Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat

Similar documents
Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

Revue des Energies Renouvelables Spécial ICT3-MENA Bou Ismail (2015) Numerical study of a single effect ejector-absorption cooling system

Energy and Buildings

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET

Ejector Expansion Refrigeration Systems

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

ANALYSIS OF REFRIGERATION CYCLE PERFORMANCE WITH AN EJECTOR

Design of a Solar-Driven Ejector Cooling System

Copyright 2012 Neal D. Lawrence

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT

PAPER-I (Conventional)

ANALYSIS OF STEAM EJECTOR BY USING COMPUTATIONAL FLUID DYNAMICS

Review Questions for the FE Examination

CONTROL VOLUME ANALYSIS USING ENERGY. By Ertanto Vetra

Chapters 5, 6, and 7. Use T 0 = 20 C and p 0 = 100 kpa and constant specific heats unless otherwise noted. Note also that 1 bar = 100 kpa.

ES Fluid & Thermal Systems Page 1 of 6 STEAM TURBINE LABORATORY

Investigations Of Low Pressure Two-Phase Steam- Water Injector

Chapter 8. Vapor Power Systems

Solar Absorption Aqua-Ammonia Absorption system simulation base on Climate of Malaysia

Eng Thermodynamics I: Sample Final Exam Questions 1

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.

A Review on Performance of Air Conditioning System using Two Phase Ejector

Chapter 10 VAPOR AND COMBINED POWER CYCLES

Chapter 9: Applications of the Laws of Thermodynamics

Applied Thermodynamics for Marine Systems Prof. P. K. Das Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

NUMERICAL INVESTIGATION OF AN R744 LIQUID EJECTOR FOR SUPERMARKET REFRIGERATION SYSTEMS

flow work, p. 173 energy rate balance, p. 174 nozzle, p. 177 diffuser, p. 177 turbine, p. 180 compressor, p. 184 (4.4b) p. 166

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

LECTURE-15. Ideal Reverse Brayton Cycle. Figure (6) Schematic of a closed reverse Brayton cycle

Second Law of Thermodynamics

Application of Exergy Analysis. Value and Limitations

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS

Hydrogen oxygen steam generator integrating with renewable energy resource for electricity generation

CFD Analysis of Nozzle Exit Position Effect in Ejector Gas Removal System in Geothermal Power Plant

20/06/2011 Seminar on Geothermal Exploitation Santiago de Chile

Application of Two Stage Ejector Cooling System in a Bus

Chapter 6 THE SECOND LAW OF THERMODYNAMICS

Low-Grade Waste Heat Recovery for Power Production using an Absorption-Rankine Cycle

EFFECT OF THE NOZZLE EXIT POSITION ON THE EFFICIENCY OF EJECTOR COOLING SYSTEM USING R134A

In this lecture... Solve problems related to First law of thermodynamics for closed and open systems Heat engines Refrigerators and heat pumps

Fundamental Investigation Of Whole-Life Power Plant Performance For Enhanced Geothermal Systems

Feedwater Flow Measurement with Venturi and Comparison to the other Parameters in NPP Krško

Performance Benefits for Organic Rankine Cycles with Flooded Expansion

Experimental investigations on impaction pin nozzles for inlet fogging system


B.Tech. Civil (Construction Management) / B.Tech. Civil (Water Resources Engineering) B.Tech. (Aerospace Engineering) Term-End Examination

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis

EXPERIMENTAL VALIDATION AND DESIGN STUDY OF A TRANSCRITICAL CO 2 PROTOYTPE EJECTOR SYSTEM. S. ELBEL, P. HRNJAK (a) ABSTRACT 1.

A review on Present development in refrigeration jet ejector system

Engineering Thermodynamics

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

Multi-Variable Optimisation Of Wet Vapour Organic Rankine Cycles With Twin-Screw Expanders

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM IV (ME-41, 42,43 & 44)] QUIZ TEST-1 (Session: )

Investigation of New Low-GWP Refrigerants for Use in Two-Phase Evaporative Cooling of Electronics

A COMBINED ORGANIC RANKINE CYCLE-HEAT PUMP SYSTEM FOR DOMESTIC HOT WATER APPLICATION

CFD on Small Flow Injection of Advanced Accumulator in APWR

Estimation of Boil-off-Gas BOG from Refrigerated Vessels in Liquefied Natural Gas Plant

