Condenser And Heat Exchanger Tube Restoration OMMI (Vol. 1, Issue 2) August 2002

Similar documents
Western Regional Boiler Association

Corrosion and Performance Issues for Immersion Service Shell and Tube Heat Exchangers

Finding the Root Cause is Critical

Case Study: Failure Analysis of Sulfuric Acid Supply Line

THE CONDENSER: A SHORT DESCRIPTION. The Problem

View from the Penthouse

Condenser Tube Life-Cycle Economics

ATI 2205 ATI Technical Data Sheet. Duplex Stainless Steel GENERAL PROPERTIES. (UNS S31803 and S32205)

All definitions are defined according to ANSI/AWWA C

Prevention Strategies Design and Coatings

Intergranular Corrosion (IGC)

AL 29-4C AL 29-4C. Technical Data Sheet. Stainless Steel: Superferritic INTRODUCTION (UNS S44735)

Curran International Full length ID coating of steam condenser tubes: Q&A By Edward L. Curran, CEO, Curran International

UPDATED CASE STUDY OF FIRESIDE CORROSION MANAGEMENT IN AN RDF FIRED ENERGY-FROM-WASTE BOILER

POLYGUARD RD-6 A FAIL SAFE PIPELINE COATING SYSTEM FOR REHABILITATION OR GIRTH WELDS ON CATHODICALLY PROTECTED PIPELINES

6. SHEATH MATERIALS, THERMOWELLS, FITTINGS, AND TERMINATIONS

Performance improvement opportunities during a condenser retube

SANDVIK 254 SMO TUBE AND PIPE, SEAMLESS

All definitions are defined according to ANSI/AWWA C b. Flanged Joint: The flanged and bolted joint as described in ANSI/AWWA C110/A21.10.

Tubing and Pipes.

DATA SHEET ZERON 100 UNS S32760 THE GLOBAL LEADER IN SPECIALTY ALLOYS ALLOYS AND PROCESSING

ATI 825 ATI 825. Technical Data Sheet. Nickel-base Alloy INTRODUCTION PRODUCT FORMS SPECIFICATIONS & CERTIFICATES (UNS N08825)

DATA SHEET ZERON 100 UNS S32760 THE GLOBAL LEADER IN SPECIALTY ALLOYS

Process Vessel Internal Corrosion Management Solutions. David Blackwell Engineering Director

Tubing Data. Contents. Tubing Selection. Tubing Handling. Tubing Material. Tubing Outside Diameter Hardness. Tubing Wall Thickness

TECHNICAL SPECIFICATION FOR CURED-IN-PLACE MANHOLE REHABILITATION LINER SYSTEM

Overhaul Issues on Vertical Pumps

EPRI Condenser Symposium A Case Study of the French Nuclear Power Industry Steam Surface Condenser Tubes Forty Years Later

Tubes and Pipes. Tubes and Pipes D-02

Stress Corrosion Risk Reduction Guide

ATI ATI 2205 Alloy (UNS S31803 and S32205) Duplex Stainless Steel. Technical Data Sheet

Condenser Tubes in Thermal Power Plants Issues and Solutions

Standard Specification for Seamless and Welded Ferritic and Martensitic Stainless Steel Tubing for General Service

Stainless Steel Aeration Equipment Specification

GROWING CHALLENGES OF HEAT EXCHANGER S OPERATION AND MAINTENANCE IN LNG PLANTS

Tubing vs. Pipe: Which is Best for Steam & Condensate Systems?

TUBESHEET / CONDENSER REPAIRS: TERMINOLOGY:

EVALUATION AND ESTIMATION OF COBALT INTRODUCTION INTO SYSTEMS BY VALVES

Maintenance Technologies for SCC which Support Stable Operations of Pressurized Water Reactor Power Plants

PROCESS GAS WASTE HEAT BOILERS WITH THIN FLEXIBLE TUBESHEET DESIGN

Factors Influencing Materials Selection in Condensing Economizers

Testing. Test drainage products according to the applicable AASHTO or ASTM specification, except as otherwise noted.

Standard Specification for Seamless and Welded Ferritic/Austenitic Stainless Steel Tubing for General Service 1

Diffused Aeration Piping Equipment

Stress Corrosion Cracking

Recent Technologies for Steam Turbines

GREEN THREAD Piping Systems

UNIVERSITY OF MISSOURI Hydronic Energy Distribution 2016 Q1

Standard Specification for Seamless and Welded Ferritic and Martensitic Stainless Steel Tubing for General Service 1

New Advancements in the Abrasion Resistance of Internal Plastic Coatings

Results are presented in Table 1. The tube was fabricated from a Type 347 and no unusual conditions were noted.

