TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS

Similar documents
TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

ANNEXURE - ' D ' TECHNICAL SPECIFICATION FOR INSULATOR PINS ( PINS FOR 11,22 AND 33 kv INSULATORS )

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

TECHNICAL SPECIFICATION FOR CONDUCTORS

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS Insulators & Lightening Arrestor GROUP K & L

TECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS.

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

SEAL & SIGNATURE OF THE TENDERER

SECTION 07 TECHNICAL SPECIFICATIONS 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER (LA)

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION

P.V.C. INSULATED UNARMOURED COPPER CABLES

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

General Requirements. Technical Specifications for Insulators of Transmission Lines

TECHNICAL SPECIFICATION

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

Technical Specifications 25 KVA/40 KVA L.T. DISTRIBUTION BOX WITH KITKATs (for Rural Area) NO. DIST/DB/ 03/2006 INDEX

Technical Specification for Live Line Tap Connectors

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME. Technical Specification (T.S)

Technical Specification for LV ABC Fuse Switch Disconnectors

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS

TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED)

Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg.

TECHNICAL SPECIFICATION A.B. CABLE

NPS/002/001 Technical Specification for Earthing Materials

TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE

2. Test Records - All records of analysis and tests shall be kept in suitable forms approved by the Bureau of Indian Standards.

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

Date: TECHNICAL SPECIFICATION FOR ACSR Panther Conductor

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

Pins Insulator. Composite/Polymers Insulators

Product Specification JUL 14 Rev. A1

NPS/002/023 Technical Specification for 132kV Power Cables.

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS

2. TEST RECORDS: All records of tests and analysis shall be kept in suitable forms approved by the Bureau.

Mar11 Rev B

3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series

TECHNICAL SPECIFICATION OF TOWER MATERIAL FOR132KV-PANTHER TRANSMISSION LINE

NPS/003/033 Technical Specification for Substation Support Structures

VERSAFIT V2 AND V4 TUBING Polyolefin, Flexible, Heat-Shrinkable, Flame-Retardant

SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF ALLUMINIUM ALLOY TUBES FOR IRRIGATION PURPOSES; WELDED TUBES ACCORDING TO IS: 7092 (PART I)-1992

SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134

INDIAN REGISTER OF SHIPPING CLASSIFICATION NOTES. Type Approval of Mechanical Joints used in Piping

Specification Technical Requirements for Revenue Electricity Meters

PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

THE KENYA POWER AND LIGHTING CO. LTD

Mar11 Rev D

SPECIFICATION SHEET JUNCTION BOXES

SUPPLY AND DELIVERY OF 200KVA EARTHING TRANSFORMER TENDER DOCUMENTS: SARAWAK ENERGY REF. NO. PLS PART I TENDER PROCEDURES

ELECTRICAL INSPECTION BULLETIN (Effective )

DATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0

765kV/400kV S/S Powergrid Raichur Rev. 00 Technical Specification for Disc Insulators & String Hardware SECTION 1

QUALITY DEPT request to have FORM 1135 for REVIEW/APPROVAL Cycle everytime form will be updated/revised.

TECHNICAL SPECIFICATION FOR 22 kv, 1.2/2.4/3.0 MVAR CAPACITOR BANK WITH DOUBLE STAR ARRANGEMENT & ASSOCIATED EQUIPMENTS

SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF TITANIUM DIOXIDE, ANATASE, FOR PAINTS ACCORDING TO IS :

TECHNICAL SPECIFICATIONS FOR CROSS LINKED POLYETHYLENE INSULATED 3 CORE llkv CABLES

MIL-L-26764B 4 March 1970 SUPERSEDING MIL-L-26764(ASG) 12 December 1963 MILITARY SPECIFICATION

CONTENTS. IEC Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60

4. GENERAL REQUIREMENTS

Version: 1.1 Date of Issue: March 2017 Page: 1 of 23

Feb12 Rev D

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

DETAIL SPECIFICATION. MICROPHONE, CARBON (MICROPHONE M-29( )/U and M-52( )/U) INACTIVE FOR NEW DESIGN AS OF 30 MARCH 1999

