Download "TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS Insulators & Lightening Arrestor GROUP K & L"

Transcription

1 TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS Insulators & Lightening Arrestor GROUP K & L

2 GROUP C Insulator Sl. No. Item Description Unit Qty KV Pin Insulator No KV Disc Insulator 45KN (T&C type ) 3 11 KV Disc Insulator 45KN (B&S type ) 4 11 KV Disc Insulator 70KN (B&S type ) No No No KV Post Insulator No KV Lightning Arrestor No KV Stay Insulator No LT Stay insulator No LT Pin Insulator(105x80)mm No LT Pin Insulator(100x75)mm No KV Post Insulator No KV Pin Insulator No KV Disc Insulator(B&S) No KV Disc Insulator(T&C) No KV Lightening Arrestor(10KA) No KV Stay Insulator No 625 NB: 1. Bidders should put their authorized signature with office seal on each page of the documents. 2. Bidders should put their offer in the Guaranteed particulars column furnished in the tender documents.

3 3. Purchaser may ask to the bidder who will qualify in Techno- Commercial evaluation of the tenders for submission of Samples for verification, if required. 4. Purchaser reserves the right to increase or decrease the above quantities during placement of purchase order or may cancel any item/items without assigning any reason thereof. Dy. General Manager (C&P) NESCO, Balasore, Odisha

4 TECHNICAL SPECIFICATION 11 KV PIN INSULATOR 1.SCOPE : The specification cover the manufacture, testing at works supply and delivery of Porcelain insulators for overhead power lines with a nominal voltage below 12KV. Both Pin and Shackle type insulators are covered. 2. APPLICABLE STANDARDS: Except when they conflict with the specific requirements of this specification, the insulators shall comply with IS : IS:731 & IS: 3188 or the latest version thereof. 3. GENERAL REQUIREMENTS: The porcelain shall be sound, free from defects, thoroughly vitrified and smoothly glazed. The design of the insulators shall be such that the stresses due to expansion and contraction in any part of the insulator shall not lead to its deterioration. The glaze shall be brown in color for insulators. The glaze shall cover the entire porcelain surface parts except those areas that serve as supports during firing. The insulators shall be suitable for use with all Aluminum Conductor or Copper conductor or ACSR upto 100 sq.mm. The insulators should withstand the conductor tension the reversible wind load as well as the high frequency vibrations set due to wind. 4. SYSTEM CONDITIONS: Frequency : 50 Hz Nominal System Voltage : 11KV Maximum System Voltage LT System : 12 KV Minimum LT Voltage : 11KV Power frequency one minute withstand Voltage(wet): 35KV 5. TYPE OF INSULATORS: The standard Pin insulators shall be of designation Type B of IS : 731 or its latest revision. 6. TESTS: a. Type tests: a) Visual examination b) Verification of dimensions

5 c) Temperature cycle test d) Dry one minute power frequency withstand test e) Wet one minute power frequency withstand test f) Mechanical strength test g) Porosity test 6.2 Acceptance test: The insulators, after having withstood the routine test shall be subjected to the following acceptance tests in the order given below: a) Verification of Dimensions. b) Temperature cycle test c) Mechanical strength test d) Porosity test 6.3 Routine tests: ii) Visual examination 7.TESTING FACILITIES: a. The Bidder must clearly indicate what testing facilities are available in the works of the manufacturer and whether the facilities, are adequate to carry out all the routine as well as type tests. These facilities should be made available to Purchaser s Engineers if deputed to carry out or witness the tests. If any tests cannot be carried out at the manufacturer s works, the reasons should be clearly stated in the tender. b. The Bidder shall furnish detailed type test reports of the offered 11KV Pine insulator as per clause 6.1 of this specification. All the above Type Tests shall be carried out at laboratories, which are accredited, by the National Accreditation Board of Testing and Calibration Laboratories (NABL) of Government of India to prove that the insulators offered meet the requirements of the specification. These Type Tests should have been carried out within five years prior to the date of opening of this tender. c. There offered L.T. shackle Insulators & pin insulators are already fully Type Tested at Laboratories accredited by the National Accreditation Board of Testing and Calibration Laboratories (NABL) within five years prior to the date of opening of the tender. There is no change in the design of Type tested L.T. shackle Insulators and those offers against this tender.

6 8. Drawings : The tender shall be accompanied with the detailed drawings showing the dimensions of the individual insulator, giving all the design dimensions of various component parts. Generally it shall be as per IS. 9. MARKING: a. Each insulator shall be legibly and indelibly marked to show the following: i) Name of Purchaser- NESCO ii)name or trade mark of the manufacturer iii) Year of manufacturer iv) ISI certificate, mark, if any. b. Marking on porcelain shall be applied before firing. 10. Packing : All insulators shall be packed in crates or boxes suitable for rough handling. Packing shall be marked with the strength and voltage rating.

7 GUARANTEED TECHNICAL PARTICULARS 11 KV PIN INSULATOR Sl. Description Specific Requirement Bidders offer No. Name of Manufacturer. & Address To be specified by the bidder Location of type testing To be specified by the bidder 1 Applicable standard Normal working voltage IS: 731,IS 3188 or the latest version 11 thereof Kv (rms) 2 High system voltage. 12 Kv (rms) 3 Visible Discharge voltage dry PF. 9 Kv (rms) 4 1 Minute withstand voltage wet PF. 65 Kv (rms) 5 1 Minute withstand voltage Kv (rms) 6 PF puncture withstand voltage. 110 Kv (rms) 7 Impulse withstand voltage : 8 Impulse flashover voltage : (+ ve) 80 Kv peak (- ve) 80 Kv peak (+ ve) 90 Kv peak (- ve) 120 Kv peak 9 Minimum failing load. 5 KN. 10 Minimum creepage distance. 240 mm. 11 Colour of glaze. Brown. 12 Weight per unit. 1.4 Kg. (Apprx.) 13 Size of insulator. (Height) 125 mm. (Diameter 125 mm. 14 Material of thimble. ) Lead. 15 Steel head. Small head. 16 Standard. IS : 731/ Tolerance. Tolerance will be allowed as per IS : 731/1971 or latest amendments if any. 18 Drawing To be submitted 19 Conforming standard As per IS NB- Every insulator should bear the marking of manufacturer s name & Purchaser s name and ISI mark. Name & Signature of Bidder with seal

8 TECHNICAL SPECIFICATIONS OF 33 KV PIN INSULATOR 1.0 Scope of Work: This Specification covers design, engineering, manufacture, assembly, stage testing, inspection & testing before supply and delivery at site of the 33KV Pin Insulator. 2.0 APPLICABLE STANDARDS Unless otherwise stipulated in this specification, the insulators shall comply with the Indian standard specification IS: and the insulator fittings with IS:2486(Pt. I )-1971 and IS:2486(Pt. II)-1974 or the latest version thereof. 3.0 INSULATORS 3.1 General Requirements The Porcelain shall be sound, free from defects, thoroughly vitrified and smoothly glazed Unless otherwise specified, the glaze shall be brown in colour. The glaze shall cover all the porcelain parts of the insulator except those areas which serve as supports during firing or are left unglazed for the purpose of assembly The design of the insulator shall be such that stresses due to expansion and contraction in any part of the insulator shall not lead to deterioration. The porcelain shall not engage directly with hard metal Cement used in the construction of the insulator shall not cause fracture by expansion or loosening by contraction and proper care shall be taken to locate the individual parts correctly during cementing. The cement shall not give rise to chemical reaction with metal fittings, and its thickness shall be as uniform as possible. 3.2 Creepage Distance The minimum creepage distance shall be as under: Highest System Voltage Normal and Moderately Polluted Atmospheres(total) Heavily polluted Atmospheres(Total) (1) (2) (3) 36 KV 580 mm 840 mm Note: For insulator used in an approximately vertical position the values given in col.(2) or (3) shall apply. For insulators used in an approximately horizontal position, the value given in col. (2) shall apply but the value in Col.(3) may be reduced by as much as 20%. 3.3 Tests: The insulators shall comply with the following tests as per IS:

9 3.3.1 Type tests a) Visual examination b) Verification of dimensions c) Visible discharge test d) Impulse voltage withstand test. e) Wet power-frequency voltage withstand test. f) Temperature cycle test. g) Electro-mechanical failing load test. h) Mechanical failing load test (for those of type B strin insulator units to which electro mechanical failing load test (g) is not applicable. i) Twenty four hours mechanical strength test (for string insulators only when specified by the purchaser). j) Puncture test k) Porosity test and l) Galvanising test Acceptance Tests The test samples after having withstood the routine tests shall be subjected to the following acceptance test in the rder indicated below: a) Verification of dimensions. b) Temperature cycle test. c) Twenty four hours mechanical strength test(for string insulator units only when specified by the purchaser) d) Electro-Mechanical failing load test. e) Puncture test f)porosity test and g) Galvanising test Routine Test a)visual examination. b) Mechanical routine test (for string insulator units only) and c) Electrical routine test (for string insulator units only) 3.4 Marking Each Insulator shall be legibly and indelibly marked to show the following. a) Name and trade mark of the manufacturer. b) Month and year of manufacture c) Minimum failing load in Newtons d) Country of the manufacturer and e) ISI Certification mark,if any. f) Specific Parameters & Layout Conditions Marking on porcelain shall be printed and shall be applied before firing.

