ON THE OPTIMIZATION OF REFRIGERATION MACHINERY

Similar documents
COMPARISON OF ENERGY EFFICIENCY BETWEEN VARIABLE AND FIXED SPEED SCROLL COMPRESSORS IN REFRIGERATING SYSTEMS

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS

Christian Ohler, ABB Switzerland Corporate Research Efficiency versus Cost - a Fundamental Design Conflict in Energy Science

Heat Pump Efficiencies simulated in Aspen HYSYS and Aspen Plus

OPTIMIZATION OF THE TRIPLE-PRESSURE COMBINED CYCLE POWER PLANT. Muammer ALUS and Milan V. PETROVI] *

Application of a cooling tower model for optimizing energy use

Optimization of parameters for heat recovery steam generator (HRSG) in combined cycle power plants

Exergy in Processes. Flows and Destruction of Exergy

Investigation of Separator Parameters in Kalina Cycle Systems

NOVEL CYCLES FOR POWER AND REFRIGERATION

DYNAMIC SIMULATION FOR DESIGN IMPROVEMENTS, COST REDUCTION AND OPERATIONAL STABILITY IN LNG PLANT DESIGN

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle

Chapter 9: Applications of the Laws of Thermodynamics

Optimization of Gas Turbine Cogeneration System for Various Heat Exchanger Configurations

Fundamental Investigation Of Whole-Life Power Plant Performance For Enhanced Geothermal Systems

Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant

Steam balance optimisation strategies

UNIT NO-03 [8 hrs] Second Law Of Thermodynamics: Introduction (Law of degradation of energy), Thermal energy reservoirs, Kelvin-Plank & Clausius

Performance of a counterflow heat exchanger with heat loss through the wall at the cold end

Heat Exchanger Exergetic Lifecycle Cost Optimization using Evolutionary Algorithms

Refrigeration Cycle. Definitions , , 11-46, 11-49,

Thermo-economic analysis of regenerative heat engines

Modified Reverse-Brayton Cycles for Efficient Liquefaction of Natural Gas

LECTURE-15. Ideal Reverse Brayton Cycle. Figure (6) Schematic of a closed reverse Brayton cycle

Performance Benefits for Organic Rankine Cycles with Flooded Expansion

PROMOTION OF ENERGY EFFICIENT DISPLAY CABINETS

SorTech package solution description

Solutions to TUTORIAL-6 (10/03/2017) Thermodynamics for Aerospace Engineers (AS1300) Second Law of Thermodynamics

Cool Producing Systems Based on Burning and Gasification of Biomass

Review Questions for the FE Examination

Thermally operated mobile air-conditioning system

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT

Principles of Engineering Thermodynamics. 8th Edition SI Version

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Exergy analysis of transcritical carbon dioxide refrigeration cycle with an expander

Ejector Expansion Refrigeration Systems

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.

Refrigeration System with Booster Hot Gas Bypass in Tropical Climate

Quiz Questions. For Process Integration. Fill in the blanks type Questions

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

THE EFFECT OF STRESS STATE ON THE SOIL-WATER CHARACTERISTIC BEHAVIOR OF A COMPACTED SANDY- CLAY TILL

B.Tech. Civil (Construction Management) / B.Tech. Civil (Water Resources Engineering) B.Tech. (Aerospace Engineering) Term-End Examination

DESIGN ANALYSIS OF A REFRIGERATED WAREHOUSE USING LNG COLD ENERGY

EFFECT OF AMBIENT TEMPERATURE, GAS TURBINE INLET TEMPERATURE AND COMPRESSOR PRESSURE RATIO ON PERFORMANCE OF COMBINED CYCLE POWER PLANT

II. SYSTEM DESCRIPTION AND MATHEMATICAL MODELING

AN EXERGY COST ANALYSIS OF A COGENERATION PLANT

SAMPLE STUDY MATERIAL

3.17. PROCESS INTEGRATION AND PINCH TECHNOLOGY

Design and Optimization of Kalina Cycle for Geothermal Energy in Kenya

Chapter 6 THE SECOND LAW OF THERMODYNAMICS

PERFORMANCE STUDY OF SOLAR THERMAL BINARY POWER CYCLES

High-efficiency low LCOE combined cycles for sour gas oxy-combustion with CO[subscript 2] capture