Supplier Quality Requirements Q Clauses

PART MATERIAL REMARK Metal Case with Pig-tail. Brass (Metal Case) Copper (Pig-tail) Star Contact Copper Silver Plated

TENDER FOR APPOINTMENT OF COURIER AGENCY AS OFFICIAL COURIER SERVICE AGENCY FOR

Quality Management System

Section - III Evaluation and Qualification Criteria

Procurement Quality Assurance Requirements

SMPM Female Cabled Connectors

Doc: STI/1166/6 July 2008

KENYA STANDARD KS 574:2017. Steel fabric for reinforcement of concrete Specification

Addendum No.1 (SUMMARY SHEET) Modifications to Tender Documents S.No. Document In Place of Please read as Remarks

: 400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu SECTION - 1

1.1 All testing apparatus shall be periodically checked and calibrated. Records of such checks/calibration shall be maintained.

IECEE OPERATIONAL DOCUMENT

Conduits. Technical Specification for Conduits and Associated Materials. JTS Version 1

TECHNICAL SPECIFICATIONS FOR AERIAL BUNCHED CABLES FOR OVERHEAD DISTRIBUTION

SECTION INSTALLATION AND/OR REPLACEMENT OF MASONRY UNITS AND REPOINTING

Mar11 Rev C

BANK REFERENCE LETTER/SOLVENCY CERTIFICATE (On Bank s Letter Head) Certified that M/s at (address) is having an account in our bank

QUALIFICATION TESTING OF FIELD WELDERS

BUREAU OF INDIAN STANDARDS CENTRAL MARKS DEPARTMENT-III

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

Transcription:

TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 11

TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS 1.0 Scope : The specification covers the manufacture, testing at works supply and delivery of procelain Insulators for overhead power lines with a nominal voltage below 1000 volts. Nothe pin and shackles type insulators are covered. 2.0 Climatic conditions : The insulators specified herein shall be suitable for outdoor use under the following climate conditions. 2.1 Maximum ambient temperature (Degree C) -- 50 2.2 Maximum temperature in shade (Degree C) -- 45 2.3 Minimum temperature of Air in shade (Degree C) -- 3.5 2.4 Relative Humidity (Percent) -- 10 to 100 2.5 Maximum annual rain fall (mm) -- 1450 2.6 Maximum wind pressure (kg/sq.m) -- 150 2.7 Maximum altitude above mean seal level (meter) -- 1000 2.8 Isoceranic level (days per year) -- 50 2.9 Seismic level (Horizontal Acceleration) -- 4.3 g 1.10 Moderately hot and humid tropical climate Conductive to trust and fungus growth 3.0 System : 3.1 The insulators will be installed be installed on three phase 433 volts. AC & 50 HZ system in which the neutral is effectively grounded. The insulators shall be designed to work continuously at a voltage. 10% in excess of the normal rated voltage. 4.0 Design Specification : 4.1 The insulators shall confirm to provisions under IS : 1445 1977 or its latest version in all respects. The dimensions of the insulators are as per Drawing No. 62.57. The Pin insulators shall be threaded to take mild steel pin of dimensions given below : SEAL & SIGNATURE OF THE TENDERER PAGE 2 OF 11

Pin Insulator Type - 1 Suitable for Head Shank Steel Threads as per profile of threads as insulators as given in Fig.5 of IS : 1445/1977 Dia. 16 mm Remarks Pin Insulators threads as per profile given in Fig.5/1445/1977 4.2 The design of the insulators shall be such that stress due to expansion and contraction in any Part of the insulators shall not lead to its deterioration. 4.3 The insulators shall be suitable for use with all Aluminium Conductor or copper conductor or ACSR up to 100 mm sq. The insulators should withstand the conductor tension the reversible wind lead as well as the high frequency vibrations set due to wind. 5.0 Insulation Characteristics : 5.1 The insulators shall have the electrical and mechanical characteristic given in the table below : Type of Insulators Power frequency flashover Voltage in KV (RMS One minute power frequency with stand voltage in KV (RMS) Power frequency puncture withstand voltage KV (RMS Dry Wet Dry Wet Pin 25 10 23 10 1.3 x the actual flashover voltage Minimum failing load kg Shackle 25 10 23 10 1150 (Type 1 1600 Type - 2) 6.0 General Requirements : 6.1 The porcelain used in the manufacture shall be sound free from defects, thoroughly vitrified and smoothly glazed. 6.2 The glaze on the insulators shall generally to White/Cream Brown except for the screw threads and the parts on which the porcelain is supported during fittings, which may be left unglazed, all other surfaces of the insulators shall be efficiently glazed. 6.3 The insulators shall be in one piece. The pin type shall a top groove and shall have dimensions as shown in the drawing. 6.4 The insulators shall be marked properly in accordance with clause 6 of ISS : 1445. 860 SEAL & SIGNATURE OF THE TENDERER PAGE 3 OF 11

