Installation, Operation and Maintenance Instructions 3.19 [81.0] 0.43 [11.0] 0.94 [23.9].29 THRU 0.43 [11.0] 1.42 [36.0] 4.80 [121.8] 1.89 [47.

Similar documents
User s Guide IP610 SERIES. I/P Converters. Shop online at. omega.com For latest product manuals: omegamanual.

XMP i. Precision Pressure Transmitter for the Process Industry with HART -Communication. Stainless Steel Sensor

XMP i. Precision Pressure Transmitter for the Process Industry with HART -Communication. Stainless Steel Sensor

Shur-Shot X-Proof Hydrogen Fluoride Alarm Operations Manual

ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200

8.27/210 * 7.28/ / / /108. n x d. b f ML00343b. Dimensions are in inches/millimeters *8.86/225 for Pg 13.5 with adapter 2.

HDI 2200 Choke Position Indicator

Digital E3 Modulevel Liquid Level Displacer Transmitter

SECTION Coriolis Mass Flow Meters

L505 VISUAL LEVEL INDICATOR. Dip-Tape Visual Level Indicator INSTALLATION AND OPERATIONS MANUAL

ILMK 382. Stainless Steel Probe. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO.

PD662 Loop-Powered Meter Instruction Manual

Agilent 16047D Test Fixture

x act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0.

SECTION PRESSURE AND DIFFERENTIAL PRESSURE GAUGES

1-300 SERIES Endover Rotator Operator s Manual for Morse End-Over-End Drum Rotators Series

SABRE P MODEL PD603 PROCESS METER Instruction Manual

Fuji Electric France S.A. DIFFERENTIAL PRESSURE (FLOW) TRANSMITTER FEATURES SPECIFICATIONS FKC...5 DATA SHEET. Functional specifications.

Flow measurement of Liquids and Gases

Precision Automatic Vacuum Control (PAVC+)

GUIDELINES FOR SUB-SYSTEM COMPLETION CERTIFICATES AND TEST RECORDS FOR ELECTRICAL INSTALLATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES

RSD250 Unwind Dancer Package WEB CONTROL PRODUCTS FORM NO. L B User Manual. MTY (81)

BMA-System#3 Technical Application Sheet

3M Water Filtration Products Model SGLP-RO Reverse Osmosis System- Quick Installation Guide

Pro-V Multivariable Flowmeter Model M23 Insertion Vortex

Table of Contents. Introduction 1. Description 1. Calibration 4. Installation 7. Operation 12. Maintenance & Troubleshooting 12

Certificate of Compliance

Wing Union/Hammer Union Pressure Sensors Models 434, 435, Issue 3. Datasheet FEATURES DESCRIPTION POTENTIAL APPLICATIONS DIFFERENTIATION

x act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0.

OM-CP-QUADPROCESS 4-Channel Low Level DC Current Data Logger. OM-CP-OCTPROCESS 8-Channel Low Level DC Current Data Logger INSTRUCTION SHEET

Particulate Filters. Filter Function. Exclusive Dense Pack Element Design. Optional Components

TUFFY T3. Side Mounting Level Controls. Worldwide level and flow solutions FEATURES MODELS APPLICATIONS AGENCY APPROVALS

RHM80. High Flow Coriolis Mass Flow Meter. Features. Applications. Benefits

VERIS Accelabar. Superior Flow Measurement Accuracy

Wash Down Duty Non-Contact Sensor

MS50 Buoyancy level switch. K-TEK products. Measurement made easy. Features. Typical applications

MD Power Supply -48Vdc +Bias Tee

EuroFID Total Hydrocarbon Analyzer

Instruction Manual HI RH/ C Transmitter. This Instrument is in Compliance with the CE Directives.

Industrial Solutions. Quality is Our Driving Force. interfaceforce.com

Quick-Start Operating Guide Document No Process Gas Cooler Copyright 2010 Terra Universal Inc. All rights reserved. Revised October 2010

INSTALLATION PROCEDURE

Pro-V Multivariable Flowmeter Model M23 Insertion Vortex

Supplemental Instruction Manual

Switch-Tek. LV41 & LV42 Series Manual. Sump Float Level Switches

Agilent 16034E Test Fixture

MODEL 3200 / 3201 CONTENTS. Installation, Operation, and Maintenance Instructions 1.0 GENERAL 2.0 INSTALLATION 3.0 OPERATION 4.

C60 Standby UPS. 800VA Models. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.

