SECTION 1000 ENGINEERING SPECIFICATION: AIR STRIPPER (REMOVABLE TRAY)

Similar documents
SECTION SANITARY WASTE INTERCEPTORS

PARTS & ACCESSORIES: EATON DUPLEX BASKET STRAINERS FEATURES OPTIONS MODEL 53BTX DUPLEX (3/4 TO 4 ) MODEL 50 DUPLEX (5, 6, 8 )

HIGH DENSITY CROSSLINKED POLYETHYLENE STORAGE TANKS WITH OXIDATION RESISTANT LINING SYSTEM (NSF/ANSI 61)

Section BUILDINGS, SHELTERS, ENCLOSURES

SECTION INFLUENT EQUALIZATION TANK PUMPS

SAFE-TANK DOUBLE WALL TANKS HIGH DENSITY CROSSLINKED POLYETHYLENE STORAGE TANKS WITH OXIDATION RESISTANT LINING SYSTEM (NSF/ANSI 61)

The following document can be provided to an Engineer, Contractor, or Owner to allow them to

Diffused Aeration Piping Equipment

SECTION FIELD ERECTED INDUCED DRAFT COOLING TOWER

ISSUE DATE JANUARY 1st, 2008 SECTION 5G FIBERGLASS PACKAGE LIFT STATION

TYPES OF SEWAGE PUMPS. Solids Handling Pumps: Grinder Pumps: Effluent Pumps:

SECTION COOLING TOWER

200 Series In-Slab Pool Fittings

ADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities

OxiPRO Q2.0 Microbial Control Technology

1.16. Sound Attenuated Enclosure

MASTER. Water Conditioning Corp. OPERATION MANUAL. PURO PRO 1200 SCP Series Modular Reverse Osmosis System. January 2012 Version

B. System Design and Performance Requirements

Rolairtrol Air Separator For Hot and Chilled Water Systems

SECTION PACKAGE BOOSTER PUMP STATIONS

Simplex Fiberglass Lift Station: Hard Piped

SPECIFICATIONS - DETAILED PROVISIONS Section Horizontal Centrifugal Water Pumps C O N T E N T S

Engineering Design Center. Standard Drawings. 1st Edition -January 2016

SECTION AIR FILTERS

TM Series Cooling Tower Specification

Read Only Copy Not For Distribution. Chapter 17. Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.2 QUANTITY OF WATER REQUIRED

Basket Strainers. Threaded. Basket. Strainers. Flanged Basket. Strainers

Aerators. Aeration and Gas Stripping

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES...

5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers.

Air Lift Pumps (Grit Pump) ST-027

MASTER. Water Conditioning Corp. OPERATION MANUAL. PURO PRO 1200 SC Series Modular Reverse Osmosis System. January 2012 Version

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

INDUSTRIAL FILTRATION EQUIPMENT LWS Filter Series

CROSBY H-SERIES DIRECT SPRING SAFETY VALVES

SYSTEM 1E LIQUID CHEMICAL STERILANT PROCESSING SYSTEM

Series A-C Single Stage Double Suction Large Split Case. TECHNICAL Brochure BAC9100

Section SPHEROID ELEVATED WATER STORAGE TANK

B. Polyethylene samples shall be submitted for Owner approval of color and quality.

Buderus SB745WS/1550 Stainless Steel Condensing Boiler

W ARR A NTY FAIRBANKS NIJHUIS 1600 SERIES SINGLE STAGE END SUCTION PUMPS. Certified to NSF/ANSI 372.