10 3.5 Packing All insulators (without fittings) shall be packed in wooden crates suitable for easy but rough handling and acceptable for rail transport. Where more than one insulator are packed in a crate, wooden separators shall be fixed between the insulators to keep individual insulators in position without movement within the crate. GURANTEED TECHNICAL PARTICULARS OF 33KV PIN INSULATOR Sl.No. Description Specified Bidder's offer 1 Manufacture Name 2 Address of Manufacture 3 Normal working voltage 33KV(rms) 4 5 High system voltage Visible Discharge Voltage dry PF 36KV(rms) 27KV(rms) 6 Dry Power frequency 1 Minute withstand voltage 95KV(rms) 7 Wet Power frequency 1 Minute withstand voltage 75KV(rms) 8 PF puncture withstand voltage 180KV(rms) 9 Impulse withstand voltage 170 KV 11 Minimum failing load 10KN 12 Minimum creepage distance 580mm 13 Colour of glaze Brown 14 Weight per unit To be submitted by bidder 15 Size of Insulator a) Height To be submitted by bidder b) Diameter To be submitted by bidder 16 Material of thimble Lead 17 Steel head Large head 18 Standard IS: 731/1971 Tolerance will be allowed as per IS:731/1971 Tolerance 19 or latest amendments if any. 20 Drawing & Sample To be submitted by bidder PACKING: All insulators shall be packed in wooden crates suitable for easy but rough handling & acceptable for road transport. Where more than one insulator are packed in a crate, Separator shall be fixed between the insulators to keep individual insulator in position without movement in the crate.

11 TECHNICAL SPECIFICATION 11 KV POST INSULATOR 1. Scope- This specification covers the manufacture, testing and works supply and delivery of 11KV post insulators. The Porcelain insulators shall conform to IS: ammended upto date. Small fittings like spring washers, nuts etc may be electro-galvanised. Frequency : ( 50 ± 3%)Hz Nominal System Voltage : 11 K V Maximum System Voltage : 12 KV No. of phases : 3 Power frequency one minute withstand(dry) : 75 KV Neutral Earthing arrangement System : Effectively Earthed 3.Requirements: The post type insulators shall be suitable for outdoor use and cap & base type. Caps & base shall have plain machined faces & zigs shall be used for drilling bolt holes on the cap & in the base for easy & perfect assembly. Regarding Test for Mechanical strength for post Insulators, all the necessary tests are as per , , & of IS: with latest amendments are to be carried out at the manufacturer s premises. For each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows : i. Requisite numbers of set Screws & Spring Washers for assembling the Post Insulator unit. ii. Requisite numbers of set screws & spring washers for fixing bus-bar Support to the cap in the top Post Insulator. iii. One set of Bolts, Nuts & Washers or Lock nuts & plain washers for mounting the Insulators on the support steel structures of bus support. iv. 5% spare Nuts & Bolts with washers shall have to be supplied of no extra cost by the purchaser with each consignment. 4. Creepage Distances : The minimum creepage distance shall 30 mm/kv. 5. Tests: Suitable number of individual units shall be subject to the following tests in accordance with IS:731/1971 with its latest amendments 6. Test Certificate : The Bidder shall furnish detailed type test reports of the offered post Insulators at the NABL approved laboratories to prove that the Disc Insulators offered meet the requirements of the specification. These Type Tests should have been carried out within five years prior to the date of opening of this tender. iii) Their offered Insulators are already fully type tested at approved Laboratory within five years prior to the date of opening of this tender. iv) There is no change in the design of type tested Insulators and those offers against this tender.

12 7. Testing Facilities : The Bidder must clearly indicate what testing facilities are available in the works of the manufacturer and whether facilities are adequate to carry out all Routine & acceptance Tests. These facilities should be available to Purchaser s Engineers if deputed or carry out or witness the tests in the manufacturer works. If any test cannot be carried out at the manufacturer's work, the reasons should be clearly stated in the tender. The insulators shall be tested in accordance with the procedure detailed in IS-731/1971 amended up to date. 8.Drawings : The tender shall be accompanied with the detailed drawings showing the dimensions of the individual insulator, giving all the design dimensions of various component parts. Generally it shall be as per IS. 9. Markings : Each insulator shall be legibly and indelibly marked to show the following: a) Name or trade mark of the manufacturer. b) Voltage Type c) Month and year of manufacturing. d) Country of Manufacturer e) ISI certificate mark 10. Packing : All insulators shall be packed in crates or boxes suitable for rough handling. Packing shall be marked with the strength and KV rating. GUARANTEED TECHNICAL PARTICULARS FOR 11 KV POST INSULATOR Slno. Description Specified Bidder s Offer 1 Name of Manufacturer. & To be specified by the bidder Address 2 Location of type testing To be specified by the bidder 3 Applicable standard IS-731/1971 with latest amendment 4 Nominal System Voltage 11 KV 5 Highest System voltage 12 KV 6 Visible discharge Test voltage 9 KV (Minimum) 7 Impulse withstand voltage 90 KVp (+ve) and 105 KVp(-ve) +(1.2/50 microsecond wave) 8 Impulse flashover 95 KVp (+ve) and 120 KVp (-ve) voltage+(1.2/50 microsecond wave) 9 1min. power frequency flashover 70 KV Voltage kv. (Dry) 10 1min. power frequency flashover 45 KV

13 Voltage kv.(wet) 11 Cantilever strength a. Upright 65 Kg(Min) b. Inverted 400 Kg(Min) 12 Tensile strength 2050 Kg 13 Torsion strength 34 m-kg 14 Compression strength 3600 Kg 15 Conforming standard As per IS 16 Drawing & Sample To be submitted by Bidder NB- Every insulator should bear the marking of manufacturer s name and ISI mark TECHNICAL SPECIFICATIONS OF 33 KV POST TYPE INSULATOR 1.Scope of Work: This Specification covers design, engineering, manufacture, assembly, stage testing, inspection & testing before supply and delivery at site of the 33 KV post type insulator 2.0 INSULATORS 2.1 General Requirements The Porcelain shall be sound, free from defects, thoroughly vitrified and smoothly glazed Unless otherwise specified, the glaze shall be brown in colour. The glaze shall cover all the porcelain parts of the insulator except those areas which serve as supports during firing or are left unglazed for the purpose of assembly The design of the insulator shall be such that stresses due to expansion and contraction in any part of the insulator shall not lead to deterioration. The porcelain shall not engage directly with hard metal Cement used in the construction of the insulator shall not cause fracture by expansion or loosening by contraction and proper care shall be taken to locate the individual parts correctly during cementing. The cement shall not give rise to chemical reaction with metal fittings, and its thickness shall be as uniform as possible. 3.0 Tests: The insulators shall comply with the following tests as per IS: & IS: 5350(PT III) Type tests a) Visual examination b) Verification of dimensions c) Visible discharge test d) Impulse voltage withstand test. e) Wet power-frequency voltage withstand test. f) Temperature cycle test. g) Electro-mechanical failing load test. h) Mechanical failing load test (for those of type B strin insulator units to which electro mechanical failing load test (g) is not applicable. i) Twenty four hours mechanical strength test (for string insulators only when specified by the purchaser).

14 j) Puncture test k) Porosity test and l) Galvanising test. 3.2 Acceptance Tests The test samples after having withstood the routine tests shall be subjected to the following acceptance test in the rder indicated below: a) Verification of dimensions. b) Temperature cycle test. c) Twenty four hours mechanical strength test(for string insulator units only when specified by the purchaser) d) Electro-Mechanical failing load test. e) Puncture test f) Porosity test and g) Galvanising test. 3.3 Routine Test a) Visual examination. b) Mechanical routine test(for string insulator units only) and c) Electrical routine test(for string insulator units only) 3.4 Marking Each Insulator shall be legibly and indelibly marked to show the following. a) Name and trade mark of the manufacturer. b) Month and year of manufacture c) Minimum failing load in Newtons d) Country of the manufacturer and e) ISI Certification mark, if any. f) Specific Parameters & Layout Conditions Marking on porcelain shall be printed and shall be applied before firing. 3.5 Packing All insulators (without fittings) shall be packed in wooden crates suitable for easy but rough handling and acceptable for rail transport. Where more than one insulator are packed in a crate, wooden separators shall be fixed between the insulators to keep individual insulators in position without movement within the crate.