Energy Balances and Numerical Methods Design Project. Production of Methyl Tertiary-Butyl Ether

Alexander Rattner MEAM-402 HW 2

Thermodynamic analysis on post combustion CO 2 capture of natural gas fired power plant

INSIDE: ASHRAE Hall of Fame

THERMOECONOMIC ANALYSIS OF MULTI STAGE FLASH- THERMAL VAPOR COMPRESSSION (MSF-TVC) DESALINATION PROCESS

pinch 70 C 70 C 4 We want to cool both the hot streams to the pinch temperature. The next step is to find the duty for the two heat exchangers:

An Economics-Based Second Law Efficiency

MULTI-OBJECTIVE OPTIMIZATION ON SUPERCRITICAL CO 2 RECOMPRESSION BRAYTON CYCLE USING KRIGING SURROGATE MODEL

CONTROL VOLUME ANALYSIS USING ENERGY. By Ertanto Vetra

Thermodynamics and Efficiency Analysis Toolbox 6 Sustainable Energy

ENGINEERING INFORMATION Hot water and steam service

a.k.a. David N. Shaw, P. E.

FLOWRATE DEPENDENT HEAT-PUMP MODEL

Thermo-Economic Analysis of a Desalination Device from the Second law of Thermodynamics Point of View and Parameter Investigation

OVERALL EFFICIENCY CONSIDERATION OF PNEUMATIC SYSTEMS INCLUDING COMPRESSOR, DRYER, PIPE AND ACTUATOR

HT A COMPUTATIONAL MODEL OF A PHASE CHANGE MATERIAL HEAT EXCHANGER IN A VAPOR COMPRESSION SYSTEM WITH A LARGE PULSED HEAT LOAD

A COMPREHENSIVE STUDY ON WASTE HEAT RECOVERY FROM INTERNAL COMBUSTION ENGINES USING ORGANIC RANKINE CYCLE

Cogeneration in a Hospital: a case Study

The Effect of the Condenser Inlet Cooling Water Temperature on the Combined Cycle Power Plant Performance

Multi-Variable Optimisation Of Wet Vapour Organic Rankine Cycles With Twin-Screw Expanders

Dresden, Germany ABSTRACT MODELING OF THE CHILLER INTRODUCTION

MULTI-OBJECTIVE OPTIMIZATION OF TURBO-EXPANDER IN ORGANIC RANKINE CYCLE SYSTEM

Energy and Exergy Analysis of M.P.C Absorption Chiller

Chapters 5, 6, and 7. Use T 0 = 20 C and p 0 = 100 kpa and constant specific heats unless otherwise noted. Note also that 1 bar = 100 kpa.

ES Analysis of Performance of Direct Dry Cooling. for Organic Rankine Cycle Systems

Thermodynamic analysis of a regenerative gas turbine cogeneration plant

IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS

Performance Analysis of Shell and Tube Heat Exchanger Using Miscible System

Bifluid Geothermal System New Generation

SELECTION OF WORKING FLUID AND EXERGY ANALYSIS OF AN ORGANIC RANKINE CYCLE

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

CLOSED-LOOP HEAT EXCHANGER FOR GROUND COUPLED HEAT PUMPS

Performance Assessment of Large Vapor Absorption System

The Part-Load Efficiency Benefit of Oil-Free, High- Speed, Direct-Drive Centrifugal Compressors

Available online at ScienceDirect. Energy Procedia 49 (2014 ) SolarPACES 2013

Farm Energy IQ. Farms Today Securing Our Energy Future. Farm Energy Efficiency Principles Tom Manning, New Jersey Agricultural Experiment Station

Modelling of Indirect Evaporative Air Coolers

Performance Evaluation of Heat Exchangers for Application to Ocean Thermal Energy Conversion System

Heat Load Calculation for the Design of Environmental Control System of a Light Transport Aircraft

THE USAGE OF LOW POTENTIAL SOURCES OF HEAT FOR PRODUCTION OF ELECTRICITY AND HOT WATER

Energy savings certificates in France Selection of calculation sheets. IEA-DSM Task XXI: Standardisation of Energy Savings Calculation

The first law of thermodynamics can be stated in terms of the heat energy transferred into the system,

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

Improvement of distillation column efficiency by integration with organic Rankine power generation cycle. Introduction

