Solar Integration into the PJM Grid

Similar documents
PJM Renewable Integration Study

Accommodating High Levels of Distributed Energy Resources

Integrating DER in PJM Transmission Operations and Planning

SPP at a Glance. Located in Little Rock. Approximately 600 employees

PJM Perspective of the EPA Clean Power Plan: Analysis

PJM Interconnection, L.L.C. ( PJM ) submits hereby submits its responses to the United

PJM PROMOD Overview. August 1, PJM

Solar Impact on Grid Operations - An Initial Assessment

New England Electricity Outlook

Integrated Grid Planning Symposium

2750 Monroe Blvd Audubon, PA

Best Practices in Conducting Grid Integration Studies

Reduced Network Modeling of WECC as a Market Design Prototype

Energy Imbalance Market Overview

Electricity Grid of the Future. Program Director: Dr. Sonja Glavaski

Transmission Planning at the Midwest ISO. Mr. Eric Laverty Senior Manager of Transmission Access Planning Midwest ISO June 26 th, 2008

Integrating variable renewables: Implications for energy resilience

The Transformation of the New England Electric Grid and the Importance of Situational Awareness Tools

Renewable Integration at ERCOT

1st International Conference on Large-Scale Grid Integration of Renewable Energy in India Durgesh Manjure, MISO Energy September 6, 2017

PJM Renewable Integration Study

Regulatory Issues and Smart Grid Transmission Solutions

Fred Stoffel. Tri-State Generation and Transmission Association, Inc. May 19, Utility Resource Planning Fundamentals

2016 Fall Reliability Conference MRO

State of the Ar t. May Utility Wind Integration Group. American Public Power Association. Edison Electric Institute

Eastern Wind Integration and

Electrification and its Implications for the California Electricity System

PJM EIS Generation Attribute Tracking System (GATS)

Integrating Variable Renewable Energy into the Grid: Sources of Flexibility Best Practices and Case Studies

California Grid Operations: Current Conditions and Future Needs

PJM Manual 14A: New Services Request Process Revision: 20 Effective Date: October 1, Prepared by Interconnection Planning Department

High Voltage Direct Current

MISO SPP Interregional Stakeholder Advisory Committee. April 8 th, 2014 Carmel, IN

Integrating High Penetrations of Variable Renewable Generation Lori Bird and Debra Lew, NREL NCSL Webinar March 28, 2012

California ISO Preparing California for a Greener and Smarter Grid

Electricity Markets. Rapid Conference May 17, Mike Rencheck Rencheck Consulting LLC

Highlights and Key Results

LOAD SERVING ENTITIES PJM REGION

Date of Request for Comment: April 7, 2017 Period of Comment: April 7, 2017 through May 5, 2017

Section 3 Characteristics of Credits Types of units. Economic Noneconomic Generation.

PJM Interconnection Economic Analysis of the EPA Clean Power Plan Proposal

An economic assessment of the benefits of storage in South Africa


New England Wind Integration Study Executive Summary

Policy and Regulatory Approaches to Grid Integration of Renewable Energy in the US

Modelling of Australia s National Energy Guarantee

La regulación del incierto futuro de los sistemas eléctricos

THERMAL ENERGY STORAGE AS AN ENABLING TECHNOLOGY FOR RENEWABLE ENERGY

Introduction to the PJM Markets

Comparison of Renewable Portfolio Standards (RPS) Programs in PJM States

MAY 1, Variable Generation Integration Costs

1.818J/2.65J/3.564J/10.391J/11.371J/22.811J/ESD166J SUSTAINABLE ENERGY. Prof. Michael W. Golay Nuclear Engineering Dept.

UNDERSTANDING YOUR UTILITY PARTNERS UTILITY ENERGY EFFICIENCY DRIVERS AND DESIGN CONSIDERATIONS

EMS of the Future. EMS Users Conference Chicago, Illinois. John McDaniel September 20, Proprietary 1 Experience you can trust.

Load Shift Working Group.

Innovation & Grid Modernization at ComEd. Laura García García Grid Strategy & Analytics Commonwealth Edison

ANTICIPATING AND ADDRESSING SECURITY CHALLENGES IN AN EVOLVING POWER SYSTEM

Critical Utility Infrastructures: The U.S. Experience

Demand Response as Flexibility Provider: what are the challenges to achieve its full potential?

