TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

Similar documents
SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

TECHNICAL SPECIFICATION FOR G.I. BARBED WIRE. (SPECIFICATION NO.MM/I/G.I.BARBED WIRE/2006) (Dt )

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

Maharashtra State Electricity Distribution Co. Ltd.

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1

TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS

Specification No. CSC-70/DH/UH/P&D/

TECHNICAL SPECIFICATION FOR CONDUCTORS

Maharashtra State Electricity Distribution Co. Ltd.

TECHNICAL SPECIFICATION OF UNARMOURED FLAT 1100 VOLTS L.T. PVC INSULATED TWIN CORE 4.0mm² CABLE WITH ROUND ALUMINIUM CONDUCTOR BLACK SHEATHED.

MGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I

2. RATED VOLTAGE: The rated voltage of the AB cables shall be 1100 volts

Maharashtra State Electricity Distribution Co. Ltd.

SPECIFICATION FOR FRLS POWER CABLES

SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY)

MATERIAL STANDARD FOR CABLES AND WIRES

5.2 The phase conductors shall be provided with one, two & three ridges for easy identification.

TECHNICAL SPECIFICATION FOR. FOUR CORE AND TWO CORE XLPE CABLES of Various SIZES 16mm 2, 10mm 2 & 6mm 2 INSULATED & XLPE SHEATHED ARMORED LT CABLES

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

11-SDMS-01 REV. 03 ( )

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS

P.V.C. INSULATED UNARMOURED COPPER CABLES

TECHNICAL SPECIFICATION FOR CONDUCTOR HARDWARE FITTING FOR 11/22/33 kv OVERHEAD POWER LINES

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

ANNEXURE - ' D ' TECHNICAL SPECIFICATION FOR INSULATOR PINS ( PINS FOR 11,22 AND 33 kv INSULATORS )

a) Temperature Variation : 5ºC to 55ºC b) Relative humidity : Upto 95% c) Altitude : 0 to 1000 Mtrs. d) No.of tropical monsoon months : 3 (Three)

137-1: 2015 CEB SPECIFICATION. XLPE INSULATED SINGLE CORE UNDERGROUND CABLES OF 11 kv RATED VOLTAGE

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. Ltd. (MUMBAI) SCHEDULE 'A' TECHNICAL SPECIFICATION FOR. 11 kv, 22 kv & 33 kv HORN GAP FUSES FOR

L1-CHE-SPE-171 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE

TECHNICAL SPECIFICATION FOR SUPPLY OF WEDGE CONNECTOR TO BE USED IN POWER DISTRIBUTION SYSTEM

TECHNICAL SPECIFICATION FOR. L.T.XLPE POWER CABLE (armoured) FOR DISTRIBUTION NETWORK

138-1: 2015 CEB SPECIFICATION. AERIAL BUNDLE CONDUCTORS - 33 kv (95mm 2 and 150mm 2 )

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

TECHNICAL SPECIFICATIONS FOR CROSS LINKED POLYETHYLENE INSULATED 3 CORE llkv CABLES

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

TECHNICAL SPECIFICATION FOR RATE CONTRACT OF INSULATING MATS

Four Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Technical Specification for Insulated Low Voltage Single Core Copper Cable

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

Four Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

Single Core, Aluminum Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

NPS/002/023 Technical Specification for 132kV Power Cables.

Technical Specification for PVC Insulated Low Voltage Neutral Screened Copper Cable

Technical Specification for Low Voltage Aerial Bundled HDPE Insulated Cables

Date: TECHNICAL SPECIFICATION FOR (LT,11KV, 33KV) PORCELAIN PIN INSULATORS

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

Single Core, Copper Conductor Extruded Cross - Linked Polyethylene (XLPE) Insulated Power Cable

NPS/002/018 Technical Specification for Pilot, Control and Telephone Cables

ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME. Technical Specification (T.S)

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

PART-II SPECIFICATION OF 22KV PIN INSULATORS. This specification covers 22KV Pin Type Insulators for 22KV H.T. over head power lines.