Heat Engines and Refrigerators

Steam balance optimisation strategies

Refrigeration Cycle With Two-Phase Condensing Ejector

Andy Schroder Mark Turner University of Cincinnati, Cincinnati, OH, 45221, U.S.A. Abstract

Low temperature cogeneration using waste heat from research reactor as a source for heat pump

ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE

POWER RECOVERY IN FLOATING LNG REGASIFICATION PLANTS

[4163] T.E. (Mechanical) TURBO MACHINES (2008 Pattern) (Common to Mech. S/W) (Sem. - II)

G. Spazzafumo Department of Industrial Engineering, University of Cassino, Italy

PERFORMANCE ANALYSIS OF ORGANIC RANKINE CYCLES USING DIFFERENT WORKING FLUIDS

St.MARTIN S ENGINEERING COLLEGE Dhulapally,Secunderabad,

EFFECT OF AMBIENT TEMPERATURE, GAS TURBINE INLET TEMPERATURE AND COMPRESSOR PRESSURE RATIO ON PERFORMANCE OF COMBINED CYCLE POWER PLANT

DESIGN ANALYSIS OF A REFRIGERATED WAREHOUSE USING LNG COLD ENERGY

OVERALL EFFICIENCY CONSIDERATION OF PNEUMATIC SYSTEMS INCLUDING COMPRESSOR, DRYER, PIPE AND ACTUATOR

Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant

Performance Comparison of Air-source Heat Pumps Using Economizer Vapor Injection and Internal Heat Exchanger in Cold Regions

Problems 2-9 are worth 2 points each. Circle T or F as appropriate for problems 6-9.

CHAPTER 4 STEAM TURBINE and CYCLE HEAT BALANCE

MCG THERMODYNAMICS II. 22 April 2008 Page 1 of 7 Prof. W. Hallett

Investigation of Separator Parameters in Kalina Cycle Systems

Holdup measurement in a gas-liquid ejector for a sodium chloride-air system

Solar Flat Plate Thermal Collector

Consider a simple ideal Rankine cycle with fixed turbine inlet conditions. What is the effect of lowering the condenser pressure on

SUMMER 15 EXAMINATION

Study on the heat transfer characteristics of an evaporative cooling tower B

Secondary Systems: Steam System

Hydraulics Laboratory Experiment Report

Exergy analysis of a flat plate solar collector

Heat Pump Efficiencies simulated in Aspen HYSYS and Aspen Plus

Investigations of N 2 O Transcritical Refrigeration Cycle Using Dedicated Mechanical Subcooling. Sanjeev Kumar 1 and Dr. D.K.

Conceptual Design of Nuclear CCHP Using Absorption Cycle

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014)

Alexander Rattner MEAM-402 HW 2

Refrigeration System with Booster Hot Gas Bypass in Tropical Climate

ENGINEERING OF NUCLEAR REACTORS OPEN BOOK FINAL EXAM 3 HOURS

ELECTROTECHNOLOGIES FOR ENERGY END-USES: APPLICATION OF MVR TO FOOD INDUSTRIES

Improvement of distillation column efficiency by integration with organic Rankine power generation cycle. Introduction

Exergy analysis of transcritical carbon dioxide refrigeration cycle with an expander

THERMODYNAMIC ANALYSIS OF R134A DMAC VAPOR ABSORPTION REFRIGERATION (VAR) SYSTEM

COPING WITH VACUUM Jim Lines, Graham Corp., USA, highlights the importance of ejector systems in urea plants.

SELECTION OF WORKING FLUID AND EXERGY ANALYSIS OF AN ORGANIC RANKINE CYCLE

Transcription:

HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat Hiroaki Yamanaka* and Masafumi Nakagawa *Author for correspondence Department of Mechanical Engineering, University of Toyohashi University of Technology, Aichi, Japan, E-mail: yamanaka@nak.me.tut.ac.jp ABSTRACT In the near future the usage of waste heat in houses will be increased. The development of refrigeration system using waste heat is particularly needed for summer season consumptions. The ejector cycle can directly convert the thermal energy into the compression mechanical energy. Moreover, water which is one of the cleanest refrigerants can be used in the ejector cycle. As the steam ejector has been researched [1-3] as air conditioning system, the huge energy needed for large latent heat for water. We propose that the high-speed steam and water mixture, so-called two-phase flow, can be utilized instead of steam. It is theoretically shown that the heat need for this system will be reduced by the latent heat of hot water in two-phase flow, if the two-phase in the ejector flow has the same potential of acceleration and compression as steam. And the nozzle efficiencies for the two-phase flow of water are also obtained by the experiment. INTRODUCTION Nowadays, saving the energy became one of the most important issues in the world since the fossil fuel will dry up in the not so long future and especially in Japan, the nuclear energy may be unavailable after the Great East Japan Earthquake. Then the clean energy such as the solar panel and the fuel cells are expected to be introduced into a large amount of houses for the electrical source. As the energy conversion efficiency of those power systems is not so high, the low temperature waste heat will be generated in houses. The low level energy must be recovered to increase the net efficiency of the power systems. In winter season, the low level waste heat in houses is available for the house heating or for the hot water supply. On the other hand, there is no need for the low temperature heat in summer time. But, if this heat had been used by air conditioning system, the problem would be solved. One solution is the ejector compression refrigeration cycle [4] which enables us to covert the low level heat into the mechanical compression energy. If the hot water is used for the refrigerant, the environment load will be reduced more because water is friendly, safe and coexistent material for human being, as the house cooling system will be widely dispersed over our society. While in usual air conditioning system, electric power is used to compress the refrigerant vapour, high pressure steam heated by the waste heat in the water ejector system are accelerate to the supersonic state and the kinetic energy of the steam is used. Although the energy conversion efficiency is low, this system has a possibility to prevail because the originally abandoned waste heat changes to the useful energy. In order to improve this system, we propose to utilize the high-speed two-phase flow instead of steam. A large amount of heat must be needed to obtain steam for latent heat of water. The p-h diagrams for the ejector refrigeration system are drawn in Figure 1. This shows that the thermal energy of high temperature and high pressure water is converted into the kinetic energy to compress the low pressure and low temperature vapour. If the acceleration and compression by two-phase flow is possible in the ejector, the heat need for this system will be reduced by the latent heat of hot water in two-phase flow. Figure 1 P-h diagram of water 933

OBJECTIVE The steam ejector refrigeration cycle using water as refrigerant had been studied. The huge energy, however, is necessary for saturated water to change into vapour state to use this cycle. Two-phase flow ejector cycle can save more energy compared with steam ejector cycle. There is almost no research about the nozzle of two-phase flow ejector for water. The object of present study is to obtain the performance of the water two-phase flow nozzle. From the results of this paper, optimized inlet conditions will be obtained and will apply to the design of two-phase ejector refrigeration system. NOMENCLATURE w [W/kg] Specific work needed for compression h [J/kg] Specific enthalpy s [J/(kgK)] Entropy q [W/kg] Specific heat p [Pa] Pressure u [m/s] Velocity A [m 2 ] Area G [kg/s] Mass flow rate z [m] Coordinate along flow from the throat x [-] Quality g [-] Mass flow ratio COP [-] Coefficient Of Performance Figure 2 Ejector refrigeration system of this study This turns the product of the thermal efficiency of engine and the COP of the air-conditioner refrigeration cycle if there is no friction loss at the connection rod between the engine and compressor. It is assumed that the pump, evaporators and condenser are ideal. The inlet condition of the pump denoted by under suffix 1, and outlet 2. The pumping work for unit mass flow is written as the enthalpy difference. Special characters [kg/m 3 ] Subscripts s d s c ex th Density Saturated state (for Pressure) Driving flow Suction flow Critical condition Experimental result Isentropic Homogeneous Equilibrium model Where h is enthalpy and s entropy. The outlet of high temperature evaporator is denoted by 3. The thermal energy absorbed is also expressed by enthalpy gain. COEFFICIENT OF PERFORMANCE The schematic diagram of the ejector refrigeration system is shown in Figure 2. This cycle consists of two loops. One is the loop from condenser to pump, high temperature evaporator, ejector and then back to condenser. The other is the loop from condenser to expansion valve, low temperature evaporator, ejector, back to condenser. The high temperature evaporator works by the waste heat, and the low temperature evaporator acts as the heat sink of refrigeration cycle. The former loop is similar to the conventional steam engine cycle, and the latter to vapour compression refrigeration cycle. Then the ejector operates as both the turbine in thermal engine and the compressor in air-conditioner. We calculate the thermal conversion efficiency of system as the following equation of Coefficient of Performance, COP. The pressure must lower than the saturation pressure of waste heat (100 ), but we use equal temperature for ideal case, where the saturation pressure ( ) is the function of temperature,. The inlet and outlet of low temperature of evaporator are denoted by 7 and 8, respectively. The same equations are obtained as equation (2). is equals to (10 ) which is saturation pressure of air-conditioner. The point between outlet of the diffuser and the inlet of condenser is denoted by 6. At the condenser, is released to the atmosphere. Then is set to (40 ) from the temperature of atmosphere. The process in the expansion valve is isenthalpic as usual assumption. 934