15 GUARANTEED TECHNICAL PARTICULARS FOR 33 KV POST INSULATOR Slno. Description Unit Specified Bidder s UNIT STACK Offer Manufacture Name Address of Manufacture Reference Standard (s) of Insulator To be Submitted by Bidder To be Submitted by Bidder IS: & IS:5350(PT-III)-1971 Height mm Insulating Part Diameter mm Pitch Circle Diameter a) Top Metal Fitting mm b) Bottom Metal Fitting mm Minimum creepage Distance 8 Cantilever Strength mm a) Upright Kgf b) Inverted Kgf Tensile Strength Kgf Torsional Strength Kgfm Compression Strength Kgf Nominal System Voltage KV(rms) a) b) Highest System Voltage Power frequency withstand voltage (Dry) Power frequency withstand voltage (Wet) Impulse-withstand test voltage(1.2x50 microsecond wave) Positive Negative KV(rms) KV(rms) KV(rms) KVP KVP Caps Padestal Material of Cap Aluminium Alloy Cap 17 Drawing & Sample To be submitted by bidder

16 11 KV Disc insulator 45 KN (T&CType) TECHNICAL SPECIFICATION FOR 11 KV 45 KN DISC INSULATORS 1. SCOPE : This specification covers the manufacture, testing and works supply and delivery of 11 KV Disc insulators. The Porcelain insulators shall conform to IS: ammended upto date. Insulators shall be of Tongue & Clevis type (T&C).Disc insulators made of glazed porcelain shall be used as insulators on dead ends or on suspension type lines of 11 KV and above. Tongue & Clevis type (T & C) disc insulators of mechanical strength not less than 45KN shall be used confirming to IS: 731/1971. These shall be mounted on metallic cross-arms with the help of suitable non-magnetic galvanised iron hardware fittings. Small fittings like spring washers, nuts etc may be electro-galvanised. 2. SERVICE CONDITIONS : The insulators to be supplied against this specification shall be suitable for satisfactory continuous operation under the following tropical conditions Maximum ambient temperature (Degree C) Minimum ambient temperature (Degree C) Relative Humidity (%) 10 to Maximum Annual Rainfall (mm) Maximum Wind pressure (kg/m.sq.) Maximum wind velocity (km/hour) Maximum altitude above mean sea level (meter) Isoceraunic level (days/year) Seismic level (Horizontal acceleration) 0.3 g Moderately hot and humid tropical climate conductive to rust and fungus growth 3. System Particulars : a) Nominal System Voltage 11 KV b) Corresponding highest system Voltage 12 KV c) Frequency 50 Hz with 3% tolerance d) Number of phase 3 e) Neutral earthing effectively grounded. f) Min. Impulse withstand voltage 75 KV 4. Standards : Unless otherwise specified elsewhere in the specifications insulators shall confirm to the latest revisions of all relevant standards. 5. General Requirements

17 i) The Porcelain insulators shall generally conform to IS: and any amendments up to date to the same. ii) Conductors : iii) The Disc Insulators will be used on lines on which the conductors will be A.A.A. Conductor of size up to 100 sq. mm. The insulators should withstand the conductor tension, the reversible wind load as well as the high frequency vibrations due to wind. Type a) Insulator shall be suitable for both the suspension and strain type of load & shall be of Tongue and Clevis type. The insulators shall conform to Type B of IS: b) Diameter of porcelain disc insulator shall be 255mm. The center to center distance between Tongue and Clevis shall be 145mm. c) Insulator Ends. Disc Insulators shall have Tongue and Cleave ends. The security clips will have to be provided as per fig. 25 of I.S (Part-2) 1989 ( amended up to date) REC Specification 3/1971(Revised 1993). d) The colour of the units shall be brown for 45 KN Disc Insulators. e) The number of units to be used both on suspension and tension strings shall be as given below : Voltage Class Suspension Strings Tension Strings. Single Double Single Double x2 3 3x x2 2 2x x2 1 1x2 iv). Electromechanical & Mechanical Strength : The mechanical and electromechanical strength of the individual and the complete Disc shall be 45 KN. v) Creepage Distances : The minimum creepage distance for each 11KV disc Insulator shall 320mm. 6.0 Tests : Suitable number of individual units and complete string shall be subject to the following tests in accordance with IS:731/1971 with its latest amendments. i) Type Tests : Following Type test shall be carried out on porcelain insulators as specified in IS: 731 /971 amended up to date. 1. Visual Examination. 2. Verification of dimensions. 3. Visible Discharge Test.

18 4. Impulse voltage withstand test. 5. Impulse voltage flashover test. 6. Wet one Minute Power Frequency withstand test and West Flashover test. 7. Temperature Cycle test. 8. Electromechanical failing load test. 9. Power frequency puncture withstand test. 10. Porosity test. 11. Galvanizing test. ii) Acceptance Tests : The test samples after having withstood the routine test shall be subject to the following acceptance tests in order indicated below: 1. Verification of dimensions. 2. Temperature Cycle test. 3. Twenty four hour mechanical test. 4. Electromechanical failing load test. 5. Power Frequency puncture withstand test. 6. Porosity test. 7. Galvanizing test. iii) Routine Tests: 1.Visual Examination 2. Mechanical test 3. Electrical test 4. Twenty four hours mechanical test 5. Electro mechanical failing load test 7 Test Certificate : The tenderer shall furnish detailed type test reports of the offered Disc Insulators as per clause 6.1 of the Technical Specifications at the NABL approved laboratories to prove that the Disc Insulators offered meet the requirements of the specification. These Type Tests should have been carried out within five years prior to the date of opening of this tender. i) Their offered Disc Insulators are already fully type tested at approved Laboratory CPRI/NABL within five years prior to the date of opening of this tender. ii) There is no change in the design of type tested Disc Insulators and those offers against this tender. iii) Such tenderers complying (i) and (ii) above shall furnish an undertaking in the format schedule. The purchaser reserves right to demand repetition of some or all the Type Test in presence of purchaser s representative at purchaser s cost. For this purpose, the tenderer shall quote unit rates for carrying out each Type Test. However, such unit rates will not be considered for evaluation of the offer. In case the unit fails in the Type Tests, the complete supply shall be rejected. 8. Testing Facilities : The tenderer must clearly indicate what testing facilities are available in the works of the manufacturer and whether facilities are adequate to carry out all Routine & acceptance Tests. These facilities should be available to Board's Engineers if deputed or carry out or witness the tests in the manufacturer works. If any test cannot be carried out at the manufacturer's work, the reasons should be clearly stated in the tender. The insulators shall be tested in accordance with the procedure detailed in IS-731/1971 amended up to date.

19 9. Material Quality and Workmanship : The quality of porcelain and hardware in case of porcelain insulators and core & housing in case of polymeric insulators shall be of the highest grade and best workmanship such as is suitable and customary for extra high tension lines and shall conform to current IS or IEC (only in absence of the relevant I.S.S.). The porcelain shall be sound, free from defect, thoroughly vitrified and smoothly glazed and brown in colour. Unless otherwise specified the glaze shall cover all exposed porcelain parts of the insulator. Glazing shall be uniform and free from defects. Small and isolated defects in the insulator glaze of a total surface less than 0.5 sq.cm. will however be ignored. Deviation on this account may be supported by relevant IS. 10 Mechanical Design : The design shall be such that stresses due to expansion and contraction in any part of insulator shall not lead to deterioration. Cement used in manufacture of the insulators shall not cause fracture due to expansion or loosening due to contraction. 11. Drawings : The tender shall be accompanied with the detailed drawings showing the dimensions of the individual Disc giving all the design dimensions of various component parts. The drawing for Insulators should clearly show the method of cementing the porcelain to the metal caps and balls. Generally it shall be as per IS. 12. Markings: 12.1 Each insulator shall be legibly and indelibly marked to show the following : a) Name or trade mark of the manufacturer. b) Voltage Type c) Month and year of manufacturing. d) Electromechanical strength in KN e) Property of NESCO The W clip shall be marked with/punched with the ball and socket sizes for which it is meant e.g.16b,20 etc Marking on porcelain shall be printed and shall be applied before firing. 13 Packing : All insulators shall be packed in crates or boxes suitable for rough handling. Packing shall be marked with the strength and KV rating.

20 GUARANTEED TECHNICAL PARTICULARS FOR 45 KN DISC. INSULATOR ( T&C TYPE) Sl. No Particulars Specific Requirement Bidders offer 1. Name of Manufacturer. & Address To be specified by the bidder 2. Location of type testing To be specified by the bidder 3 Applicable standard IS-731/1971 with latest amendment 4 Type of insulator T&C type Disc insulator 5 Nominal System Voltage 11 KV 6 Highest System voltage 12 KV 7 Visible discharge Test voltage (Minimum) 9 KV 8 Dry Impulse withstand voltage +(1.2/50 microsecond wave) 75 KV 9 Dry Impulse flashover voltage+(1.2/50 microsecond wave) 90 KV 10. Dry 1 min. power frequency withstand Voltage kv. 60 KV 11 Wet 1 min. power frequency withstand Voltage. 35 KV 12 1 min. power frequency flashover Voltage kv. (Dry) 65 KV min. power frequency flashover Voltage kv.(wet) 45KV 14 Power frequency puncture voltage 105 KV 15 Mechanical Routine test load 18 KN 16 Mechanical impact strength 45 KN 17 Shattered strengths (Glass).. KV 18 Electromechanical Failing Load 45 KN 19 Safe working load 18 KN 20 Minimum Failing Load 45 KN 21 Creepage Distance 320 mm 22 Type and Grade of Materials : i) Insulators Porcelain ii) Cap iii) Pin iv) Locking Malleable Casting or S.G Forged pin Split pin v) Cement Portland 23 Type of semi conducting Glaze Ceramic 24 Colour of Insulators Dark Brown 25 Weight of single disc. kg. 4 Kg(Approx.) 26 Number of Insulators per crate 4 nos./ 6 nos. 27 Cross weight of Loaded crate Kg 28 Whether drawing showing dimensional details have been furnished along with bid. To be enclosed by bidder NB : Every insulator should bear the marking of Purchaser s name/ Manufacturer s name and ISI mark.