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

MGVCL/MM/1043/13-14/11 KV Disc Insulators (Porcelain)

4x270 MW TSGENCO BHADRADRI TPS

XLPE CABLE (11KV - Aluminium)

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 22 kv, SINGLE CORE, 95mm 2 COPPER

TECHNICAL SPECIFICATIONS

SEAL & SIGNATURE OF THE TENDERER

TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE

3 120 Sq.mm and Single & Multicore LT PVC/XLPE Cable are hereby revised

CONSULTATIONS TECHNICAL GUIDELINE. HVDC extruded cable

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS:

PUBLIC WORKS DEPARTMENT NOTICE INVINTING QUOTATION

2.2 Copies of any records and other connected papers that may be required by the Bureau shall be made available at any time on request.

SECTION 07. TECHNICAL SPECIFICATIONS OF 11 KV XLPE CU CABLE (1x500 mm 2 )

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDER NO.8/2013 FOR THE SUPPLY OF CONDUCTORS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Technical Specification for Helical Fittings for Overhead Power Lines

Maharashtra State Electricity Distribution Company Limited. SPECIFICATION NO. MMC: MSC-II/Multi Meter box/smc/2018/10 TECHNICAL SPECIFICATION FOR

MANUFACTURER'S QUALITY ASSURANCE PLAN (QAP - Instrumentation cables)

TECHNICAL SPECIFICATIONS OF LAYING OF UNDER GROUND POWER CABLE FOR TRANSMISSION LINE

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION The ELECTRICITY (PEDE) TENDER DOCUMENTS FOR

GEMSCAB INDUSTRIES LIMITED STANDARD PLAN FOR HT XLPE CABLES AS PER IS:7098(PART-II)

U.V resistance UL Sunlight Resistance. Flame retardant IEC

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath

Test Report No.: Page 2 of 35

SPECIFICATION OF HT-LT STAY (GUY) INSULATORS:

EHV XLPE CABLES CDCC LINE

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION

TECHNICAL SPECIFICATION FOR L.T. MOULDED CASE CIRCUIT BREAKER. FOR PROTECTION OF DISTRIBUTION T/Fs UPTO 200 KVA CAPACITY

SPECIFICATION FOR STAY INSULATORS (PORCELAIN)

Technical Specification for Substation 11kV and 22kV Single Core Underground Cable

PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year

TECHNICAL SPECIFICATION FOR OUTDOOR TYPE DISTRIBUTION PLOT & SERVICE JUNCTION BOX

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

SPECIFICATION FOR HT-LT STAY (GUY) INSULATORS:

Underground Electrical Cabling works at Gandhidham-Adipur under NCRMP-II (Project Funded By the World Bank)

26/35kV Copper XLPE Insulation Electric Cable

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

TECHNICAL SPECIFICATION FOR MS BEAMS 116X100 11MTR LONG FOR SUB-STATIONS

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara:

Transcription:

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 14

TECHNICAL SPECIFICATION FOR LT XLPE POWER CABLES (SPECIFICATION NO.MM/I/LTXLPE/2006) 1. SCOPE: The specification covers design, manufacture, shop testing, packing and delivery of 1100 Volts grade, Aluminium conductor, XLPE insulated multi core power cables in the State of Maharashtra.. 2. SERVICE CONDITIONS: Equipment to be supplied against this specification shall be suitable for satisfactory continuous operation under the following tropical conditions. 2.1 Maximum ambient temperature (deg C) 50 2.2 Maximum temperature in shade (deg C) 45 2.3 Minimum temperature in air (deg C) in shade 3.5 2.4 Maximum Relative Humidity (%) 100 2.5 Maximum annual Rainfall (mm) 1450 2.6 Maximum Wind Pressure (kg/mm2) 150 2.7 Maximum altitude above mean sea level (Meters) 1000 2.8 Isoceraunic level (days/year) 50 2.9 Seismic level (Horizontal acceleration) 0.3 g. 2.10 Ground temperature (deg. C ) 30 2.11 Thermal Resistivity of soil ( deg. C cm / watt ) 150 2.12 Depth of laying for 1.1 kv (cm) 75 2.13 Cables installed singly for twin / multi core cables and 3 Nos. of single core cables in Trefoil Touching 2.14 Moderately hot and humid tropical climate, conducive to rust and fungus growth. SEAL & SIGNATURE OF THE TENDERER PAGE 2 OF 14

