Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM

Similar documents
DISPLACEMENT VENTILATION

Compliance Evaluation: ASHRAE Standard Ventilation for Acceptable Indoor Air Quality

Ventilation. Demand-controlled ventilation (DCV) Demand-Controlled. With ASHRAE Standard Based

Technical Report #1 ASHRAE Standard 62: Ventilation Compliance Evaluation

The Palestra Building London, England

Mechanical Technical Assignment One ASHRAE Standard Compliance Evaluation

YORK UNITIZED ENERGY RECOVERY VENTILATOR (ERV) Superior air-flow 300 6,200 CFM

Underf loor For Schools

IAQ & Energy Impact of Exhaust Air Transfer Ratio

Changes to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE

How to Reduce Energy Use in Your Labs by Up to 50%

ASHRAE Standard 62.1 Ventilation Report

Evaluation of Underfloor Air Distribution

Calculating the Efficiency of Energy Recovery Ventilation and its Effect on Efficiency and Sizing of Building HVAC Systems

Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D.

DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS

Update to ASHRAE Ventilation Standards. William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA

2019 Title 24 Codes & Standards Enhancement (CASE) Proposal Nonresidential Ventilation & Indoor Air Quality (IAQ)

LEED And Your Indoor Environment

Energy Recovery Ventilation Equipment

ASHRAE 62.2: What s New in 2016

Walter Reed National Military Medical Center Bethesda, MD

ACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features

Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies.

A. The project is intended to achieve LEED Certification at the Silver Level per the U.S. Green Building Council LEED for Schools 2007 rating system.

Application of Advanced Energy Technologies

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Ceiling Radiant Cooling Panels

PRESENTATION BY: Sean P. Murray Energy/Facility Use Manager St. Lucie County Public Schools. Art Munns Senior Project Engineer OCI Associates, Inc.

MEP's Letter of Assurance

IMPACT OF THE SEMCO ANTI-STICK FACE COATING ON THE COLLECTION AND CLEANING OF ENVIRONMENTAL TOBACCO SMOKE FROM THE WHEEL SURFACE RESEARCH FINDINGS

MEP's Letter of Assurance

LEED v4 Building Design and Construction Quiz #8 EQ

Progressive Design Concepts for the Evolving Learning Environment

LEED. Leadership in Energy and Environmental Design

NJ AIHA CIH Review Industrial Ventilation

Product Data. 50TC Cooling Only/Electric Heat Packaged Rooftop 15 to 25 Nominal Tons. (Unit shown with optional economizer.

Indoor Air Quality (IAQ) Tailoring Lease Specifications S-852

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms

Energy Recovery Application Manual

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

ASHRAE STANDARD Ventilation for Acceptable Indoor Air Quality

NOTE: Some guidance on a performance approach to natural ventilation systems design is provided in the Supplement to this Standard.

Milwaukee, WI. Darron Rempel

Do European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering

Product Data. (Unit shown with optional economizer.)

MEP Engineer's Letter of Assurance


WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia

Do Risks Outweigh Potential Rewards?

Development of Design Guidance for K-12 Schools: From 30% to 50% Energy Savings

LEED 2009 for New Construction and Major Renovations

CARRIER PRODUCTS AND LEED CERTIFICATION

CERTIFICATE OF FIELD VERIFICATION & DIAGNOSTIC TESTING (Page 1 of 8)

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Fresh Air Ideas SUPPORTING GREEN INITIATIVES WITH INNOVATION

Designing Air-Distribution Systems To Maximize Comfort

South Carolina Society for Hospital Engineers

Walter Reed National Military Medical Center Bethesda, MD

Articles. Figure 2. Typical set-up of personalized ventilation system.

Chilled Beams. The new system of choice?