40'-0" PIPE SUPPORT (TYP.) (SEE DWG. NO. SK-2 OR DWG. NO. SK-4)

TECHNICAL SPECIFICATION DANTECO HERMANNS. CONTAINER FOR BULK POWDER Equipped with HERMANNS Aeration and Conveyance Device

RECOMMENDED SPECIFICATIONS FOR AREO-POWER 10 PPM OIL WATER SEPARATORS WITH THROUGH SHELL CONNECTIONS

ONE PIPE LENGTH MAX (REFER TO 1/4"/FT SLOPE (MIN) 5'-0" (MIN) OR 4" LATERAL NOTE #1) INCREASER RIGHT-OF-WAY/ 4"x6" REFER TO TYPICAL EXCAVATION,

Electric Service Standards

Gerber M Series Site Requirements

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

SUPERSTEAM USG LINE UNFIRED STEAM GENERATOR. Humidification. Sterilization. Pharmaceutical

Series Sump and Sewage Systems

VIKING BOLTED-LID BASKET-TYPE LINE STRAINERS

Masoneilan * Series Control Valve

SECTION POLYVINYL CHLORIDE (PVC) WATERLINE

Glossary Irrigation Terminology

Welcome: What is U-Drain? Drain Materials. Flow

SECTION A-A. Control Panel

SECTION MANHOLES AND STRUCTURES. A. Section Includes: 1. Manholes for water, storm drain and sanitary sewer systems.

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM

NOTICE OF DISCONTINUATION,

ELM6375DX DRAINABLE ADJUSTABLE LOUVER EXTRUDED ALUMINUM

Buderus SB625WS/640 Stainless Steel Condensing Boiler

1.02 Related Sections A. Section Heating, Ventilation and Air Conditioning (HVAC). C. Section Pneumatic and Electric Control HVAC.

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY PIPE HANGERS, Section PIPE HANGERS, SUPPORTS, AND RESTRAINTS

LIQUID-SPECIFIC PRODUCT LINE: ABRASIVE LIQUID PUMPS SERIES DESCRIPTION OPERATING RANGE: IMPROVEMENTS NOMINAL FLOW RATES:

SECTION MECHANICAL SPECIFICATION GRIT COLLECTION EQUIPMENT

D-35 Series. Up to 37 gpm (140 l/min) D-35 Specialized Designs

SECTION STORM UTILITY DRAINAGE PIPING PART 1 - GENERAL 1.1 SUMMARY 1.2 SUBMITTALS 1.3 PROJECT CONDITIONS

Noise Control. Commercial, Industrial, and Environmental Products and Solutions.

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)

15020 LABORATORIES. C. Section Building Automation and Control System Guidelines

STAINLESS STEEL SHEETS

Pioneer Forced Draft Cooling Tower Specifications

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

Essex County College - West Essex Campus Addition And Renovations Dib # / SECTION DOMESTIC WATER PIPING SPECIALTIES

Vapor Extraction / Groundwater Extraction (VE/GE) System Initial Report

VPL-3200B Residential Vertical Platform Lift Technical Specifications

QUALITY ASSURANCE SPECIFICATION WELDING HEAT TREATMENT PAGE 1 OF 6

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH

Stainless Steel Aeration Equipment Specification

SECTION SLUDGE HOLDING TANK DECANTER PUMP

1511 Series. Consolidated * Valves. Safety Valve

SINGLE STAGE END SUCTION PUMPS AURORA Series. Distributed By: Model 3804

ACOUSTICAL DUCT & PIPE LAGGING INDUSTRIAL NOISE CONTROL PRODUCTS

Pre-Sloped Drain System

Installation Instructions

Water Quality Specification for Power Supplies

Introduction. Disclaimer. Table of contents

FAIRBANKS NIJHUIS SUBMERSIBLE SOLIDS HANDLING PUMPS.

DRAINS AND CLEANOUTS. 1. Division 7 - Thermal and Moisture Protection Piping (Plumbing).