3. STANDARDS: 3.1 Unless otherwise specified elsewhere in this specification, the rating as well as performance and testing of the LT XLPE power cables shall conform to the latest revisions available at the time of placement of order of all the relevant standards as listed in, but not limited to Annexure-I. 4. GENERAL TECHNICAL REQUIREMENTS: 4.1 ARMOURED CABLES 1100 Volts Grade L.T. cable with stranded H2/H4 grade aluminium conductor, XLPE insulated, colour coded, laid up, with fillers and/or binder tape where necessary provided with extruded PVC inner sheath, single galvanized round steel wire / strip armoured and provided with PVC outer sheath. Both inner and outer sheath shall be of Type ST-2 as per IS: 5831-1984 and cable shall be conforming to IS: 7098 ( Part 1 ) - 1988 ( amended upto date ) and bearing ISI mark. In case of single core cable armouring shall be of aluminum. 4.2 INSULATION, INNER SHEATH AND OUTER SHEATH : Insulation, inner sheath and outer sheath shall be applied by separate extrusion. Inner sheath shall be applied by extrusion only. Bedding of PVC tape for inner sheath is not acceptable. Colour of outer sheath shall be black. The quality of insulation should be good and insulation should not be deteriorated when exposed to the climatic conditions. 4.3 SEQUENTIAL MARKING OF LENGTH ON CABLE Non erasable Sequential Marking of length shall be provided by embossing on outer sheath of the cable for each meter length. 4.4 CONTINUOUS A.C. CURRENT CAPACITY: Continuous a.c. current capacity shall be as per Table given below. Conductor sizes in sq.mm. Continuous A.C. current capacity in Amps. When laid direct in the ground 30 deg.c. 70 sq.mm 165 175 95 sq mm 200 224 When laid in air40 deg.c. SEAL & SIGNATURE OF THE TENDERER PAGE 3 OF 14

120 sq mm 225 240 150 sq mm 255 305 185 sq mm 285 315 240 sq mm 325 385 300 sq mm 370 410 400 sq mm 425 470 4.5 SHORT CIRCUIT CURRENT Short circuit current of LT XLPE cable shall be as per Table given below. 5. TESTS : Duration of Short Circuit in sec Area of Al. conductor Short circuit current in ka T A I=0.094 x A/sq.rt (t) 1 70 sq.mm 6.58 1 95 sq.mm 8.93 1 120 sq.mm 11.28 1 150 sq.mm 14.10 1 185 sq.mm. 17.39 1 240 sq.mm. 22.56 1 300 sq.mm. 28.20 1 400 sq.mm. 37.60 5.1 TYPE TESTS: All the type tests in accordance with IS: 7098 (Part 1) - 1988 (amended upto date) shall be performed on cable samples drawn by Employer s representative. Type tests are required to be carried out from the first lot of supply on a sample of any one size of cable ordered. In case facilities of any of the type tests are not available at the works of the supplier, then such type test shall be carried out by the supplier at the independent recognized laboratory at the cost of supplier. Sample for the type test will be drawn by the Employer's representative and the type test will be witnessed by him. Supplier, however, can claim exemption from carrying out type test as above, provided such type test were already conducted for M.S.E.D.C.L. ( previous M.S.E.B.) in the past within five years and the test certificates thereof submitted to our C.E.(Dist) / CE (Infra Plan). Chief Engineer (Dist) / CE (Infra Plan) may at his option grant waival SEAL & SIGNATURE OF THE TENDERER PAGE 4 OF 14