7.0 Testing facilities : The tenderer must clearly indicate what testing facilities are available in the works of the manufacturer and whether the facilities are adequate to carry out all the routine as well as type tests. These facilities should be made available to Board s Engineers if deputed to carry out or witness should be made any tests cannot be carried out at the manufacturers works, the reasons should be clearly stated in the tender. 8.0 Tests : The insulators shall be tested in accordance with the procedures detailed in IS : 1445/1977 which are reproduced below : 8.1 Routine Tests : 8.2 Type Tests : Type tests shall be made on the insulators that has passed the routine tests. For requirements of insulators up to 2000 no. One insulators shall be selected for the type test mentioned below. However, maximum no. of insulators to be tested in the lot shall be limited to twenty to twenty numbers only. a) Dry one minute power frequency À Withstand test & dry flash over test À As per IS: 1445/1977 b) Wet one minute power frequency À withstand and wet flash over test À As per IS : 1445/1977 8.3 Acceptance tests : The number of insulators for the acceptance tests mentioned below shall be selected at random from the lot in accordance with the table below : Lot size Sample size of Insulators Up to 500 3 501 to 800 12 801 to 3200 16 3201 to 8000 18 8001 to above 20 8.3.1 The insulators, after having withstand the routine test shall be subjected to the following tests in the order given below : SEAL & SIGNATURE OF THE TENDERER PAGE 4 OF 11

a) Verification of dimensions À b) Temperature cycle test À As per IS : 1445 c) Mechanical failing load test À d) Power frequency puncture withstand test À e) Porosity test À The insulators selected in accordance with 8.3 shall be up to two equal parts and subjected to the tests indicated. Tests Part of sample a) & b) Both Parts c) & e) First Part d) Second Part 9.0 Rejection : 9.1 Criteria of conforming and Rejection : 9.1.1 If only one insulators fails to comply with any one of the tests given in 8.3.1 (a) to (b) a fresh quantity equal to twice the first quantity shall be subjected to retesting. The retesting shall comprise the test in which the failure occurred preceded by house, test which may be considered to have influenced the results of the original tests if no failure occurs, the lot shall be accepted. 9.2 It two or more insulators fail to comply with any sample tests given in 8.3.1 (a) to (d) or if any failure occurs on insulators subjected to retesting described in 8.2, the complete lot shall be withdrawn for further examination by the manufacturer after which the lot of any part thereof may be resubmitted for tests. 9.3 The number then selected shall be three times the first quantity chosen for tests. This testing shall comprise the test in which the failure occurred proceeded by those test which may be considered to have influenced the results of the original test. If failure occurs the last lot shall be rejected. Insulators which do not conform to the requirements of 8.1 and 8.2 shall be rejected. 10.0 Test Certificates : 10.1 Along with the tender, the tenderer shall submit the test certificate for all routine, type and sample tests specified above. 10.2 If required, the board shall subject the consignment of insulators supplied to the aforementioned test. The testing under this clause will be carried out in any laboratory including boards own laboratory. Notice of such tests will be given by the Board to the supplier by ordinary post. However, the date of testing will not be postponed or altered at the request of the supplier. The supplier is at liberty to be present during this test. SEAL & SIGNATURE OF THE TENDERER PAGE 5 OF 11