21 11KV (LIGHTNING ARRESTERS) TECHNICAL SPECIFICATION FOR 9 KV 10 KA DISTRIBUTION CLASS HEAVY DUTY SURGE ARRESTERS (LIGHTNING ARRESTERS) 1.0 SCOPE: 1.1 This specification provides for the design, engineering, manufacture, assembly, stage testing, inspection and testing before despatch, packing, forwarding and delivery of Metal Oxide (gapless) Surge Arresters complete with accessories 11 KV system as specified hereunder. 1.2 It is not the intent to specify completely herein all the details of design and construction of Surge Arresters, However, Surge Arresters shall conform in all respects to the high standard of design and workmanship and be capable of performing in continuous commercial operation up to Bidder's guarantee in a manner acceptable to Purchaser, who will interpret the meanings of drawings and specifications and shall have the power to reject any work or material which in his judgment are not in accordance therewith. The Arresters offered shall be complete with all parts, necessary for their effective and trouble free operation. Such components shall be deemed to be within the scope of supply, irrespective of whether they are specifically brought out in the commercial order or not. 2.0 STANDARDS: 2.1 The Surge Arresters shall conform to the latest editions and amendments available at the time of supply, of the standards listed hereunder: Note: S. Standard Title No. Ref No. 1. IEC 99-4 Specification Part. 4 for Surge Arresters without gap for AC system. 2 IS:3070 (Part-III) Specification for Lightning Arresters for alternating current System 3 IS:2629 Recommended practice for hot dip galvanising of iron and steel. 4 IS:2633 Method for testing uniformity of coating on Zinc coated articles. 5 IS:5621 Specification for large hollow porcelain for use in electrical installation. 6 IS:2147 Degree of protection provided by enclosures for low voltage switchgear and control gear. 7. Indian Electricity Rules i) For the purpose of this specification all technical terms used hereinafter shall have the meaning as per IEC specification. ii) For the parameters of the Arrester which are not specified in IEC specification for Surge Arresters, the provisions of ISS 3070 (Part.III) shall be applicable.

22 2.2 Surge Arresters meeting with the requirements of other authoritative standards, which ensure equal or better quality than the standards mentioned above shall also be acceptable. Where the equipment offered by the Bidder conforms to other standards, salient points of difference between the standards adopted and the specified standards shall be clearly brought out in the offer. Four (4) copies of the reference standards in English language shall be furnished along with the offer CLIMATIC CONDITIONS: 3.1 The Surge Arresters and accessories shall be suitable for continuous satisfactory operation under climatic conditions listed below. 1. Maximum ambient Air 50 C Temperature in shade (deg.c). 2. Minimum Ambient Air (-) 5 C Temperature in shade(deg.c). 3. Maximum daily average ambient air temperature 40 C 4. Maximum relative humidity(%) 100% 5. Height above mean sea level 1000M 6. Maximum wind pressure 260 Kg m² 7. Average No. of thunder Storm 70 days. Days / annum. 8. Average annual rainfall (mm) 1500 mm 9. Average No. of months of 4 tropical monsoon condition p.a. All the electrical devices shall be given tropical and fungicidal treatment to enable their satisfactory operation in the above climatic conditions. 4.0 PRINCIPAL PARAMETERS: The Surge Arresters offered under this specification shall conform to the parameters given below. S. No Particulars System parameters for 9 KV Distribution type 1 Nominal system voltage (kv rms) 11 2 Highest system voltage (kv rms) /50 microsecond impulse voltage with stand level a Transformer and reactors (kvp) 75 b Other equipment and lines (kvp) 75 4 Minimum prospective symmetrical fault 10 current for 1 second at Arrester location (KA rms) 5 Anticipated levels of temporary over voltage and its duration.

23 a Voltage(p.u.) 1.5 b Duration(Seconds) 1/10 6 System frequency(hz) 50 + / Neutral Grounding Effectively earthed 8 Number of Phases Three Note 1. 1 p.u. = 12 x 2KV peak / GENERAL TECHNICAL REQUIREMENTS: 5.1 The Surge Arresters shall conform to the technical requirements as per Annexure-A. 5.2 The energy handling capability of each rating of Arrester offered, supported by calculations, shall be furnished in the offer The Station Type Surge Arresters shall be fitted with pressure relief devices and arc diverting ports and shall be tested as per the requirements of IEC specification for minimum prospective symmetrical fault current as specified in Annexure-A The grading ring on each complete Arrester for proper stress distribution shall be provided if required for attaining all the relevant technical parameters. 5.4 PROTECTIVE LEVELS: The basic insulation levels and switching impulse withstand levels of the lines and equipment to be protected have been specified in clause 4.0, "Principal Parameters". The protective characteristics of the Arresters offered shall be clearly specified in the schedule of guaranteed technical particulars. 5.6 GENERAL REQUIREMENTS: The materials and components not specifically stated in this specification but which are necessary for satisfactory operation of the equipment are deemed to be included in the scope of supply unless specifically excluded Unless otherwise brought out separately by the Bidder in the schedule of deviations the Surge Arresters offered shall conform to the specification scrupulously. All deviations from the specification shall be brought out in the schedule of deviations. The discrepancies between the specification and the catalogues or literature submitted as part of the offer shall not be considered as valid deviations unless specifically brought out in the schedule of deviations Any deviation which has not been specifically brought out in the schedule of deviations of the Bid Proposal Sheets, shall not be given effect to. The deviations brought out in the schedule shall be supported by authentic documents, standards and other references Each individual unit of Surge Arresters shall be hermetically sealed and fully protected against ingress of moisture. The hermetic seal shall be effective for the entire life time of the Arrester and under the service conditions as specified. The Bidder shall furnish sectional view of the Arrester, showing details of sealing employed The bidder shall furnish in the offer, a sectional view of pressure relief device employed in the Station type Surge Arresters offered The Surge Arresters shall be suitable for hot line washing.

24 5.7 Construction: All the units of Arresters of same rating shall be interchangeable without adversely affecting the performance The Surge Arresters shall be outdoor and suitable for pedestal/ clamp type mounting All the necessary flanges, bolts, nuts, clamps etc., required for assembly of complete Arrester with accessories and mounting on support structure to be supplied by the Purchaser shall be included in Bidder's scope of supply The drilling details for mounting the Arrester on Purchaser's support shall be supplied by the Supplier The minimum permissible separation between the Surge Arrester and any earthed object shall be indicated by the Bidder in his offer PORCELAIN / POLYMERIC HOUSING: The housing may be of Porcelain or Polymeric Where the bidders are quoting for Surge Arresters with Porcelain Housing, all porcelain housings shall be free from lamination cavities or other flaws affecting the maximum level of mechanical and electrical strengths The porcelain shall be well vitrified and nonporous The creepage distance of the Arrester housing shall be as per Annexure-A The porcelain petticoat shall be preferably of self cleaning type (Aerofoil design). The details of the porcelain housing such as height, angle of inclination, shape of petticoats, gap between the petticoats, diameter (ID and OD) etc., shall be indicated by the Bidder in his offer in the form of a detailed drawing The Arrester housing shall conform to the requirements of IEC specification GALVANISATION, NICKEL PLATING ETC.: All ferrous parts exposed to atmosphere shall be hot dip galvanised as per IS:2629 as amended from time to time. Tinned copper / brass lugs shall be used for internal wiring. Screws used for electrical connections shall be either made of brass or nickel plated Ground terminal pads and name plate brackets shall be hot dip galvanised The material shall be galvanised only after completing all shop operations ACCESSORIES AND FITTINGS: All necessary accessories and earthing connection leads shall be in the Bidder's scope of supply Terminal connector conforming to IS: 5561 shall be supplied along with the arrester The grounding terminal shall be suitable for accommodating Purchaser's grounding

25 connection to steel earth mat Name Plate: The arrester shall be provided with non-corrosive legible name plate indelibly marked with the following information: 1. Purchaser s Name : NESCO 2. Order No.: 3. Manufacturer's name, address, trade mark and identification no. of the Arrester being supplied. 4. Rated Voltage. 5. Maximum continuous operating voltage. 6. Type. 7. Rated Frequency. 8. Nominal discharge current. 9. Line discharge class. 10. Pressure relief current in ka rms. 11. B.I.L. of the equipment to be protected. 12. Year of manufacture. 13. Date of despatch. 14. Date of Expiry of Warranty TESTS: 6.1 TEST BEFORE DESPATCH: The Surge Arrester of various rating and accessories shall be subjected at maker's works before despatch, to the following tests as per relevant standards. A) ROUTINE TEST ON EACH UNIT AS PER RELEVANT STANDARDS: 1. Measurement of reference voltage. 2. Residual voltage test. 3. Satisfactory absence from partial discharges and contact noises. 4. For arrester units with sealed housing leakage check shall be made on each unit. 5. Current distribution test for multi Column arrester. 6.2 TYPE TESTS: The bidder shall furnish valid and authenticated type test reports from a Govt. approved / Govt. recognized / NABL Accredited laboratory of similar rating and design of tendered material along with detailed dimensional drawing duly signed & verified by testing agency also showing size & numbers of blocks dimensions contained in the housing along with bid as per requirement of the Tender Specification. Such type test certificates should not be older than 5 years as on the date of bid opening. For this purpose date of conducting type test will be considered. The type test certificates shall be furnished either in original or copy duly attested by notary. The bidder should furnish documentary evidence in support of the laboratory whose type test have been furnished, that the said laboratory is a Govt. / a Govt. approved / a Govt. recognized / NABL accredited laboratory / ILAC accredited (in case of foreign laboratory). The bids of only those bidders shall be considered to be meeting the type test criteria who furnishes complete type test certificate with the bid as per above provision : Following type tests shall be conducted on one unit of each rating as per relevant standard.