COP The ejector is supposed to be divided into four parts. They are the driving nozzle, the suction nozzle, the mixing section and the diffuser. The process in nozzles, mixing and diffuser is assumed to be ideal and then isentropic. We denote outlet of the driving and the suction nozzle and mixing section as 4, 9 and 5, respectively. And the pressure is decided as the COP of this system obtains the maximum value. The calculated relationship between the qualities at inlet of the ejector and the COP of two phase flow ejector as water refrigerant is shown in Figure 3. As mentioned above, the temperature of waste heat, atmosphere and air-conditioner is set to 100, 40 and 10 Figure 3 indicates that the COP gets higher with the decreasing quality and maximum value at considerably low quality. The best inlet quality for this condition is about 0.3. This means that the two-phase flow ejector system of the air conditioner using the waste heat is better solution compared with steam ejector. The kinetic energies at the inlets and outlet of ejector are neglected, because of the large inlet and outlet flow areas. In the mixing section, mass, momentum and energy conservations hold, and following equations are obtained. As the outlets of two nozzles are connected to mixing section, the relations below must be hold. And the mass flow rate of driving and suction flow is defined by and. All thermal parameters in this system are determined by the 2 variable and. For example, the area is determined by from the continuity equations and then finally by. In this system, the outlet pressure of the ejector must be saturation pressure of atmosphere. The ratio of mass flow rate is determined by this restriction. EXPERIMENTAL EQUIPMENT The experimental apparatus shown in Figure 4 consists of high pressure tank, heater, mixing section, two-phase flow nozzle, condenser and flow meter. The tank is covered by thick thermal insulator. The connecting tubes between apparatuses are covered by neoprene foam rubbers to prevent the thermal loss. The temperature inside the tank is regulated to be constant by the control unit. When the temperature inside the tank became steady at 150, saturated steam flows out from the upper side of the tank and saturated liquid from the lower side. Controlling the each flow by the valve, and coordinating the mass flux of the each phase, we obtain the arbitrary quality of the two-phase flow. The mass flow of saturated steam is measured by capillary flow meter and the total mass flow at outlet after the condenser is monitored by Coriolis flow meter in liquid state. Then the flow rate of saturated liquid can be calculated by subtracting the steam flow from the total flow. As a result, the quality at the nozzle inlet is obtained. As saturated steam has specific volume about 1000 times bigger than saturated liquid, the diameter of the liquid inlet at the mixing section is designed to be much smaller than that of the steam inlet in order to make the velocity of both flows same order. Moreover, from the standpoint of the inter phase heat transfer at the surface of the droplet, it is needed to make the diameter of droplet smaller to obtain larger heat transfer area per unit mass of liquid phase. 0.16 0.14 0.12 Temperature Control Unit On/Off Valve ΔP Con-di nozzle 0.08 0.06 flow regulating valve Mixing Section Tank Thermocouple On/Off Valve 0.04 0.02 Theoretical Curve 0.00 Quality at the Inlet of Ejector Thermocouple Heater On/Off Valve flow regulating valve Thermodac Computer Condenser Mass Flow Meter Figure 3 COP of the ejector refrigeration system Figure 4 Experimental Apparatus 935

