BTC 13505A

TEST REPORT No. VTT-S

19 th INTERNATIONAL CONGRESS ON ACOUSTICS MADRID, 2-7 SEPTEMBER 2007 A METHODOLOGY TO MEASURE THE ACOUSTIC PERFORMANCE OF ACCESS FLOORS

This page was. intentionally. left blank

ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1-1/4" Fabri Trak

Acoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A August 2016 CONSTRUCTION

Evidence of Performance Joint sound reduction of filling material

NOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT

CONDUCTED: 19 August 2013 Page 1 of 7. ON: #1 N3CD Pan Metal Deck - Plain 1.5 pcf, 5.25" x 1.5" over 2" Poly ISO Board

CONDUCTED: 21 August 2013 Page 1 of 7. ON: #19 W2CD Pan Metal Deck - 1.5pcf Encapsulated Fiberglass Insulation 5.25"x1.5" over 2" Poly ISO Board

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: FabriSpan. TYPE: Ceiling System. Summary of Test Results

NO. 19 WILBERFORCE ROAD COXHEATH, MAIDSTONE, KENT ME17 4HD SOUND INSULATION TESTING. On behalf of: Oscar Acoustics

H R2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CR LAURENCE CO., INC. Series/Model: 487-AR. Type: Office Partition

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: FABRI TRAK SYSTEMS, INC. SERIES/MODEL: 1" FABRI TACK

F R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to PROTECTO WRAP COMPANY

ASTM C 423 SOUND ABSORPTION TEST REPORT. Rendered to: NEW ENGLAND SOUNDPROOFING SERIES/MODEL: 9000AP REVRB. TYPE: Acoustical Wall Panel

F R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90, ASTM E 492, ASTM E Rendered to

Transcription:

Reference no. T1638-1 Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO 10140 3) AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Report prepared for: Jacobsen Creative Surfaces PO Box 3151 Brighton VIC 3186 Australia Report prepared by: Dr. Michael Kingan Mr. Gian Schmid Acoustics Testing Service The University of Auckland

Reports from Auckland UniServices Limited should only be used for the purposes for which they were commissioned. If it is proposed to use a report prepared by Auckland UniServices Limited for a different purpose or in a different context from that intended at the time of commissioning the work, then UniServices should be consulted to verify whether the report is being correctly interpreted. In particular it is requested that, where quoted, conclusions given in UniServices reports should be stated in full. Page 2 T1638-1

LABORATORY MEASUREMENT OF THE REDUCTION OF TRANSMITTED IMPACT SOUND BY FLOOR COVERINGS ON A STANDARD FLOOR (According to ISO 10140-3) Prepared For: Jacobsen Creative Surfaces PO Box 3151 Brighton VIC 3186 Australia Prepared by: Acoustics Testing Service Department of Mechanical Engineering University of Auckland AUCKLAND UNISERVICES LTD. THE UNIVERSITY OF AUCKLAND PRIVATE BAG 92019 AUCKLAND Mr. Gian Schmid. Dr. Michael Kingan. Page 3 T1638-1

Reduction of impact sound pressure level according to ISO 10140-3 Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor Client: Jacobsen Creative Surfaces and Nordic Built Pty Ltd. Date of test: 18-Jul-16 Test rooms: Reverberation Chambers A and B Description and identification of the test specimen and test arrangement: Source chamber side: 3240 x 3175mm of Pergo Mansion Oak, Plank PerfectFold 3.0 laminate flooring (71.5kg) loose laid on Silent Shield underlay (2.95kg) loose laid on a concrete slab. Receiving chamber side: nil Source chamber was Chamber A and receiving chamber was Chamber B. Deviation from standard: The bare test floor used is of uniform thickness for an area of only 2.6m x 2.6m. The description of the bare test floor is given in the full report. Mass per unit area: 11.035 kg/m 2 Air temp in the test rooms: 16 o C Air humidity in test rooms: 61 % Receiving room volume: 153 m 3 65.0 60.0 L n,0 L Frequency One-third One-third f octave octave Hz db db 50 53.7 2.6 63 47.8-0.4 80 53.8 2.1 100 61.7 1.3 125 63.5 0.1 160 64.4 2.4 200 67.6 2.8 250 70.7 3.3 315 71.5 5.1 400 69.9 6.6 500 71.3 7.0 630 71.7 11.9 800 71.4 17.5 1000 72.4 19.9 1250 72.5 23.0 1600 71.4 28.8 2000 72.6 35.2 2500 72.8 40.5 3150 72.8 44.3 4000 71.4 44.4 5000 68.4 43.0 Reduction of impact sound pressure level, L, db 55.0 50.0 45.0 40.0 35.0 30.0 25.0 20.0 15.0 10.0 5.0 0.0 Notes: #N/A = Value not available. Bold values are used to calculate L w. < indicates that the true value is lower. L n,0 are the bare floor impact sound levels. Rating according to ISO 717-2: -5.0 50 63 80 100 125 160 200 250 315 400 500 630 800 1000 Frequency, f, Hz 1250 1600 2000 2500 3150 4000 5000 L w = 18 db C I,Δ = -11 db C I,r = -1 db C I,50-2500 = 0 db These results are based on a test made with an artificial source under laboratory conditions (engineering Method) with the specified reference floor. No. of test report: T1638-1 First test on sample Name of test institute: University of Auckland Acoustics Testing Service. Date: 26-September-2016 Signature: Page 4 T1638-1

ANNEX A. PHOTOS AND DETAILS OF THE TEST SPECIMEN Figure 1: Boards in place on underlay. Figure 2: Packaging for floor boards Figure 3: Packaging for Silent Shield Underlay Page 5 T1638-1