26 1. Insulation withstand test. 2. Residual voltage test. 3. Bending test on arrester housing assembly. 4. Long duration current impulse withstand test. 5. Operating duty test. 6. Pressure relief test (Only for station type) 7. Test of arrester disconnectors (For 9 KV Feeder Type) 8. Artificial pollution test on porcelain. 9. Partial discharge test. 10. Housed arresters. a) Temperature cycle test. b) Porosity test. 11. Galvanising test on exposed ferrous metal parts. 12. Any other type test which are not specified above but covered as per amendment/latest edition of relevant IS/IEC. 6.3 TEST ON BOUGHT OUT ITEMS: Tests are not required to be performed on bought out equipments/items like, Terminal connector etc. at the works of manufacturer. Furnishing Test Certificate of bought out items from the original equipment manufacturers shall be deemed to be satisfactory evidence. Inspection of the tests at Sub- contractors works will be arranged by the supplier whenever required. 6.4 ROUTINE/ACCEPTANCE TESTS: The following tests shall be got conducted in presence of purchaser's representative, as per stipulation of the relevant standards. Acceptance tests whenever possible shall be conducted on the complete arrester unit. No. of samples to be selected for acceptance tests shall be nearest lower whole number to the cube root of the number of arresters to be supplied. 1. Measurement of power frequency reference voltage on the complete arrester at the reference current measured at the bottom of the arrester. 2. Lightning Impulse residual voltage. 3. Partial discharge test. 4. Visual inspection & verification of dimension. 5. Special thermal stability test. 6. Galvanising test on Ferrous metal parts. 7. Any other tests as per IS. 6.5 TOLERANCE ON TEST RESULTS: As per relevant standards/specifications CHECKING AT STORES (TEST AT CTL): One out of every 50 nos. Surge Arresters will be selected for checking at Store for visual, dimensional, weight, marking etc. as per relevant ISS/GTP/approved drawing. 7.0 INSPECTION: All the tests (as mentioned at Clause 6.4) and Inspection shall be made at the place of manufacturer unless otherwise especially agreed upon by the bidder and purchaser at the time of purchase. The bidder shall afford the inspection officer(s) representing the purchaser all reasonable facilities without charges, to satisfy him that the material is being supplied in accordance with this specification. The purchaser has the right to have the tests carried out at his own cost by an independent agency whenever there is a dispute regarding the quality of supply.

27 The Inspection may be carried out by the purchaser at any stage of manufacture/before despatch as per relevant standard. Inspection and acceptance of any material under the specification by the purchaser, shall not relieve the bidder of his obligation of furnishing material in accordance with the specification and shall not prevent subsequent rejection if the material is found to be defective. The Bidder shall keep the purchaser informed in advance, about manufacturing programe so that arrangements can be made for inspection. The purchaser reserves the right to insist for witnessing the acceptance/routine testing of the bought out items. GUARANTEED TECHNICAL PARTICULARS FOR SURGE ARRESTERS METAL OXIDE (GAPLESS) S. No. Particulars Requirement of parameters 1 Name of Manufacturer. & Address To be specified by 2 Location of type testing the To be bidder specified by 3 Applicable standard IS:3070 (Part-III) or the latest version thereof 4 Rated arrester voltage (KV) 9 Bidder s offer 5 Maximum continuous operating 10 voltage (MCOV) KV (rms) 6 Installation Outdoor 7 Class Distribution Class 8 Type of construction Single column, single phase 9 Nominal discharge current corresponding to 8 / 20 micro second wave shape (KA peak) Type of mounting Pedestal 11 Connection (between phase to earth) / Phase to Earth (between phase to phase) 12 Line discharge class 2 13 Ratio of switching impulse residual voltage to rated voltage of arrester As per provision of IEC 99 4 (latest amended) 14 Minimum prospective symmetrical fault current for pressure relief test (KA rms) Terminal connector suitable for the upto 100 mm² single a) conductor b) Take off For both vertical & horizontal 16 Voltage (corona extinction) (KV rms) Rated voltage of arrester

28 17 Partial discharge As per provision of IEC 99 4 (latest amended) 18 Whether insulating base and No discharge counter with milli ammeter are required 19 Minimum creepage distance of arrester 300 mm housing 20 Drawing To be submitted by bidder Name & Signature of Bidder with seal SCOPE TECHNICAL SPECIFICATION OF 33KV LIGHTNING ARRESTOR 14.1 This Specification provides for the design, manufacture, inspection and testing before dispatch, packing and delivery F.O.R. (destination) of metal oxide (gapless) Surge Arresters with discharge counters, insulating base, terminal connectors and other accessories as specified here in. Following is the list of documents constituting this Specification. : (i) Technical Specification (TS) (ii) Check-List. Annexure-B (iii) Calibration Status of testing equipments and meters/ Instruments. Annexure-C (iv) Check-list towards Type Test Reports. Annexure-D Note : Annexure-B,C,& D are to be filled up by the Bidder. All the above along with amendments thereof shall be read and interpreted together. However, in case of a contradiction between the Technical Specification and any other volume, the provisions of this volume will prevail The Surge Arrester shall conform in all respects to high standards of engineering, design, workmanship and latest revisions of relevant standards at the time of offer and purchaser shall have the power to reject any work or materials, which in his judgment is not in full accordance therewith STANDARDS:- Except to the extent modified in the Specification, the Surge Arrester shall conform to the latest editions and amendments of the standards listed hereunder. Sl. No. Standard Title. 1 IEC-99-4 Ref. No. Specification for Surge Arresters without gap for AC System. 2 IS:2147 Degree of protection, provided by enclosures for low voltage switchgear and control. 3 IS:2629 Recommended practice for hot dip galvanization of iron and steel. 4 IS:2633 Method for testing uniformity of coating on zinc coated articles.

29 5 IS:3070 Specification for surge arresters for alternating current 6 IS:5621 system. Specification for large hollow porcelain for use in electrical & IEC installation. 7 IEC-60-1 High-Voltage Test technique. 8 IEC-270 Partial discharge measurements. 9 IEC-99-1 Non-linear resistor type gapped arresters for a.c. systems. 10 Indian Electricity Rules, IEC Shed profile of hollow porcelain Insulator Surge Arresters with the requirement of other authoritative standards, which ensure equal or better quality than the standards, mentioned above shall also be acceptable. Where the equipment offered by the supplier conforms to other standards, salient points of difference between the standards adopted and the specified standards shall be clearly brought out in the offer. 4 (Four) copies of the reference standards in English language shall be furnished along with the offer GENERAL TECHNICAL REQUIREMENTS: The Surge Arrester shall confirm the technical requirements The energy handling capability of each rating of Arrester offered, supported by calculations, shall be furnished with the offer The Surge Arresters shall be fitted with pressure relief devices and arc diverting paths and shall be tested as per the requirements of IEC for minimum prospective symmetrical fault current as specified in Appendix-I A grading ring shall be provided if required, (for attaining all the relevant technical parameters) on each complete Surge Arrester PROTECTIVE LEVELS: Surge Arresters shall be capable of providing protection to sub-station equipments, designed for the withstand levels, given in the following table. Sl. Equipment to be protected Insulation Level of 36KV System No. L.I. Level (KVP) 1 Power Transformers Instrument Transformers Reactors Circuit Breakers/Isolators. (i) Phase to ground. 170 Surge arrester shall be suitable for the following duty cycles of circuit breaker at the following system voltages: 14.7 DUTY REQUIREMENT: 36 KV Circuit Breaker sec-co-3 min-co Surge Arresters shall be of heavy-duty station class and gapless type without any series or shunt gaps. i. Surge Arresters shall be capable of discharging over voltages occurring during switching of unloaded transformers, lines, capacitors and reactors.

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - 1. SCOPE: - This specification covers 11KV Disc Type & 11KV/ 22KV Pin Type Insulators for 11/22KV H.T. over head power lines. 2. APPLICABLE

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 66 kv LIGHTNING ARRESTORS GETCO/ENGG/TECH SPECI.- 66 KV LA/R4/Jan11 Sign

More information

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008 Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4

More information

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION GETCO/E/TS-C&C

More information

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION GETCO/E/TS C&C057/R0 DT.

More information

General Requirements. Technical Specifications for Insulators of Transmission Lines

General Requirements. Technical Specifications for Insulators of Transmission Lines Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission

More information

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION GETCO/E/TS C&C057/R0 DT.

More information

SEAL & SIGNATURE OF THE TENDERER

SEAL & SIGNATURE OF THE TENDERER MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. LTD. SCHEDULE - `A' TECHNICAL SPECIFICATION FOR 11 kv & 22 kv A.B. SWITCH. SPECIFICATION NO:RE/II/A.B.SWITCH/2005 INDEX -----------------------------------------------------------------------------------------------------------------------

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 400 kv, 220 kv & 132 kv LIGHTNING ARRESTORS (SURGE ARRESTORS) GETCO/ENGG/TECH

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS DEVKON KIT AND HAND GLOVES GROUP F Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 1 Group-F Sl no. Material Description Unit Quantity

More information

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.