from carrying out type tests if the test certificates are acceptable.in case of other Government recognized laboratories / Test House valid approved Government certificate shall be enclosed alongwith test. 5.2 ROUTINE TESTS: All the Routine tests as per IS: 7098 (Part 1) - 1988 amended upto date shall be carried out on each and every delivery length of cable. The result should be given in test report. The details of facility available in the manufacturer's works in this connection should be given in the bid. 5.3 ACCEPTANCE TESTS: All Acceptance tests as per IS-7098 (Part-I) 1988 as amended upto date including the optional test and Flammability Test shall be carried out on sample taken from the delivery lot. 5.4 The following additional acceptance test should be carried out on PVC compounds used for outer sheath, as per IS: 5831-1984 ( amended upto date ) 1.Hot Deformation Test. 5.4.1 TESTING FACILITIES AND DETAILS OF EQUIPMENTS : The supplier / tenderer shall clearly state as to what testing facilities are available in the works of manufacturer and whether the facilities are adequate to carry out type, routine and acceptance tests mentioned in IS: 7098 ( Part 1 ) - 1988 (amended upto date ) on the cable including test as per specification. The facilities shall be provided by the bidder to Employer s representative for witnessing the tests in the manufacturer s works. If any test cannot be carried out at manufacturer s works reason should be clearly stated in the tender. 6 PACKING AND MARKING : 6.1 a) Upto 120 sq. mm. Size : Cables shall be supplied in continuous standard length of 500 meters with plus minus 5% ( five percent ) tolerance wound on non returnable wooden drums of good quality or on non-returnable steel drums without any extra cost to the Employer. b) Above 120 sq.mm. size : Cables shall be supplied in continuous standard length of 250 meters with plus minus 5% ( five percent ) tolerance wound on non returnable wooden drums of good quality or on non-returnable steel drums without any extra cost to the Employer. SEAL & SIGNATURE OF THE TENDERER PAGE 5 OF 14

6.2 Non standard length : 5% ( five percent ) of the ordered quantity of respective size shall be acceptable in non-standard length which shall not be less than 100 meters in length. 6.3 The following particulars shall be properly legible embossed on the cable sheath at the intervals of not exceeding one meter through out the length of the cable. The cables with poor and illegible embossing shall be liable for rejection. a) Manufactures name. b) Voltage grade. c) Year of manufacture. d) M.S.E.D.C.L. e) Successive Length. f) Size of cable g) ISI mark 6.4 Packing and marking shall be as per clause No. 18 of IS 7098 ( part I)/1988 amended up to date. 6.5 Supplier should provide statistical data regarding cables of all sizes viz.- 1) Weight of one meter of finished product of cable of various sizes and ratings. 2) Weight of one meter of bare conductor used for cables of various sizes and ratings. 7. QUALITY ASSURANCE PLAN: A detailed list of bought out items which got into the manufacture of cables should be furnished indicating the name of the firms from whom these items are procured.. The bidder shall submit the quality assurance plan followed by him/manufacturer in respect of the bought out items, items manufactured by him & raw materials in process as well as final inspection, packing & marking. The Company may at its option order the verification of these plans at manufacturer's works.. 5. SCHEDULE The tenderer shall fill in the following schedules which are part and parcel of the tender specifications and offer. If the schedules are not submitted duly filled in with the offer, the offer shall be liable for rejection. Schedule A - Guaranteed Technical Particulars SEAL & SIGNATURE OF THE TENDERER PAGE 6 OF 14

Schedule B Schedule C Schedule D Schedule E requirements - Schedule of Deviations - Tenderer s Experience - Schedule of Deviations from specified standards - Deviation from specified test The deviations from the specifications shall be brought out in the schedules of deviations ( schedules B, D and E ). Unless otherwise brought out specifically by the tenderer in the schedules of deviations( schedules B, D and E ), the items offered shall be deemed to confirm to all clauses of the specification. The discrepancies if any between the specifications & the catalogue or literatures submitted as part of the offer by the bidder shall not be considered as valid deviations and no representations in this regard will be entertained unless these are specifically brought out in the schedules of deviations as stated above. SEAL & SIGNATURE OF THE TENDERER PAGE 7 OF 14

SCHEDULE A GURANTEED TECHNICAL PARTICULARS OF L.T.XLPE 1. Manufacturer s name 2. ISI. Registration No. and validity date. 3. Voltage Grade 4. Conductors: a) Material and Grade b) Size of conductor (sq. mm.) i) Main core ii) Neutral core NO.OF CORES X SIZE IN sq.mm c) Max D.C. resistance of conductor at 20 deg.c(ohm/km) i) Main core ii) Neutral core d) No. of strands/core. i) Main core ii) Neutral core e) Form of conductor. 5. Insulation:- a) Material and Grade b) Nominal thickness (mm) i) Main core ii) Neutral core 6. Inner Sheath: a) Material & Type SEAL & SIGNATURE OF THE TENDERER PAGE 8 OF 14