Certificate of Compliance

SPRING LOADED THERMOCOUPLE CONFIGURATIONS

Rosemount Compact Orifice Flowmeter Series

Sentinel LNG. Panametrics Ultrasonic Flowmeter for Cryogenic Liquids. GE Sensing & Inspection Technologies. Benefits. Applications

Over pressure Switching pressure difference (typical) Lower range Upper range

Read and understand this manual for safely usage.

Sby SR Instruments, Inc.

Functional safety in the process industry

DANIEL LIQUID TURBINE METER REMOTE MOUNTING BOX

Original instructions JSNY7 Magnetic switch

4 1 /2 MARK 73-5 AMERICAN FLOW CONTROL. It s What We Know. AMERICAN-DARLING FIRE HYDRANT AMERICAN-DARLING 4 1 /2 MARK 73-5 FIRE HYDRANT

AT9000 Advanced Transmitter Absolute Pressure Transmitters

Rosemount 1152 Alphaline Nuclear Pressure Transmitter

Service Entrance Cable Fittings

Compressed Air Systems. Compressed Air Filters. Balston Microfiber Filter Assemblies. Product Features

Liquid level switch BW 17

High Capacity Weigh Modules

Load cells Type: RTB Safety Instructions

Magnetic float switch For vertical installation Model FLS for nuclear power plants

MANUAL. ENGLISH Antenna Booster Ordercode: D1425. Highlite International B.V. Vestastraat EX Kerkrade the Netherlands

Adjustable Fused Power Supply

THE KENYA POWER AND LIGHTING CO. LTD

Model 140MX Flowmeter Functional Overview

Ecologix Environmental Systems, LLC

Glass Reinforced Polyester Enclosures BPG. Glass Reinforced Polyester Enclosures

Compressed Air Filters. Particulate, Liquid, and Oil Removal ,250 scfm. kaeser.com

Industrial Electrolytic Conductivity Cells for UDA2182 Series and APT Series

WHOLE HOUSE FILTER &

Thermoelectric Coolers. All Models INSTRUCTION MANUAL. Rev. G 2016 Pentair Equipment Protection P/N

Thermoelectric Cooler

Pressure transducers DMU 02 Vario (flush)

Industrial flue gas probes. Instruction manual

Accessories for Sample Gas Probe GAS 222

PRESSURE SWITCHES D-LT Electro-mechanical pneumatic pressure switches. 18D-LT x2 Electro-mechanical pneumatic pressure switches.

AIR CHAMP PRODUCTS. Micro Clutch and Micro Brake FORM NO. L J-0110

F64G - Olympian Plus Plug-In System General purpose filter

Installation, Operation & Maintenance Manual

Single-Use Sensors. TruFluor and TruTorr Excellence in bio-processing measurement

VBC Manual MManualManual. Installation and user manual for the VBC

KDS. All Metal Variable Area Flowmeter. for liquids and gases. Measuring range: l/h l/h water 5-50 Nl/h...

Sensor unit MC2 for toxic gases and oxygen with analog output

Carbon Canister Vapor Polisher

Operating Instructions

SPRING LOADED THERMOCOUPLE CONFIGURATIONS THERMOWELL & REPLACEABLE INSERT II 2G/D Ex e TCRE/WE

Red Eye Multiphase Water-Cut Meter

Daniel Orifice Fittings and Meter Tubes

Installation. Basic Rack Power Distribution Units AP9560 AP9561

Global Water Instrumentation, Inc.

Dual Port isolated USB Charger

Daniel TM Ultrasonic Flow Meters

2/2 % ) Direct Acting Subminiature Solenoid Valves. 1/8" and 1/4" NPT. Features. Construction. Electrical

Transcription:

Type 595XP Explosion Proof I/P Transducer Installation, Operation and Maintenance Instructions Ø2.90 [73.7] 3.19 [81.0] 2.89 [73.3] MANIFOLD WITHOUT FLOW BOOSTER (M) 3.19 [81.0] UNIT WITH FLOW BOOSTER (P) 4.23 [107.4] 0.34 [8.5] 0.43 [11.0] 0.94 [23.9].29 THRU 1.34 [33.9] 1.06 [27.0] MOUNTING 5.16 [131.0] 0.43 [11.0] 1.42 [36.0] 1/2 NPT CONDUIT PORT M20 X 1.5-6H "K" OPTION 1/2 NPT "K2" OPTION 1/16[1.6] SUPPLY PORT 1/16[1.6] OUTPUT PORT 0.41 [10.5] 1.00 [25.4].40 [10.0] 2.25 [57.1] 1/2 NPT CONDUIT PORT M20 X 1.5-6H "K" OPTION 1/2 NPT "K2" OPTION 3.19 [81.0] 2.90 [73.7] 1/4 NPT SUPPLY PORT.65 [16.4].59 [15.0] 1.27 [32.1] 1/8 NPT GAUGE PORT 4.80 [121.8] UNIT WITHOUT FLOW BOOSTER (N) 1.89 [47.9] 1/2 NPT CONDUIT PORT M20 X 1.5-6H "K" OPTION 1/2 NPT "K2" OPTION.48 [12.1].30 [7.7] 1/4 NPT OUTPUT PORT 1.42 [36.1].33 [8.4] 1.27 [32.1] 1/4 NPT SUPPLY PORT Use this coding system to order: (Drawing downloads available at http://www.controlair.com) Contents Section Description Page 81.0 Columbia Drive, Installation Amherst, New & Approvals Hampshire 03031 USA 3 Phone: 2.0 (603) 886-9400 Operation Fax: (603) 889-1844 7 sales@controlair.com 3.0 Maintenance www.controlair.com 7 4.0 Troubleshooting 8 5.0 Warranty 8 * ATEX Ex ia INTRINSICALLY SAFE, Ex nl and Ex nanl APPROVAL ONLY **R OPTION MUST BE COMBINED WITH K OR K2 OPTION 8 Columbia Drive, Amherst, New Hampshire 03031 USA Phone: (603) 886-9400 Fax: (603) 889-1844 sales@controlair.com www.controlair.com 441-622-099 Type 595XP

DANGER, WARNING, CAUTION and statements DANGER WARNING CAUTION Refers to conditions or hazards which could result in serious personal injury or death. Refers to conditions or hazards which could result in personal injury. Refers to conditions or hazards which could result in equipment or property damage. Alerts you to facts or special instructions. ALL DANGER, WARNING, AND CAUTION NOTICES MUST BE COMPLIED WITH IN FULL. SPECIFICATIONS Functional Specifications P Connection (with Flow Booster) M & N Connection (without Flow Booster) INPUT 4-20 MA Outputs 3-15 psig 0.20-1.0 BAR 3-27 psig 0.20-1.8 BAR 6-30 psig 0.40-2.0 BAR Air Consumption 0.1 scfm (2.83 Nl/min) 2.00 scfh (1 Nl/min) @ 20 psig supply (1.4 BAR) 4.94 scfh (2.47 Nl/min) @ 85 psig supply (6.0 BAR) 8.36 scfh (4.18 Nl/min) @150 psig supply (10.0 BAR) Supply Pressure Note: Supply pressure must be a minimum of 5 psig (0.3 BAR) above maximum output 3-15: 22 psig (1.5 BAR) max 3-27, 6-30: 42 psig (2.8 BAR) max 150 psig (10.0 BAR) max. Flow Capacity 2.4 scfm (67.92 Nl/min) max. Same as Air Consumption Temperature Limits -40 0 F to 158 0 F (-40 0 C to 70 0 C) *Low Temperature (L) Option: -67 0 F to 158 0 F (-55 0 C to 70 0 C) Relative Humidity Impedance Loop Load Performance Specifications Linearity (Independent) Hysteresis Deadband Repeatability Mounting Orientation 75% average - 95% short time non-condensing 260 Ohms @ 70 0 F 5.2 Volts @ 70 0 F <±0.5% of span <±0.3% of span <±0.1% of span <±0.3% of span; <±0.15% of span typical <±0.5% / 90 degree change Air Supply Sensitivity <.3% / 1.5 psig (0.10 BAR) change <±0.6% / 25 psig (1.72 BAR) change Vibration Effect Temperature Effect Physical Specifications <±1% up to 10g and 20-80 Hz <±0.75% / 10 0 F change Housing NEMA 4X (IP 65) Port Sizes Pneumatic 1/4 NPT, & 1/16 manifold mount Electric 1/2" NPT, M20 x 1.5 (ATEX K ) or 1/2" NPT (ATEX K2 ) Media Electrical Connections Mounting Clean, dry, oil-free, instrument air, filtered to 40 micron Terminal block Direct (standard) or 2 pipe (optional) Materials Housing: Chromate-treated aluminum with epoxy paint. NEMA 4X (IP65) Elastomers: Buna-N Trim: Stainless steel; brass; zinc-plated steel Weight * ATEX Ex ia INTRINSICALLY SAFE, Ex nl and Ex nanl APPROVAL ONLY 1.4 lb 441-622-099 Type 595XP Page 2