More information

Technical Specification for LV ABC Fuse Switch Disconnectors

Technical Specification for LV ABC Fuse Switch Disconnectors Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and

More information

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 REVISION NO. 0 NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 PAGE NO. 1 OF 24 DATE OF ISSUE (MONTH/YEAR) TOTAL NO. OF PAGES (Including cover

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS SPEC.NO. MSEDCL/ DIST:MSC-III/SPRING LOADED CONNECTOR BOX/05/10/R0/ 200510 TECHNICAL SPECIFICATIONS FOR TAMPER PROOF SERVICE CONNECTION BOX FOR L.T. LINES / CONSUMER MAINS (20.05.2010) Page 1 of 14 Clause

More information

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEB SPECIFICATION 005-1: 2012 P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS PAGE 1. Scope 03

More information

P.V.C. INSULATED UNARMOURED COPPER CABLES

P.V.C. INSULATED UNARMOURED COPPER CABLES 083 : 2007 CEB SPECIFICATION P.V.C. INSULATED UNARMOURED COPPER CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for P.V.C. INSULATED UNARMOURED COPPER CABLES CEB Specification 083 : 2007 CEYLON

More information

TECHNICAL SPECIFICATION A.B. CABLE

TECHNICAL SPECIFICATION A.B. CABLE TECHNICAL SPECIFICATION A.B. CABLE 1.0 NATURE OF WORK The work covered by this Specification is for L.T lines in A.B cable as specified herein and in the attached Schedules. The overhead distribution lines

More information

TECHNICAL SPECIFICATION FOR CONDUCTORS

TECHNICAL SPECIFICATION FOR CONDUCTORS TECHNICAL SPECIFICATION FOR CONDUCTORS SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 9 TECHNICAL SPECIFICATION FOR CONDUCTORS SPECIFYING TECHNICAL PARAMETERS OF THE CONDUCTOR SPECIFICATION NO. RE/ II/ ACSR

More information

THE KENYA POWER AND LIGHTING CO. LTD

THE KENYA POWER AND LIGHTING CO. LTD THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATION for SINGLE PHASE STATIC METERS FOR ACTIVE ENERGY Compiled by NAME DESIGNATION SIGNATURE DATE Ephantus Nyagah Ag. Senior Engineer Checked by Approved by

More information

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS Page no. :1 of 11 SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS Prepared by: Eng. T. Lev (-חתום-) Checked by: I. Bester (-חתום (- Approved by: Eng. Y. Samoocha (-חתום (- 1 Page no.

More information

SPECIFICATION SHEET JUNCTION BOXES

SPECIFICATION SHEET JUNCTION BOXES SPECIFICATION SHEET JUNCTION BOXES 8484-SS8201-8010 0 DOCUMENT NO REV SHEET 1 OF 1 CLIENT : HPCL, MUMBAI PROJECT : LPG BOTTLING PLANT, ANANTAPUR PLANT : - LPG BOTTLING PLANT ISSUED FOR : PROPOSAL ENQUIRY

More information

Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg.

Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg. DAKSHIN HARYANA BIJLI VITRAN NIGAM LIMITED Specification No. S-95/DD-177 Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg. Chief Engineer/P&D, DHBVN, Hisar. Issue

More information

Technical Specification for Live Line Tap Connectors

Technical Specification for Live Line Tap Connectors Ergon Energy Corporation Limited Technical Specification for Live Line Tap ETS-06-01-01 Check this is the latest Process Zone version before use. Specification ETS 06-01-01 Ver 1 Contents 1. Purpose and

More information

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols Ergon Energy Corporation Limited Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols ETS-01-05-01 Check this is the latest Process Zone version before use. Specification ETS 01-05-01

More information

TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED)

TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED) TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED) Regd. & Corporate Office: Visnagar Road, MEHSANA 384 001 (North Gujarat) Telephone: (02762) 222880, 222080-81 Fax: (02762)

More information

BIDDING DOCUMENT. Tavua 33 kv Substation Extension. Supply of 36kV Single Break Disconnectors, Structures and Accessories TENDER NO: MR 170/2015

BIDDING DOCUMENT. Tavua 33 kv Substation Extension. Supply of 36kV Single Break Disconnectors, Structures and Accessories TENDER NO: MR 170/2015 Tavua Substation 33 kv Extension Project Bidding Document: Revision 1 FIJI ELECTRICITY AUTHORITY BIDDING DOCUMENT Tavua 33 kv Substation Extension Supply of 36kV Single Break Disconnectors, Structures

More information

Not Applicable DD/MM/YY Completed Forms to be submitted by 30/08/2013 : Hrs IST. Date of Opening for Technical Bids 30/08/2013 : 14.

Not Applicable DD/MM/YY Completed Forms to be submitted by 30/08/2013 : Hrs IST. Date of Opening for Technical Bids 30/08/2013 : 14. DETAIL INFORMATION Contact Person and Address M.NALLATHAMBI SENIOR MANAGER / CCDP PURCHASE DEPARTMENT/R&D and CR UNIT HPBP BHEL, TIRUCHY, INDIA PIN : 620 014 Email mnthambi@bheltry.co.in Telephone 0091

More information

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR 003: 2008 CEB SPECIFICATION SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for Specification For All Aluminium Alloy Stranded Conductor CEB Specification

More information

TECHNICAL SPECIFICATION OF TOWER MATERIAL FOR132KV-PANTHER TRANSMISSION LINE

TECHNICAL SPECIFICATION OF TOWER MATERIAL FOR132KV-PANTHER TRANSMISSION LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF TOWER MATERIAL FOR132KV-PANTHER TRANSMISSION LINE GETCO/E/TS TM051/R0

More information

2. TEST RECORDS: All records of tests and analysis shall be kept in suitable forms approved by the Bureau.

2. TEST RECORDS: All records of tests and analysis shall be kept in suitable forms approved by the Bureau. SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF CARBON STEEL BILLETS, BLOOMS, SLABS AND BARS FOR FORGINGS ACCORDING TO IS:1875-1992 (Fifth Revision) 1. LABORATORY: A laboratory shall be maintained

More information

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium

More information

TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE

TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE Annexure-A TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE 1.0 SCOPE 1.1 This specification covers the design, manufacture, testing at works, supply / delivery & transportation of 11 mtr long

More information

TECHNICAL SPECIFICATION FOR PRESTRESSED CEMENT CONCRETE POLES ( F.O.S. 2.5) FOR 11 KV AND LT LINES ( REC SPECIFICATION NO.

TECHNICAL SPECIFICATION FOR PRESTRESSED CEMENT CONCRETE POLES ( F.O.S. 2.5) FOR 11 KV AND LT LINES ( REC SPECIFICATION NO. TECHNICAL SPECIFICATION FOR PRESTRESSED CEMENT CONCRETE POLES ( F.O.S. 2.5) FOR 11 KV AND LT LINES ( REC SPECIFICATION NO. 15 / 1979) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7

More information

SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134

SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134 Common Spec-2134.doc - 1-3.01 SCOPE: SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134 This specification covers the design, manufacture, assembly, testing and delivery of

More information

HIGH MAST CAMERA POLE ASSEMBLY GENERAL

HIGH MAST CAMERA POLE ASSEMBLY GENERAL 10-3.24 HIGH MAST CAMERA POLE ASSEMBLY GENERAL The Contractor must furnish and install the following equipment for high mast camera pole assembly as described herein and as shown on the plans: 1. Camera

More information

BHARAT HEAVY ELECTRICAL LIMITED, JHANSI Specification No.

BHARAT HEAVY ELECTRICAL LIMITED, JHANSI Specification No. NOTE : SCOPE : BHARAT HEAVY ELECTRICAL LIMITED, JHANSI Specification No. CRJ/9577 Item No. SP/CRJ/9577/1 & SP/CRJ/9577/2 Location NEW M.G.HOUSE Quantity 2 NOS. DESIGN, MANUFACTURING, SUPPLY, ERECTION &

More information

Surge arrester 3EB4. with polymeric composite housing for operating aboard traction units

Surge arrester 3EB4. with polymeric composite housing for operating aboard traction units Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders

More information

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained. DOC: STI//1 SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF ACCORDING TO IS/IEC:2003 1. LABORATORY A laboratory shall be maintained which shall be suitably equipped and staffed, where different tests

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

Specification for 11 KV outdoor GOD Air Break Isolator along with earth switch,post insulators, CT, PT and the Double pole Structure.