b) Calculated diameter over laid up cores. c) Minimum thickness (mm) 7. Armouring: a) Material & Type b) Calculated diameter under armour c) Nominal diameter/thickness of armouring wire/strip 8. Outer Sheath: a) Material & Type b) Calculated diameter under the outersheath c) Minimum thickness (mm) d) Shall the sequential numbers be provided e) Colour of outer sheath 2.1.1 Approximate Overall diameter of cable (mm) 2.2.2 Approximate net weight of cable (kg/km) 2.2.3 Standard Drum length (Metre) 2.2.4 Drum a) Type b) I.S. Reference c) Gross weight. 2.1.5 Continuous A.C. current capacity (Amps) a) When laid in the ground.(30 deg.c) b) When laid air (40 deg. C.) 14. Short Circuit rating of conductor for duration of one second in KA. SEAL & SIGNATURE OF THE TENDERER PAGE 9 OF 14

SCHEDULE B DEVIATION FROM SPECIFICATION SR.NO. CLAUSE NO DETAILS OF DEVIATION NAME OF FIRM-------------------------------------------------------------------------- NAME & SIGNATURE OF TENDERER-------------------------------------------- DESIGNATION--------------------------------------------------------------------------- DATE---------------------------------------------------------------------------------------- SEAL & SIGNATURE OF THE TENDERER PAGE 10 OF 14

SCHEDULE C SCHEDULE OF TENDERER S EXPERIENCE Tenderer shall furnish here a list of similar orders executed/under execution by him whom a reference may be made by Purchaser in case he considers such & reference necessary. Sr.No. Name of Client & Description of order Value Order of Period of supply & commissioning 1 2 3 4 5 Name & address to whom reference may be made NAME OF FIRM------------------------------------------------------------------------------------ NAME & SIGNATURE OF TENDERER------------------------------------------------------ - DESIGNATION------------------------------------------------------------------------------------- DATE------------------------------------------------------------------------------------------------- SEAL & SIGNATURE OF THE TENDERER PAGE 11 OF 14

SCHEDULE D SCHEDULE OF DEVIATIONS FROM SPECIFIED STANDARDS Sr.No Particulars Stipulation of specified standards Standard Ref. Stipulations Standard Ref. Stipulation of standard adopted by tenderers Stipulations Remarks NAME OF FIRM------------------------------------------------------------------------------------ NAME & SIGNATURE OF TENDERER------------------------------------------------------ DESIGNATION ------------------------------------------------------------------------------------ DATE-------------------------------------------------------------------------------------------------- SEAL & SIGNATURE OF THE TENDERER PAGE 12 OF 14

SCHEDULE E DEVIATION FROM SPECIFIED TEST REQUIREMENTS SPECIFIED IN RELEVANT AND PRESENT SPECIFICATIONS Sr.No. Name of Test Standard No. & Clause No. Requirement of Standards Proposed deviation Reasons for deviation 1. Type Test 2. Additional Test 3. Acceptance Test 4. Routine Test NAME OF FIRM----------------------------------------------------------------------------- NAME & SIGNATURE OF TENDERER---------------------------------------------- DESIGNATION------------------------------------------------------------------------------ DATE ------------------------------------------------------------------------------------------ SEAL & SIGNATURE OF THE TENDERER PAGE 13 OF 14

ANNEXURE-I LIST OF STANDARDS (All amended up-to-date) SR. STANDARD NO. TITLE NO. 1. IS: 7098( Part 1 )-1988 Specification for XLPE insulated, PVC sheathed cables for working voltages upto and including 1100 Volts. 2. IS : 5831-1984 Specification for PVC insulation and sheath of electric cables. 3. IS: 8130-1984 Specification for conductors for insulated electric cables and flexible cords. 4. IS: 3975-1988 Specification for Mild Steel wires, formed wires and tapes for armouring of cables. 5. IS: 10462 ( Part I ) 1983 Fictitious calculation method for determination of dimensions of protective covering of cables. SEAL & SIGNATURE OF THE TENDERER PAGE 14 OF 14