1. INSTALLATION AND APPROVALS 1.1 Pre-Installation Requirements 1.1.1 Environment: Suitable for installation in the following locations: Intrinsically safe operation in hazardous locations outdoors (NEMA 4X, CSA. ENC. 4 & IP65) Explosion Proof Installation in hazardous locations outdoors (NEMA 4X, CSA. ENC. 4 & IP65) See section 1.5, 1.6 and 1.7 for Factory Mutual (FM), Canadian Standards (CSA) and ATEX approvals. WARNING The I/P transducer enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation to prevent impact or friction. DANGER All wiring must be made to all local and national codes appropriate to the area of installation. 1.1.2 Electrical Input: 4-20 ma dc current source. It is recommended that shielded cable be used and that the shield be grounded to unit and earth ground. See Figure 1 on page 4 for location of ground screw. 1.1.3 Air supply: Clean, dry, oil free instrument air filtered to 40 micron. Clean all pipe lines to remove dirt and scale prior to installation. Failures attributable to instrument air supply contamination are not covered by the warranty. 1.1.4 ATEX Specific Conditions of Use The user shall permanently mark the protection type chosen by adding a tick mark in the appropriate box that corresponds to the type of hazardous area installation (i.e. Ex db, Ex tb, Ex ia, Ex nanl or Ex nl). See figure 2. Once the type of protection has been marked, it shall not be changed. The flameproof joints of the equipment are not intended to be repaired. Consult the manufacturer if repair of the flameproof joints is necessary. Refer to the manufacturer s instructions to reduce the potential of an electrostatic charging hazard due to impact or friction on the equipment enclosure. 1.2 Mounting 1.2.1 The Type 595XP has been designed to mount inline, to a standard valve yoke (bracket included with unit), or to a 2 (5.1 cm) pipe (optional mounting kit 448-542-016 required). 1.3 Pneumatic Connections 1.3.1 Clean all pipe lines to remove dirt and scale prior to installation. 1.3.2 Supply air must be filtered to 40 microns and free of moisture and lubricants. 1.4 Electrical Connections 1.4.1 The Type 595XP is supplied with a 1/2" NPT electrical conduit connection as standard and K2 option, M20 x 1.5 for ATEX K option (see Figure 1). 1.4.2 A two (2) position terminal block that is wire ready is supplied for 22-12 AWG wire. Wire should be stripped approximately 1/4" before insertion. The terminals are labeled + and - on the terminal board (see Figure 1). 1.4.3 It is recommended that shielded cable be used and that the shield be grounded at the unit (ground screw provided) and to earth ground. CAUTION Observe polarity. Reverse polarity will not damage the unit, but unit will not operate. Conduit should be connected to prevent condensation from collecting in the unit. 441-622-099 Type 595XP Page 3

Figure 1 Figure 2 SPAN ADJUSTMENT ZERO ADJUSTMENT NEGATIVE TERMINAL (-) POSITIVE TERMINAL (+) TYPE 595XP ControlAir Inc. M20 x 1.5-6H FOR ATEX (K) OPTION 1/2 NPT FOR ATEX (K2) OPTION AND STANDARD FM/CSA ATEX COVER LOCK GROUND 1.5 FM Approvals (FM) & Canadian Standards Association (CSA) Approvals Intrinsically Safe: Non-Incendive: Class I, Div. 1, Groups A, B, C & D Class I, Div. 2, Groups A, B, C & D Class II, Div. 1, Groups E, F & G Class II, Div. 2, Groups E, F & G Class III, Div. 1, Fibers Class III, Div. 2, Fibers Enclosure Nema 4X (IP65) Enclosure Nema 4X (IP65) Rated 4-20 ma, 40 VDC Max. Temp. Code T6 Temp. Code T4 Ta = + 70 0 C Ex ia Explosion Proof: Entity Parameters: Class I, Div. 1, Groups B, C & D Vmax = 40 VDC Ci = 0 uf Enclosure Nema 4X (IP65) Imax = 150 ma Li = 0 mh Temp. Code T6 Dust Ignition Proof: Class II & III, Div. 1, Groups E, F & G Enclosure Nema 4X (IP65) Temp. Code T6 Entity Installation Requirements: Vmax > Vt OR Voc Imax > It OR Isc Ca > Ci + Ccable La > Li + Lcable Note: Cable capacitance and inductance must be considered when connecting to pressure transducer. 441-622-099 Type 595XP Page 4