In the school year, U.S. K-12 public schools provided instruction to over 46 million

EES Energy Efficient Systems Rotary Screw Air Compressors kw Horsepower

Analysis 2: Mechanical System

THERMA-FUSER VARIABLE AIR VOLUME DIFFUSER SYSTEMS

ASHRAE 62.1 Outside Air Reduction

Product Data. 48TC Gas Heat/Electric Cooling Packaged Rooftop 15 to 25 Nominal Tons. (Unit shown with optional economizer.) C09248

2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment

McCarran International Airport Terminal 3

TAB (test-adjustbalance) in the Sustainable Environment & Lessons Learned. HVAC Excellence Conference & Training March 17-18, 2013 Tom Hanlon

Do-It-Yourself Energy Audit. Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering

OEM WHEEL EQUIPMENT ENTHALPY RECOVERY WHEELS INDOOR AIR QUALITY VENTILATION ENERGY RECOVERY

OEM WHEEL EQUIPMENT ENTHALPY RECOVERY WHEELS INDOOR AIR QUALITY VENTILATION ENERGY RECOVERY

Rebel commercial packaged rooftop systems

HELPING HVAC PROFESSIONALS TAKE THE LEED ACHIEVING LEED CERTIFICATION

Advanced Variable Air Volume Control Sequences. Steven T. Taylor, PE Taylor Engineering Alameda, CA

Paul W. Francisco University of Illinois at Urbana Champaign

Building & Fire Appeals Board

Italcementi Center for Research and Innovation

Integration of Mechanical System Redesign. Geothermal Heat Pumps with DOAS

Modeling for LEED. Refer to Additional LEED credits on page 6 90 for a list of credits TRACE 700 may help to achieve.

Lab Ventilation Safety & Energy Efficiency. Agenda & Objectives

Analysis of the air conditioning systems in a blown films manufacturing plant in the southeastern United States

LIFE CYCLE COST OF DISPLACEMENT VENTILATION IN AN OFFICE BUILDING WITH A HOT AND HUMID CLIMATE

I S O. Eco-Smart Energy Recovery Ventilator

Rhode Island Commercial Codes FAQs

The ASHRAE Energy Code: How it Will Affect Your Projects

VENTILATION REQUIREMENTS TO PREVENT PIT AIR UP-DRAFTING IN

Using CFD to Wring Out Energy Efficiency in Laboratory Settings

780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016

CASE STUDY. Two Dogs and Two Cats Insufficient Air Exchange with High CO2

Errata Sheet. LEED for Schools Reference Guide First Edition for the document titled:


Construction Indoor Air Quality (IAQ) Management Plan

Chilled Water Plant Redesign

Central Chiller Plants

Centre for Sustainability of the Built Environment

THE REVISION OF STANDARD 62: WHAT A DIFFERENCE A DECADE MAKES

Research Analysis: Building Envelope and LEED Credits Introduction

Transcription:

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard 62.1-2010 By KlasC. Haglid, P.E., R.A., CEM 1

Klas C. Haglid, P.E., R.A., CEM - Bio ASHRAE Distinguished Service Award 2011 ASHRAE Handbook, HVAC Applications and Management, Chapter 37, Author, Klas C. Haglid P.E. R.A. ASHRAE Standard 189.1, Corresponding Member GPC 32P -Sustainable, High Performance Operations & Maintenance, Voting Member, Contributing, Co-Author Technical Committee 5.5 -Air-To-Air Energy Recovery, Handbook Subcommittee Chairman, Past Chairman Technical Committee 7.6 - System Energy Utilization, Voting Member Technical Committee 7.8 -Owning and Operating Costs of Commercial Buildings, Past Chairman ASHRAE Standard 84-1991R, Voting Member Reviewed draft of ASHRAE Standard 84-1991R and provided engineering details for efficiency calculations. 2

Objectives Complying with ASHRAE Std. 62.1-2010 to improve IAQ while increasing energy efficiency ASHRAE Std. 90.1 can be accomplished with: Displacement Ventilation Demand Controlled Ventilation Energy Recovery Ventilators Variable Speed Drives 3

ASHRAE Std. 62.1-2010 Ventilation for Acceptable Indoor Air Quality How to determine minimum prescriptive ventilation rates How to use Demand Side Ventilation to meet ASHRAE Standard 62.1-2010 4

Definitions acceptable indoor air quality: air in which there are no known contaminants at harmful concentrations as determined by cognizant authorities and with which a substantial majority (80% or more) of the people exposed do not express dissatisfaction. ASHRAE Standard 62.1-2010 pg. 3 5

Definitions Demand Control Ventilation (DCV): any means by which the breathing zone (Vbz) can be varied to the occupied space or spaces based on the actual or estimated number of occupants and/or ventilation requirements of the occupied zone ASHRAE Standard 62.1-2010 pg. 4 6