Pressure [MPa] The testing convergent-divergent nozzle is designed for the flow rate of 3.0 g/s and the quality of 0.2 at the inlet of nozzle by considering the capacity of high pressure tank. For this case, the pressure inlet condition is 0.27 MPa, and temperature 130. Figure 5 shows the geometries of nozzle. It is made of Poly Ether Sulfone, which has low thermal conductivity. The geometries at outlet of the nozzle were designed as to apply to the two-phase flow ejector in the future. There are 5 pressure taps at convergent section and 4 at divergent section on the side wall of the nozzle. K type thermocouples are inserted into those pressure taps and pressure distributions are obtained to evaluate the performance of the nozzle. Furthermore, to carry out the visualization experiment of the flow in the nozzle, the side wall of another set is also made of Polycarbonate with no taps. correspond to the nozzle throat and z = 10 mm to nozzle outlet. When the outlet pressure became higher, the flat pressure distributions appear at the divergent section of the nozzle. But pressures at the convergent section are not changed by the outlet pressure. The flat pressure distribution is thought to be two-phase flow shock waves. Gas dynamics shock waves always have the steep increase in pressure, while two-phase flow shock waves has flat distribution because of large inertia of liquid phase [5]. 0.45 0.40 0.35 0.30 0.25 X=0.32 Gcex=5.02[g/s] Gcth=3.64[g/s] 0.20 0.15 0.05-10 0 10 20 30 40 Distance from throat [mm] Figure 6 Pressure Distribution Appearance of the shock wave To make sure the appearance of two-phase flow shock waves in the flow channel, the visualization experiment has done. The picture is taken by the digital camera while the outlet pressures of the nozzle are changed by the outlet valve. The typical pictures of this experiment are shown in Figure 7 to 9. The inlet condition for the quality is 0.83, and outlet pressures are, 0.15 and 0.25 MPa for Figure 7, 8, 9 respectively. Figure 5 Structure of two-phase flow nozzle EXPRIMENTAL RESULT The experiment is carried out by changing the quality of the nozzle inlet. The flow rate of steam and hot liquid from the high pressure tank and the static pressure distributions along the nozzle are measured for each experiment. The range of the inlet quality is 0.3-1.0. At quality of 0.3, the highest COP for the two-phase ejector is obtained by the theory in previous section. The pressure at the outlet of the nozzle is also changed to examine how high the pressure recovers behind the nozzle. The outlet pressure ranges from 0.09 to 0.22 MPa. Figure 7 Visualization Picture with MPa at outlet Dependence of the nozzle outlet pressure One of the most typical pressure distributions along the convergent-divergent nozzle are shown in Figure 6. z=0 mm Figure 8 Visualization Picture with 0.15 MPa at outlet 936

Correction of the critical flow in theory (G cex -G cth )/G cex [%] Pressure[MPa] Figure 9 Visualization Picture with 0.25 MPa at outlet There is no apparent change of the contrast by two-phase flow along the channel in Figure 7. But, the slight contrast change normal to flow direction by two-phase flow shock wave appears at the downstream of the nozzle in Figure 8. When the outlet pressure becomes higher in Figure 9, the contrast change by the two-phase flow wave intrudes into the divergent section of the nozzle. The positions of the contrast change in those figures coincide with the start point of flat pressure distributions in Figure 6. It is evident from this experiment that the two-phase flow shock waves have flat pressure distributions. Evaluation of the Critical Mass flow rate As shown in Figure 6, pressure profiles at the convergent section of the nozzle are not changed by the back pressure. This means that the mass flow rate is not varied with nozzle outlet pressure, because the velocity and the quality at the throat maintain at constant values. In fact, the measured flow rate by Coriolis flow meter is not changed. Therefore, the critical condition is established and we call this flow rate as critical mass flow rate. The critical mass flow rate does not depend on back pressure but depend on inlet conditions. This is also true from our experiment. The measured critical mass flow rate increased with the decreasing inlet quality. The dependence of quality is shown in Figure 10. G th is the mass flow rate predicted by Isentropic Homogenous Equilibrium theory. This model assumes the temperature and the velocity of each phase are equal to each other and the isentropic velocity of two-phase flow at the nozzle throat corresponds with the sound speed of two-phase flow. G ex is the measured mass flow rate by our experiment. The differences between G ex and G th are also increased by the inlet quality. Figure 10 indicates that the non-equilibrium phenomena between phases are increased at small inlet quality. The results of our experiment shown in Figure 6 are well agreed with the study of Isbin et al., Starkman et al. and Akagawa [6]. It means the flow of this experiment could be considered as the homogeneous flow. The pressure distribution for different inlet quality Figure 11 shows the static pressure distribution in the nozzle when the qualities at inlet were arbitrary changed with a fixed the pressure at outlet. The solid lines in Figure 11 are the predicted pressure profile by Isentropic Homogenous Equilibrium model. The measured pressures are higher than that predicted ones. The departures of experimental data from theory are increased by the decreasing quality. This tendency is the same as that of the critical flow rate shown in Figure 10. It is thought that the non-equilibrium phenomena between phases are occurred for low quality. The pressure recovery is observed at the downstream of nozzle. This comes from the compression work of two-phase flow ejector. The kinetic energy of two-phase flow is converted into the pressure energy behind the nozzle where correspond to the mixing section and the diffuser. If the vapours from the evaporator were sucked at the nozzle outlet, they would compressed by this pressure increase by the two-phase flow ejector. 60 55 50 45 40 35 30 25 20 15 10 5 Experimental result 0 Quality of the flow at inlet of teh nozzle 0.40 x=0.83 Theoritical curve x=0.67 Theoritical curve 0.35 x=0.45 Theoritical curve x=0.37 Theoritical curve 0.30 x=0.32 Theoritical curve 0.25 0.20 0.15 0.05-10 0 10 20 Distance from throat[mm] Figure 10 Difference of critical mass flow between experiment and the theory Figure 11 Pressure Distribution 937