Heat pumps. Oilon ChillHeat. Optimized cooling and heating performance

Comparison of combined heat and power systems using an organic Rankine cycle and a low-temperature heat source

EXERGY CONVERSION IN THE JAPANESE SOCIETY

Revue des Energies Renouvelables Spécial ICT3-MENA Bou Ismail (2015) Numerical study of a single effect ejector-absorption cooling system

Transcription:

GÖRAN WALL Exergy Studies, Solhemsgatan 46, SE-431 44, Mölndal, Sweden, Email: Goran.Wall@exergy.se published in International Journal of Refrigeration Vol. 14., pp. 336-340. 1991. Abstract. We present the application of thermoeconomics to the optimization of a heat-pump. The method is well suited for application to thermodynamic processes and yields exergy losses. The marginal cost of an arbitrary variable can also be calculated. The efficiencies of the compressor, condenser, evaporator, and electric motor are chosen as variables which are to be optimized. Parameters such as the price of electricity and the temperature of the delivered heat may vary among optimizations, and results are presented for different parameter values. The result shows that the efficiency of the electric motor is most important. À L OPTIMISATION D UN SYSTEME DE REFRIGERATION RESUME: Cet article présente l application d une étude thermique et économique de l optimisation d un modèle de cycle de pompe à chaleur. Cette méthode convient bien à l application aux processus thermodynamiques et donne peu de pertes d exergie. Le coût marginal d une variable arbitraire peut aussi être calculé. Les rendements du compresseur, du condenseur, de l évaporateur et du moteur électrique sont choisis comme les variables de décision à optimiser. Des paramètres tels que le prix de l éctricité et la température à laquelle la chaleur est fournie peuvent varier suivant les optimisations, les résultats sont présentés pour différentes valeurs des paramétres. Le résultat montre que le rendement du moteur électrique est le plus important. NOMENCLATURE a annuity factor, dimensionless C cost per unit time, SEK/yr E exergy, J E el electricity used per year, J/yr h specific enthalpy, J/kg H enthalpy, J k constant factor m mass flow, kg/s NTU number of heat transfer units, dimensionless n c quantity of substance c, kg n i depreciation time for component i, yr P power, W p pressure, Pa p el price of electricity, SEK/J r interest rate, dimensionless T temperature, K T 0 reference temperature, K t operating time per unit time, dimensionless S entropy, J/K V volume, m 3 x state parameters y optimization or decision variable z decision parameters S tot total entropy production, J/K equations of state Φ j The optimization program is available on diskette by sending USD 10 in cash to the author.

Φ 0 objective function, SEK/yr efficiency, dimensionless µ chemical potential, J/kg marginal cost, SEK/yr Subscripts c substance el electricity i component k refers to optimization variables r refrigerant wc water on cold side wh water on hot side 0 reference state ON THE OPTIMIZATION OF REFRIGERATION MACHINERY INTRODUCTION This study origins from earlier work 1 and the purpose of this paper is to introduce the method of thermoeconomics to refrigeration engineering. The construction of technical systems, which are often based on experience, educated guess-work and personal evaluations, could be improved by an analysis of the effects of different potential solutions in terms of cost. Usually, a maximum cost permitted for each part of the system is set, and the market prices determine to what extent efficient components can be afforded. Such systems always cost at least as much as and often more than they would if thermoeconomic optimization were used. El-Sayed and Tribus 2 developed the concept of thermoeconomics, in which the objective function is optimized, subject to given economic and technical constraints. The purpose of thermoeconomics is to improve analyses of systems by introducing ways of concurrently suggesting improvements. PHYSICAL ENVIRONMENT Mass Energy Entropy Pressure Temperature Chemical potentials COST SYSTEM RELATIONS ECONOMIC ENVIRONMENT Prices Interest rates Values Information Constraints Fig. 1. The system in a physical and an economic environment. By optimizing the total cost of a system in operation, we always find the best system within the given physical and economic conditions. We can also calculate the marginal costs of the exergy losses in each component. These values are very important in the selection of research and development measures, or in the improvement of an existing system. The system is described in relation to the physical (pressure, temperature, and chemical potentials of the appropriate substances) and economic environments (prices of goods and prices of capital or interest rates). These two environments are interrelated by cost relations based on physical quantities, see Fig. 1. With regard to the physical environment, the energy and mass flows are evaluated in physical terms, i.e., in terms of exergy per unit time. The difference between all incoming exergy flows and all outgoing 2