1.6 ATEX Approvals (Option K) Entity Parameters: Ui (Vmax) = 40 VDC Ci = 0 uf Ii (Imax) = 150 ma Li = 0 mh Pi =.7 W Max. II 1G II 3G II 2G II 2D 1725 ATEX (FM) Flame proof FM 08ATEX0049X II 2 G Ex db IIB + H2 T6 Gb Ta = -40 0 C to +75 0 C II 2 D Ex tb IIIC T85 0 C Db Ta = -40 0 C to +75 0 C 1.7 EC Declaration of Conformity We, ControlAir, Inc. 8 Columbia Drive Amherst, NH 03031 Declare that the Type 595XP Transducer family to which this declaration applies, comply with these standards: EN 60079-0:2012 + A11 :2013 EN 60079-1:2014 EN 60079-11:2012 EN 60079-15:2005 EN 60079-31:2014 EN 60529:1991 + A1:2000 + A2:2013 EN 1127-1:2011 Following the provisions of EMC directive 2014/34/EU 441-622-099 Type 595XP Page 5

1.8 INSTALLATION DRAWING NO. 431-990-055 1. (North America) Control equipment connected to the Associated Apparatus must not use or generate more than 250 Vrms or Vdc. 2. (North America) The IS Barriers or Equipment (Associated Apparatus) must be FM Approved and CSA certified and the configuration of associated Apparatus must be FM Approved and CSA certified under the Entity Concept. The Associated Apparatus may be installed within the Hazardous (Classified) location for which it is certified. The Associated Apparatus and hazardous location loop apparatus manufacturer's control drawings must be followed when installing this equipment. An AEx [ib] Associated Apparatus is suitable only for connection to Class I, Zone 1, Hazardous (Classified) Locations and is not suitable for Class I, Zone 0, or Class I, Division 1 Hazardous (Classified) Locations. (ATEX) The IS Barriers or other Associated Apparatus shall comply with the ATEX directive 2014 / 34 / EU. 3. (US) Installation should be in accordance with ANSI/ISA RP12.06.01 "Installation of Intrinsically Safe Systems for Hazardous (Classified) Locations" and Article 500 of the National Electrical Code (ANSI/NFPA 70) (Canada) Installation should be in accordance with Section 18 of the Canadian Electrical Code. (ATEX) Installation shall be in accordance with the applicable local installation rules Energy Limitation Parameters specified. 4. (North America) All units suitable for Type 4X installations. 5. (North America) Units are suitable for Class I, Division 2, Groups A, B, C, and D hazardous (classified) locations. Transducers to be installed in accordance with the (US) National Electrical Code (ANSI/NFPA 70) Division 2 hazardous (classified) location wiring techniques (Canada) Canadian Electrical Code. 6. The Intrinsic Safety Entity concept allows the interconnection of two Intrinsically safe devices with entity parameters not specifically examined in combination as a system when: Entity Parameters for: MODELS TYPE 595 Ui (Vmax) = 40 V Ii (Imax) = 150 ma Ci=0 Li=0 Pi = 0.7 watts Ui or Vmax >Uo or Voc Ii or Imax > Io or Isc or It Ca or Co > Ci + Ccable La or Lo > Li Lcable Pi > Po. 7. No revision to this drawing is permitted without prior FM Approval and CSA Certification. T595XP TRANSDUCER + (RED) - (BLACK) 3 4 28V SINGLE CHANNEL POLARIZED 1 2 4-20mA 0V RAIL TYPE 1 SYSTEM CONTROLLER T595XP TRANSDUCER + 4-20mA 3 28V 1 (RED) TWO- CHANNEL - POLARIZED 4-20mA 4 2 (BLACK) DIODE 1-5V TYPE 2 SYSTEM 0V RAIL CONTROLLER T595XP TRANSDUCER + (RED) - (BLACK) 3 4 28V TWO- CHANNEL POLARIZED 10V 1 2 4-20mA 4-20mA 1-5V TYPE 3 SYSTEM HAZARDOUS LOCATION NONHAZARDOUS LOCATION 0V RAIL CONTROLLER 431-990-055 441-622-099 Type 595XP Page 6