Heat Treatment of Tubes for Condenser, Feedwater Heater, and Shell & Tube Heat Exchangers

Standard Specification for Seamless and Welded Ferritic/Austenitic Stainless Steel Tubing for General Service 1

SANDVIK 3R65 TUBE AND PIPE, SEAMLESS

SEASTROM Manufacturing Co., Inc Seastrom Street Twin Falls, Idaho Fax (208)

ASTM Standards for Pipe & Fittings

WYATT Orifice flow PrOducTs

Plymouth Feedwater Heater Tubing F O R T H E P O W E R G E N E R AT I O N I N D U S T R Y

Curramix 2500 Coating at NACE 2017

ATI 601 ATI 601. Technical Data Sheet. Nickel-base Alloy INTRODUCTION PRODUCT FORMS SPECIFICATIONS & CERTIFICATES (UNS N06601)

HYDRONIC PIPING CHAPTER 12

Accelerated Crevice Corrosion of Duplex Stainless Steels in Wet Limestone FGD Environments. Deba Maitra, Special Metals Corporation PCC Energy Group

Furmanite s engineered composite repair technology

Observations from Several Condition Assessments of Prestressed Concrete Cylinder Pipe used at Energy Generation Facilities

Condenser Cleaning, NDE and Leak Detection Part I: Condenser Cleaning

Flexpro. For Enhanced Joint Integrity. Style PN Normally used in male/female, tongue & groove, and other recessed flange configurations.

ATI 904L ATI 904L. Technical Data Sheet. Stainless Steel: Superaustenitic INTRODUCTION COMPOSITION CORROSION RESISTANCE (UNS N08904)

1. Scaling. H.O.: H-5/21, KRISHNA NAGAR, DELHI Tel.: , Fax:

SANDVIK 6R44 TUBE AND PIPE, SEAMLESS

SECTION IRRIGATION PIPELINE LINING (CURED-IN-PLACE PIPE)

SANDVIK 3R60 TUBE AND PIPE, SEAMLESS

SANICRO 30 TUBE AND PIPE, SEAMLESS

Water & Industrial Products Catalog

Standard Specification for Seamless and Welded Austenitic and Ferritic/Austenitic Stainless Steel Sanitary Tubing 1

U.S. Department of Transportation Pipeline and Hazardous Materials Safety Administration Plastic Pipe

Fossil Materials and Repair - Program 87

SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL

Series 400 Structural repair system that doubles the strength of the original timber pile. SeaShield Marine Systems. Features

Standard Specification for Seamless and Welded Austenitic Stainless Steel Sanitary Tubing 1

AL 29-4C For Heating and Ventilating

2016 Feedwater Heater Technology Conference

Remote Plasma Source Chamber Anodization

Super Austenitic Alloy N08367 Service Water Piping Review

ASTM Standards B127 B160 B161 B162 B163 B164 B165 B166 B167 B168 B333 B335 B407 B408 B409 B423

SYNLOOP WASTE HEAT BOILER IN AMMONIA PLANTS

RECOVERY BOILER WATER AND FIRE SIDE DAMAGE MECHANISMS April 2015 Western Canada BLRBAC. Craig Reid, M.A.Sc., P.Eng. Acuren Group Inc., Richmond, B.C.

Single-Jacketed Tubing

SANDVIK 3R12 FOR MEDICAL APPLICATIONS TUBE AND PIPE, SEAMLESS

SECTION SANITARY SEWERAGE PART 1 GENERAL 1.01 RELATED DOCUMENTS

SECTION STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY 1.2 SUBMITTALS 1.3 PROJECT CONDITIONS

Proceedings of the National Seminar & Exhibition on Non-Destructive Evaluation. NDE 2011, December 8-10, 2011

Alloy C194 vs. Alloy C122 for Air Conditioning and Refrigeration Applications

Nickel & Stainless Steel. Product Range

L104 PTFE L120 PTFE. Type S Gasket. applications. For use on ASME B 16.5 flanges. May be used for above ground or subsea

NORRIS. Drive Rods. Engineered performance. Designed tough.

ARC COMPOSITES for Abrasion

Static Mixers. Operation, Installation and Maintenance Instructions. Custom Engineered Solutions. to Meet Your Specific Industry Needs

SPECIFICATIONS FOR HONEYCOMB INTERNAL FLOATING ROOFS

Area of Use for Z100 (UNS S32760) Superduplex Stainless Steel Wireline.