Con Edison. Evolution of Con Edison efforts in Energy Efficiency and Demand Management:

Survey of Modeling Capabilities and Needs for the Stationary Energy Storage Industry

Medium voltage products. Technical Application Papers No. 17 Smart grids 1. Introduction

Smart Grid Concept, Applications and Lessons Learned from Recent Deployments

Tucson Electric Power 2017 Integrated Resource Plan. Southern Arizona Regional Solar Partnership Jeff Yockey, PE

Flexible energy for efficient and cost effective integration of renewables in power systems

Renewables Portfolio Standards in the United States: A Status Update

Michael Sampson - June 21, Regulatory Challenges of Technical Innovation POWER SYSTEM TRANSFORMATION

EVALUATION OF MIDWEST ISO INJECTION/WITHDRAWAL TRANSMISSION COST ALLOCATION DESIGN. Prepared by Scott Harvey and Susan Pope

The Renewable Energy Zones Transmission Planning Process. Nathan Lee National Renewable Energy Laboratory 5 June 2017

Solar PV Capacity Additions Forecast for PJM States:

Mountain West Transmission Group Frequently Asked Questions Updated through September of 2017

Update on FERC, NERC, DOE & Congress John P. Hughes President & CEO Electricity Consumers Resource Council Washington DC

Hydroelectric Pumped Storage Potential and Renewable Energy Integration in the Northwest

Executive summary OECD/IEA Executive Summary

Northwest Power and Conservation Council NW Power Markets Symposium Products & Transactions

Applying PROBE for Congestion Analysis and Grid Planning

MARKET EFFICIENCY STUDY PROCESS AND PROJECT EVALUATION TRAINING

GRID CODE COMPLIANCE TESTING OF RENEWABLES NEW REQUIREMENTS AND TESTING EXPERIENCES

Congestion Assessment and Resource Integration Studies. A Report by the New York Independent System Operator

MISO Energy Storage Study Phase 1 Report

2015 Economic Planning Study Assumptions

Jan Strack and Huang Lin March 14, 2017

Integrated Capacity Analysis Working Group - Long Term Refinement Topics Scoping Document

NCSL Transmission Policy Institute Denver, CO

Renewable Energy Economics and Technology Status - Program 84

PJM Manual 27: Open Access Transmission Tariff Accounting Revision: 88 Effective Date: November 16, 2017

Impact of Regional Greenhouse Gas Initiative and Renewable Portfolio Standards on Power System Planning

Committed Offer: Offer on which a resource was scheduled by the Office of the Interconnection for a particular clock hour for the Operating Day.

CONNECTION & COSTS. Mary Doswell Alternative Energy Solutions December 7 th, 2010

Congestion and Marginal Losses

Solar and Smart Grid Training Design, Installation, Business Saving Energy Together

The Effect of the Volt/Var Control of Photovoltaic Systems on the Time-Series Steady-State Analysis of a Distribution Network

APRIL 23, Capacity Value of Wind Assumptions and Planning Reserve Margin

Managing Flexibility in MISO Markets

Nuclear-renewable hybrid energy systems for non-electric applications

Net Demand Variability (NDV) Summary

Southern California Edison

Integrating Energy Efficiency and Demand Response

Benefits from Generation and Storage on the Distribution System

20 MW Flywheel Energy Storage Plant

Transcription:

Solar Integration into the PJM Grid Ken Schuyler Manager, Renewable Services PJM Interconnection September 14, 2017

Integrating Solar in PJM PJM Background PJM Initiatives to Address Impacts Analysis of Impacts of Increasing Solar PJM Renewable Integration Study Long Term Forecast of Solar PV Evolving Solar Grid Interconnection Standards Solar Eclipse Lessons Learned 2

Key Statistics PJM as Part of the Eastern Interconnection Member companies 1,000+ Millions of people served 65 Peak load in megawatts 165,492 MW of generating capacity 176,569 Miles of transmission lines 82,546 2016 GWh of annual energy 792,314 Generation sources 1,304 Square miles of territory 243,417 States served 13 + DC 21% of U.S. GDP 27% of generation in Eastern Interconnection 28% of load in Eastern Interconnection produced in PJM 20% of transmission assets in Eastern Interconnection As of 2/2017 3