ANNEX B. ADDITIONAL INFORMATION ABOUT EQUIPMENT USED INSTRUMENTATION EQUIPMENT TYPE / SERIAL No. CHAMBER C SOURCE ROOM 1/2" Microphone 4165 / 1622303 Preamplifier 2619 / 9459549 Rotating Boom 3923 / 936497 CHAMBER A RECEIVING ROOM 1/2" Microphone 4190 / 2150379 Preamplifier 2619 / 945952 Rotating Boom 3923 / 936496 Calibration of the above equipment was conducted by Electroacoustic Calibration Services (ECS), an IANZ registered laboratory. BOTH ROOMS Calibrator 4231 / 2241899 Analyzer 01dB Stell / 01381 Page 6 T1638-1

ANNEX C. SUMMARY OF THE MEASUREMENT OF IMPACT SOUND INSULATION OF FLOORS INSTALLATION OF TEST SAMPLE The floor covering is installed on a concrete floor plug that is positioned in the opening between two large reverberation chambers chambers B and A. These chambers are vibration isolated from each other, which results in a structural discontinuity at the middle of the test opening. This gap is covered over by a wooden collar, which seals the gap and provides for ease of fixing of samples. The concrete floor plug is made of concrete reinforced with steel and is covered with a layer of hard resin. The dimensions of the floor 3200mm 140mm plug are given in the following elevation diagram. 295mm 140mm 155mm 145mm 255mm 155mm If the floor covering is flexible, three samples to be tested are laid by the client following the techniques normally used in practice for that type of floor covering, with the constraint that the concrete floor plug be protected by a layer of thin self adhesive plastic tape if necessary. METHOD The normalized impact sound pressure levels are obtained in accordance with the recommendations of ISO standard 10140-3 2010-09-01 Laboratory measurements of sound insulation of building elements. Part 3: Measurement of impact sound insulation The tapping machine is placed on the three different covering samples. The impact sound pressure level is measured in the room below the floor, using a rotating microphone, in third octave frequency bands. The tapping machine is also placed on the bare concrete floor plug in positions on both sides of each floor covering sample, and the sound pressure level is again measured in the chamber below the floor. The difference between the sound levels for when the tapping machine is on the samples and for when the tapping machine is on the bare floor gives the reduction of transmitted impact sound by the floor covering L. The impact sound pressure levels are normalized against the room absorption. The room absorption is calculated from the reverberation time and room volume. The reverberation time is measured from the decay of a steady state sound field. Corrections are applied, where necessary, for airborne sound transmission and background noise. The airborne sound transmission is determined using a loudspeaker and the microphone. RESULTS The third octave band change in impact sound pressure levels L are presented in both table and graph formats. The third octave band normalized impact sound pressure levels for the bare floor, L n,0, are also presented in table. Single figure ratings are also presented. The weighted change of impact sound pressure level L w, determined according to ISO 717-2, is presented. L w is determined by fitting a reference curve to the third octave band normalized impact sound pressure levels from 100Hz to 3150Hz for the change in impact sound pressure levels ΔL which have been added to the normalized impact sound levels of a standard floor (as given in ISO 717-2). From this curve a weighted change of impact sound pressure level L w is produced, and gives a single figure determination of the improvement of the normalized sound levels transmitted through the floor from impacts, which the floor covering can give (higher is better). Page 7 T1638-1

ANNEX D. DESCRIPTION OF THE REVERBERATION CHAMBERS AT THE UNIVERSITY OF AUCKLAND There are three large interconnected reverberation chambers at the Acoustics Research Centre, two at ground level (Chambers C and A) and the third (Chamber B) below A. All three reverberation chambers may be described as hexagonal prisms; each has 6 vertical sided walls, perpendicular to the floor. The roofs of chamber A and C are plane, but inclined at 12 degrees from horizontal. Chamber B has a plane, horizontal roof which is the floor of chamber A above it. The floor of chamber B is also horizontal, but has two angled sections at its North West and south east ends. The centre section is horizontal because a floor jack is installed there. The floor jack may be raised hydraulically to the ceiling of chamber B, the centre of which consists of a floor plug between the two chambers. This plug may be disconnected from chamber A and lowered down into chamber B, leaving a 3.2 m x 3.2 m opening between the two chambers. This allows for the measurement of airborne and impact insulation of floor and roof elements. The wall of chamber C adjacent to chamber A is left open, and the corresponding wall of chamber A consists of a pair of iron doors that are clamped against the chamber. The clamps may be removed and the iron doors pulled back, leaving the entire wall area (4.6 m wide x 2.74 m high) between the chambers open. This allows for the measurement of airborne sound insulation of wall elements. Chamber A has a rotating vane diffuser in a central position with an area (both sides) of about 53 m 2. It has the shape of two cones with their bases joined, with the two opposite quadrants of one cone open and the complementary quadrants in the other cone open. Chamber C has a similar rotating vane diffuser but it is smaller, having a total area of about 27 m 2. In addition, up to ten static diffusers may be employed if needed. These are constructed of two laminated layers of dense Formica, of dimensions 1 m x 1 m. The Formica elements are riveted to a frame constructed of aluminium T section. Four aluminium arms may be bolted onto the frame to allow the diffusers to be mounted as desired. Chamber A Chamber B Chamber C VOLUME (m 3 ) SURFACE AREA (m 2 ) 202 ± 3 203.6 ± 0.9 153 ± 2 173 ± 1 209 ± 4 214 ± 0.9 Page 8 T1638-1

The three Reverberation Chambers are linked by heavy steel doors and a removable Standard Industrial Floor Section which is removed and repositioned by a hydraulic hoist. The three chambers are vibration isolated from one another so that sound can only pass from one to the other via the intervening Test Wall or Test Page 9 T1638-1