On-Site Leaching Chamber Specifications & Features. Design & Installation Manual Ohio

Underground Exhaust System

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

REV. 9/08. Mounting Structure PRE-INSTALLATION GUIDE for Ergon Skybooms

Price Single Duct Terminal Units

CHAPTER 12 TRICKLING FILTER PLANTS

ROOF DRAINS TABLE OF CONTENTS

WATER POWERED HIGH EXPANSION FOAM GENERATORS

IOWA WASTEWATER FACILITIES DESIGN STANDARDS CHAPTER 20 DISINFECTION

SECTION VIBRATION ISOLATION

Transcription:

SECTION 1000 ENGINEERING SPECIFICATION: AIR STRIPPER (REMOVABLE TRAY) PART 1 GENERAL 1.1 SCOPE 1.1.1 The manufacturer shall furnish a low profile, multi-tray Air Stripper for removal of volatile organic compounds from water. System shall be manufactured by QED Environmental Systems, Inc. and represented by or pre-approved equivalent. 1.2 PROCESS DESCRIPTION 1.2.1 The air stripper process must allow influent water to be piped to the air stripper inlet distribution port. The water is then allowed to flow over a weir and through a series of sieve/aeration trays as it descends to a sump at the bottom of the unit. Air forced up through the sieve holes in each tray forms a froth of bubbles, generating a large gas/liquid contact surface area. Depth of froth and unit air-to-water ratio are carefully controlled to optimize the contaminant removal process. This allows mass transfer of contaminants from the water into the rising air, which is exhausted at the top of the unit. A demister pad prevents release of water droplets in the exhaust. 1.3 SUBMITTALS 1.3.1 Manufacturer shall submit the following with the bid: 1.3.1.1 Product data for selected model, including rated flow capacity, dimensions, weights (dry and operating), accessories, and warranty coverage. 1.3.1.2 Drawings and/or data sheets containing all information necessary to relate the equipment to the specifications. 1.3.1.3 List of all instrumentation to be provided, with descriptive information for each component. See attached Air Stripper Data Sheet for list of required instrumentation.

PART 2 PRODUCTS 2.1 GENERAL 2.1.1 The air stripper shall be an E-Z Tray TM Removable-Tray Air Stripper or pre-approved equivalent (low profile, multiple sieve tray design using pressure rather than vacuum to generate airflow). See Data Sheet for model number. 2.1.2 All components and options shall meet requirements specified on the Data Sheet attached to this specification. 2.2 EQUIPMENT DESIGN REQUIREMENTS 2.2.1 Standard product design shall include one low-profile aeration unit shell with the following specifications: 2.2.1.1 The shell shall accommodate slide-out removable, interchangeable sieve trays for easy cleaning. 2.2.1.2 Access to the individual trays shall be provided via a removable hatch, without requiring removal of influent, effluent, or air discharge piping. The hatch shall be constructed of transparent material to allow visual observation of stripper operation. Optional hinged door(s) allows tray access without the need to fully remove hatch(s). 2.2.1.3 The air stripper shell dimension shall be no smaller than the size specified on the attached Data Sheet. 2.2.1.4 The shell shall be of one piece welded construction; to minimize seal and gasket requirements, 5 sides shall be imperforate except for welded or flanged fittings used for air, liquid, or sensor connections. 2.2.1.5 The air stripper shall be equipped with integral sump, tray support tracks, and a high efficiency demister, plus an external sump gauge to allow visual observation of water level, plus a high efficiency demister. Demister shall effectively remove water droplets at air flow velocity greater than stripper blower maximum capacity. See Data Sheet for demister specifications.

2.2.1.6 Shell construction shall be of uncoated stainless steel; see Data Sheet for specific requirements. Construction must be suitable for all loads placed on shell, including but not limited to: loads resulting from internally supported parts, weight of operating liquid, piping, structural supports, internal or external pressure. 2.2.1.7 Shell design shall include mounting brackets suitable for holddown on a skid or floor, plus forklift cutouts and/or lifting lugs to allow the unit to be moved easily without damage. 2.2.2 Standard product design shall include removable sieve trays with the following specifications: 2.2.2.1 Trays shall be constructed of stainless steel with a slide-out design. See Data Sheet for full specifications. 2.2.2.2 Trays shall have latches designed to hold them in position on the shell slide tracks. 2.2.2.3 Trays shall include a mechanical flow control device which will regulate water volume in each tray, preventing air short circuiting. 2.2.2.4 Trays shall be supplied with engineered perforations, sized and located to maintain not less than the specified active area of optimum mass transfer (not including seal pot or downcomer area). See Data Sheet for full specification. 2.2.2.5 Design shall allow the option of purchasing a set of spare trays. (This option reduces system downtime by allowing operation to resume without a delay for tray cleaning. It may also permit easier tray cleaning -- i.e. by setting trays aside, calcium or iron fouling can dry on them so it can simply be cracked off.) 2.2.2.6 Design shall allow the option of purchasing two part trays. (This option reduces tray weight to allow easier removal during tray cleaning.) 2.2.3 Standard product design shall include piping connections. 2.3 OPERATION AND PERFORMANCE PARAMETERS 2.3.1 Stripper must be fully accessible for cleaning from front hatch only. Models 72.X and 96.X shall be fully accessible for cleaning from front and back hatches only.