exergy flows must be minimized and the efficiency must be maximized. In the economic environment all energy and mass flows are evaluated instead in terms of economic value or costs. The main function is now the cost per unit time, (i.e., operation and capital costs minus income), which should be minimal. Thermoeconomic optimization is an economic optimization subject to the physical constrains of the system. THERMOECONOMIC OPTIMIZATION The objective function Φ 0 is defined as a function of state parameters {x j }, where {x j } is abbreviation for x 1, x 2, x j x n, decision variables {y k }, and decision parameters {z l }, i.e. where j=1, 2,, n, k=1, 2,, m, and l=1, 2,, r. The equations of state are The optimization is formulated as follows: Φ 0 = Φ 0 ({x j },{y k },{z l }), (1) Φ j ({x i },{y k },{z l }) = 0, j = 1, 2,, n. (2) minimize Φ 0 = Φ 0 ({x i },{y k },{z l }), (3) subject to Φ j ({x i },{y k },{z l }) = 0, j = 1, 2,, n. (4) The exergy losses due to irreversibilities in a stationary state is determined for each component by regarding in and outflows of exergy. The exergy content is E = H T 0 S µ c 0 n c. (5) c For the system, we obtain a sum for all components, which gives the total rate of exergy loss. This may also be written as the product of the reference temperature and total entropy production, i.e., T 0 S tot. 3

REFRIGERATION MACHINERY Heat pump systems offer much more efficient means of producing heat than traditional combustion or electrical short circuit technologies. Heat pump systems are therefore becoming more common as the prices of fuels and electricity increase. The configuration of the system in this study is defined in Fig. 2. It consists of a compressor, a condenser, an expansion valve, an evaporator, and an electric motor. water in 8 2 5 4 9 water out liquid mixture gas 6 3 3 Expansion valve 1 5 Electric motor 7 2 water out 11 mixture 4 1 10 water in Fig. 2. Heat pump system with 5 components and 11 flows. The refrigerant is superheated after passing through the evaporator, step 1-2, and supercooled after passing through the condenser, step 5-6. The actual state of the refrigerant after the compression, 3, differs from that of a reversible process, 3 rev, due to the limited efficiency of the compressor. The heat produced from the system is h 3 h 6, the heat input is h 2 h 7, and the work supplied to the compressor is h h 3 2. The electricity input required to operate the system becomes (h 3 h 2 )/ 5, where 5 is the efficiency of the electric motor. The system is completely defined apart from the decision variables {y k } which are the efficiencies of the compressor, the condenser, the evaporator, and the electric motor. These are defined as follows y 1 = 1 = h 3rev h 2 h 3 h 2, (6) y 2 = 2 = T 9 T 8 T 4 T 8, (7) y 3 = 4 = T 11 T 10 T 1 T 10, (8) y 4 = 5 = m r (h 3 h 2 ) P. (9) Each set of these variables determines a state of the system. The exergy flows and exergy losses can now easily be determined for each component. The objective is to minimize the total life cycle cost, which includes both the operating (electricity) cost and the capital cost, for a given amount of produced heat. The operating cost increases if the investments decrease and vice versa. For the designer the market value of the product (heat) and a given required profit sets an upper limit for the total cost of the system. The problem is to split this cost between the operating cost and the capital cost for each component. (The costs for parts slightly affected by alternative construc- 4