2. OPERATION 2.1 Calibration 2.1.1 All units are shipped from the factory calibrated, direct acting. Factory calibration is susceptible to shift due to handling during transit. ControlAir recommends that all units be recalibrated prior to use. 2.1.2 Though the units are shipped fully calibrated it is suggested that the user check the calibration to ensure that settings and operation match the application requirements. ATEX option units come with a factory installed cover lock screw. Screw must be removed before removing cover. Screw must be replaced upon replacing cover. See Figure 1, Section 1.4 It is not necessary to remove the plastic cover of the unit for calibration. 2.2 Calibration 2.2.1 In direct acting operation, the unit is calibrated so that minimum input signal corresponds to minimum output pressure and increasing input signal results in increasing output pressure. 2.2.2 Apply the minimum input signal of the range being used (e.g. 4 ma). 2.2.3 Observe the output pressure. If necessary, adjust the zero screw until reaching minimum output pressure setting. Turn zero screw clockwise to increase and counter clockwise to decrease. 2.2.4 Apply the maximum input signal of the range being used (e.g. 20 ma). 2.2.5 Observe the output pressure. If necessary, adjust the span screw until reaching maximum output pressure setting. Turn span screw clockwise to increase pressure, counter clockwise to decrease pressure. 2.2.6 After setting the span it will be necessary to recheck the zero. Repeat steps 1-4 until both end points are at required values. 3. MAINTENANCE AND REPAIRS Under normal circumstances, no maintenance should be required. 3.1 Instrument Air Filtration 3.1.1 Failures due to instrument supply air contamination are not covered by warranty. 3.1.2 Use of oil and/or water saturated instrument air can cause erratic operation. 3.1.3 Poor quality instrument air can result in unit failure. It is recommended that a filter regulator (such as ControlAir Type 300) be placed upstream of each unit where oil and/or water laded instrument air is suspected. 3.2 Factory Repairs 3.2.1 In the event of unit failure, the Type 595XP can be returned to the factory through point of purchase for warranty repair if the warranty period has not expired. 3.2.2 All units returned for repair must be authorized prior to receipt at the factory. Contact a representative at the point of purchase to receive a Return Authorization Number. 441-622-099 Type 595XP Page 7

3.3 Filter Replacement 3.3.1 Supply pressure can become obstructed should the felt filter element become clogged. To replace filter (P/N: 445-777-018), remove slotted plug and carefully remove filter using tweezers. Insure no dust or dirt particles remain in filter chamber. Insert new filter into chamber in orientation as shown in figure 3. Replace slotted plug, insuring o-ring is properly seated. For N-connection, remove Nema cap screw using a 5/64 hex key. Figure 3 Replacing Filter P - Connection N - Connection FILTER FILTER NEMA CAP SCREW 4. TROUBLESHOOTING PROBLEM LOOK FOR SOLUTION No or low output Wires reversed Zero adjustment Clogged filter Supply pressure too low Reverse input wires (see Figure 1) Reset zero (2.2.3) Replace filter (see Figure 3) Increase supply pressure (see specs) Unstable / low output Electrical connection Check connection/signal (1.1.2) Erratic operation Liquid/contamination in air supply Supply pressure Clean air supply (1.1.3) Verify supply pressure (see specs) Output equals supply pressure Improper pneumatic connections Insure that supply is connected to IN port and output is connected to OUT port (1.3.3, 1.3.4) If problems are not solved by troubleshooting procedures, contact a factory applications engineer at (603) 886-9400 for further assistance. 5. WARRANTY & DISCLAIMER ControlAir, Inc. products are warranted to be free from defects in materials and workmanship for a period of eighteen months from the date of sale, provided said products are used according to ControlAir, Inc. recommended usages. ControlAir, Inc. s liability is limited to the repair, purchase price refund, or replacement in kind, at ControlAir, Inc. s sole option, of any products proved defective. ControlAir, Inc. reserves the right to discontinue manufacture of any products or change products materials, designs or specifications without notice. Note: ControlAir does not assume responsibility for the selection, use, or maintenance of any product. Responsibility for the proper selection, use, and maintenance of any ControlAir product remains solely with the purchaser and end user. WARNING These products are intended for use in industrial compressed-air systems only. Do not use these products where pressures and temperatures can exceed those listed under Before using these products with fluids other than air, for non-industrial application, life-support systems, or other applications not within published specifications, consult ControlAir, Inc. 441-622-099 rev. 04/30/18 Type 595XP Page 8