PJM Evolution 4

Reliability Grid Operations Supply/Demand Balance Transmission monitoring 1 PJM Focus on Just 3 Things Regional Planning 15-Year Outlook 2 Market Operation Energy Capacity Ancillary Services 3 5

PJM Generation Mix 2016 Annual Energy Percentage of Renewable Energy is Small but Growing Renewable Energy 6

State Renewable Portfolio Standards (RPS) require suppliers to utilize wind and other renewable resources to serve an increasing percentage of total demand. PJM States with RPS State RPS State Goal State RPS Targets NJ: 20.38% by 2021 MD: 25% by 2020 DE: 25% by 2026 DC: 50% by 2032 PA: 18%** by 2020 IL: 25% by 2026 OH: 12.5% by 2026 NC: 12.5% by 2021 (IOUs) MI: 10% + 1,100 MW by 2015 VA: 15% by 2025 IN: 10%** by 2025 DSIRE: www.dsireusa.org August 2017 Minimum solar requirement ** Includes non-renewable alternative energy resources 7

Projected Renewable Energy Requirements 35,000 117 GWhs of Energy (13.8% of PJM load) by 2032; 28 GW of Wind, 8 GW of Solar 10,000 28,000 8,000 21,000 6,000 14,000 7,000 PJM Wind PJM Solar 4,000 2,000 0 0 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029 2030 2031 2032 8

Impact of Increasing Wind and Solar Penetration Impacts due to variability and uncertainty: Minute-to-Minute Additional generation needed to provide regulation Intra-Hour Conventional generators must adjust output Day Ahead Forecast errors cause over- or underscheduling 9

Impact of Increasing VER Penetration Regional markets reduce Variable Energy Resource integration costs Characteristic Impact to Integration Cost Larger balancing areas Reduces overall increase in variability Less regulation and ramping service required Faster markets, i.e., shorter scheduling intervals (5-15 minutes) Less regulation required to accommodate intra-hour variations Larger geographic area Increases weather diversity and reduces overall variability Centralized wind and solar power forecasting Regional / Interregional Transmission Planning Cost-effective approach to reduce scheduling impacts Cost-effective upgrades to ensure grid reliability and mitigate congestion 10

PJM Initiatives to Address Impacts Energy Markets / Operations Implemented a centralized wind power forecast service Solar power forecast is in progress Implemented changes to improve wind resource dispatch / control Demand Response / Price Responsive Demand improves operational flexibility Frequency Regulation pay for performance rewards better performing resources (like storage) Interchange Scheduling compliant with FERC Order 764 (15-minute intervals) Transmission Planning Light load criteria implemented to improve grid reliability Expansion planning considers public policy impacts (i.e., RPS) Grid interconnection enhanced standards for new inverter-based resources (wind and solar) Evaluating Potential Grid Impacts PJM Renewable Integration Study (PRIS) - assessed grid impacts Advanced Technology Research Program (ATRP) Pilot programs to evaluate new technologies and remove barriers to participation in PJM markets and operations. 11

PJM Renewable Integration Study

PJM Renewable Integration Study (PRIS) Project Team GE Energy Consulting overall project leadership, production cost and capacity value analysis AWS Truepower development of wind and solar power profile data EnerNex statistical analysis of wind and solar power, reserve requirement analysis Exeter Associates review of industry practice/experience with integration of wind/solar resources Intertek Asset Integrity Management (Intertek AIM), formerly APTECH impacts of increased cycling on thermal plant O&M costs and emissions PowerGEM transmission expansion analysis, simulation of sub-hourly operations and real-time market performance 13

Study Scenarios Scenario Renewable Penetration in PJM Wind/Solar (GWh) Wind + Solar Siting 2% BAU Reference Existing wind Existing Plants + solar (Business as Usual) 14% RPS Base Case 14% 109 / 11 Per PJM Queue & RPS Mandates 20% LOBO 20% 150 / 29 Low Offshore + Best Onshore 20% LODO 20% 150 / 29 Low Offshore + Dispersed Onshore 20% HOBO 20% 150 / 29 High Offshore + Best Onshore 20% HSBO 20% 121 / 58 High Solar + Best Onshore 30% LOBO 30% 228 / 48 Low Offshore + Best Onshore 30% LODO 30% 228 / 48 Low Offshore + Dispersed Onshore 30% HOBO 30% 228 / 48 High Offshore + Best Onshore 30% HSBO 30% 179 / 97 High Solar + Best 14 Onshore Years Simulated Comments 3 years Benchmark Case for Comparing Scenarios 3 years Siting based on PJM generation queue and existing state mandates 3 years Onshore wind selected as best sites within all of PJM 1 year Onshore wind selected as best sites by state or region 1 year High offshore wing with best onshore wind 1 year High solar with best onshore wind 3 years Onshore wind selected as best sites within all of PJM 1 year Onshore wind selected as best sites by state or region 1 year High offshore wing with best onshore wind 1 year High solar with best onshore wind