2.3.2 Dry weight of individual trays or other removable components must not exceed 75 pounds (to allow one-person cleaning). Optional split tray design reduces maximum weight to 28 pounds. 2.3.3 Design shall require a maximum clearance not to exceed 4 at the rear and at least one side to allow placement in a corner without interfering with operation or cleaning. (For models 72.X and 96.X, this requirement is for one side only.) 2.3.4 Air to water ratio shall be kept in accordance with generally accepted chemical engineering practice as defined in Perry s Handbook; see Data Sheet for exact specifications. 2.3.5 Design flow shall be as specified on attached Data Sheet or on Performance Model Run printout. 2.3.6 Design temperature (water and air) and site altitude shall be as specified on attached Data Sheet or on Performance Model Run printout. 2.3.7 Design influent and effluent concentrations shall be as specified on attached Data Sheet or on Performance Model Run printout. 2.3.8 Air stripper shall be installed in accordance with manufacturer s recommendations, including but not limited to the following: 2.3.8.1 If an exhaust stack is installed to provide venting of the stripped air, the size of the exhaust shall be in accordance with manufacturer s recommendations (see Data Sheet for specification). 2.3.8.2 If air stripper exhaust is to be passed through a subsequent treatment device (such as vapor phase activated carbon), back pressure shall not exceed manufacturer s recommendations (see Data Sheet for specification). If design post-treatment back pressure exceeds this level, a suitable auxiliary blower consistent with manufacturer s recommendations must be installed.

ENGINEERING DATA SHEET 1 AIR STRIPPER (REMOVABLE TRAY) GENERAL PRODUCT DATA Model Max. Dry Oper. Area required Active Nom. *Oper. No. Flow Weight Weight Dimension Trays per tier Area air flow Clearance (GPM) (lbs) (lbs) ( DxWxH) (no x lbs) (sq ft) (cfm) (inches) 4.4 1-50 630 985 29 x 27 x 82 4 x 29 2.8 210 27 4.6 1-50 780 1,219 29 x 27 x 102 6 x 29 2.8 210 27 6.4 1-65 790 1,285 37 x 27 x 82 4 x 40 3.8 320 35 6.6 1-65 978 1,591 37 x 27 x 102 6 x 40 3.8 320 35 8.4 1-75 955 1,580 49 x 27 x 82 4 x 50 5.6 420 47 8.6 1-75 1,182 1,956 49 x 27 x 102 6 x 50 5.6 420 47 12.4 1-120 1,165 2,105 73 x 27 x 82 4 x 60 8.8 600 71 12.6 1-120 1,442 2,606 73 x 27 x 102 6 x 60 8.8 600 71 16.4 1-150 1,625 2,870 49 x 52 x 84 8 x 50 11.1 850 47 16.6 1-150 2,011 3,553 49 x 52 x 104 12 x 50 11.1 850 47 24.4 1-250 2,100 3,980 73 x 52 x 84 8 x 60 17.5 1300 72 24.6 1-250 2,599 4,926 73 x 52 x 104 12 x 60 17.5 1300 72 36.4 1-375 3,200 6,085 73 x 100 x 104 12 x 60 26.25 1900 72 36.6 1-375 3,900 7,532 73 x 100 x 124 18 x 60 26.25 1900 72 48.4 1-500 5,000 12,500 73 x 120 x 104 16 x 60 35 2600 72 48.6 1-500 5,500 13,000 73 x 120 x 124 24 x 60 35 2600 72 72.4 1-750 6,400 14,600 146 x 100 x 104 24 x 60 52.5 3800 2x72 72.6 1-750 7,800 15,100 146 x 120 x 124 36 x 60 52.5 3800 2x72 96.4 1-1000 11,000 25,000 146 x 124 x 104 32 x 60 70 5200 2x72 96.6 1-1000 11,500 30,000 146 x 124 x 124 48 x 60 70 5200 2x72 * Additional clearance required for tray removal. Models 96 and 72 need tray removal clearance at front and back. One side requires space for piping, blower, appurtenances, etc. (depends on design layout).