Specification for 11 KV outdoor GOD Air Break Isolator along with earth switch,post insulators, CT, PT and the Double pole Structure. Page 1 of Specification for 11 KV outdoor GOD Air Break Isolator along with earth switch,post insulators, CT, PT and the Double pole Structure. Hindustan Petroleum Corporation Ltd 8 S.V. Marg, Ballard

More information

ITEM 686 TRAFFIC SIGNAL POLE ASSEMBLIES (STEEL)

ITEM 686 TRAFFIC SIGNAL POLE ASSEMBLIES (STEEL) ITEM 686 TRAFFIC SIGNAL POLE ASSEMBLIES (STEEL) 686.1. Description. This Item shall govern for designing, fabricating, furnishing and erecting steel traffic signal pole assemblies of the various types

More information

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D Document type Page Verksamhetsstyrande 1 (5) Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D17-0008968 1.0 Organisation Valid from Valid until Regionnätsaffärer

More information

A-Series Aluminum Gantry Crane

A-Series Aluminum Gantry Crane SPANCO PRODUCT SPECIFICATIONS 1 A-Series Aluminum Gantry Crane This guide can be used to prepare a bid specification for the incorporation of an A-Series Gantry Crane into a competitive bid project or

More information

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv K-LINE INSULATORS LIMITED TORONTO, ONTARIO, CANADA Catalogue D-DS DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv ISO9001 SAI GLOBAL FILE No. 000117 Distribution Silicone Insulators

More information

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES GETCO/E/TS

More information

Energy Division Insulators

Energy Division  Insulators Energy Division http://energy.tycoelectronics.com Insulators R Insulators Tyco Electronics Energy Division covers a wide range of polymeric, hybrid and porcelain insulators. For decades all these products

More information

Distribution Code Review Panel. Product Approval Procedure

Distribution Code Review Panel. Product Approval Procedure Distribution Code Review Panel Product Approval Procedure Version 1.3 October-2013 INDEX Item page 1) List of Abbreviations 2 2) Introduction 3 3) Clause-1 Requirements and Submission methods 4 4) Clause-2

More information

MIL-L-26764B 4 March 1970 SUPERSEDING MIL-L-26764(ASG) 12 December 1963 MILITARY SPECIFICATION

MIL-L-26764B 4 March 1970 SUPERSEDING MIL-L-26764(ASG) 12 December 1963 MILITARY SPECIFICATION 4 March 1970 SUPERSEDING MIL-L-26764(ASG) 12 December 1963 MILITARY SPECIFICATION LIGHT, MARKER, AIRPORT APPROACH, HIGH INTENSITY, TYPE MB-2 This specification has been approved by the Department of the

More information

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM Page 1 of 6 SECTION 08 32 20 LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS SLIDING DOORS. SECTION INCLUDES OVERHEAD SLIDING TUBE ASSEMBLY, MOUNTING

More information

NPS/002/001 Technical Specification for Earthing Materials

NPS/002/001 Technical Specification for Earthing Materials Version:- 6.0 Date of Issue:- October 2017 Page 1 of 14 NPS/002/001 Technical Specification for Earthing Materials 1. Purpose The purpose of this document is to detail the requirements of Northern Powergrid

More information

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) SECTION 13125 ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

TECHNICAL SPECIFICATION FOR 22 kv, 1.2/2.4/3.0 MVAR CAPACITOR BANK WITH DOUBLE STAR ARRANGEMENT & ASSOCIATED EQUIPMENTS

TECHNICAL SPECIFICATION FOR 22 kv, 1.2/2.4/3.0 MVAR CAPACITOR BANK WITH DOUBLE STAR ARRANGEMENT & ASSOCIATED EQUIPMENTS Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST: MSC-III/06/2009 TECHNICAL SPECIFICATION FOR 22 KV 1.2/2.4/3.0 MVAR CAPACITOR BANK WITH DOUBLE STAR ARRANGEMENT AND ASSOCIATED

More information

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

NPS/002/020 Technical Specification for 11 & 20kV Power Cables Version:- 3.1 of Issue:- Nov - 09 Page 1 of 11 NPS/002/020 Technical Specification for 11 & 20kV Power Cables 1. Purpose The purpose of this document is to detail Northern Powergrid (the Company) requirements

More information

1.1 All testing apparatus shall be periodically checked and calibrated. Records of such checks/calibration shall be maintained.

1.1 All testing apparatus shall be periodically checked and calibrated. Records of such checks/calibration shall be maintained. SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF SINGLE PHASE a.c. INDUCTION MOTORS FOR GENERAL PURPOSE ACCORDING TO IS 996:2009 (Including Amendment No.1) 1. LABORATORY A laboratory shall be maintained

More information

EVALUATION REPORT. PFC-5551 Reissued April 1, Filing Category: DESIGN Steel (038)

EVALUATION REPORT. PFC-5551 Reissued April 1, Filing Category: DESIGN Steel (038) ICBO Evaluation Service, Inc. 5360 WORKMAN MILL ROAD WHITTIER, CALIFORNIA 90601-2299 A subsidiary corporation of the International Conference of Building Officials EVALUATION REPORT Copyright 2001 ICBO

More information

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

B. Provide liquid-filled secondary substation transformers as indicated on drawings. SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED

More information

B. Polyethylene samples shall be submitted for Owner approval of color and quality.

B. Polyethylene samples shall be submitted for Owner approval of color and quality. Glass Rail ENGINEERED DASHERBOARD SPECIFICATIONS PART 1 - GENERAL 1.01 PROJECT SCOPE A. Contractor shall furnish and install one complete set of steel framed dasherboards as indicated on the drawings and

More information

SECTION 1 - INTENT, SYSTEM REQUIREMENT, DESIGN CRITERIA AND SCOPE

SECTION 1 - INTENT, SYSTEM REQUIREMENT, DESIGN CRITERIA AND SCOPE Customer : Tamil Nadu Transmission Corporation Limited. Section 1 SECTION 1 - INTENT, SYSTEM REQUIREMENT, DESIGN CRITERIA AND SCOPE 1.0.0 INTENT OF SPECIFICATION 1.1.0 This specification covers the design,

More information

1. Cast-in-place concrete is specified in Section

1. Cast-in-place concrete is specified in Section SECTION 03 38 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for furnishing and installing post-tensioned slabs, jacks, jacking and anchors at Parking Structure, and record

More information

An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application

An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application Introduction Designed for Indoor and outdoor applications Non-tension tap and splice applications Used

More information

SECTION CHAIN-LINK FENCES AND GATES 02821/1

SECTION CHAIN-LINK FENCES AND GATES 02821/1 SECTION 02821 - CHAIN-LINK FENCES AND GATES 02821/1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Chain-Link Fences: 2. Gates: horizontal slide or swing. 3. Fences installed where

More information

SECTION 1043 FENCE MATERIAL

SECTION 1043 FENCE MATERIAL SECTION 1043 FENCE MATERIAL 1043.1 Scope. This specification covers the material required in the construction of chainlink fence and woven wire fence. 1043.2 Basis of Acceptance. The basis of acceptance

More information

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS SECTION 08 32 20 CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION UTTAR & DAKSHIN HARYANA BIJLI VITRAN NIGAM Specification No. CSC- XVIII/DH/UH/P&D/2009-2010 TECHNICAL SPECIFICATION FOR OUTDOOR TYPE SINGLE PHASE OIL IMMERSED COMPLETELY SELF PROTECTED DISTRIBUTION TRANSFORMERS

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION 1.0 SPECIFICATION OF FLAMEPROOF DISTRIBUTION BOARD, FIXTURES, POWER DISTRIBUTION SYSTEM INCLUDING CABLE LYING & TERMINATION. 1.0.1 Scope The following Specification flameproof Distribution

More information

INNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES

INNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES INNOVATIVE LIFE-CYCLE CONCEPTS FOR MEDIUM-VOLTAGE SWITCHGEAR ON BROWN COAL SURFACE MINING DEVICES Dr. S. Ruhland, Dr. U. Riedl ALSTOM Sachsenwerk GmbH, Germany The requirements for medium voltage switchgear

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- T/0018/ DMRC-E-TR-CABLE-2 SPECIFICATIONS FOR 33 kv CABLES FOR ELEVATED AND Issued on: Date Stage

More information

Translation from German (14 pages in all) Translation of the German original version not revised by the Deutsches Institut für Bautechnik

Translation from German (14 pages in all) Translation of the German original version not revised by the Deutsches Institut für Bautechnik Translation from German (14 pages in all) Translation of the German original version not revised by the Deutsches Institut für Bautechnik National Deutsches Institut für Bautechnik 1 Technical ANSTALT

More information

TESTING PTE EARTHING

TESTING PTE EARTHING 1 SCOPE This section of the Power Systems Live Working Manual details the procedures to be followed to achieve Safety from the System when carrying out examination, testing and remedial work on PTE (Pole

More information

QUOTATION ENQUIRY. Frequency Range Output AC Voltage Regulation (Batt. Mode) ±10% Frequency Range (Batt. Mode)

QUOTATION ENQUIRY. Frequency Range Output AC Voltage Regulation (Batt. Mode) ±10% Frequency Range (Batt. Mode) ANNEXURE-I-A QUOTATION ENQUIRY Ref: IIT (BHU)/IPCell/2017-18/UPS/1 KVA/574 Due Date: 26.09.2017 Date:16.09.2017 Upto 1:00 pm (Last date of quotation receiving) (Date of tender enquiry) To. Dear Sir, Please

More information

TECHNICAL SPECIFICATIONS OF SUB STATION STRUCTURES

TECHNICAL SPECIFICATIONS OF SUB STATION STRUCTURES GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF SUB STATION STRUCTURES GETCO/E/TS-STR 2301/R8 PROCUREMENT Dtd. 06.02.2013