Transcription:

Condenser And Heat Exchanger Tube Restoration OMMI (Vol. 1, Issue 2) August 2002 Condenser And Heat Exchanger Tube Restoration Peter Tallman, CTI Industries Inc., USA Steven Doubek, Wisconsin Electric Power, USA Mr Peter Tallman graduated from Providence College in 1979 with a B.S. degree in Business Marketing. He joined CTI Industries, Stratford, CT, in 1985 as Operation Manager. In 1995 became General Manager, which is his current position in the company. Abstract It is common experience that many failures of condenser and heat exchanger tubes in the electric utility industry occur within the first six inches of the bundle. In the past, the accepted solution for repairing this highly localized tube damage has been full retubing, even though usually more than 95% of the tube bundle length remains largely unaffected. With this in mind, a new restoration technique was developed in the mid-1970 s. It makes use of thin-walled metallic inserts, variously referred to as I.D. tube shields, or sleeves, which are expanded into the existing tube ends, adding years of additional service to the exchanger at a fraction of the cost of retubing. Introduction It is common experience that many failures of condenser and heat exchanger tubes in the electric utility industry occur within the first six inches of the bundle. Frequently encountered forms of such tube end damage are erosion, impingement attack, stress corrosion cracking and pitting/crevice corrosion. The damage variously manifests itself as tube thinning, grooving, localized pitting and cracking, all of which can ultimately lead to leakage and tube failure. In the past, the accepted solution for repairing this highly localized tube damage has been full retubing, even though usually more than 95% of the tube bundle length remains largely unaffected. However, this is a radical solution, which is very costly and time consuming. Today, with the emergence of deregulation of electric utilities, a proven, cost-effective alternative to retubing must be strongly considered by plant engineers. Historically, the most familiar stratagem for protecting damaged tube ends against further erosion or erosion-corrosion, and thus extend condenser tube life, is the use of plastic inserts. These inserts or tube protectors are only partly effective because they are not pressure tight and therefore unsuited for restoring leaking tubes to service. Also, plastic inserts can cause end step erosion and tend to become dislodged over time, especially during cleaning and back-

Condenser And Heat Exchanger Tube Restoration OMMI (Vol. 1, Issue 2) August 2002 2 With the objective of dealing with these shortcomings, a new restoration technique was developed in the mid-1970 s. It makes use of thin-walled metallic inserts, variously referred to as I.D. tube shields, or sleeves, which are expanded into the existing tube ends, adding years of additional service to the exchanger. The characteristics and capabilities of metallic tube inserts are described below. Also, briefly covered for sake of completeness are tube restoration/protection methods that make use of non-metallic materials. Common Heat Exchanger Tube Failure Mechanisms Inlet end erosion is a common problem with copper alloy condenser tubes, caused by the kinetic force of the cooling water, particularly if it contains entrained abrasive solids. Changes in flow direction, eddying and air bubbles combine to create highly turbulent conditions at tube inlets, resulting in impairment of protective passive films on the tube I.D. About six inches into the tube, turbulent flow conditions change to laminar flow, and fluid erosivity is sharply reduced. Other factors that can contribute to high turbulence are unfavorable design configurations of the waterbox and inlet piping. With fluids containing corrosive constituents, tube wastage can be greatly exacerbated. This so-called erosion-corrosion is a synergistic phenomenon wherein the combined action of erosion and chemical attack are greater than their separate effects. Corrosive process fluids most commonly cause erosion-corrosion. However, it can also occur with waters, as for example with brasses exposed to sulfide and/or ammonia treated cooling waters. Stress Corrosion Cracking (SCC) is another fairly common failure mode in heat exchanger tubing. It is caused by the combined action of tensile & compressive stresses and corrosion. SCC frequently occurs in the rolled area immediately beyond the tubesheet, especially with overrolling, and is metal-environment specific. Well-known forms are ammonia SCC of copper base alloys, chloride SCC of austenitic stainless steels and alkali SCC (caustic embrittlement) of carbon and alloy steels. These failure mechanisms can occur in the outlet tube ends, as well as the inlets. Other types of corrosion encountered in tube ends and at tube-to-tubesheet joints are pitting attack and crevice corrosion. Crevice corrosion is a virulent form of deep local penetration, experienced most often with austenitic (Cr-Ni) stainless steels exposed to chlorides. Both SCC and crevice corrosion are greatly accelerated at elevated temperatures. Damage at this critical location of the inlet tubesheet and tube ends can also be caused by mechanical factors (e.g. improper tube expansion) and by poorly executed tube-to-tubesheet welds.