Hourly Analysis Key Findings The PJM system, with additional reserves and transmission buildout, could handle renewable penetration levels up to 30%. The principal impacts of higher penetration of renewable energy into the grid include: Lower Coal and CCGT generation under all scenarios Lower emissions of criteria pollutants and greenhouse gases No loss of load and minimal renewable energy curtailment Lower system-wide production costs Lower generator gross revenues* Lower average LMP and zonal prices * Note: This study did not evaluate potential impacts on PJM Capacity Market results due to reduced generator revenues from the wholesale energy market, nor did it evaluate the impact of renewables to rate payers. It is conceivable that lower energy prices would be at least partially offset by higher capacity prices. 15

Renewables and the Regulation Requirement PJM Renewable Integration Study shows a need for regulation reserves to increase under all scenarios, especially under High Solar scenarios. 16

Primary Study Recommendations Adjustments to Regulation Requirements Develop a method to determine regulation requirements based on forecasted levels of wind and solar production. Day-ahead and shorter term forecasts could be used for this purpose. Renewable Energy Capacity Valuation Consider an annual or bi-annual application of ELCC methodology in order to calibrate PJM s renewable capacity valuation methodology in order to occasionally adjust the applicable capacity valuation of different classes of renewable energy resources in PJM. Mid-Term Commitment & Better Wind and Solar Forecast Consider using a mid-range wind and solar forecast in real-time operations to update the commitment of intermediate units (such as combined cycle units that could start in a few hours). This would result in less reliance on higher cost peaking generation. Exploring Improvements to Ramp Rate Performance Explore the reasons for ramping constraints on specific units, determine whether the limitation are technical, contractual, or otherwise, and investigate possible methods for improving ramp rate performance. 17

Incorporating Solar in PJM Long-Term Load Forecast

RPS and NEM Policy Assumptions by State 19

PA Solar PV Capacity Additions Forecasted 20

Evolving Grid Interconnection Standards

After contingencies: it is bad if generators trip offline. Germany case. 1. Bad fault lots of load shed frequency rise 2. DER trip on overfrequency!! Simulated timelines W/ ride through W/ ride-through & frequency response! Normal frequency range 3. No ride-through: frequency control very bad. 22

Current PJM Enhanced Inverter Requirements Applicability: non-synchronous generators that entered the New Service Queue on or after May 1, 2015 (AB1 queue or later) that sign an Interconnection Services Agreement Distribution-connected units that sign WMPAs are not subject to PJM s requirements for interconnection. Required functionality: Ride through (mandatory) of abnormal voltage and frequency according to NERC PRC-024 Voltage regulation (capability) 0.95 leading/lagging measured at high side of facility substation transformers (or measured at the generator s terminals if entered queue prior to Nov 1, 2016 as per FERC Order 827). Ramp limit (capability) Frequency response (capability) (underfrequency: if available) 23

Requirements of 1547 revision Applicability: future: possibly certain statejurisdictional and FERC-jurisdictional DER. Requirements Ride-through (mandatory) of voltage & frequency Voltage regulation (capability): fixed power factor, volt-var, watt-var, fixed reactive power, volt-watt Frequency response (capability) (underfrequency: if available) Communications interface (capability): SEP2, DNP3, or SunSpec Modbus Enter service ramp limit (mandatory) 1547 revision: expected out in 2018. Test procedures (revised 1547.1 ) published ~2019+. UL1741 after. Regulators or utilities together with NERC Reliability Coordinators (e.g., PJM) to specify 1547 categories and adjustments. Some time required. Where PJM cites to 1547 today (e.g., manual 14a), PJM may revise language in response to 1547 revision. 24