11. Marking : As per IS : 1445/1977 12. Packing: All insulators shall be packed in suitable double gunny bags and shall be transported by road. 13. Inspection : The Board may be depute an Engineer to witness the routine and sample tests at their manufacturers works for which advance intimation shall be given the manufacturers whenever a lot is ready for dispatch. 14. Schedule : The tenderer shall fill in the following schedule which is part and parcel of the tender specification and offer. If the schedules are not submitted duly filled in with the offer, the offer shall be liable for rejection. Schedule A - Guaranteed technical particulars Schedule B - Schedule of deviation Schedule C - Tenderer s experience Schedule D - Schedule of deviation form Specification standards Schedule E - Deviation from specified test Requirements. Unless otherwise brought out separately by the tenderer in the schedule of deviations (Schedule B, D & E ) for this item offered shall be deemed to confirm to the specification scrupulously. All deviations from the specification shall be brought out in the Schedules of deviation (Schedule B, D & E ). The discrepancies between the specification and the catalog or literature submitted as part of the offer shall not be considered as valid deviation unless specifically brought out in the schedule of deviation as stated above. SEAL & SIGNATURE OF THE TENDERER PAGE 6 OF 11

SCHEDULE A GURANTEED TECHNICAL PARTICULARS The guaranteed technical particulars as given below shall be furnished. 1. TYPE OF INSULATORS: 2. APPLICABLE IS ; 3. SYSTEM VOLTAGE AND FREQUENCY 4. CONFIRMATION TO DRAWING NO: 62.57 5. POWER FREQUENCY FLASHOVER VOLTAGE (DRY) 6. POWER FREQUNCY FLASHOVER VOLTAGE (WET) 7. ONE MINUTE POWER FREQUENCY WITHSTAND VOLTAGE (RMS (DRY) 8. POWER FREQUENCY WITHSTAND VOLTAGE (RMS) (WET) 9. POWER FREQUENCY PUNCTURE WITHSTAND AND VOLTAGE 10. MINIMUM FAILING LOAD 11. TYPE TEST REPORTS ENCLOSED : YES OR NOT. 12. PACKING 13. NET WEIGHT OF ONE INSULATORS SEAL & SIGNATURE OF THE TENDERER PAGE 7 OF 11

SCHEDULE - B SCHEDULE OF DEVIATIONS FROM SPECIFICATION SR.NO. CLAUSE NO. DETAILS OF DEVIATION NAME OF FIRM NAME & SIGNATURE OF THE TENDERER DESIGNATION DATE SEAL & SIGNATURE OF THE TENDERER PAGE 8 OF 11

SCHEDULE C SCHEDULE OF TENDERER S EXPERIENCE Tenderer shall furnish here a list of similar orders executed/under execution by him to whom a reference may be made by Purchaser in case in considers such & reference necessary. Sr.No Name of Client & Description order Value of Order Period of supply & commissioning Name & address to whom reference may be made 1 2 3 4 5 NAME OF FIRM--------------------------------------------------------------- NAME & SIGNATURE OF TENDERER---------------------------------- DESIGNATION----------------------------------------------------------------- DATE----------------------------------------------------------------------------- SEAL & SIGNATURE OF THE TENDERER PAGE 9 OF 11

SCHEDULE D SCHEDULE OF DEVIATIONS FROM SPECIFIED STANDARDS SR. Particulars Stipulation of Specified Standards Standard Ref. Stipulation Stipulation of standard adopted by terderers Standard Stipulation Ref. Remarks NAME OF FIRM--------------------------------------------------------------- NAME & SIGNATURE OF TENDERER---------------------------------- DESIGNATION----------------------------------------------------------------- DATE----------------------------------------------------------------------------- SEAL & SIGNATURE OF THE TENDERER PAGE 10 OF 11

SCHEDULE E DEVIATION FROM SPECIFIED TEST REQUIREMENTS SPECIFIED IN RELEVANT AND PRESENT SPECIFICATIONS Sr. No. Name of Test Standard No. & Clause No. Requirement of Standard Proposed deviation Reasons for deviation NAME OF FIRM--------------------------------------------------------------- NAME & SIGNATURE OF TENDERER---------------------------------- DESIGNATION----------------------------------------------------------------- DATE----------------------------------------------------------------------------- SEAL & SIGNATURE OF THE TENDERER PAGE 11 OF 11