Condenser And Heat Exchanger Tube Restoration OMMI (Vol. 1, Issue 2) August 2002 3 I.D. Tube Shields Metallic thin-walled inserts or shields were introduced in 1976. This restoration process protects, restores and seals off any leaks at the damaged tube ends. The shields are manufactured to specific dimensions while retaining ductility required for expansion. A thinwalled construction, I.D. chamfer of the outlet end and metal-to-metal expansion greatly reduces the chance of end step erosion, a common occurrence with other tube inserts. As in the case of the heat exchanger tubing, selecting the proper shield alloy is critical. Material can be selected from a range of different alloys, depending on existing tube material and their failure mechanism. Choices of shield material range from copper alloys, conventional stainless steel, superaustenitic stainless steels and nickel-base alloys. This allows the plant to select an alloy to combat a specific failure mechanism such as chloride pitting, stress corrosion cracking, ammonia grooving, etc. The installation process is carried out in-situ beginning with wire brushing tube I.D. s allowing for a pressure tight seal to hold the shield in place. After the tubes are blown clear with compressed air, I.D. measurements are taken to determine expansion requirements. Shields are then inserted into each tube end. A hydroswage mandrel is inserted into the shields. The mandrel is coupled to the strain volume control hydroswage pump, which is preset to achieve full-length expansion of the shields. A hybrid expansion is then accomplished by roller expanding the shields at the tubesheet to torque controlled settings and also at the deep end - or last inch - of the shields. The final step is to flare the shields so that they conform to the tubesheet profile. This repair is not a temporary repair but a true restoration that will add years of service to the existing condenser. One West Coast facility in the USA states that the first condenser which was sleeved was intended to be a short-term five year fix. These same tubes are still in service twenty years later with no problems. Besides condensers, shields have been installed in high-pressure heat exchangers (29 MPa / 4200 psi) and high temperature service (650 C/1200 F). In some cases, though not typical, shields have been able to bridge tubes that have been completely severed. Tube restoration by means of metallic inserts is a cost-effective repair method offering the following favorable features and capabilities: Restore and protect the damaged tube ends. Restore tube-to-tubesheet joint strength. Provide pressure tightness. Return plugged, leaking tubes to service. Enable the tubes to maintain mechanical cleaning capabilities. Minimizes end-step erosion possibility. Installation during low-load conditions. Have no ill effects on heat transfer. Reduce outage time. Extend bundle life.

Condenser And Heat Exchanger Tube Restoration OMMI (Vol. 1, Issue 2) August 2002 4 Because of the thin-wall construction and the expansion of the shield, tube openings are reduced by only a fraction compared to considerably thicker plastic inserts. Plastic Inserts Flanged or flared plastic inserts or tube protectors were originally developed for the specific purpose of alleviating inlet end erosion. They are typically four to eight inches long, and furnished in a range of conventional thermoplastics or fluoroplastics. Installation is either by press fit or by cementing in with an adhesive. Plastic inserts are furnished in pre-set standard diameters based on new tube dimensions, which makes them an inexpensive commodity. However, they do not provide for tube wall loss or irregular wear of the tube I.D. Even though the downstream end of the insert is tapered, end-step erosion takes place in the tubes immediately beyond the inserts. This is caused by the turbulence of the circulating water exiting the insert and entering the parent tube I.D. Therefore, although the inlet end erosion has subsided, a new problem has been created. Another drawback in the design of the plastic insert is the reduced I.D. at the flanged area. Depending on the insert O.D., the thickness of the insert can range from 1.07 to 3.3 mm (0.042 to 0.130 inches). This could mean a reduction of the original tube I.D. of over 30%, severely restricting the amount of circulating water entering the tube. Other problems associated with plastic inserts are that they: Do not restore structural integrity to weakened tube-to-tubesheet joints Do not restore plugged/leaking tubes to service Do not fit properly in eroded tubes Prevent proper mechanical tube cleaning Frequently become loose or dislodged Promote crevice corrosion Cannot be installed into outlet tube ends Epoxy Coatings Application of epoxy coatings has recently emerged as a suitable method for restoring eroded / corroded I.D. surfaces of condenser tubes, as an extension of its application on tubesheets and waterboxes. Coating systems applied are phenolics, epoxy phenolics and fluoropolymers. Coating performance and life is critically dependent on meticulous surface preparation and coating application, particularly on pitted surfaces, and requires specially developed devices. Unfortunately, the quality assurance necessary to ensure proper surface preparation of the tube I.D. s remains suspect. Because this is still considered new technology, the effective life of this type of repair is still unknown.