More information

SPECIFICATION FOR REINFORCED SOIL WALL

SPECIFICATION FOR REINFORCED SOIL WALL SPECIFICATION FOR REINFORCED SOIL WALL 1.0 EXTENT OF WORK The work shall consist of Reinforced Soil walls built in accordance with this specification and in conformity with the lines, levels and details

More information

Polymer Post Insulators for 46 to 500kV Applications

Polymer Post Insulators for 46 to 500kV Applications CATALOG 142 Polymer Post Insulators for 46 to 500kV Applications NGK-Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A. TABLE of CONTENTS Process and Design Features...2 Materials...3 Application

More information

Guide to Documentation and Marking Part 6 General Accessories and Components for Slings

Guide to Documentation and Marking Part 6 General Accessories and Components for Slings Guide to Documentation and Marking Part 6 General Accessories and Components for Slings Document reference LEEA 059-6 version 2 dated 23.02.15 Introduction. This guide is aimed at manufacturers, distributors

More information

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1 GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1.01 WORK INCLUDED PART 1: GENERAL A. Provide for all labor, equipment, materials, and services to furnish and install VERSA SHIELD Window

More information

SECTION REINFORCING STEEL

SECTION REINFORCING STEEL SECTION REINFORCING STEEL 1. DESCRIPTION This specification shall govern the furnishing and placing of reinforcing steel, deformed and smooth, of the size and quantity designated on the plans and in accordance

More information

DOMESTIC GAS REGULATORS

DOMESTIC GAS REGULATORS CNG & CITY GAS DISTRIBUTION PROJECT FOR BID DOCUMENT FOR DOMESTIC GAS REGULATORS UNDER DOMESTIC COMPETITIVE BIDDING Bid Document No.: TNGCL/C&P/P(101)/PRV/2013-14 Dated 06/06/2013 VOLUME II OF II PREPARED

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists SECTION 412213- BRIDGE CRANES Part 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

TECHINICAL SPECIFICATIONS

TECHINICAL SPECIFICATIONS TECHINICAL SPECIFICATIONS 1. 9 Mtr 300Kg long PSC Pole 2. 8 Mtr long PSC Pole GROUP A GROUP B 3 11KV F Clamp 4 11 KV 'V' Cross Arm 5 Back Clamp for 'V' 6 11 KV GI Pin 7 11KV T&C H.W Fitting 8 20mm HT Stay

More information

COMPILED BY APPROVED BY FUNCTIONAL RESP AUTHORISED BY V SINGH. Date: 16/03/2009. Date: 16/03/2009. Date: 19/03/2009 Date: 26/03/2009

COMPILED BY APPROVED BY FUNCTIONAL RESP AUTHORISED BY V SINGH. Date: 16/03/2009. Date: 16/03/2009. Date: 19/03/2009 Date: 26/03/2009 SPECIFICATION Document Classification: Controlled Disclosure Title: Distribution Specification: Part 8 Unique Identifier: 34-434 COMMON BASE AND STANDARD Document Type: PASSIVE UNITS FOR SINGLE- PHASE

More information

SECTION LIGHT DUTY SLIDING AND STACKING GLASS DOOR SYSTEMS

SECTION LIGHT DUTY SLIDING AND STACKING GLASS DOOR SYSTEMS Page 1 of 9 SECTION 10 2238.13 LIGHT DUTY SLIDING AND STACKING GLASS DOOR SYSTEMS USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED FOLDING GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

SECTION-I TECHNICAL SPECIFICATIONS

SECTION-I TECHNICAL SPECIFICATIONS SECTION-I TECHNICAL SPECIFICATIONS 1. General Information and Scope 1.1 Scope 1.1.1 The following 400 kv double circuit transmission lines are included in the scope of the Contractor for various packages.

More information

TEESTAVALLEY POWER TRANSMISSION LTD.

TEESTAVALLEY POWER TRANSMISSION LTD. TEESTAVALLEY POWER TRANSMISSION LTD. TECHNICAL SPECIFICATION FOR TRANSMISSION LINE TOWER PACKAGES A1 & A2 VOLUME-II SPECIFICATION NO.: TOWER PACKAGE- A1 & A2 (This document is meant for the exclusive purpose

More information

Protective Capony RTC-16

Protective Capony RTC-16 Protective Capony RTC-16 ASSEMBLY AND OPERATION MANUAL Protective Canopy RTC-16 Assembly and Operation Manual CONTENT: 1 APPLICATION...3 2 OPERATION CONDITIONS...3 3 TECHNICAL SPECIFICATIONS...3 4 DELIVERY

More information

SECTION MECHANICAL EQUIPMENT - GENERAL REQUIREMENTS

SECTION MECHANICAL EQUIPMENT - GENERAL REQUIREMENTS SECTION 11000 MECHANICAL EQUIPMENT - GENERAL REQUIREMENTS PART 1 - GENERAL 1.1 DESCRIPTION A. This section contains general information required to install mechanical equipment as shown on the plans and

More information

Pins Insulator. Composite/Polymers Insulators

Pins Insulator. Composite/Polymers Insulators Composite/Polymers Insulators Electric network in India operates under very harsh environments. Industrial pollution, marshy land, hilly and unfriendly terrain, extreme weather, coastal region etc. make

More information

No.: MTL/PUR/13/06/Pt.XVI/(J)/10 DATE :

No.: MTL/PUR/13/06/Pt.XVI/(J)/10 DATE : No.: MTL/PUR/13/06/Pt.XVI/(J)/10 DATE : 24.05.2006 ASSAM GAS COMPANY LIMITED AN ISO 9001;2000 COMPANY ( A GOVT. OF ASSAM UNDERTAKING ) P.O. DULIAJAN, PIN 786 602 DIST. DIBRUGARH (ASSAM) Sealed tenders

More information

STOCKHOLDING DOCUMENT MANAGEMENT SERVICES LIMITED FORMERLY KNOWN AS SHCIL PROJECTS LIMITED

STOCKHOLDING DOCUMENT MANAGEMENT SERVICES LIMITED FORMERLY KNOWN AS SHCIL PROJECTS LIMITED STOCKHOLDING DOCUMENT MANAGEMENT SERVICES LIMITED FORMERLY KNOWN AS SHCIL PROJECTS LIMITED REQUEST FOR PROPOSAL (RFP) 130616 FOR SUPPLY INSTALLATION AND COMMISSIONING OF STEEL MEZZANINE FLOORING AT MAHAPE

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.PROV 604 NOVEMBER 2017 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

Corium Brick Rainscreen System Specifications

Corium Brick Rainscreen System Specifications CORIUM BRICK RAINSCREEN SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Work Included: The Work of this Section shall include but not be limited to the following: 1. Corium brick plates 2. Galvanized and coated

More information

E-Series Steel Gantry Crane

E-Series Steel Gantry Crane SPANCO PRODUCT SPECIFICATIONS 1 E-Series Steel Gantry Crane This guide can be used to prepare a bid specification for the incorporation of an E-Series Gantry Crane into a competitive bid project or application.

More information

DETAIL SPECIFICATION. MICROPHONE, CARBON (MICROPHONE M-29( )/U and M-52( )/U) INACTIVE FOR NEW DESIGN AS OF 30 MARCH 1999

DETAIL SPECIFICATION. MICROPHONE, CARBON (MICROPHONE M-29( )/U and M-52( )/U) INACTIVE FOR NEW DESIGN AS OF 30 MARCH 1999 INCH-POUND MIL-DTL-11193E 20 August 2009 SUPERSEDING MIL-M-11193D(SigC) 31 July 1960 DETAIL SPECIFICATION MICROPHONE, CARBON (MICROPHONE M-29( )/U and M-52( )/U) INACTIVE FOR NEW DESIGN AS OF 30 MARCH

More information

Comparison of BS and BS EN for steel materials

Comparison of BS and BS EN for steel materials Comparison of BS and BS EN for steel materials Appendix This table only highlights the comparison of BS and BS EN on steel materials, which are relevant to plan approval. Title of BS BS BS EN Title of

More information

STATE UNIVERSITY CONSTRUCTION FUND. UNIVERSITY CON DIRECTIVE 5-1 Issue date: October 2014

STATE UNIVERSITY CONSTRUCTION FUND. UNIVERSITY CON DIRECTIVE 5-1 Issue date: October 2014 STATE STRUCTION FUND DIRECTIVE 5-1 Issue date: October 2014 STRUCTURAL STEEL 1. General: It is the Fund's policy that the design of the structural steel is the prime responsibility of the project's Structural

More information

SCOPE OF WORK FOR PILING JOB

SCOPE OF WORK FOR PILING JOB SCOPE OF WORK FOR PILING JOB 1.0 PURPOSE This document defines the scope of works and specific requirements for the tank pad construction including pile foundation system for the proposed tanks at Wadala

More information

CORRIGENDUM. The tender date for POLARIMETER to be used at SCS, NISER is further extended as per the following.

CORRIGENDUM. The tender date for POLARIMETER to be used at SCS, NISER is further extended as per the following. CORRIGENDUM REF.: Tender No. NC-67-13-14 The tender date for POLARIMETER to be used at SCS, NISER is further extended as per the following. 1. Date & Time of Submission: 27.02.2014 (Up to 12:30 P.M.) 2.

More information

SECTION PLATE CONNECTED WOOD TRUSSES

SECTION PLATE CONNECTED WOOD TRUSSES SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:

More information