tions of the system, such as pipes connecting the components, are just added as constants since they have no effect on the optimization.) The following assumptions, concerning the size of and external conditions on the system, are made: heat produced 6.5 kw (energy power), operation time/yr 5000 hr, price of electricity SEK 0.25/kWh (SEK 6 US$ 1), and temperature of the produced heat (T 9 ) 60 C. Let us assume the following simple cost relations for the 5 components to be valid in the region of optimization for this system as defined below. 2 C 1 = a 1 k 1 V 2 0.9 1 p 3 p 2 ln p 3 p 2 (10) C 2 = a 2 k 2 m wh 2 1 2 = a 2 k 2 m wh e NTU 2 1, (11) Expansion Valve C 3 = a 3 k 3 m r, (12) C 4 = a 4 k 4 m wc 4 1 4 = a 4 k 4 m wc e NTU 4 1), (13) Electric Motor 5 C 5 = a 5 k 5 P. (14) 1 5 Furthermore the annuity factors of the different capital investments are defined as r a i = 1 (1+ r) n i. (15) The depreciation time n i may vary for each component due to variations in economic lifetime and maintenance costs such as renovations, etc. Figure 3 shows the investment costs as a function of the efficiencies. A typical knee, from the penalty function, can be observed for the compressor and the electric motor at specific values of the efficiencies, approximately at 86 and 94 % respectively. If the compressor and the electric motor are regarded as given, or limited to a number of possibilities, the decision space is limited to one, or a number of, two dimensional rooms, defined by the efficiencies of the condenser and the evaporator, i.e., the only two decision variables. These relations may be changed due to other assumptions of the system, e.g., non linear relations to the size of the system. 5

9000 8000 Costs of investments (SEK) 7000 6000 5000 4000 3000 2000 1000 0 66 Electric motor Efficiency (%) 70 75 80 85 90 95 Fig. 3. Costs of investments as a function of the efficiencies. The investment costs are depreciated according to the annuity method, which gives a cost per unit time for every component. The total cost per unit time, i.e., the objective function, is the sum of these costs and the cost of the electricity used, during the same period of time, 5 Φ 0 = C i + tp el E el. (16) i =1 RESULTS AND CONCLUSIONS The optimization is achieved by calculating the value of the objective function Φ 0 and the marginal costs { k } for every set of the variables {y k } according to k = Φ 0 y k, k = 1, 2, 3, 4. (17) From these values a new set of variables {y k } is determined by using the Newton-Raphson method. Thus the system moves towards the nearest minimum from the given start values. However, the problem is strongly non-linear which means that there is no general method for finding the global minimum. Instead common sense and insight into how the system works must be used to determine the value of a solution. A computer program has been developed for finding the optimum system. The calculation of the thermodynamic data, for the assumed refrigerant R12, are based on similar computer-based calculations by Reynolds. 3 The equations of state for the system are formulated so as to avoid iterations. The actual minimizing procedure is carried out with a small number of iterations. When the sum of the marginal costs k is less than a predefined value the optimization is completed. Let us assume a system with the following values for the efficiencies of the compressor, the condenser, the evaporator, and the electric motor, i. e., the decision variables, 0.7, 0.8, 0.7, and 0.75. Other refrigerants may also be used by simple changes in the program. These roughly correspond to real values of a system of this size. 6

The total cost then becomes SEK 3676/yr of which SEK 3025/yr relate to electricity. From the optimization we get the following values of the efficiencies: compressor 0.80, condenser 0.82, evaporator 0.72 and electric motor 0.91. The total cost now amounts to SEK 3167/yr of which SEK 2237/yr relate to electricity. By increasing the investments from SEK 651/yr to SEK 930/yr, the total cost of the system becomes SEK 509/yr (about 14%) less than for the assumed system, see left side of Fig. 4. At the same time the exergy losses decrease from 1464 W to 839 W, i.e., by 625 W (T 0 = 0 C). From Fig. 4 we also see that it is the improvement of the electric motor that gives the largest single exergy saving. Thus, the optimization in this case saves both money and exergy. 4000 Cost (SEK/year) 1600 Exergy loss (W) 3500 1400 Electric motor 3000 1200 2500 Electricity Electric motor 1000 Expansion valve 2000 800 1500 Expansion valve 600 1000 400 500 200 0 Assumed system Optimum system 0 Assumed system Optimum system Fig. 4. Costs and exergy losses for the assumed and the optimum systems. The expansion valve accounts for a larger fraction of the total exergy loss in the optimum system, which further justifies investment in research and development to improve it. The result indicates the electric motor to be the most critical component to improve. The electric motor is assumed to cost approximately 2.4 times as much at 91% efficiency than at 75% efficiency, which must be regarded as realistic. (But, it may even cost up to 7.7 times as much and still be competitive with the assumed system.) It may also be added that the coefficient of performance (COP) increases from 2.69 for the assumed system to 3.63 for the optimum system. In order to further show the usefulness of the method the dependence on or sensitivity to the cost of electricity and the temperature of the produced heat (T 9 ) has also been studied. Figure 5, 6, and 7 shows the relationship between the component costs and the price of electricity, when this varies between SEK 0.2 and 2/kWh, when the temperature of the produced heat is 50, 60, or 70 C. At 50 C (T 9 ) the total cost increases from SEK 2296/yr to SEK 13891/yr at SEK 2/kWh. This can be seen in relation to the fact that if the optimum system at SEK 0.2/kWh had been used at SEK 2/kWh, then the total cost would be SEK 15913, i.e., an increase in the cost of SEK 2022/yr. (For the assumed system the total cost would instead be SEK 24851, i.e., a cost increase of SEK 10960/yr.) From Figs. 5-7 we see that all components should 7