COP The energy conversion efficiency The energy conversion efficiency of the nozzle The speeds of two-phase flow flushed out from the nozzle are estimated from the pressure profiles shown in Figure 11. The reactions on the nozzle are calculated from the pressure distribution and this force is put to equal to momentum increase of two-phase flow. The energy conversion efficiencies of the nozzle are plotted against the inlet quality in Figure 12. The energy conversion efficiency is gradually decreased with the inlet quality. As mentioned above, the non-equilibrium phenomena are increased for small quality. 1.0 0.8 0.6 0.4 0.2 0.0 Figure 12 Energy conversion efficiency Evaluation of COP of the ejector cycle with the used nozzle 0.16 0.14 0.12 0.08 0.06 0.04 0.02 Experimental ejector IHE model Quality at the inlet of nozzle 0.00 Quality at the inlet of ejector Experimental result Approximation line Figure 13 COP of the ejector cycle with the used nozzle At this stage, it is worthwhile to evaluate the performance of the ejector air conditioning system with the nozzle used in the experiment. Theoretical COP resented in previous section is calculated by using the energy conversion efficiency of the nozzle shown in Figure 11. The resultant of COP is plotted by solid line in Figure 13. The dotted line that is the same as in Figure 3 is also plotted to compare. There is large difference between two lines. This means that the energy conversion efficiency of the nozzle has large impact on the COP of the ejector system. The considerably small COP at low quality is caused by the low efficiency of the nozzle. This result shows that the two-phase flow nozzle with much higher energy conversion efficiency is needed to develop the high COP ejector cycle using water refrigerant. CONCLUSION The nozzle performance of two-phase flow ejector air conditioning system is experimentally examined in this study. And the COP of the ejector refrigeration system is theoretically estimated. Following results are obtained. (1) It is theoretically elucidated that the efficiency of ejector refrigeration system using waste heat is improved by using two-phase flow nozzle. (2) The present visualization experiment shows that the two-phase flow shock wave appears with the flat pressure distributions in the divergent part of the nozzle. (3) The non-equilibrium phenomena between phases are occurred for low quality. And this lowers the energy conversion efficiency. (4) Since the COP of the ejector refrigeration cycle using waste heat is largely affected by the nozzle efficiency, the nozzle used in this study has not ability to apply to the two-phase ejector refrigeration system. The two-phase flow ejector is theoretically expected to attain the high COP compared with the steam ejector. However, it is elucidated from our experiments that the nozzle efficiency for two-phase flow rapidly decrease with the decreasing quality. The high efficiency two-phase flow nozzle must is be developed for the refrigeration system using water as a refrigerant. REFERENCES [1] Masafumi Nakagawa, Chikara Sato, Performance of the ejector for the steam refrigeration cycle, proceeding of the conference of Japanese Institution of Mechanical Engineers in Tokai area, 2010 [2] G.K. Alexis, E.D. Rogdakis, A vertification study of steam-ejector refrigeration model, Proceedings of Applied Thermal Engineering 23(2003), pp. 29-36 [3] Kanjanapon Chunnanond, Satha Aphornratana, An experimental investigation of a steam ejector refrigerator: the analysis of the pressure profile along the ejector, Received 20 March 2003; accepted 24 July 2003 [4] Masafumi Nakagawa, Refrigeration Cycle with Two-Phase Ejector, Refrigeration, Vol.79, No. 925, 2004, pp.856-861 [5] Masafumi Nakagawa, Atsushi Harada, Two-phase Ejector for Refrigeration Cycle and Shock Waves Appearing in the Supersonic Two-phase Flow Nozzle, proceeding of Japanese J. Multiphase Flow Vol. 24 No.1 (2010), pp.21-28 [6] Japanese Institution of Mechanical Engineers, The handbook about the technique of gas-liquid two-phase flow, published by Corona, 2006, pp.430-435 938