6.1.1 Ventilation Rate Procedure The following procedure for determining the minimum prescriptive ventilation rates can be used on any zone type. 6.1.1 Takes into consideration: Space type Number of Occupants Floor Area Typical contaminant sources and source strength 7

Ventilation Rate Procedure Breathing Zone (bz) Outdoor Airflow (OA) V bz = R p P z + R a A z where: R p = outdoor airflow rate required per person as determined from Table 6-1*. P z = zone population R a = outdoor airflow rate required per unit area as determined from Table 6-1*. A z = zone floor area *Table 6-1 from ASHRAE Standard 62.1-2010 8

Two Parts to the Formula Type and size of space? How many people? 9

First Part of the Equation Rate Per Person Rp Zone Pop Pz cfm for people ASHRAE Std. 62.1 2010 10

Second Part Rate Per Person Rp Zone Pop Pz cfm for People Rate Per Area Ra Zone Area Az cfm for Area 11

Combined cfm for People Vbz cfm for Area Breathing Zone Outdoor Airflow 12

Office Example What is the prescriptive design for outdoor air (cfm) of a 1500 square foot office with 12 occupants? Eq6-1 : V bz = R p P z + R a A z Design inputs for office space: Pz= 12 people Az= 1,500 square feet of floor area V bz = (5x12) + (.06 x 1500) = 60 + 90 = 150 cfm 13

School Example What is the prescriptive design for outdoor air (cfm) of a 1100 square foot classroom with 30 students? Eq6-1 : V bz = R p P z + R a A z From Table 6-1: R p = 10 cfm/person R a = 0.12 cfm/ft 2 Design inputs from school classroom project for ventilation: P z = 30 people A z = 1100 square feet V bz = (10 x 30) + (.12 x 1100) = 300 + 132 = 432 cfm 14

General Manufacturing Example (Excludes Heavy Industrial and processes using chemicals) What is the prescriptive design for outdoor air (cfm) of a 50,000 square foot coat hanger production facility with 20 machinists? Eq6-1 : V bz = R p P z + R a A z From Table 6-1: R p = 10 cfm/person R a = 0.18 cfm/ft 2 Increase Production facility input data: P z = 20 people A z = 50,000 square feet of floor area V bz = (10 x 20) + (.18 x 50000) = 200 + 9,000= 9,200 cfm Notice the Area outdoor air rate (Ra) increased for a manufacturing facility. 15

Ventilation Rate Procedure Zone Outdoor Airflow V oz = V bz /E z (E z ) The zone air distribution effectiveness shall be determined using ASHRAE Std. 62.1-2010, Table 6-2. (Partial Table) 16

Methods of Providing Outdoor Air to Zone Dilution Ventilation Displacement Ventilation 17

Dilution Ventilation It s important to design ventilation system to have maximum air distribution. This will help eliminate dead space and short circuiting of air flow Poor distribution of air across classroom breathing zone 18

Dilution Ventilation Typical in U.S. construction Outdoor air is brought into space and dilutes contaminant concentrations in the space. Adequate air mixing 19

Air Mass Exchange Diagram shows good air circulation providing fresh air on one end of room and exhaust pulling air out on the other end to maximize removing contaminant concentrations by displacing room temperature air across a Breathing Zone 20

Displacement Ventilation (DV) Uses natural convection to provide Buoyancyassisted forced ventilation Effectively removes contaminants from people and objects locally ASHRAE Std. 62.1-2010 Table 6-2 recognizes DV to be 1.2 times more effective than traditional dilution ventilation Some applications measured DV to be 2 to 2.5 more effective than traditional dilution ventilation 21

Displacement Ventilation Using displacement ventilation and then measuring air quality of the space is an effective way to improve IAQ Often times, balancing airflow according to how effective the displacement ventilation system is can reduce required airflow by 50% This saves energy and reduces latent loads Can be achieved with Variable Speed Drives (VSD) 22

Demand Controlled Ventilation (DCV) any means by which the breathing zone outdoor airflow (Vbz) can be varied to the occupied space or spaces based on the actual or estimated number of occupants and/or ventilation requirements of the occupied zone. ASHRAE Std. 62.1-2010 pg. 4 23

Example of DCV Methods Fan Relays ERV EA SOA CO2 Sensor comes on over 700 ppm and turns off under 600 ppm People ERV- Energy Recovery Ventilator EA- Exhaust Air SOA- Supply Outside Air 24

DCV CO 2 concentrations in outdoor air generally range from 300 to 500 ppm ASHRAE std. 62.1 2007 and 2010 recognize 700 ppm of CO 2 above outdoor ambient levels or 1000 to 1200 ppm to be acceptable air quality for an indoor space. Reference page 37 of Appendix C Displacement Ventilation with CO 2 Demand Controlled Ventilation properly engineered and installed will keep CO 2 levels well below 1000 ppm DCV can reduce runtime from 168 hours per week to 30 hours per week for a classroom. That is an 82% reduction in runtime. 25

Fan Affinity Laws Assuming fan diameter and air density are constant Eq(1) : Eq(2) : Eq(3) : 26

Fan Affinity Laws Eq(1) : 100 cfm @ 100 rpm 200 cfm @ 200 rpm 27

Fan Affinity Laws Eq (2) : 100 cfm @ 100 rpm 200 cfm @ 200 rpm Pressure is squared 0.3 WC @ 100 rpm 0.9 WC @ 200 rpm 28

Fan Affinity Laws Eq (3) : 0.3 WC @ 100 rpm 0.9 WC @ 200 rpm Energy Expended is Cubed 0.3 WC @ 1 BHP 0.9 WC @ 8 BHP 29

Example What is the percent difference in BHP required to run a ventilation system if alternative 2 has a 50% increase in static pressure from alternative 1? Alternative 1 Conditions: CFM = 8,000 SP = 1 in wg BHP = 5 RPM = 1000 30

Example Continued Rearranging Eq(2): RPM 2 = SP 2 /SP 1 x RPM 1 RPM 2 = 1.5/1 x 1000 = 1225 Eq(3): BHP 2 = BHP 1 x ( RPM 2 /RPM 1 ) 3 BHP 2 = 5x ( 1225/1000) 3 = 9.2 BHP 9.2-5/5 = 84% Increase A 50% increase in static pressure results in an 84% increase in power consumption 31

Not All ERVs Are the Same ERV Features to Compare: Airflow Arrangement Thermal Effectiveness Pressure Drop Fan Efficiency Maintenance Sound Levels 32

Heat Exchanger Airflow Arrangement ASHRAE states: Counter-flow heat exchangers are theoretically capable of achieving 100% Sensible Effectiveness* Parallel Flow heat exchangers: 50% (Max) Cross-flow heat exchangers and Enthalpy Wheels: 50-75% (Max) *Note: Source: 2012 ASHRAE Handbook HVAC Systems and Equipment, Chapter 26: Air-to-Air Energy Recovery Equipment. 33

High Efficiency Fans Typical fan efficiency can range from 5 to 10 W/cfm A high efficiency fan can be expected to be approximately 0.2 W/cfm The EER of an ERV s performance is formulated by the BTUs recovered divided by the watts of power consumed from the fan energy. EER = BTUs Recovered Watts of Fan Power 34

Thermal Efficiency vs. Overall Efficiency 160 140 120 100 80 60 40 20 0 Effectiveness (%) Fan Power (W) EER (BTU/W) High Eff. ERV Typical ERV Typical ERV has an EER of around 11. High efficiency ERV can be well above 120. Combining premium Efficiency fans with High efficiency ERVs and a low static pressure system can yield great energy savings 35

Efficiency = Payback A short term savings in build cost is outweighed by sustainable gains over present consumption. 36

Maintenance Costs are Essential There s more to a product than its initial costs and efficiency Maintenance and efficiency equal long term and continuous ROI Corrosion resistant equipment Minimal moving parts Low static pressure Appropriate filters and size Efficient fans Location/Operation 37

Tools to Meet ASHRAE Std. 62.1 and Improve IAQ While Increasing Energy Efficiency, ASHRAE Std. 90.1 Displacement Ventilation Demand Controlled Ventilation CO2 controls or other contaminant monitoring sensors ERV Counter flow heat exchanger Low Pressure Drops High efficiency fans Variable Speed Drives Air balancing Better control 38

39