Condenser And Heat Exchanger Tube Restoration OMMI (Vol. 1, Issue 2) August 2002 5 Other problems associated with epoxy coatings are that they: Do not restore structural integrity to weakened tube-to-tubesheet joints. Do not restore plugged/leaking tubes to service. Cannot be applied during low-load conditions. Can be damaged by certain types of mechanical cleaning Can create condensate contamination by abrasive grit passing through weakened or failed tubes. Condenser Sleeving Port Washington Station The Port Washington Station is a 320 MW, coal-fired power plant located in Port Washington, WI, USA. It consists of four (4), 80 MW Units. Unit 1 was placed in service in 1935, Unit 2 in 1940, Unit 3 in 1945 and Unit 4 in 1948. Each unit utilizes a single Allis- Chalmers horizontal, multi-steam pass and single water pass, oval designed condenser. The tubesheet is fabricated from Muntz metal. There are 9,020 Admiralty Brass tubes with a 22mm (7/8 in) O.D. x 18 BWG and 7.9m (26 ft) in length. In 1957, 152 mm (6 in) plastic inserts were installed in the inlet end of each condenser tube which had not been previously plugged. This was done due to the forced outages caused by inlet end erosion. While initially this stopped the outages, leaks began to appear immediately downstream of the plastic inserts due to end step erosion, again forcing units off-line. The inlet end erosion was merely transferred further down the length of tube, to the ends of the plastic inserts. In 1988, Unit 1 was taken off-line and the condenser retubed using 90/10 CuNi and 304 SS (for the upper impingement area). This kept the unit off-line for 4 weeks with a total project cost of US$392,000. Unit 1 has had only a couple of leaks in defective tubes since. With a current plant life design parameter of 2010, the following options were considered to maintain reliability and minimize costs for the remaining three (3) condensers: 1) Retube the condensers at a cost of approximately $475,000 each. 2) Sleeve the inlets of the existing tubes at a cost of approximately $75,000 each. 3) Do nothing and continue plugging tubes as they leak. Because the major failure mechanism was inlet end erosion followed by end step erosion, in order to lower costs while maintaining reliability, tube sleeving was selected as the preferred method for condenser tube life extension. Unit 2 was sleeved in March of 1999 at a cost of $84,959, the higher cost being attributed to a larger quantity of plastic inserts and adhesive which needed removal. Unit 3 was sleeved in December of 1996 at a cost of $73,000. Unit 4 was sleeved in March of 1998 at a cost of $72,600. All sleeves were fabricated from 90/10 CuNi, in 254mm (10 in) lengths and hybrid

Condenser And Heat Exchanger Tube Restoration OMMI (Vol. 1, Issue 2) August 2002 6 expanded into the existing tubes. This resulted in a savings of nearly $1.2 million to the company. In 1992 we were experiencing an average pluggage percentage of approximately 0.5% annually and was sweeping upwards. We are currently averaging 0.1% annually, or, 80% less than before the sleeves were installed. Useful References Bianchi, G., et al., Horse Shoe Corrosion of Copper Alloys in Flowing Sea Water: Mechanism, and Possibility of Cathodic Protection of Condenser Tubes in Power Stations, Corrosion, Vol. 34, No. 11, November 1978. Gasparini, R. et al., Mechanisms of Protective Film Formation on Cu-Alloy Tubes with FeSO4 Treatment, Corrosion Science, Vol. 10, No. 3 (March 1970), pp. 157-163. March, P.A., Velocity Distributions and Turbulence Intensities at Tubesheets in a Two-Pass Condenser Model, ASME Paper 78-JPGC-NE-6 presented at Joint Power Generation Conference, Sept. 10-14, 1978, Dallas, Texas. A Comparison of Liquid Impact Erosion and Cavitation Erosion: Preece, C.M., Bell Laboratories, Murray Hill, NJ 07974, Brunton, J.H., Engineering Department, Cambridge University, Cambridge (Gt. Britain), April 26, 1979. Corrosion-Related Failures in Power Plant Condenser, NP-1468 Technical Planning Study TPS 79-730 Final Report, August 1980. Prepared by: Battelle, Columbus Laboratories, 505 King Ave., Columbus, Ohio, Beavers, J.A., Agrawal, A.K., Berry, W.E. Seminar Proceedings: Prevention of Condenser Failures The State of the Art CS-4329- SR, Proceedings, December 1985, Palo Alto, California, November 13-15, 1984, Edited by B.C. Syrett.