INSTALLATION DATA Model +Water +Water Air *Exhaust Water #Max. back Inlet Outlet Inlet Stack Size drain pressure ( FNPT) ( FNPT) ( OD pipe) (inches) ( FNPT) ( H 2 O) 4.4 2 3 4.63 6.63 1 10 4.6 2 3 4.63 6.63 1 5 6.4 3 3 4.63 6.63 1 10 6.6 3 3 4.63 6.63 1 5 8.4 3 4 4.63 6.63 1 10 8.6 3 4 4.63 6.63 1 5 12.4 4 4 6.63 6.63 1 10 12.6 4 4 6.63 6.63 1 5 16.4 4 4 6.63 8.63 1 10 16.6 4 4 6.63 8.63 1 5 24.4 4 6 8 flange 8.63 1 10 24.6 4 6 8 flange 8.63 1 5 36.4 8 6 10 flange 12 flange 1 5 36.6 8 6 10 flange 12 flange 1 5 48.4 8 8 10 flange 12 flange 1 5 48.6 8 8 10 flange 12 flange 1 5 72.4 8 10 12 flange 16 flange 1 5 72.6 8 10 12 flange 16 flange 1 5 96.4 8 10 12 flange 16 flange 1 5 96.6 8 10 12 flange 16 flange 1 5 + Models 36.X and larger use flange inlet and outlet connections * Minimum recommended nominal diameter of exhaust stack, if added # Maximum clean-tray exhaust back-pressure allowed without auxiliary blower

ENGINEERING DATA SHEET 2 AIR STRIPPER (REMOVABLE TRAY) REF ITEM SPECIFICATION (S) 1.3.1.3 Standard Sump pressure gauge: Differential pressure gauge, diaphragm-actuated dial type, 0-50 H 2 O range Sump sight gauge: Clear tube connected to sump water drain for visual sump water level monitoring Recommended options Sump high level switch: PVC jacketed SPST, 20VA Sump low pressure switch: SPST, 15VA, EXP Options High pressure switch: SPST, 15VA, EXP Air flow sensor: Pitot tube Air flow gauge: Differential pressure gauge, diaphragm-actuated dial type: 0-0.25 H 2 O range (6.X models) 0-0.5 H 2 O range (4.X, 8.X) 0-1 H 2 O range (12.X, 24.X) 0-2 H 2 O range (16.X) Liquid flow meter: (check if included) Digital in-line or mechanical brass nutating disk Pump on/off switch: PVC jacketed SPST, 20VA 2.2.1.5 Demister: High efficiency polypropylene (98% removal of droplets @ 10 microns) 2.2.1.6 Shell material (check one): 304 stainless steel (uncoated) Wall thicknesses: 10 GA (0.14 ) 2.2.2.1 Tray material: 304 stainless steel 2.3.4 Minimum air/water ratio: 50:1 2.3.5 Design flow for this spec: GPM Or see attached 2.3.6 Design temperature for this spec: F (water) Or see attached F (air) Or see attached Site altitude: feet above sea level Or see attached 2.3.7 Design concentrations for this Contaminant Influent ppb Effluent ppb spec: