Amendments to the January 2016 Design Criteria Manual & Supplementary Master Municipal Construction Documents

Similar documents
PART 5 WATER SYSTEMS

Town of New Tecumseth Engineering Design Criteria and Standards for Subdivisions and Capital Works Projects

ENGINEERING DESIGN & IMPROVEMENT STANDARDS

CITY OF ASTORIA PUBLIC WORKS ENGINEERING DIVISION ENGINEERING DESIGN STANDARDS FOR IN-FILL DEVELOPMENT

CITY STANDARD DETAILS FOR CITY OF JACKSONVILLE FLORIDA DEPARTMENT OF PUBLIC WORKS

DIVISION 3 PAVEMENT (FLEXIBLE AND RIGID) CONSTRUCTION SPECIFICATIONS

DOCUMENT ADDENDUM No. 2

CHECK THE LOWER RIGHT CORNER OF EACH DETAIL FOR THE LATEST REVISION.

Summary of the 2011 Changes

GWINNETT COUNTY STORM SEWER PIPE STANDARDS

ONE PIPE LENGTH MAX (REFER TO 1/4"/FT SLOPE (MIN) 5'-0" (MIN) OR 4" LATERAL NOTE #1) INCREASER RIGHT-OF-WAY/ 4"x6" REFER TO TYPICAL EXCAVATION,

VILLAGE OF LOMBARD CONTRACT DOCUMENT NUMBER SS BID PROPOSAL

RICHFIELD CITY CONSTRUCTION STANDARDS

This is only a general checklist; please refer to the CVWD Development Design Manual (DDM) for all requirements and regulations.

Drainage structure refers to manholes, catch basins, leaching basins, inlets and drop inlets. Drainage structures are designated as follows.

SECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL PRECAST CONCRETE MANHOLES

Electrical Work. NOV Embankments Over Swamps and Compressible Soils

M I N N E S O T A D O T BID TABULATION SUMMARY JOB PAGE 1 ON 03/16/94 MINNESOTA PROJECT NO.S: STP 5822(002)

STORM AND SURFACE WATER 4-1 GENERAL...4-1

Surface Infrastructure Restoration for Utility Cuts DIVISION 14 Shallow Buried Utilities Section _Mar29_2016.pdf Page 1 of 20 INDEX

Municipal Inspection and Construction Guidelines Section I Roadworks SECTION I ROADWORKS I-1 GENERAL

SECTION TRENCHING & BACKFILLING

SPECIFICATIONS FOR STREET CONSTRUCTION WITHIN THE TOWN OF PLAINVILLE

SECTION MANHOLES AND STRUCTURES. A. Section Includes: 1. Manholes for water, storm drain and sanitary sewer systems.

G2-0 List of Active Ministry of Transportation of Ontario Drawings (MTOD s)

SPECIAL SPECIFICATION 3504 Septic Tank System

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

New Fulton State Hospital Energy Control Center and Services Building (ECC/SVC) Project Number: M

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY PHASE II

DIVISION 3: SEWER. Improvement Design Standards City of Dundee Oregon. Division 3 : Sewer Page 1

ADDENDUM NO. 1. for the VETERANS PARK RENOVATIONS CITY OF TALLADEGA, ALABAMA. Posting Date: June 20, 2013

Section 401. PIPE CULVERTS

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

Engineering Design Center. Standard Drawings. 1st Edition -January 2016

CW WATERMAINS TABLE OF CONTENTS

G2-0 LIST OF ACTIVE MTODs

DESIGN STANDARDS. Division 02 Existing Conditions- Site Work. General

DUKE UNIVERSITY CONSTRUCTION STANDARDS

SANITARY SEWERS. B. Construct or relocate building sanitary sewer services, stubs, and connections.

2. A preconstruction meeting with the TWA s staff is required prior to initiating construction.

CITY OF LETHBRIDGE INFRASTRUCTURE SERVICES DEPT. CONSULTING ENGINEER S LAND DEVELOPMENT FIELD SERVICES GUIDELINES

SECTION EXCAVATION AND BACKFILL FOR UTILITIES AND STRUCTURES

G2-0 LIST OF ACTIVE MTODs

SECTION MEASUREMENT AND PAYMENT

INSPECTION AND ACCEPTANCE FOR MAINTENANCE

CHAPTER 6. Sanitary Sewer

Transportation, Engineering and Development Business Group Standard Construction Plan Notes for Development Projects January 2013

ITEM D-701 PIPE FOR STORM DRAINS AND CULVERTS

MFOA/AMCTO FALL SEMINAR SERIES TANGIBLE CAPITAL ASSETS ACCOUNTING TOPIC: VALUATION OF ROADS AND OTHER NETWORKS

Construction Specifications

SECTION FACILITY SANITARY SEWERS

REVISION INFORMATION FOR STANDARD CONSTRUCTION SPECIFICATIONS

G2-0 LIST OF ACTIVE MTODs

CHAPTER 200 STORM SEWER CONSTRUCTION STANDARDS

PITTSBURGH TECHNOLOGY CENTER PUBLIC IMPROVEMENTS SITE PREPARATION CONTRACT NO. 11 BID TABULATION BID OPENING DATE: MARCH 11, 2008

Project Type: Drainage and Storm Systems

SECTION WATER MAINS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA

Storm Drainage

SITE SERVICES GUELPH TRANSIT OPERATIONS & MAINTENANCE SECTION WATSON ROAD FACILITY PAGE 1 OF 6 WATER RECLAMATION PROJECT JUNE 2013

Design Specifications & Requirements Manual

BILL OF QUANTITY ENGINEERING & MANAGEMENT CONSULTING CENTRE. "Beit Hanoun Emergency Water Supply Project"

OKLAHOMA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISIONS FOR BUY AMERICA

Attachment D-1: Civil/Structural Scope of Work

CURRENT NORTH LAS VEGAS ADDENDA

CITY OF DES PLAINES-CONCRETE PROGRAM SIDEWALK, CURB AND DRIVEWAY GUIDELINES

WASTEWATER REVIEW CHECKLIST. Project Number: Reviewed By: Telephone:

Fabrication and Installation Table of Contents

CULINARY WATER PROJECT COST ESTIMATES & LOCATION MAPS. Appendix B

Contact the Jurisdictional Engineer for materials allowed by each jurisdiction.

***************************************************************************************************************

SECTION STORM DRAIN

ULTRA FLO Storm Sewer Pipe

CONSTRUCTION SPECIFICATION FOR KEYHOLE EXCAVATION AND PERMANENT REINSTATEMENT OF KEYHOLE CORES TABLE OF CONTENTS

Special Provision No. 405F03 March 2005

CW 3620 INSTALLATION OF UNDERGROUND TRAFFIC SIGNAL SERVICES TABLE OF CONTENTS

CULINARY WATER SYSTEMS

E. GILMAN STREET, N. PINCKNEY STREET, AND N. BUTLER STREET RESURFACING WITH UTILITIES ASSESSMENT DISTRICT CONTRACT NO DATE: 9/22/17

A.2.a Random Riprap... Table

SECTION STORM DRAINAGE UTILITIES. B. Section : Site Restoration and Rehabilitation

SECTION 14 - RESTORATION OF SURFACES TABLE OF CONTENTS

CLEVELAND DIVISION OF WATER CONSTRUCTION STANDARDS. Details Index

CHAPTER 500 STREET PAVEMENTS, CURB, GUTTER AND SIDEWALK CONSTRUCTION SPECIFICATIONS

DUKE UNIVERSITY CONSTRUCTION STANDARDS

SECTION UTILITY MANHOLES AND STRUCTURES

Index. Composition and Order of Plan Set. Utility Plan... 5

Baseline Document Change Announcement

Municipal Engineering Standards Development Agreement Request Form

SECTION DUCTILE IRON FITTINGS. A. This section includes materials, installation, and testing of ductile iron fittings 48 inches and smaller.

Storm Drainage Structures

SECTION STORM UTILITY DRAINAGE PIPING

SECTION 14 - RESTORATION OF SURFACES TABLE OF CONTENTS

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

City of Naples Utilities Department Wastewater Collections Division

SUBDIVISION AND OFF-SITE SERVICING CERTIFICATION REQUIREMENTS Rev 5 May 25, 2017

CIRCLE K SUB-CONTRACTOR BID FORM

Underground Piping for Private Hydrants & Sprinkler Supply Line

CONSTRUCTION PLAN REVIEW CHECKLIST FOR PRIVATE DEVELOPMENT

DESIGN GUIDELINES AND TECHNICAL STANDARDS

City of Elgin SUBDIVISION FINAL ENGINEERING Engineering Submittal Checklist

ADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities

Transcription:

General Figure 2.3.1 16 Revise Revised Figure 2.3.1: New Development Areas where Secondary Suites Apply to include two new areas (#4 and 5). Water 3.3.2 Watermains 31 Add Added wording in Section 3.3.2.3 regarding the sizing design and minimum diameter required for looping water mains Water 3.3.6 Hydrants 35 Add Added wording in Section 3.3.6.1 to clarify minimum distance of hydrant from end of cul de sac /road Design Criteria Manual Water Figure 3.5.1 39 Add Added Figure 3.5.1: Soils Vulnerable to Seismic Events to digital PDF file and renumbered pages within Water Section and Table of Contents accordingly Sanitary Sewer 4.3.4 Manhole Structures 49 Revise Revised wording in Section 4.3.4.1 (g) to require manhole "at property line" for 200mm diameter service or larger" Stormwater / Drainage 5.4.4 Manholes 97 Revise Revised wording in Section 5.4.4.1 (g) to be 250mm diameter or larger and at the property line Stormwater / Drainage 5.4.5 Catch Basins 100 Revise Revised wording in Section 5.4.5.2 and 5.4.5.3 to include maximum surface area to a catch basin, and when catch basins are to be connected to manholes General Conditions Document unchanged 18 Revise 2.2.1: Ductile Iron Pipe Added wording requiring nitrile gaskets when hydrocarbon soils encountered 19 Revise 19 Revise 2.2.4: Fittings Under Ductile Iron / Compact Ductile Iron Main category, add "Sigma " as an Approved Product / Manufacturer 2.2.4: Fittings / Couplings / Joint Restraints Under all categories for fittings, couplers, flange adpators, repair clamps, etc., clarify requirement for Type 304 Stainless Steel hardware including all bolts, nuts and rods. (List of Approved Materials and ) 20 Revise 20 Deletion 2.3.1: Gate Valves Revised wording to clarify approved material types and products for diameters 2.3.4: Blow-off Valves Deleted multiple references to 50mm gate valves 20 Revise 2.3.6: Water Valve Boxes Clarified water valve boxes to be circular cast iron (MR6 style). 20 Addition 2.3.7: Service Valve Boxes Added wording regarding concrete water meter boxes require metal lid 21 Revise 2.7: Underground Service Line Valves and Fittings Revised wording to clarify when gate valves are required for service connection 21 Revise 2.3: Plastic Pipe, Mainline Smooth Profile Revise heading to read "Plastic Pipe Mainline Smooth Profile" Page 1 of 5

22 Revise 22 Deletion 22 Deletion 23 Deletion 23 Revise 23 Deletion 2.3: Service Connections Deleted wording regarding services that require a manhole at the property line and incorporated this requirement into the Design Criteria Manual 2.3: Inspection Chamber Deleted wording regarding IC to be pre-plugged 2.3: Inspection Chamber Deleted concrete water boxes from approved product for inspection chamber cover. 2.2.2: PVC Pressure Pipe Delete wording requiring nitrile gaskets on sewage forcemains 2.2.5: Fittings Revised wording to clarify Type 304 stainless steel hardware required 2.2.8: Low Pressure Deleted wording requiring nitrile gaskets on sewage forcemains (List of Approved Materials and ) 23 Revise 24/25 Revise 2.3.2: Gate Valves Revised wording to clarify approved material types and products for diameters Various Sub-Sections Revised elevation threshold for Lowland areas from 10.0m to 7.0m 24 Revise 2.2: PVC Pipe, Mainline Smooth Wall Revised heading to read: "PVC Pipe, Mainline Smooth Wall" 26 Deletion 2.6: Inspection Chamber Deleted wording regarding IC to be pre-plugged 26 Deletion 2.6: Inspection Chamber Deleted concrete water boxes from approved product for inspection chamber cover. 33 42 13 Pipe Culverts 26/27 Revise Various Sub-Sections Revised elevation threshold for Lowland areas from 10.0m to 7.0m 33 42 13 Pipe Culverts 26 Revise 2.1 Corrugated Steel Pipe Revised wording to Aluminized II Coating 33 44 01 Manholes and Catch Basins 27 Revise 2.1 Precast Manhole sections Added Diamond Precast to the approved list of manufacturers Page 2 of 5

Section 03 30 20: Concrete Walks, Curbs and Gutters 2.0 30 Addition 2.1: Materials Added wording to SS 2.1.7 to include sealing of coloured concrete after installation. Section 31 15 60: Dust Control 3.0 Execution 37 Revise 3.1: Application Revised wording to SS 3.1.1 to exclude flushing of roads 1.0 General 39 Append 1.8: Limitations of Open Trench Append wording regarding City permission required to leave open trenches within roadways 2.0 40 Revise 2.2: Use of Specified Materials Revised wording to 2.2.3 to clarify trench backfill to be imported granular material as per SSD -G.4 3.0 Execution 40 Revise 3.5: Backfill and Compaction Revised wording to 3.5.4.4 on minimum compaction testing requirements 3.0 Execution 40 Revise 3.6: Surface Restoration Added revision to MMCD wording regarding temporary pavement patching of local roads, lanes and driveways to be within 48 hours of excavation. Section 32 17 23: Painted Pavement Markings 2.0 55 Revise 2.1: Materials Revised numbering for temporary markings and added 2.1.7 for Permanent Pavement Markings Section 32 91 21: Topsoil and Finish Grading 2.0 57 Revise 2.10: Growing Medium Revised the accepted range for some of the parameters in Table 2 Section : 2.0 64 Revise 2.2: Mainline Pipe, Joints and Fittings Revised wording in SS 2.2.4.10.1 for tie-rods to be stainless steel Section : 2.0 64 Revise 2.2: Mainline Pipe, Joints and Fittings Revised wording to SS 2.2.7.2 to be "Cast Iron Pipe Size" Section : 3.0 Execution 66 Revise 3.10 Service Connection Installation Revised wording to SS 3.10.11 to delete references in MMCD 3.10.11 to service connection diameters Section : 2.0 76 Revise 2.2: Pipe, Joints and Fittings Revised Wording to SS 2.2.2.4 to be "Cast Iron Pipe Size" Section : 2.0 77 Revise 2.2: Pipe, Joints and Fittings Revised Wording to SS 2.2.5.13 to include PVC and PVCO Section : 2.0 79 Revise 2.3: Spiral Rib Pipe - Steel Revised wording to clarify spiral rib steel not permitted for storm sewer Section : 2.0 79 Revise 2.6: Service Connections Revised diameter to 250mm or larger require manhole at the main Page 3 of 5

General SSD-G.1 - Revise Revised offset between sanitary and storm service connections General SSD-G.1.1 - Add Add inspection chamber detail, to replace MMCD S9, and make it applicable to both sanitary and storm service IC's General SSD-G.4 - Revise Revised trench backfill requirements for Collector Roads General SSD-G.5 - Revise Revised asphalt thickness, and material type for driveways, and varied by landuse Drainage SSD-D.8 - Revise Added dimensions for asphalt apron width Drainage SSD-D.9 - Revise Revised title to include "Curb" Drainage SSD-D.12 - Revise Clarified drain rock to be "clear crushed" and clarified filter cloth note Transportation SSD-R.1 through R.7 - Revise Revised median and boulevard topsoil to be 450mm growing medium Standard Drawings Transportation SSD-R.12 - Revise Added clarity on alternate inspection chamber location, in lane section, if approved by the City Transportation SSD-R.13 - Revise Revised sidewalk thickness notes to include reference to driveway letdown detail drawing which identifies the sidewalk thickness required at driveways Transportation SSD-R.13.1 - Revise Revised sidewalk thickness notes to include reference to driveway letdown detail drawing which identifies the sidewalk thickness required at driveways Transportation SSD-R.15.1 - Revise Revised object marker sign post location and added detail for bull nose median at left turn lane Transportation SSD-R.15.2 - Revise Revised title of drawing. Also revised object marker sign post location Transportation SSD-R.15.3 - Revise Revised title of drawing. Also revised object marker sign post location Transportation SSD-R.16 - Revise Clarified median curb to be reverse, narrow base barrier curb and gutter per MMCD Transportation SSD-R.17 - Revise Removed decorative sign plate from top of fence posts Transportation SSD-R.18.1 - Revise Revised notes to indicate concrete pad in travel/curb lane may be required by City for high volume bus locations Page 4 of 5

Transportation SSD-R.18.2 - Revise Revised notes for electricalduct to be stubbed flush with concrete pad Transportation SSD-R.21.1 - Revise Revised thickness of granular subbase to 200mm Transportation SSD-R.21.2 - Revise Revised concrete joint details /notes and style of curb Transportation SSD-R.24, 24.1 and 24.2 - Revise Revised flare of concrete driveway to project through to back of sidewalk Transportation SSD-R.24.3 - Revise Revised sidewalk thickness note to clarify and be consistent amongst details Transportation SSD-R.27 - Revise Revised asphalt material for walkways to be UC #2 Transportation SSD-R.28.2 - Revise Clarified curb and gutter to be narrow base per MMCD Standard Drawings Transportation SSD-R.29 - Revise Added expansion joint details Transportation SSD-R.29.1 - Revise Revised stamped concrete pattern to be Random Rock Transportation SSD-R.30 - Revise Revised stamped concrete pattern to be Random Rock Sewer SSD-S.1 - Revise Revised Note #4 to refer to Design Criteria Manual regarding service connection diameter that requires a manhole Sewer SSD-S.6 - Revise Revised Valve Box to be MR6 Style or equivalent Water SSD-W.1 - Revise Revised diameters and valve types for corporation and curb stop to vary by diameter Water SSD-W.4 - Revise Revise valve box to be Circular Cast Iron (MR6 Style) and on both risers Page 5 of 5