become more expensive, thus more efficient, when the price of electricity increases. This might have been anticipated, but the exact interrelations could not have been foreseen. 500 Cost [SEK/yr] Temperature of output heat = 50 C 400 300 200 100 0.2 0.4 0.6 Price of electricity [SEK/kWh] 0.8 1.0 1.2 1.4 El. motor 1.6 1.8 2.0 Fig. 5. Component costs as a function of the price of electricity when output heat is 50 C. 600 500 Cost [SEK/yr] Temperature of produced heat = 60 C 400 300 200 100 0.2 0.4 0.6 Price of electricity [SEK/kWh] 0.8 1.0 1.2 1.4 El. motor 1.6 1.8 2.0 Fig. 6. Component costs as a function of the price of electricity when output heat is 60 C. 8

700 600 Cost [SEK/yr] Temperature of produced heat = 70 C 500 400 300 200 0.2 0.4 0.6 Price of electricity [SEK/kWh] 0.8 1.0 1.2 1.4 El. motor 1.6 1.8 2.0 Fig. 7. Component costs as a function of the price of electricity when output heat is 70 C. When the temperature of the produced heat (T 9 ), is changed from 40 to 80 C, at an electricity price of SEK 0.25/kWh, the total cost increases from 2203 to SEK 4333/yr and the COP changes from 5.6 to 2.6. The heat produced (energy) is 6500 W, but the rate of exergy changes from 434 to 799 W (T 0 = 0 C) which better explains the increased cost. When the temperature increases from 40 to 80 C the total system, but not necessarily each component, must be more efficient, see Fig. 8. Within a total increase of component costs and efficiencies, we see that, it is more economical to choose a less expensive evaporator. The explanation is simply that investments in other parts of the system pay off better. 9

350 Cost [SEK/yr] 300 Price of electricity = SEK 0.25 /kwh 250 200 150 Condensor Electric motor 100 40 45 50 Temperature [ C] 55 60 65 70 75 80 Fig. 8. Component costs as a function of the temperature of the produced heat. Similarly, many other relations may be described by using the computer program for the system. The program can easily be rewritten for other refrigerants or cost relations. The purpose of this study is merely to show the gain achieved by applying the method of thermoeconomics to an example of a refrigeration machinery. The exact numerical results for describing thermoeconomics as a method for improving technical processes have therefore been neglected. It must be noted that thermoeconomics can never replace long experience and high technical and economic competence. Manufacturers will always be driven by two strong driving concerns: minimum cost and minimum performance standards. However, if they considered the system as a way to produce heat they should offer minimum cost of heat rather than minimum cost of poor equipment. In any case, thermoeconomics will always be an important complementary tool. REFERENCES 1. G. Wall, Exergy a Useful Concept, Thesis, Physical Resource Theory, Chalmers University of Technology, S-412 96 Göteborg, Sweden, 1986, G. Wall, ENERGY, Vol. 11, pp. 957-967, 1986, and Wall, G., in David R. Tree and Douglas C. Hittle Eds., Progress in the Design and Construction of Refrigeration Systems, pp. 91-97, Purdue Univ.(1988). 2. Y. M. El-Sayed and M. Tribus, Strategic use of thermoeconomics for systems improvement, in R. A. Gaggioli ed., Efficiency and Costing, ACS Symp. ser. No. 235, 1983. 3. W. C. Reynolds, Thermodynamic properties in SI Graphs, Tables and Computational Equations for 40 Substances, Dep. Mech. Eng., Stanford Univ., CA 94305, U.S.A., 1979. 10

11