PJM Smart Inverter Technical Demonstrations Goal: refine recommended settings for PJM enhanced inverter requirements and for coordinating possible state-level ride-through requirements. Partnerships with several utilities in two states and one state commission. One or more smart inverter installations for testing of actual behavior to refine input for large-scale models. Test plan with most of the functions described in the 1547 revision. Large scale modeling in PSS/E of regional reliability impact/benefit of significant deployment of DER with vs. without ride through and voltage regulation. Documented results expected early next year. 25

Solar Output During August 21, 2017 Total Solar Eclipse

13:30 13:40 13:50 14:00 14:10 14:20 14:30 14:40 14:50 15:00 15:10 15:20 15:30 15:40 50 to 75% 25 to 50% Impact on PJM: If sunny day, up to ~2,500 MW increase in need for non-solar generation during event Source of eclipse map: NASA Source of PJM solar map: PJM Environmental Information Services 27

Estimated Solar Output on August 21, 2017 Thousands Hundreds 8 6 4 2 0 3 2 1 Grid-Connected Solar Output Behind-the-Meter Solar Output Up to ~500 MW lost in 1 hour Up to ~2,000 MW lost in 1 hour 0 6:00 8:00 10:00 12:00 14:00 16:00 18:00 20:00 Overcast - More Conservative Overcast - Less Conservative Sunny - More Conservative Sunny - Less Conservative 28

Estimated and Actual Solar Output on August 21, 2017 Hundreds Thousands 8 6 4 2 0 3 2 1 Grid-Connected Solar Output Behind-the-Meter Solar Output Loss of 520 MW Loss of ~1,700 MW 0 6:00 8:00 10:00 12:00 14:00 16:00 18:00 20:00 Low - More Conservative Low - Less Conservative High - More Conservative High - Less Conservative Estimated Actual 29

Thousands 140 130 120 110 100 90 80 ~5,000 MW decrease in load during eclipse RTO Load and Solar Output on August 21, 2017 8 7 6 5 4 3 2 1 Hundreds 70 0 0:00 2:00 4:00 6:00 8:00 10:00 12:00 14:00 16:00 18:00 20:00 22:00 0:00 Load (MW) Grid-Connected Solar Output (MW) 30

Thousands 140 130 120 110 100 90 80 ~3 F decrease in temperature at least partially responsible for load decrease RTO Load and Temperature on August 21, 2017 88 86 84 82 80 78 76 74 72 70 70 0:00 2:00 4:00 6:00 8:00 10:00 12:00 14:00 16:00 18:00 20:00 22:00 0:00 Load (MW) Hourly Temperature (Degrees Fahrenheit) 31

18000 Example of Load Impacted by Temperature Reduction ComEd Load vs. Temperature During August 1 Thunderstorms 85 17000 83 16000 81 15000 79 14000 77 13000 75 12000 11000 10000 Similar changes in temperature have had immediate impacts on load, but not as drastic as those observed during eclipse 73 71 69 9000 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 0 67 Five-Minute Load Hourly Temperature 32

Factors Contributing to Load Changes Factor that Impacted Load Direction of Impact Expected Amount of Impact Reduced behind-the-meter solar + ~1,700 MW Increased lighting load + Low Human behavior Inconclusive not quantifiable Decreased temperature Inconclusive forecast models not trained on intra-hour values 33

Lessons Learned Projections of solar output during eclipse were largely accurate Load decreased by twice amount that solar output decreased May be different in 2024 with additional installed solar Human behavior is important factor that is not well understood Behind-the-meter assumptions will be difficult to verify Current load forecast models are not trained to reflect significant intra-hour temperature changes Additional coordination needed for accurate weather forecasts 34

Additional Information PJM Initiatives: PJM Learning Center: Alternative & Renewable Generation» http://learn.pjm.com/energy-innovations/alternative-renewable-gen.aspx PJM Renewable Integration Study (PRIS) Reports» http:///committees-and-groups/subcommittees/irs/pris.aspx PJM 2017 Load Forecast Report» http:///-/media/library/reports-notices/load-forecast/2017-load-forecastreport.ashx PJM s Evolving Resource Mix & System Reliability Report» http:///-/media/library/reports-notices/special-reports/20170330-pjmsevolving-resource-mix-and-system-reliability.ashx 35